    Synchrophasors and the Smarter GridSynchrophasors and the Smarter Grid

  • 7/28/2019 IEEE PES Boston Synchrophasors

    2/60

    Copyright SEL 2011

    A synchrophasor is a phasor measurement withrespect to an absolute time reference. With this

    measurement we can determine the absolute phaserelationship between phase quantities at different

    locations on the power system.

    SynchrophasorSynchrophasor

  • 7/28/2019 IEEE PES Boston Synchrophasors

    3/60

    Copyright SEL 2011

    Absolute Time Synchronization HasAbsolute Time Synchronization Has

    Fundamentally Changed the WorldFundamentally Changed the World

    GPS RCVR

    PMU 1

    A B

    Satellite

    GPS RCVR

    PMU 2

    IRIG-B IRIG-B

    Mag/Ang Mag/Ang

  • 7/28/2019 IEEE PES Boston Synchrophasors

    4/60

    Copyright SEL 2011

    t

    Time WaveformTime Waveform

    and Phasor Representationand Phasor Representation

    Reference

    A

    2

  • 7/28/2019 IEEE PES Boston Synchrophasors

    5/60

    Copyright SEL 2011

    A Timing Mark on a Generator ShaftA Timing Mark on a Generator Shaft

  • 7/28/2019 IEEE PES Boston Synchrophasors

    6/60

    Copyright SEL 2011

    Synchrophasors Provide aSynchrophasors Provide a SnapshotSnapshot

    of the Power Systemof the Power System

    P= |V1| |V2|sin/ X = sin-1(PX / |V1| |V2|)

    V10 V2 P

    Increase StablePower Transfer

  • 7/28/2019 IEEE PES Boston Synchrophasors

    7/60

    Copyright SEL 2011

    Synchrophasor System ComponentsSynchrophasor System Components

    System Components

    Clocks

    PMUs

    PDCs

    Visualization

    Secure communications

  • 7/28/2019 IEEE PES Boston Synchrophasors

    8/60

    Copyright SEL 2011

    ISO

    Neighbor Utility Control Center

    Visualization SELVisualization SEL--50785078

    Utility Control Center

    GPS ClockGPS Clock

    Security GatewaySecurity Gateway

    Station PDCStation PDC

    System PDCSystem PDC

    PDCPDC

    Super PDCSuper PDC

    PMUPMUPMUPMU

    Other Substations

    SystemSystem

    ArchitectureArchitecture

  • 7/28/2019 IEEE PES Boston Synchrophasors

    9/60

    Copyright SEL 2011

    Timing Accuracy RequirementsTiming Accuracy Requirements

    Synchrophasors require 500 ns

    Modern Clocks provides 100 ns

    GPS synchronized clocks typically used

  • 7/28/2019 IEEE PES Boston Synchrophasors

    10/60

    Copyright SEL 2011

    Synchrophasor System ComponentsSynchrophasor System Components

    System Components

    Clocks

    PMUs

    PDCs

    Visualization

    Secure communications

  • 7/28/2019 IEEE PES Boston Synchrophasors

    11/60

    Copyright SEL 2011

    Phasor Measurement Units (PMUs)Phasor Measurement Units (PMUs)

  • 7/28/2019 IEEE PES Boston Synchrophasors

    12/60

    Synchronized Phasor MeasurementSynchronized Phasor Measurement

    and Distance Protectionand Distance Protection

  • 7/28/2019 IEEE PES Boston Synchrophasors

    13/60

    Copyright SEL 2011

    Enabling PMU Capability in the RelayEnabling PMU Capability in the Relay

    SCADA

    Disturbance RecordHigh-Speed Control

    Just Say Yes!

  • 7/28/2019 IEEE PES Boston Synchrophasors

    14/60

    Copyright SEL 2011

    C37.118 Signal Processing FilterC37.118 Signal Processing Filter

    Selecting the Frequency ResponseSelecting the Frequency Response

  • 7/28/2019 IEEE PES Boston Synchrophasors

    15/60

    Copyright SEL 2011

    Synchrophasor System ComponentsSynchrophasor System Components

    System Components

    Clocks

    PMUs

    PDCs

    Visualization

    Secure communications

  • 7/28/2019 IEEE PES Boston Synchrophasors

    16/60

    Copyright SEL 2011

    Data Concentration & ArchivingData Concentration & Archiving

    Time Alignment and Superpacket Creation

    Protocol Conversion

    Data Parsing

    Data Rate Change

    Archive Maximum Data Locally

  • 7/28/2019 IEEE PES Boston Synchrophasors

    17/60

    Copyright SEL 2011

    PDC ArchitecturePDC Architecture

  • 7/28/2019 IEEE PES Boston Synchrophasors

    18/60

    Copyright SEL 2011

    Synchrophasor System ComponentsSynchrophasor System Components

    System Components

    Clocks

    PMUs

    PDCs

    Visualization

    Secure communications

  • 7/28/2019 IEEE PES Boston Synchrophasors

    19/60

    Copyright SEL 2011

    Bus Voltage

    Line MVA

    Frequency

    Instantaneous

    Phase Angles

    Trended Phase Angles

    PMU ID

    Visualizing SynchrophasorsVisualizing Synchrophasors

  • 7/28/2019 IEEE PES Boston Synchrophasors

    20/60

    Copyright SEL 2011

    Synchrophasor System ComponentsSynchrophasor System Components

    System Components

    Clocks

    PMUs

    PDCs

    Visualization

    Secure communications

  • 7/28/2019 IEEE PES Boston Synchrophasors

    21/60

    Copyright SEL 2011

    ISO

    Neighbor Utility Control Center

    Visualization SELVisualization SEL--50785078

    Utility Control Center

    GPS ClockGPS Clock

    Security GatewaySecurity Gateway

    Station PDCStation PDC

    System PDCSystem PDC

    PDCPDC

    Super PDCSuper PDC

    PMUPMUPMUPMU

    Other Substations

    SystemSystem

    ArchitectureArchitecture

  • 7/28/2019 IEEE PES Boston Synchrophasors

    22/60

    Copyright SEL 2011

    Substation Security

    Information SecurityInformation Security

    EndEnd--toto--End SecurityEnd Security

  • 7/28/2019 IEEE PES Boston Synchrophasors

    23/60

    Copyright SEL 2011

    Securing the InformationSecuring the Information

    Establish an electronic security perimeter Use multilayered system architecture that

    includes a firewall Encrypt communications in/out of

    substation Disable unused ports on all devices Send C37.118 data using UDP Secure

    (UDP_S)

  • 7/28/2019 IEEE PES Boston Synchrophasors

    24/60

    Multi-layered Secure Architecture

  • 7/28/2019 IEEE PES Boston Synchrophasors

    25/60

    Copyright SEL 2011

    SCADA Speed Sufficient for ManySCADA Speed Sufficient for Many

    Special Protection SchemesSpecial Protection Schemes

    Systemoperators

    need databeforethings start

    to happen

  • 7/28/2019 IEEE PES Boston Synchrophasors

    26/60

    Copyright SEL 2011

    Sometimes the Need for Speed Is Not ObviousSometimes the Need for Speed Is Not Obvious

    64 Minutes

  • 7/28/2019 IEEE PES Boston Synchrophasors

    27/60

    Copyright SEL 2011

    It Can Fall Apart in Three MinutesIt Can Fall Apart in Three Minutes

    64 Minutes

  • 7/28/2019 IEEE PES Boston Synchrophasors

    28/60

    Copyright SEL 2011

    Synchrophasors Are a Flexible ToolSynchrophasors Are a Flexible Tool

    State measurement

    Disturbance recording Modal analysis Dynamic response

    measurementand

    High-Speed Protection

    and Control

  • 7/28/2019 IEEE PES Boston Synchrophasors

    29/60

    Copyright SEL 2011

    Synchrophasor ApplicationsSynchrophasor Applications

  • 7/28/2019 IEEE PES Boston Synchrophasors

    30/60

    Copyright SEL 2011

    Synchrophasors Provide aSynchrophasors Provide a SnapshotSnapshot

    of the Power Systemof the Power System

    P= |V1| |V2|sin/ X = sin-1(PX / |V1| |V2|)

    V10 V2 P

    Increase StablePower Transfer

  • 7/28/2019 IEEE PES Boston Synchrophasors

    31/60

    Copyright SEL 2011

    Streaming Data Better than SCADAStreaming Data Better than SCADA

    --Imagine Driving in 5 Second BlinksImagine Driving in 5 Second Blinks

  • 7/28/2019 IEEE PES Boston Synchrophasors

    32/60

    Copyright SEL 2011

    Synchrophas

    or Data is

    Critical

  • 7/28/2019 IEEE PES Boston Synchrophasors

    33/60

    Copyright SEL 2011Courtesy of Entergy Corp.Courtesy of Entergy Corp.

  • 7/28/2019 IEEE PES Boston Synchrophasors

    34/60

    Copyright SEL 2011Courtesy of Entergy Corp.Courtesy of Entergy Corp.

  • 7/28/2019 IEEE PES Boston Synchrophasors

    35/60

    Copyright SEL 2011

    Synchrophasors Detect IslandSynchrophasors Detect Island

    Courtesy of Entergy Corp.Courtesy of Entergy Corp.

  • 7/28/2019 IEEE PES Boston Synchrophasors

    36/60

    Copyright SEL 2011

    Florida Power & Light: DistributedFlorida Power & Light: Distributed

    Generation AntiGeneration Anti--IslandingIslanding

    Angle

    Freq

    df/dtVoltage

  • 7/28/2019 IEEE PES Boston Synchrophasors

    37/60

    Copyright SEL 2011

    SEGIS AntiSEGIS Anti--Islanding DemoIslanding Demo

    Advanced Energy led ODOT solar project: 100 kW installation

    Stage 3 demo planned for August 11

  • 7/28/2019 IEEE PES Boston Synchrophasors

    38/60

    Copyright SEL 2011

    SEGIS Field Testing ResultsSEGIS Field Testing Results

    Island event Longest trip 1.1 seconds

    Utility functions Curtailment Ramp rate

    Power factor

  • 7/28/2019 IEEE PES Boston Synchrophasors

    39/60

    Copyright SEL 2011

    Archiving SystemArchiving System

    SEL-3306

    Disturbance RecordingDisturbance Recording

    Event Capture andEvent Capture andAnalysisAnalysis

  • 7/28/2019 IEEE PES Boston Synchrophasors

    40/60

    Copyright SEL 2011

    Utilities Are Operating Closer to the EdgeUtilities Are Operating Closer to the Edge

    MarginMargin

    1.0 1.3 1.5 1.7PU Nominal Load

    1.0

    0.5

    0.0

    Operating

    Point

    Bifurcation

    Point

  • 7/28/2019 IEEE PES Boston Synchrophasors

    41/60

    Copyright SEL 2011

    EskomEskoms Voltage Stability Assessments Voltage Stability Assessment

    SystemSystem

  • 7/28/2019 IEEE PES Boston Synchrophasors

    42/60

    Copyright SEL 2011

    UT Pan Am

    Austin

    McDonald

    Observatory

    Austin 120V and

    Harris 69kV

    Waco

    Houston(SEL)

    Boerne(SEL)

    Brazos Electric

    PMU

    Austin Energy

    PMU

    Fundingprovided by

    EPRI

    Wind

    country

    Concentrated distant load

    Blue outlines:Central ERCOT

    2

    The Texas Synchrophasor Network

    E i Th i E i l I d A

  • 7/28/2019 IEEE PES Boston Synchrophasors

    43/60

    Bus 7

    WIND

    Bus 7

    WIND500 km

    Local conventional

    Pload,conv Pgen,conv

    Pexport

    Thevenin ImpedancejXTH

    CentralERCOT

    Vangle = 0

    Vangle =

    Use the Excel Solver with angle measurements to minimize least-squared error

    and obtain Xth

    Estimate Thevenin Equivalent Impedances Across

    the Grid with Synchrophasors

    8

    )sin(21 TH

    X

    VVP

    A 2 Hz Mode in Ambient Oscillation Forms with

  • 7/28/2019 IEEE PES Boston Synchrophasors

    44/60

    Copyright SEL 2011

    2 Hz

    Cluster

    March 18, 02:00 03:00

    Wind Generation > 20%

    March 12, 02:00 03:00

    Wind Generation 2%

    Big Wind (20%) with 2 Hz ClusterSmall Wind (2%) without 2 Hz Cluster

    A 2 Hz Mode in Ambient Oscillation Forms with

    High Wind Generation

    9

    1 hour

    O S

  • 7/28/2019 IEEE PES Boston Synchrophasors

    45/60

    Copyright SEL 2011

    Only SynchrophasorsOnly Synchrophasors

    Provide AngleProvide AngleDifferenceDifference

    FrequencyFrequency

    AngleAngleDifferenceDifference

    Charts provided by University of Texas

  • 7/28/2019 IEEE PES Boston Synchrophasors

    46/60

    Copyright SEL 201146

    46

    Integration of Renewable EnergyIntegration of Renewable Energy

    With over 28GW of wind

    power in the SPPinterconnection queue, thisis a big deal!

    OG&E requiring a PMU atthe point of interconnectionfor every wind farm

    Important to monitor powerquality and dynamicresponse

  • 7/28/2019 IEEE PES Boston Synchrophasors

    47/60

    47

    Oscillations Due to Wind FarmOscillations Due to Wind Farm

    Wind farm PMU shows

    many undesirablecomponents, the worstat 14Hz

    Big Creek Controls RectorBig Creek Controls Rector

  • 7/28/2019 IEEE PES Boston Synchrophasors

    48/60

    Copyright SEL 2011

    Big Creek Controls RectorBig Creek Controls Rector

    Static VAR CompensatorStatic VAR Compensator

    C37.118 to SCADA based FACTS ControlC37.118 to SCADA based FACTS Control

  • 7/28/2019 IEEE PES Boston Synchrophasors

    49/60

    Copyright SEL 2011

    C37.118 to SCADA based FACTS ControlC37.118 to SCADA based FACTS Control

    SCADAMaster

    DNP3

    IEEE C37.118

    Information

    Processor

    SRPSRP S h WAV S hS h WAV S h

  • 7/28/2019 IEEE PES Boston Synchrophasors

    50/60

    Copyright SEL 2011

    SRPSRP SynchroWAVe SynchroscopeSynchroWAVe Synchroscope

    115 kV

    Bus

    230 kV

    Bus

    13.8 kV

    Bus

    SEL-421

    SEL-421

  • 7/28/2019 IEEE PES Boston Synchrophasors

    51/60

    Copyright SEL 2011

    SRP Operator Closes Tie Based

    on Synchrophasors, 2004

    RelayRelay--toto--RelayRelay

  • 7/28/2019 IEEE PES Boston Synchrophasors

    52/60

    Copyright SEL 2011

    yy yy

    Synchrophasors forSynchrophasors forGenerator SheddingGenerator Shedding

    Generator Shedding Based on AngleGenerator Shedding Based on Angle

  • 7/28/2019 IEEE PES Boston Synchrophasors

    53/60

    Copyright SEL 2011

    g gg gChicoasenChicoasen AngosturaAngostura

    WideWide Area Protection at Relay SpeedsArea Protection at Relay Speeds

  • 7/28/2019 IEEE PES Boston Synchrophasors

    54/60

    Copyright SEL 2011

    WideWide--Area Protection at Relay SpeedsArea Protection at Relay Speeds

    Modal AnalysisModal Analysis

  • 7/28/2019 IEEE PES Boston Synchrophasors

    55/60

    Copyright SEL 2011

    Modal AnalysisModal Analysis

    Shows System ResponseShows System Response

    1996 Event

    Slow Oscillations Facilitate ControlSlow Oscillations Facilitate Control

  • 7/28/2019 IEEE PES Boston Synchrophasors

    56/60

    Copyright SEL 2011

    Slow Oscillations Facilitate ControlSlow Oscillations Facilitate Control

    P= |V1| |V2|sin/ X

    Raise

    Voltage ReduceVoltage

    0.4 Hz 2.5 sec.

    A New Tool for Old ProblemsA New Tool for Old Problems

  • 7/28/2019 IEEE PES Boston Synchrophasors

    57/60

    Copyright SEL 2011

    SynchrophasorsSynchrophasors

    Are cost effective

    Provide accurate time-synchronizedevent information

    Can be used to meet NERC PRC-002-2

    requirements Are being used for new approaches in

    protection and control

    Apply Synchrophasors NowApply Synchrophasors Now

  • 7/28/2019 IEEE PES Boston Synchrophasors

    58/60

    Apply Synchrophasors NowApply Synchrophasors Now

    Disturbancerecording

    Relay-to-relaycontrol

    Modal analysis

    Special protection

    schemes System control

    DonDont Imagine Itt Imagine It Engineer ItEngineer It

  • 7/28/2019 IEEE PES Boston Synchrophasors

    59/60

    Copyright SEL 2011

    DonDon t Imagine Itt Imagine It Engineer ItEngineer It

    What Can You Do WithWhat Can You Do With

    Synchrophasors?Synchrophasors?

    URLs for More Application InformationURLs for More Application Information

  • 7/28/2019 IEEE PES Boston Synchrophasors

    60/60

    Copyright SEL 2011

    ppppSEL website:

    Eskom Voltage Stabilty

    https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=6378

    Solar Generator Control PV Poweredhttps://www.selinc.com/WorkArea/DownloadAsset.aspx?id=8494

    Generator Black-startSRP

    https://www.selinc.com/WorkArea/DownloadAsset.aspx?id=3194

    Anti-islanding at FPLhttps://www.selinc.com/WorkArea/DownloadAsset.aspx?id=6375

    UT Texas with Dr. Mack Gradyhttps://www.selinc.com/WorkArea/DownloadAsset.aspx?id=7264

    SCE Static VAR Controlhttps://www.selinc.com/WorkArea/DownloadAsset.aspx?id=3487

    Using Modal Analysis to Mitigate Power System Oscillationshttps://www.selinc.com/WorkArea/DownloadAsset.aspx?id=5322

    Another useful website - North American SynchroPhasor Initiative (NASPI) website:http://www.naspi.org/

    OGE presentation , Entergy presentation and many others