ieee powertech uni
TRANSCRIPT
-
8/12/2019 Ieee Powertech Uni
1/66
Tutorial on theProtection ofSynchronousGenerators
By: Hugo Davila, P.Eng
IEEE- PES
-
8/12/2019 Ieee Powertech Uni
2/66
Sponsored by Power System Relaying Committee (PSRC)
Power Engineering Education Committee
-
8/12/2019 Ieee Powertech Uni
3/66
Why This Tutorial WasUndertaken
Surveys indicate little understanding of the subject
Older generators not being upgraded to C37Guidelines
New protection concepts not being implemented
-
8/12/2019 Ieee Powertech Uni
4/66
Response of PSRC Update C37 Guidelines
Prepare this tutorial
-
8/12/2019 Ieee Powertech Uni
5/66
Tutorial Approach Use expertise within PSRC to educate
Task force effort
Prepare regional relay program
-
8/12/2019 Ieee Powertech Uni
6/66
Tutorial ScopeSection
1
2
3
4
Subject
Fundamentals
Stator Phase Faults
Field GroundProtection
Stator GroundProtection
-
8/12/2019 Ieee Powertech Uni
7/66
Tutorial ScopeSection
5
67
Subject
Abnormal Frequency
Overexcitation
VT Signal Loss
-
8/12/2019 Ieee Powertech Uni
8/66
Tutorial ScopeSection
8
9
Subject
Loss of field
Out of step
-
8/12/2019 Ieee Powertech Uni
9/66
Tutorial ScopeSection
10
11
Subject
Current Unbalance
System Backup
-
8/12/2019 Ieee Powertech Uni
10/66
Tutorial ScopeSection
12
13
14
Subject
InadvertentEnergizing
Generator BreakerFailure
Generator Tripping
-
8/12/2019 Ieee Powertech Uni
11/66
Fundamentals
-
8/12/2019 Ieee Powertech Uni
12/66
Fundamental Section Basic Synchronous Generators
Connections to the system
Short Circuits
Generator Grounding
C37 Guidelines
Device Numbers
-
8/12/2019 Ieee Powertech Uni
13/66
Basic Synchronous Generator
-
8/12/2019 Ieee Powertech Uni
14/66
Synchronous Generator Types
-
8/12/2019 Ieee Powertech Uni
15/66
-
8/12/2019 Ieee Powertech Uni
16/66
-
8/12/2019 Ieee Powertech Uni
17/66
-
8/12/2019 Ieee Powertech Uni
18/66
Direct Connected Generatorto Power System
-
8/12/2019 Ieee Powertech Uni
19/66
Unit Connected Generator toPower System
-
8/12/2019 Ieee Powertech Uni
20/66
Symmetrical Trace of a GeneratorShort-Circuit Current
-
8/12/2019 Ieee Powertech Uni
21/66
Generator Short-Circuit Currents Phase B
-
8/12/2019 Ieee Powertech Uni
22/66
Generator Terminal Fault Current
-
8/12/2019 Ieee Powertech Uni
23/66
Low Impedance Grounding
-
8/12/2019 Ieee Powertech Uni
24/66
High Impedance Grounding
-
8/12/2019 Ieee Powertech Uni
25/66
Device Function Discussed inTutorial Section
21 Distance Relay. Backup for systemand generator zone phase faults.
11
24Volts/Hz protection for generator
overexcitation. 6
32 Reverse power relay. Anti-motoringprotection.
14
40 Loss-of-field protection. 8
46 Negative sequence unbalancecurrent protection for the generator.
10
-
8/12/2019 Ieee Powertech Uni
26/66
Device Function Discussed inTutorial Section
49 Stator Thermal Protection. 14
51GN Time overcurrent ground relay. 4 & 11
51TN Backup for ground faults. 4 & 11
51V Voltage-controlled or voltage-restrained time overcurrent relay.Backup for system and generatorphase faults.
11
59Overvoltage protection.
6
59GN Overvoltage relay. Stator groundfault protection for a generator.
4
-
8/12/2019 Ieee Powertech Uni
27/66
Device Function Discussed inTutorial Section
79 Loss-of-synchronism protection. 9
81 Frequency relay. Bothunderfrequency protection.
5
86 Hand-reset lockout auxiliary relay. 14
87G Differential relay. Primary phase-fault protection for the generator.
2
87N Stator ground fault differential . 4
87T Differential relay. Primaryprotection for the transformer. 2
87U Differential relay for overallgenerator and transformerprotection.
2
-
8/12/2019 Ieee Powertech Uni
28/66
Typical Unit Generator Transformer Configuration
-
8/12/2019 Ieee Powertech Uni
29/66
-
8/12/2019 Ieee Powertech Uni
30/66
Generator StatorPhase FaultProtection
-
8/12/2019 Ieee Powertech Uni
31/66
Introduction High Fault Current
Long Repair Time
$$$
-
8/12/2019 Ieee Powertech Uni
32/66
High Speed Relays Percentage Differential
High Impedance Differential
Self-Balancing Differential
-
8/12/2019 Ieee Powertech Uni
33/66
Percentage Differential
-
8/12/2019 Ieee Powertech Uni
34/66
-
8/12/2019 Ieee Powertech Uni
35/66
High-Impedance Differential
-
8/12/2019 Ieee Powertech Uni
36/66
Self-Balancing Differential
-
8/12/2019 Ieee Powertech Uni
37/66
-
8/12/2019 Ieee Powertech Uni
38/66
Split-Phase Protection Using a SingleWindow Current Transformer
-
8/12/2019 Ieee Powertech Uni
39/66
-
8/12/2019 Ieee Powertech Uni
40/66
Back-up Overall Differential Relay
System Backup Relay
Negative Sequence Relay
Transformer Backup Relay
-
8/12/2019 Ieee Powertech Uni
41/66
Generator Phase Fault Backup OverallDifferential Scheme
-
8/12/2019 Ieee Powertech Uni
42/66
-
8/12/2019 Ieee Powertech Uni
43/66
Introduction
Detection of ground faults in the field circuits
-
8/12/2019 Ieee Powertech Uni
44/66
Field Ground A single ground fault will not:
Affect the operation of a generator
Produce any immediate damaging effects
The first ground fault will:
Establish a ground reference for induced voltages Increase stress to ground at other points in the field winding
-
8/12/2019 Ieee Powertech Uni
45/66
Field Ground A second ground fault will:
Be more likely to occur
Be a whiz bang of a fault
It will result in:
A portion of the field winding being short circuited causingvibration
Rotor iron heating from the unbalanced currents
Arcing may heat the rotor locally
-
8/12/2019 Ieee Powertech Uni
46/66
Time Delay Ground Relays Prevent misoperation from temporary grounds
caused by system transients
Some utilities have changed from alarm to trip
-
8/12/2019 Ieee Powertech Uni
47/66
-
8/12/2019 Ieee Powertech Uni
48/66
Field Ground DetectionUsing a dc Source
-
8/12/2019 Ieee Powertech Uni
49/66
Field Ground Detection Using aVoltage Divider
-
8/12/2019 Ieee Powertech Uni
50/66
Field Ground Detection Using PilotBrushes
-
8/12/2019 Ieee Powertech Uni
51/66
Tripping Practices Are not well established
Some utilities trip
Others alarm risking a second ground fault andmajor damage
Generator protection survey 82% of generators employ field ground relays
Only 30% trip for a field ground
-
8/12/2019 Ieee Powertech Uni
52/66
Backup Protection Vibration detection equipment
A brush seating verification scheme
-
8/12/2019 Ieee Powertech Uni
53/66
Stator WindingGround FaultProtection
-
8/12/2019 Ieee Powertech Uni
54/66
IntroductionThe Method of Generator Neutral Grounding
Determines its Performance During Ground Faults
Solidly Grounded
Low Impedance
High Impedance Ungrounded
-
8/12/2019 Ieee Powertech Uni
55/66
Low Impedance Stator Grounding Industrial
Smaller Sized Units
-
8/12/2019 Ieee Powertech Uni
56/66
Low Impedance Grounding GeneratorsBussed Together
-
8/12/2019 Ieee Powertech Uni
57/66
Generator Ground Differential UsingProduct Type Relay
-
8/12/2019 Ieee Powertech Uni
58/66
High Impedance Stator Grounding Conventional Protection Scheme
100% Protection Scheme
-
8/12/2019 Ieee Powertech Uni
59/66
100 Stator Ground FaultProtection Methods 3rd Harmonic
Voltage Injection
-
8/12/2019 Ieee Powertech Uni
60/66
High ImpedanceGrounded Generator
-
8/12/2019 Ieee Powertech Uni
61/66
Third Harmonic Voltages for DifferentConditions in a Typical Generator
-
8/12/2019 Ieee Powertech Uni
62/66
Third Harmonic Residual Terminal VoltageBased Ground Fault Protection Scheme
-
8/12/2019 Ieee Powertech Uni
63/66
-
8/12/2019 Ieee Powertech Uni
64/66
-
8/12/2019 Ieee Powertech Uni
65/66
-
8/12/2019 Ieee Powertech Uni
66/66