imax xtra e. - storage.googleapis.com · all dimensions in mm the following minimum clearances must...

12
IMAX XTRA E. 80kW MODULAR / CONDENSING The Imax Xtra range of condensing boilers is offered in ten models with outputs from 80 to 560 kW suitable for floor standing application in either single or multiple applications. • Robust cast aluminium silicon alloy heat exchanger • In-built commissioning and fault diagnostics • Volt free contacts and BMS operation standard • Meets Building Regulations (Part L2) • Compact size – small footprint • Fits through standard doorways • Conventional or room sealed flue options • Direct weather compensation option • NOx <40mg/kWh (Class 5) • 2 year parts and labour warranty • High 5:1 turndown • Up to 107.5% nett efficiency (fully condensing) IDEAL COMMERCIAL BOILERS PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN T: 0844 5436060 F: 0844 5436181 E: [email protected] IDEALCOMMERCIALBOILERS.COM DIMENSIONS AND CLEARANCES All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 150mm 500mm REAR 700mm FRONT 600mm For full details of all configurations & specifications, please refer to the Imax Xtra sales brochure. BOILER DIM A DIM B DIM C 80kW 600 1150 796 FEATURES AND BENEFITS L SIDE 450mm

Upload: others

Post on 07-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

IMAX XTRA E.80kWMODULAR / CONDENSING

The Imax Xtra range of condensing boilers is offered in ten models with outputs from 80 to 560 kW suitable for floor standing application in either single or multiple applications.

• Robust cast aluminium silicon alloy heat exchanger

• In-built commissioning and fault diagnostics

• Volt free contacts and BMS operation standard

• Meets Building Regulations (Part L2)

• Compact size – small footprint

• Fits through standard doorways

• Conventional or room sealed

flue options

• Direct weather compensation option

• NOx <40mg/kWh (Class 5)

• 2 year parts and labour warranty

• High 5:1 turndown

• Up to 107.5% nett efficiency

(fully condensing)

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

All dimensions in mm

The following minimum clearances must be maintained for operation and servicing:

TOP R SIDE150mm500mm

REAR700mm

FRONT600mm

For full details of all configurations & specifications, please refer to the Imax Xtra sales brochure.

BOILER DIM A DIM B DIM C

80kW 600 1150 796

FEATURES AND BENEFITS

L SIDE450mm

Page 2: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

TECHNICAL SPECIFICATIONS.

FLUE/AIR INLET

Flue Size mm 150

Flue Gas Volume m³/h 121.0

Flue Gas Temperature 80/60 °C 80

Max Flue Resistance Pa 100

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.2

Power Consumption watt 250

Modulating Input V/dc 0-10V

Fuse Rating amp 3

Controls Voltage V 24 or 240

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm No

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Modulating Sequencer Control for controlling multiple boiler installations Yes

Programmable Room Thermostat Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Sequencer DHW Sensor Kit Yes

Flow, Return and Gas Header Kit n/a

RS Air Duct Connector n/a

Horizontal Flue Connector n/a

Vertical Flue Connector n/a

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

IMAX XTRA 80kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*2 year warranty subject to Terms and Conditions. 2 year parts and labour warranty available when registered within 30 days of installation.

GENERAL

Dry Weight KG 132

Boiler Dimensions mm 1150 (H) x 600 (W) x 796 (D)

Boiler Clearances mm Front: 600 Left Side: 450 Right Side: 150 Rear: 700 Top: 500

Seasonal Efficiency % 95.7

Min/Max Gas pressure (Nat Gas) mbar 15 - 21

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 8.1

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 23.3 – 78.6

Boiler Output (Mean 40°C) kW 25.8 – 82.2

Boiler Input (Gross cv) kW 88.8

Gas Inlet Size G¾”

NOx Rating/emissions at 0% O mg/kWh Class 5 (26)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 264

Hydraulic Resistance (20°C ∆T) mbar 80

Nominal Flow Rate (11°C ∆T) l/s 1.78

Nominal Flow Rate (20°C ∆T) l/s 0.98

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.196

Min Flow Temperature °C 20

Max Flow Temperature °C 90

Min Working Pressure bar 0.3

Max Working Pressure bar 6

Max Static Head Of Water metres 61

Condensate Connection mm 21.5

High Limit Set Point °C 100 flow, 100 return

105 H/Ex

Flow & Return Size G2”

Water Content litres 11.0

FLOOR STANDING NOx CLASS 5 BIM

211167

Page 3: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

120kWMODULAR / CONDENSING

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Imax Xtra sales brochure.

IMAX XTRA E.

The Imax Xtra range of condensing boilers is offered in ten models with outputs from 80 to 560 kW suitable for floor standing application in either single or multiple applications.

• Robust cast aluminium silicon alloy heat exchanger

• In-built commissioning and fault diagnostics

• Volt free contacts and BMS operation standard

• Meets Building Regulations (Part L2)

• Compact size – small footprint

• Fits through standard doorways

• Conventional or room sealed

flue options

• Direct weather compensation option

• NOx <40mg/kWh (Class 5)

• 2 year parts and labour warranty

• High 5:1 turndown

• Up to 107.5% nett efficiency

(fully condensing)

All dimensions in mm

TOP R SIDE150mm500mm

REAR700mm

FRONT600mm

BOILER DIM A DIM B DIM C

120kW 600 1150 796

FEATURES AND BENEFITS

L SIDE450mm

Page 4: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

TECHNICAL SPECIFICATIONS.

FLUE/AIR INLET

Flue Size mm 150

Flue Gas Volume m³/h 182.0

Flue Gas Temperature 80/60 °C 80

Max Flue Resistance Pa 100

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.2

Power Consumption watt 250

Modulating Input V/dc 0-10V

Fuse Rating amp 3

Controls Voltage V 24 or 240

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm No

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Modulating Sequencer Control for controlling multiple boiler installations Yes

Programmable Room Thermostat Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Sequencer DHW Sensor Kit Yes

Flow, Return and Gas Header Kit n/a

RS Air Duct Connector n/a

Horizontal Flue Connector n/a

Vertical Flue Connector n/a

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

IMAX XTRA 120kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*2 year warranty subject to Terms and Conditions. 2 year parts and labour warranty available when registered within 30 days of installation.

GENERAL

Dry Weight KG 150

Boiler Dimensions mm 1150 (H) x 600 (W) x 796 (D)

Boiler Clearances mm Front: 600 Left Side: 450 Right Side: 150 Rear: 700 Top: 500

Seasonal Efficiency % 95.7

Min/Max Gas pressure (Nat Gas) mbar 15 - 20

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 12.1

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 23.3 – 118

Boiler Output (Mean 40°C) kW 25.8 – 123.4

Boiler Input (Gross cv) kW 133.3

Gas Inlet Size G1”

NOx Rating/emissions at 0% O mg/kWh Class 5 (26)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 281

Hydraulic Resistance (20°C ∆T) mbar 85

Nominal Flow Rate (11°C ∆T) l/s 2.68

Nominal Flow Rate (20°C ∆T) l/s 1.47

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.294

Min Flow Temperature °C 20

Max Flow Temperature °C 90

Min Working Pressure bar 0.3

Max Working Pressure bar 6

Max Static Head Of Water metres 61

Condensate Connection mm 21.5

High Limit Set Point °C 100 flow, 100 return

105 H/Ex

Flow & Return Size G2”

Water Content litres 14.3

FLOOR STANDING NOx CLASS 5 BIM

211168

Page 5: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

160kWMODULAR / CONDENSING

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Imax Xtra sales brochure.

IMAX XTRA E.

The Imax Xtra range of condensing boilers is offered in ten models with outputs from 80 to 560 kW suitable for floor standing application in either single or multiple applications.

• Robust cast aluminium silicon alloy heat exchanger

• In-built commissioning and fault diagnostics

• Volt free contacts and BMS operation standard

• Meets Building Regulations (Part L2)

• Compact size – small footprint

• Fits through standard doorways

• Conventional or room sealed

flue options

• Direct weather compensation option

• NOx <40mg/kWh (Class 5)

• 2 year parts and labour warranty

• High 5:1 turndown

• Up to 107.5% nett efficiency

(fully condensing)

All dimensions in mm

TOP R SIDE150mm500mm

REAR700mm

FRONT600mm

BOILER DIM A DIM B DIM C

160kW 600 1150 796

FEATURES AND BENEFITS

L SIDE450mm

Page 6: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

TECHNICAL SPECIFICATIONS.

FLUE/AIR INLET

Flue Size mm 150

Flue Gas Volume m³/h 242.0

Flue Gas Temperature 80/60 °C 80

Max Flue Resistance Pa 150

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.95

Power Consumption watt 400

Modulating Input V/dc 0-10V

Fuse Rating amp 5

Controls Voltage V 24 or 240

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm No

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Modulating Sequencer Control for controlling multiple boiler installations Yes

Programmable Room Thermostat Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Sequencer DHW Sensor Kit Yes

Flow, Return and Gas Header Kit n/a

RS Air Duct Connector n/a

Horizontal Flue Connector n/a

Vertical Flue Connector n/a

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

IMAX XTRA 160kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*2 year warranty subject to Terms and Conditions. 2 year parts and labour warranty available when registered within 30 days of installation.

GENERAL

Dry Weight KG 168

Boiler Dimensions mm 1150 (H) x 600 (W) x 796 (D)

Boiler Clearances mm Front: 600 Left Side: 450 Right Side: 150 Rear: 700 Top: 500

Seasonal Efficiency % 95.7

Min/Max Gas pressure (Nat Gas) mbar 15 - 20

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 16.1

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 29.1 – 157.3

Boiler Output (Mean 40°C) kW 32.3 – 164.5

Boiler Input (Gross cv) kW 177.7

Gas Inlet Size G1”

NOx Rating/emissions at 0% O mg/kWh Class 5 (35)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 297

Hydraulic Resistance (20°C ∆T) mbar 90

Nominal Flow Rate (11°C ∆T) l/s 3.57

Nominal Flow Rate (20°C ∆T) l/s 1.96

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.392

Min Flow Temperature °C 20

Max Flow Temperature °C 90

Min Working Pressure bar 0.3

Max Working Pressure bar 6

Max Static Head Of Water metres 61

Condensate Connection mm 21.5

High Limit Set Point °C 100 flow, 100 return

105 H/Ex

Flow & Return Size G2”

Water Content litres 17.5

FLOOR STANDING NOx CLASS 5 BIM

211169

Page 7: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

200kWMODULAR / CONDENSING

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Imax Xtra sales brochure.

IMAX XTRA E.

The Imax Xtra range of condensing boilers is offered in ten models with outputs from 80 to 560 kW suitable for floor standing application in either single or multiple applications.

• Robust cast aluminium silicon alloy heat exchanger

• In-built commissioning and fault diagnostics

• Volt free contacts and BMS operation standard

• Meets Building Regulations (Part L2)

• Compact size – small footprint

• Fits through standard doorways

• Conventional or room sealed

flue options

• Direct weather compensation option

• NOx <40mg/kWh (Class 5)

• 2 year parts and labour warranty

• High 5:1 turndown

• Up to 107.5% nett efficiency

(fully condensing)

All dimensions in mm

TOP R SIDE150mm500mm

REAR700mm

FRONT600mm

BOILER DIM A DIM B DIM C

200kW 600 1150 1048

FEATURES AND BENEFITS

L SIDE450mm

Page 8: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

TECHNICAL SPECIFICATIONS.

FLUE/AIR INLET

Flue Size mm 200

Flue Gas Volume m³/h 302.0

Flue Gas Temperature 80/60 °C 80

Max Flue Resistance Pa 150

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.95

Power Consumption watt 400

Modulating Input V/dc 0-10V

Fuse Rating amp 5

Controls Voltage V 24 or 240

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm No

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Modulating Sequencer Control for controlling multiple boiler installations Yes

Programmable Room Thermostat Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Sequencer DHW Sensor Kit Yes

Flow, Return and Gas Header Kit n/a

RS Air Duct Connector n/a

Horizontal Flue Connector n/a

Vertical Flue Connector n/a

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

IMAX XTRA 200kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*2 year warranty subject to Terms and Conditions. 2 year parts and labour warranty available when registered within 30 days of installation.

GENERAL

Dry Weight KG 198

Boiler Dimensions mm 1150 (H) x 600 (W) x 1048 (D)

Boiler Clearances mm Front: 600 Left Side: 450 Right Side: 150 Rear: 700 Top: 500

Seasonal Efficiency % 95.7

Min/Max Gas pressure (Nat Gas) mbar 15 - 20

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 20.1

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 43.1 – 196.6

Boiler Output (Mean 40°C) kW 47.3 – 207.8

Boiler Input (Gross cv) kW 221.1

Gas Inlet Size G1”

NOx Rating/emissions at 0% O mg/kWh Class 5 (26)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 314

Hydraulic Resistance (20°C ∆T) mbar 95

Nominal Flow Rate (11°C ∆T) l/s 4.51

Nominal Flow Rate (20°C ∆T) l/s 2.48

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.496

Min Flow Temperature °C 20

Max Flow Temperature °C 90

Min Working Pressure bar 0.3

Max Working Pressure bar 6

Max Static Head Of Water metres 61

Condensate Connection mm 21.5

High Limit Set Point °C 100 flow, 100 return

105 H/Ex

Flow & Return Size G2”

Water Content litres 18.4

FLOOR STANDING NOx CLASS 5 BIM

211170

Page 9: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

240kWMODULAR / CONDENSING

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Imax Xtra sales brochure.

BOILER DIM A DIM B DIM C

240kW 600 1150 1048

IMAX XTRA E.

The Imax Xtra range of condensing boilers is offered in ten models with outputs from 80 to 560 kW suitable for floor standing application in either single or multiple applications.

• Robust cast aluminium silicon alloy heat exchanger

• In-built commissioning and fault diagnostics

• Volt free contacts and BMS operation standard

• Meets Building Regulations (Part L2)

• Compact size – small footprint

• Fits through standard doorways

• Conventional or room sealed

flue options

• Direct weather compensation option

• NOx <40mg/kWh (Class 5)

• 2 year parts and labour warranty

• High 5:1 turndown

• Up to 107.5% nett efficiency

(fully condensing)

All dimensions in mm

TOP R SIDE150mm500mm

REAR700mm

FRONT600mm

FEATURES AND BENEFITS

L SIDE450mm

Page 10: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

TECHNICAL SPECIFICATIONS.

FLUE/AIR INLET

Flue Size mm 200

Flue Gas Volume m³/h 363.0

Flue Gas Temperature 80/60 °C 80

Max Flue Resistance Pa 150

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.95

Power Consumption watt 400

Modulating Input V/dc 0-10V

Fuse Rating amp 5

Controls Voltage V 24 or 240

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm No

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Modulating Sequencer Control for controlling multiple boiler installations Yes

Programmable Room Thermostat Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Sequencer DHW Sensor Kit Yes

Flow, Return and Gas Header Kit n/a

RS Air Duct Connector n/a

Horizontal Flue Connector n/a

Vertical Flue Connector n/a

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

IMAX XTRA 240kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*2 year warranty subject to Terms and Conditions. 2 year parts and labour warranty available when registered within 30 days of installation.

GENERAL

Dry Weight KG 215

Boiler Dimensions mm 1150 (H) x 600 (W) x 1048 (D)

Boiler Clearances mm Front: 600 Left Side: 450 Right Side: 150 Rear: 700 Top: 500

Seasonal Efficiency % 95.7

Min/Max Gas pressure (Nat Gas) mbar 15 - 20

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 24.2

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 47.0 – 235.9

Boiler Output (Mean 40°C) kW 56.1 – 249.4

Boiler Input (Gross cv) kW 266.5

Gas Inlet Size G1”

NOx Rating/emissions at 0% O mg/kWh Class 5 (26)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 330

Hydraulic Resistance (20°C ∆T) mbar 100

Nominal Flow Rate (11°C ∆T) l/s 5.42

Nominal Flow Rate (20°C ∆T) l/s 2.98

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.596

Min Flow Temperature °C 20

Max Flow Temperature °C 90

Min Working Pressure bar 0.3

Max Working Pressure bar 6

Max Static Head Of Water metres 61

Condensate Connection mm 21.5

High Limit Set Point °C 100 flow, 100 return

105 H/Ex

Flow & Return Size G2”

Water Content litres 24.0

FLOOR STANDING NOx CLASS 5 BIM

211171

Page 11: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

280kWMODULAR / CONDENSING

IDEAL COMMERCIAL BOILERS

PO Box 103, National Avenue Kingston upon Hull, East Yorkshire, HU5 4JN

T: 0844 5436060F: 0844 5436181E: [email protected]

IDEALCOMMERCIALBOILERS.COM

DIMENSIONS AND CLEARANCES

All dimensions in mm

The following minimum clearances must be maintained for operation and servicing:

For full details of all configurations & specifications, please refer to the Imax Xtra sales brochure.

BOILER DIM A DIM B DIM C

280kW 600 1150 1048

IMAX XTRA E.

The Imax Xtra range of condensing boilers is offered in ten models with outputs from 80 to 560 kW suitable for floor standing application in either single or multiple applications.

• Robust cast aluminium silicon alloy heat exchanger

• In-built commissioning and fault diagnostics

• Volt free contacts and BMS operation standard

• Meets Building Regulations (Part L2)

• Compact size – small footprint

• Fits through standard doorways

• Conventional or room sealed

flue options

• Direct weather compensation option

• NOx <40mg/kWh (Class 5)

• 2 year parts and labour warranty

• High 5:1 turndown

• Up to 107.5% nett efficiency

(fully condensing)

All dimensions in mm

TOP R SIDE150mm500mm

REAR700mm

FRONT600mm

FEATURES AND BENEFITS

L SIDE450mm

Page 12: IMAX XTRA E. - storage.googleapis.com · All dimensions in mm The following minimum clearances must be maintained for operation and servicing: TOP R SIDE 500mm 150mm REAR 700mm FRONT

TECHNICAL SPECIFICATIONS.

FLUE/AIR INLET

Flue Size mm 200

Flue Gas Volume m³/h 423.0

Flue Gas Temperature 80/60 °C 80

Max Flue Resistance Pa 150

ELECTRICAL

Electrical Supply 230/240V 50Hz 1 Ph

Current (Max No Pump) amp 1.95

Power Consumption watt 400

Modulating Input V/dc 0-10V

Fuse Rating amp 5

Controls Voltage V 24 or 240

Insulation Class IP IP20

CONTROL OPERATION

On/Off 0-10V DC Yes

OpenTherm No

High Limit Protection Yes

Low Water Protection Yes

Volt Free Common Alarm Yes

Boiler Run Indication Yes

OPTIONAL EXTRAS

Modulating Sequencer Control for controlling multiple boiler installations Yes

Programmable Room Thermostat Yes

Outside Sensor Kit Yes

Tank Sensor Kit Yes

Room Sensor Kit Yes

Sequencer DHW Sensor Kit Yes

Flow, Return and Gas Header Kit n/a

RS Air Duct Connector n/a

Horizontal Flue Connector n/a

Vertical Flue Connector n/a

Please note that the above information is correct at time of publication. Ideal Commercial Heating Limited has a policy of continuous development and therefore reserves the right to alter specifications without prior notification.

IMAX XTRA 280kW

W: IDEALCOMMERCIALBOILERS.COM E: [email protected]: 0844 5436060

GET A QUOTE.

*2 year warranty subject to Terms and Conditions. 2 year parts and labour warranty available when registered within 30 days of installation.

GENERAL

Dry Weight KG 233

Boiler Dimensions mm 1150 (H) x 600 (W) x 1048 (D)

Boiler Clearances mm Front: 600 Left Side: 450 Right Side: 150 Rear: 700 Top: 500

Seasonal Efficiency % 95.7

Min/Max Gas pressure (Nat Gas) mbar 15 - 20

BURNER PRE MIX

Fuel (Type G20) Natural Gas

Fuel Consumption (Nat Gas) m³/h 28.2

Flame Protection Ionisation

Ignition Spark

Boiler Output (Mean 70°C) kW 51.0 – 275.2

Boiler Output (Mean 40°C) kW 55.9 – 290.9

Boiler Input (Gross cv) kW 310.9

Gas Inlet Size G1”

NOx Rating/emissions at 0% O mg/kWh Class 5 (26)

HYDRAULICS

Hydraulic Resistance (11°C ∆T) mbar 347

Hydraulic Resistance (20°C ∆T) mbar 105

Nominal Flow Rate (11°C ∆T) l/s 6.32

Nominal Flow Rate (20°C ∆T) l/s 3.47

Min Flow Rate (20°C ∆T) (MAX MOD) l/s 0.694

Min Flow Temperature °C 20

Max Flow Temperature °C 90

Min Working Pressure bar 0.3

Max Working Pressure bar 6

Max Static Head Of Water metres 61

Condensate Connection mm 21.5

High Limit Set Point °C 100 flow, 100 return

105 H/Ex

Flow & Return Size G2”

Water Content litres 27.2

FLOOR STANDING NOx CLASS 5 BIM

211172