New Features of IL-AMF25-Timer-1.1 Page 1 of 1
InteliLite AMF25-Timer-1.1 – New features / ©ComAp – February 2007 / IL-AMF25-Timer-1.1 New
features.pdf
ComAp, spol. s r.o.Svetova 7180 00 Praha 8Czech Republic
ISO 9001 Certified
C o m Ap s .r .o
.
Q u a l i t y
M a n a g e m e
n t
Tel.: +420 2 66790611Fax: +420 2 66316647E-mail: [email protected]
Internet: http://www.comap.cz
1. Available firmware, archives and documentation
Firmware
Mhx file
IL-AMF25-Timer-1.1.mhx Arch ives
Archive
IL-AMF25-Timer-1.1.ail
Documentation
PDF files Descript ion
IL-AMF-2.5.pdf IL-AMF User Guide
2. Main changes in IL-AMF25-Timer-1.1
New features
Internal timer for TEST mode
New function was added to the controller. It is timer which allows to test gen-set function with the definedperiod. Controller is behaving according to TEST mode description in the manual (see IL-AMF-2.5.pdf) whenthe TEST duty is active.
Two parameters related to the new function were added:Test period – Period of the test repetitionRange: 0-240 days
Step: 1 day
Test duration – Duration of the Test mode duty (starts after expiration of the Test period)Range: 0-240 minutesStep: 1 minute
If both parameters (Test period and Test duration) are set to zero, the timer is disabled.If a controller is switched off, the timer is reset and new counting starts after switching the controller on. Ifthe engine is started, the timer is reset, too. Automatic Test may be carried out only if the controller is in AUT mode. If the Test period time elapses andthe controller is in OFF or MAN mode, controller waits for switching over to AUT mode and starts automatictest then.