impact of power electronics on electrical system design

Upload: anandjoy4u

Post on 08-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    1/29

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    2/29

    RELIANCE PATALA GANGA

    IN 1981

    PHASE - I

    2

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    3/29

    SINGLE LINE DIAGRAM

    3

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    4/29

    4

    400 KW INDUCTION MOTOR HAS TO BE INSTALLED FOR

    SPECIAL PURPOSE.

    DESIGN POINTS

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    5/29

    5

    For400 KW Motorwith K=7.2, Running P.F.=0.9, Efficiency=0.92

    Starting Capacity of Motor (Ps ) = KVA

    Motor With 415V, Starting current = A

    Motor with 6.6 KV, Starting Current = A

    3MVA, 22/0.433KV Transformer Rated Secondary Current is A

    Transformer Sizing for400 KW MotorPs = Starting Capacity of Large Motor

    L = Load efficiency

    PM = Rated output of Largest Motor (KW)

    Cos US = Starting Power factor of largest Motor

    %R = Percent resistance for transformer

    %X = Percent reactance for transformer

    I = Voltage Regulation of transformer

    PT = Transformer rated capacity (KVA)

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    6/29

    6

    MOTOR IS CONNECTED TO 6.6KVSWITCH BOARD

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    7/29

    7

    AS PER IS 2026 std-1977

    1600 KVA TransformerWith in tolerance %R = 0.5

    With in tolerance %X= 5

    MOTOR Starting P.F. = 0.25

    During starting or re acceleration of large

    Motor under normal load running,

    The Voltage Regulation at the TransformerSecondary Terminals shall be 15% or less

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    8/29

    8

    Cost AnalysisConsidering the costs for following

    22 KV Switch Board to Transformer 22 KV HT Cable of 3c x 400Sqmm

    1600 KVA, 22/6.9 KV Transformer

    Transformer secondary to 6.6 KV Switch Board 6.6KV HT Cable of 3C x

    400Sqmm

    6.6 KV Switch Board.

    Approximately

    In addition to equipment , allotted area and routing of the cable etc are the most

    expensive.

    Due to the high starting current , cost is effectively increased.

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    9/29

    In this case, we have chosen Slip Ring IM to limitIn this case, we have chosen Slip Ring IM to limit

    starting currentstarting current

    Slip Ring

    Induction Motor

    Squirrel CageInduction Motor

    Speed can be controlled easily

    Excellent starting torque for highinertia loads.

    Low starting current

    Speed is resistance variable over50% to 100% full speed.

    Efficiency is low.

    Resistive loss during acceleration.

    Low cost, Long life

    High efficiency

    Large ratings available

    large number of standardizedtypes

    Starting inrush current is highcauses additional voltage dip from

    the source to the motorSpeed control requires variablefrequency source

    9

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    10/29

    10

    SLIP RING (WOUND ROTOR) INDUCTION MOTOR

    Typical Circuit diagram

    Increasing the rotor resistance

    Applied to wound-rotor (slip-ring) motors.

    The rotor resistor(s) is (are) bypassed as the motor accelerates.

    Starting current is reduced.Starting torque is increased.

    However, the projected speed reduces by raising

    the rotor resistance.

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    11/29

    11

    SLIP RING (WOUND ROTOR) INDUCTION MOTORTORQUE CURRENT-SPEED CURVES

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    12/29

    12

    As per the optimum design point of view,

    NOTE:IN 1981, SOFT STARTER IS UNAVAILABLE

    SLIP RING INDUCTION MOTOR OF 400 KW IS INSTALLED.

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    13/29

    RELIANCE PATALA GANGA

    IN 1985

    PHASE - II

    13

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    14/29

    14

    SINGLE LINE DIAGRAM

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    15/29

    15

    Where

    Actual Calculation of TVD =

    WhereXid Transient Reactance of Selected DG

    Xe Reciprocal of vectorial magnitude of Motor Start KVA

    Transient Reactance of DG is 0.23 ( Approximately)

    For 800 KW Motor Required DG Capacity = 9268.68 KVA

    For 1150 KW Motor Required DG Capacity= 13322.96 KVA

    Selected Total DG Capacity for 800 KW is 10000 KVA

    1150 KW is 15000 KVA

    Actual Transient Voltage Dip for 800 KW is 14.5%

    Actual Transient Voltage Dip for 1150 KW is 13.5%

    DG Capacity = Starting KVA of Biggest Motor x Transient Reactance ofDG x ( )

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    16/29

    16

    1150 KW and 800 KW motors are connected to 6.6 KV Bus fed

    from DGs as shown below

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    17/29

    17

    All DGs cannot start simultaneously.

    Motor has to start immediately, for continuous operations.

    Solution for this to start the motor with Auto Transformer Starter

    Auto Transformer Starter

    The motor terminal voltage is not a function of load current andremains constant during the acceleration time

    Due to the turn ratio advantages the primary line current is lessthan the secondary motor currents. A three-coil autotransformer isconnected in a wye configuration and connected to the motor insuch a way as to supply reduced voltage to the motor when the linevoltage is applied to Autotransformer.

    Taps are provided different values of reduced voltage( NEMA standards are 80%,65% and 50% of the full line voltage)

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    18/29

    18

    Advantages:

    For hard to start loads, adjustable starting torque, can be usedwith any standard motors and less strain on the motor.

    Auto Transformer Starter Circuit Diagram

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    19/29

    RELIANCE PATALA GANGA

    IN 1993

    PHASE - III

    19

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    20/29

    20

    LINE DIAGRAMSeries reactor

    The reactor is connected inseries

    with the stator windings.

    The starting current is limited

    by increasing the motorimpedance.

    The torque is reduced, due to the

    voltage drop across the reactor.

    The reactor has to sustain the

    starting current.

    The reactor is bypassed after the

    acceleration period is over.

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    21/29

    21

    Depending on the motor kW rating & application the driveselections should be done

    Before Selecting any motor for application the motor torque curve

    & load torque requirement should be matched

    Soft Starter VFD.

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    22/29

    22

    Soft starterReduced voltage is applied through

    controlled ac chopper.

    Provides improved controllability during

    starting.

    The voltage is ramped up by controlling

    of the solid-state switches.

    The switches are controlled such thatthe current is limited to 3-5p.u.

    The solid-state switches are bypassed

    after the motor reaches the rated speed

    to avoid switching losses.

    U

    M3~

    V W

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    23/29

    23

    Soft Starter Features:A) Control Methods

    Torque Control - Start / Stop RampTorque control, quadratic

    Pump Application Control (Start & Stop)

    Jog Forward & Reverse

    Dynamic vector braking (Dynamic DC-Brake)

    Reverse current braking (Soft brake)

    Zero speed shut off without sensorB) Protection

    Over and Under voltage protection

    Voltage imbalance protection

    Phase reversal protection

    Phase loss protectionThermal overload protection

    Shaft power protection Max and Min

    Limit number of starts per hour

    C) Keypad Display

    D) I/O Interface

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    24/29

    24

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    25/29

    25

    VFD CIRCUIT DIAGRAM

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    26/29

    26

    VFD Working Principle

    Adjustable-speed drives for ac motors, control the frequency andvoltage of the motor to adjust its speed.

    Disadvantages:

    High cost: Not recommended when speed adjustment is not needed.

    Harmonics are injected into the motor. Special motors are required (e.g.

    with forced ventilation, bigger frame sizes, higher insulation levels, ).

    VFDs are nonlinear loads and draw non-sinusoidal currents from the grid.

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    27/29

    27

    Soft starters are usually current or voltage controlled, not

    frequency

    Soft starters do not have the ability to control speed

    Soft starters will have significant price benefits

    Soft starters will have a smaller foot print on larger HP

    application

    Comparison between Soft starter and VFD

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    28/29

    28

    Power Electronics optimize the system performance and

    reliability and Cost

    Reduce the need for large area and equipments.

    Conclusion

  • 8/7/2019 Impact of Power Electronics on Electrical System Design

    29/29

    29