Immersion cooling and power
POWERBOXMastering Power
Patrick Le Fèvre – 2019-12-06 – Rev 1.0.0
![Page 2: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/2.jpg)
POWERBOX Mastering Power
POWERBOXHow does immersion cooling work?
2
→ Immersion cooling involves putting electronics directly in a non-conductive fluid, allowing heat to be transferred directly from components into the heat transfer fluid
→ In traditional cooling systems, heat must transfer through several levels of thermal interface materials, air, heat exchangers and working fluids
→ Immersion cooling simplifies thermal design and increases heat transfer efficiency
![Page 3: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/3.jpg)
POWERBOX Mastering Power
POWERBOXTwo-phases immersion cooling
3
→ Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling and condensation of the engineered fluids. This simple approach features almost no moving parts.
→ Electronic components are submerged in a non-conductive liquid bath in an accessible, sealed enclosure
→ The generated heat boils fluid into a gaseous state and it rises to the top of the enclosure
→ The gas condenses on the lid or a condensation coil and rains back into the bath to repeat the cycle
→ Heat transfer efficiencies can exceed boiling water in a material that can safely come in direct contact with electronics
![Page 4: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/4.jpg)
POWERBOX Mastering Power
POWERBOXSingle-phase immersion cooling
4
→ In single-phase immersion cooling the fluid has a higher boiling point and remains in its liquid phase throughout the process.
→ Electronic components are submerged in a non-conductive liquid bath in an accessible, sealed enclosure
→ The heat from the chip is transferred to the fluid
→ Pumps are often used to flow the heated fluid to a heat exchanger, where it is cooled and cycled back into the bath
![Page 5: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/5.jpg)
POWERBOX Mastering Power
POWERBOXAdvantages over conventional air cooling
5
→ Higher efficiency and energy savings (>90% electricity savings)
→ Reduced capital and operational expenses→ Improved performance→ Higher density→ Improved hardware reliability→ Faster time to market→ Fits any form, size or shape of electronics
components and boards→ Non-flammable, inherent fire protection→ Works in confined spaces and extreme
environments (hot & humid etc.).→ Reduced environmental impact
Source 3M and Allied Control
![Page 6: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/6.jpg)
POWERBOX Mastering Power
POWERBOXAdvantages over conventional air cooling
6
→ Silent OperationNo fans anymore required to cool servers and rooms reducing noise and maintenance cost
→ Electro Chemical MigrationImmersing servers into dielectric fluid dissipates any risk with ECM
→ Tin & Zinc WhiskersIn case of whisker formation they will be rapidly removed, limiting growth and filtered in the circulation system
→ Stable and constant thermal environment:As the cooling fluid is constantly pumped and heat is quickly extracted from any hot components, IT hardware components are exposed to less stress and less temperature fluctuations.Source Submer
![Page 7: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/7.jpg)
POWERBOX Mastering Power
POWERBOXPower to immersed applications
7
→ Main datacentersDatacenters and high capacity routers are usually powered by a 48V DC bus and voltage stepdown to local payload. Main power supplies and usually not immersed, only POL on the board are in contact with the liquid
→ Sub-serversSub-servers are using highly integrated architecture and power supply immersed. In many case the power supply is molded and a copper plate use to conduct the heat to liquid
→ Industrial embedded serversThis third category is the one using open frame power supply immersed and requiring specific attention during the design
![Page 8: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/8.jpg)
POWERBOX Mastering Power
POWERBOXWhat to consider?
8
→ The type of cooling solution will influence the design rules for the power supply and the type of components to use
→ Cooling fluids have higher dielectrics than air though creepage distance should be considered with attention
→ All immersed boards must be cleaned with high attention to avoid contamination
→ Labels and other glued parts must be qualified for the specific fluid to sustain on place during operation
→ Board layout optimized to facilitate liquid circulation
Source 3M and Sahithi Reddy Nagilla thesis
![Page 9: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/9.jpg)
POWERBOX Mastering Power
POWERBOXDesign process
9
→ Cooling agent evaluation in regards to metal compatibility (e.g. certain cooling agent increasing electro migration between copper and aluminum)
→ Location of the power supply within the system, defining layout and shape
→ Creepage distances evaluation→ Components selection to privilege efficient
cooling and immersed technology compatibility (e.g. electrolytic capacitors reaction to permanent immersion)
→ Cleaning process compliant with the cooling agent
![Page 10: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/10.jpg)
POWERBOX Mastering Power
POWERBOXOur capabilities
10
→ Designing power solutions for demanding applications since 1974
→ More than 3500 custom design power solutions delivered to market
→ Deep knowledge in powering Marine and sub-sea applications and dealing with similar requirements as for immersed computer
→ Part of Nordic research network, including university involved in energy efficiency and new technologies
→ International presence and video-conferencing system connecting our experts with customers all around the world
![Page 11: Immersion cooling and power · 2020-05-11 · Two-phases immersion cooling 3 → Two-phases passive immersion cooling exponentially increases heat transfer efficiency from boiling](https://reader035.vdocuments.site/reader035/viewer/2022081222/5f7bfc1dfcaa3d51062fce14/html5/thumbnails/11.jpg)
POWERBOXMastering Power