FLORIDA SOLAR ENERGY CENTER Creating Energy Independence Since 1975 A Research Institute of the University of Central Florida Impact of Energy-Efficiency Parameters on Home Humidity Rob Vieira Florida Solar Energy Center

Upload: others

Post on 28-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

FLORIDA SOLAR ENERGY CENTER

Creating Energy Independence Since 1975

A Research Institute of the University of Central Florida

Impact of Energy-Efficiency Parameters on Home Humidity

Rob VieiraFlorida Solar Energy Center

Page 2: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Purpose

Some energy efficiency measures only address sensible loads. As these measures are implemented

Can today’s HVAC equipment maintain acceptable humidity levels?

Are there some key efficiency measures that could improve humidity in homes that implement sensible load reduction strategies?

Page 3: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Terms

Sensible: HeatLatent: Moisture

Page 4: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Presentation Scope

Single-family detached homesMulti-family residences can often have less envelope sensible load due to fewer exposed surfaces but have not been the focus of many research studies – they are not covered in this presentation

Existing studies that focus on humidity levels in homes

Page 5: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Parameters Studied

Efficient Windows (experimental & simulated)Various Efficiency Measures (simulated)Duct Leakage (experimental)HVAC Operations (experimental)HVAC Flow and Fan Operation (experimental) HVAC Time Delay Relay (experimental and simulated)Internal Loads

Page 6: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Progress Energy Funded FSEC Study – 1999

Page 7: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Site #198 – insulated double-pane windows (4 of 170 homes)

Page 8: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Influence of Windows on Heatingand Cooling Energy and Demand

Case Annual Heating Annual Cooling Peak Heating Peak Cooling

Single GlassDouble Glass

1067485

57543318

2.601.85

2.932.77

Note: Homes with all double glass: sites 23, 32, 110 and 198.There were 166 homes in the single glass sample.

Page 9: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Influence of insulated glass for windows on peak winter day heating – Jan. 5, 1999

Time of Day: January 5, 19990 2 4 6 8 10 12 14 16 18 20 22 24

Avg.

Hea

ting

Elec

tric

Load

(kW

)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

Homes with Single Glass (n= 147)Homes with Double Glass (n= 4)

Peak Period

Page 10: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Peak summer day air conditioning demand profile – August 30, 1999

Hour of Day (EST)2 4 6 8 10 12 14 16 18 20 22 24

Ave

rage

Spa

ce C

oolin

g kW

0.0

0.5

1.0

1.5

2.0

2.5

3.0

Double Paned (n=4):30.56 kWhSingle Paned (n=147): 43.84 kWh

PeakPeriod

Page 11: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

High Performance Windows High Performance Windows ––Mercedes Home StudyMercedes Home Study

Monitoring can answer direct and indirect questionsWhat will they save?

EnergyPeak demand

How will it impact interior humidity?

Page 12: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Base and Improved Window SpecsMercedes Homes Research Project

Solar Heat Gain Coefficient

Winter Night U-Factor

Standard Single Pane Aluminum Windows

0.77 1.23

High Performance Windows -Spectrally Selective, Thermally broken

0.36 0.47

Page 13: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

West facing window in the two test homes during a hot afternoon

Page 14: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Comparative space cooling demand profile of two test homes over the hot 17-day period in Sept.

Hour of Day (EST)2 4 6 8 10 12 14 16 18 20 22 24

Ave

rage

Spa

ce C

oolin

g kW

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

Standard Home: Single Glass Total= 36.5 kWhImproved Home: Hi-Perf Glass Total = 31.1 kWh

PeakPeriod

Page 15: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Comparative space heat demand profile on January 28, 2000. Morning low temperature was 43ºF

Time of Day: January 28, 20000 2 4 6 8 10 12 14 16 18 20 22 24

Hea

ting

Elec

tric

Dem

and

(kW

)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

Standard Home (Single Glass) Total = 80.1 kWhImproved Home Hi-Perf Glass Total = 51.0 kWh

Peak Period

Page 16: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Annual Interior Temp & RHAnnual Interior Temp & RH

ExperimentalControl

Page 17: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Annual Interior Temp & RHAnnual Interior Temp & RH

Control, Single Glass: Avg Temp= 76.0 F, RH= 50.7%

Solar Control Glass: Avg Temp= 75.5 F, RH= 52.1%

Page 18: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Simulated Impact of Solar Control Windows

75 F set point in summer72 F set point winterNo change in AC sizeAnnual average relative humidity

41.6% Single Glass43.7% Solar Control Glass2% increase in interior RHSimilar to empirical study

Page 19: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Simulated AC demand on peak cooling day

Hour of Day (EST)

2 4 6 8 10 12 14 16 18 20 22 24

Spac

e C

oolin

g El

ectr

ic D

eman

d (k

W)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

0

Std Home (Single Glass): Total= 45.3 kWhImproved Home (Hi-Perf Glass): Total= 38.8 kWh

PeakPeriod

Page 20: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Simulated impact of generic high performance solar control window on peak heating day for Tampa Dec. 18th

Time of Day: December 18th Tampa TMY22 4 6 8 10 12 14 16 18 20 22 24

Hea

ting

Elec

tric

Load

(kW

)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

Y A

xis

3

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

Std Home (Single Glass) Total= 42.1 kWhImproved (Hi-Perf Glass): Total = 35.8 kWh

Peak Period

Aux. Strip Heat

Page 21: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Parameters Studied

Efficient Windows (experimental & simulated)Various Efficiency Measures (simulated)Duct Leakage (experimental)HVAC Operations (experimental)HVAC Flow and Fan Operation (experimental) HVAC Time Delay Relay (experimental and simulated)Internal Loads

Page 22: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Efficiency Measures vs. RH for Simulated Tampa Home

Case CoolingkWh HeatingkWh Avg RH%Standard Building: 5958 585 48.4%

Low-E solar windows 4213 292 51.3%

White Roof 5186 595 49.3%

100% CFL Lighting 5602 625 48.7%

Reduce Infiltration 5517 481 46.1%

FSEC EnergyGauge USA analysis, 2007

Page 23: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Parameters Studied

Efficient Windows (experimental & simulated)Various Efficiency Measures (simulated)Duct Leakage (experimental)HVAC Operations (experimental)HVAC Flow and Fan Operation (experimental) HVAC Time Delay Relay (experimental and simulated)Internal Loads

Page 24: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Impact of Duct Leakage –FSEC lab experiment

40

45

50

55

60

65

70

Rel

ativ

e H

umid

ity (%

)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Hour of Day

No Leak 0%RL, 30% SL

Relative Humidity in Roomwith duct leakage in vented attic

FSEC LabAttic with steel

joists, good connection to conditioned space

Page 25: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Attic Dew Point

Outside

Typical attic

Page 26: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Parameters Studied

Efficient Windows (experimental & simulated)Various Efficiency Measures (simulated)Duct Leakage (experimental)HVAC Operations (experimental)HVAC Flow and Fan Operation (experimental) HVAC Time Delay Relay (experimental and simulated)Internal Loads

Page 27: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Cooling Equipment

Rated sensible heat ratio (SHR) is about 75%Latent heat ratio (LHR) is about 25%However, LHR increases

With higher room humidityWith lower system air flow rates

Page 28: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Measured SHR as a Function of Room Dew Point Temperature

Room temperature held constant at 78F.

Page 29: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

RH Maintained Even with Mechanical Ventilation

Automatic simulation of sensible and latent occupancy loads. 6 ventilation strategies Cooling set point 75F, A/C adequate to maintain RH below 60% for all strategies examined.

Presented paper: "Assessing Six Residential Ventilation Techniques in Hot and Humid Climates," Proceedings of ACEEE 2004 Summer Study on Energy Efficiency in Buildings, Washington, DC, August 2004. .

Strategies

No mechanical ventilation

Spot ventilation

Outside air

OA - 10/20 cycle - Dehumidification

OA - 10/20 cycle

Energy recovery ventilator

OA - Humidistat

Hourly profiles

#4 #6

Case 4 uses ~15% more energy than case 6

RH out

RH in

Page 30: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

SEER and latent removal are independent at steady state

“We conclude that the latent removal of small unitary equipment is not a function of efficiency.

Furthermore, the latent removal characteristics of this type of equipment have not changed significantly over time…”

David Godwin, “Latent Capacity of Unitary Equipment,” ASHRAE TO-98-9-2

Page 31: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Parameters Studied

Efficient Windows (experimental & simulated)Various Efficiency Measures (simulated)Duct Leakage (experimental)HVAC Operations (experimental)HVAC Flow and Fan Operation (experimental)HVAC Time Delay Relay (experimental and simulated)Internal Loads

Page 32: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Optimization of Latent vs Sensible Cooling

During hot and humid weather, there is a sensible cooling load and a latent cooling load.

A high air flow rate will produce the highest sensible cooling efficiency.A lower air flow rate will produce the highest latent cooling efficiency.

Page 33: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Impact of Air Flow

Evaporator Air Flow (cfm/ton)100 150 200 250 300 350 400 450

Per

form

ance

(%)

40

50

60

70

80

90

100

110

120

Total Capacity: 100%= 27272 Btu/hSensible Capacity: 100%= 18081 Btu/h Latent Capacity: 100% = 9192 Btu/h

Source: FSEC Lab Tests

Page 34: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Field Data: Latent Performance Fan “Auto” vs. “On”

Sweetser - Downstairs AC Unit

0.0 0.2 0.4 0.6 0.8 1.0Runtime Fraction

0.8

1.0

Sen

sibl

e H

eat R

atio

(-)

Steady State SHR = 0.855

Auto Fan ModeConstant Fan Mode (08/18/02 to 09/04/02)

(Model: twet=15 min, gamma=2.2, Nmax=3)

Page 35: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

FSEC Data – Continuous Fan

0.35

0.21

Zero Line

(Khattar)

Page 36: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Parameters Studied

Efficient Windows (experimental & simulated)Various Efficiency Measures (simulated)Duct Leakage (experimental)HVAC Operations (experimental)HVAC Flow and Fan Operation (experimental) HVAC Time Delay Relay (experimental and simulated)Internal Loads

Page 37: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Time Delay – Lab ResultsWet-coil: 80F air inlet, 60.4F dew point

Fan Operation

Gross EER (Btu/Wh)

Net EER considers fan heat and power(Btu/Wh)

Auto, no overrun

11.15 9.47

90 second overrun

11.09 (-1%) 9.10(-4%)

Page 38: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Time Delay Relay -simulated

Indoor Humidity - AUTO Fan vs 90-sec Overrun

0

200

400

600

800

1000

1200

1400

1600

1800

40 50 60 70 80

Relative Humidity (%)

Freq

uenc

y (h

rs)

90-sec. TDRAUTO

Miami with 75°F cooling setpoint, ASHRAE 62.2-2004 continuous vent.

RH > 60%AUTO: 1,583 hrs90sec TDR: 2,854 hrs

Notes: Mechanical ventilation simulated into space not coil. Used TRN-ResDH, a TRNSYS-based hour-by-hour building energy simulation tool

Shirey, D.B., H.I. Henderson and R.A. Raustad. 2006. Understanding the Dehumidification Performance of Air-Conditioning Equipment

at Part-Load Conditions. Final Report, FSEC-CR-1537-05

Page 39: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Parameters Studied

Efficient Windows (experimental & simulated)Various Efficiency Measures (simulated)Duct Leakage (experimental)HVAC Operations (experimental)HVAC Flow and Fan Operation (experimental) HVAC Time Delay Relay (experimental and simulated)Internal Loads

Page 40: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Growth in Consumer Electronics Will Increase Sensible Heat Load

EIA projects electricity consumption to grow 3.5 percent annually for color TVs and computer equipment through 2025, to more than double the level of consumption in 2003.

Page 41: Impact of Energy-Efficiency Parameters on Home Humidity...Double Glass 1067 485 5754 3318 2.60 1.85 2.93 2.77 ... Final Report, FSEC-CR-1537-05 . Parameters Studied ... effect on ability

Conclusions

More efficient windows or other envelope measures can reduce sensible loads and save energy, with slight increases in RH in typical single-family homes Duct leakage, time delay relay and fan speed settings of HVAC equipment can have moderate to large effect on ability of equipment to remove moisture Fan set to continuous “on” mode greatly reduces moisture removalPlug loads (sensible heat) are increasing and may counter some reductions in sensible heat from envelope improvements