[ieee 2013 international conference on circuits, power and computing technologies (iccpct) -...
TRANSCRIPT
2013 International Conference on Circuits, Power and Computing Technologies [ICCPCT-2013]
An Optimal P MU Placement Technique for the Topological Observability of aPart of the NER
Grid of In dia Dr. A. K. Sinha
Department of Electrical Engineering Ramesh Kumar
Department of Electrical Engineering Chaynika Saikia
Department of Electrical Engineering
National Institute ofTechnology Silchar
Assam, INDIA Pin: 788010
National Institute ofTechnology Silchar
Assam, INDIA Pin: 788010 National Institute ofTechnology Silchar
Assam, INDIA Pin: 788010 chaynika. [email protected], ashokesinha200 [email protected], [email protected]
Satyabrata Rudrapaul Department of Electrical Engineering
National Institute ofTechnology Silchar
Assam, INDIA Pin: 788010 aj ay. [email protected]
Abstract- This paper considers the analysis of network
observability and optimum PMU placement problem under
normal operation conditions. The aim of the optimum PMU
placement (OPP) problem is to provide minimum number of
PMU installations to ensure full observability of the particular
power system. The approach used in this paper is based on the
topological observability of the system. The technique used is
based on integer linear programming. The proposed technique
has been firstly verified on IEEE 14- bus and New England 39-bus system. It has then been implemented on a part of the 77- bus
North Eastern grid of India. The part considered in the paper
comprises of the states- Nagaland, Manipur, South Assam,
Mizoram, Tripura, Meghalaya and Palatana. Lines wh ich are
currently under construction and under outage have not been
considered.
Index Terms- Optimum PMU placement problem, Integer
Linear Programming, North Eastern Grid of India, topological
observability.
I. INTRODUCTTON
S YNCHRONIZED phasor measurement unit (PMU) were fIrst
introduced in the early 1990s, and since then it has been
widely used with many applications [1]. The applications
include state estimation, power system monitoring, power
system protection and power system control. The conventional
state estimators use a set of measurements which inc1ude bus
voltages, real and reactive power flows, power injections in
order to estimate the bus voltage phasors of the system. These
measurements were obtained through Supervisory Control and
Data Acquisition (SCADA) systems which could only provide
the bus voltage magnitudes but unable to provide the bus
phase angle measurements in real time. With the employment
of PMUs, this problem can be diminished. The Remote
Terminal Units (RTUs) can therefore be replaced by PMUs
since the data gathered by the RTUs are unsynchronized and
do not contain information about the dynamic stability of the
system.
978-1-4673-4922-2/13/$31.00 ©20 13 IEEE 142
Bristi Saikia Department of Electrical Engineering
National Institute ofTechnology Silchar Assam, INDIA Pin: 788010
saikia. [email protected]
The measurements obtained by the PMUs are time
synchronized via Global Positioning System (GPS) with an
accuracy of 1 microsecond. The phasor measured at the same
instant of time provide snapshot of the power system network
and by comparing the snapshot with two consecutive time
instants, it can monitor the steady state as weH as the dynamic
state of the system.
The PMUs are relatively costly and hence to minimize the
cost, the PMUs should be strategically placed in the power
system network. The objective is therefore to optimally place
the PMUs in the system in order to achieve fuIl network
observability.
Different authors have implemented different techniques for the optimal placement of the PMUs. A binary search algorithm has been developed in [2] in order to attain full network observability under normal operating conditions as weIl as single branch outage. A BPSO based methodology for the placement of PMUs for complete observability of a power system has been shown by the authors in [3]. A Tabu search method for meter placement for the purpose of state estimation has been introduced in [4]. In [5]-[6], the OPP optimization is solved using PSA T, a MATLAB based toolbox, and DeFS method is compared with other methods. Even though this algorithm is computationally faster, but the solution is not optimum, because the optimization criterion is stiff and unitary. In [7], the spanning trees of the power system graph are used to [md the optimal locations of PMUs based on the concept of depth of unobservability [8]. OPP has been dealt with in [9] as the first attempt, using a dual search algorithm by combination of a modifIed bisecting search and a simulated annealing method. Bacteria Foraging (BF) technique has also been used by the authors in [lO] for the OPP problem.
Though PMU has not yet been deployed in India, a novel attempt has been made to introduce it here and fInd a strategic method for the OPP problem and implement it on a part of the North Eastern Grid of India.
The rest of the paper has been organized as folIows. In section 11, the observability rules while employing PMUs are introduced. In section III, the proposed method has been explained. Section IV briefly describes the system under
2013 International Conference on Circuits, Power and Computing Technologies [ICCPCT-2013]
which the work has been done. The simulation results have been presented in section V. Section VI provides concluding remarks along with the purpose of the work being done.
11. OBSERVABIUTY RULES
Power system observability holds importance for finding out the real time state estimation. The network is said to be observable if sufficient measurements are observable, such that all the states of the system, as weil as the current and voltage phasors at all the buses can be estimated. There are three classes of algorithms used for this purpose, namely,
numerical, topological and hybrid techniques. For a network to be numerically observable, its gain or measurement Jacobian matrix should be of full rank [11]. A network is said to be topologically observable if it contains at least one spanning measurement tree of fuU rank [12]. Since numerical observability technique involves calculation of huge matrices, topological approach is more preferable. Thus, this approach has been used in the work. The topological observability techniques focus on finding a spanning tree of full rank with the placement of the PMUs for Wide Area Monitoring (W AM) purpose.
While formulating the OPP problem, there are certain rules and assumptions which are to be followed [13].
The first rule implies that if the current and the voltage phasors at one end of the branch are known, by using Ohm's law, the voltage at the other end of the bus can be calculated.
The second rule implies that if the voltage phasors at both ends of the branch are known, the branch current can be calculated.
III. FORMULATION OF THE OPP PROBLEM
In order to minimize the total cost of the PMU installation,
while ensuring that the system is observable, the problem can
be reduced to a binary decision variable problem, defined as,
X' = p, if PMU is in bus - i ! t O,otherwise (1)
If the PMUs are to be placed in an N-bus system and the cost
of installation of a PMU is taken to be the same in all the
buses and that value is taken as 1 p.u., the OPP problem can
be formulated as follows:
N
Minimize L Xi i=l
T such that, X= [XI X2 ... Xn]
Xi D {O,l} F(X) � 1
Here, F(X) is a vector of functions representing the
constraints. The constraint formulation depends upon the type
of measurement considered and also varies as per the system.
The ILP technique used here has been explained in details in
[14].
In this work, only the voltage/current phasor measurements
143
have been considered. The constraint formulation has been
explained for a 7- bus system as shown in Fig 1.
Fig. I. The sampie 7-bus system
Since it is assumed that a PMU placed at a bus can provide the
phasor values of all the branch currents connected to that bus,
apart from the bus voltage phasors, the phasor voltages at all
the neighboring bus can be computed. Thus a matrix M can be
obtained having the elements as given below,
m . . = fl, if i = j or if bus i and j are connected !] t 0, otherwise
Thus, the product of the matrices M and X gives the
constraint function F(X). Elements of this matrix will always
be greater than or equal to one, which means that there must
be at least one PMU at one of the buses of the constraint
function. The constraints for a 7 bus system can be given as
folIows: F\: XI+X2� 1 F2: XI+X2+X3+X6+X7� 1 F3: X2+X3+X4+X6� 1
F4: X3+X4+X5+X7� 1
Fs: X4+X5� 1
F6: X2+X3+X6� 1
F7: X2+X4+X7 � 1
IV. NORTH EASTERN GRID FOR INDIA
(2)
The North Eastern Region (NER) comprises of seven states viz. Arunachal Pradesh, Assam, Manipur, Meghalaya, Mizoram, Nagaland and Tripura. NHPC, NEEPCO & OTPCL are the Central Generating Companies presently operating in the region with installed capacity of 105 MW,II30 MW & 363 MW respectively. Depending on the network connectivity, NER Grid is broadly classified as folIows: 1. 400/220 kV Network 0/ POWERGRID as backbone o/NER Grid 2. 220/ 132 kV Network 0/ Assam System 3. 220/ 132 kV Network 0/ Arunachal Pradesh System 4. 400 / 220 / 132 kV Network comprising 0/ Nagaland, Manipur, South Assam, Mizoram, Tripura, Meghalaya and Palatana.
The fourth system has been considered as the practical system on which the ILP method has been implemented. This network consists of six states. The connectivity of this
2013 International Conference on Circuits, Power and Computing Technologies [ICCPCT-2013]
400/2201132 kV system with all the states has been explained in [15].
V. SIMULATION
A. IEEE 14-bus system
The IEEE 14-bus system has 14 buses as shown in Fig 2. Hence the vector X contains 14 binary decision variables. The complete ILP problem can be formulated for the 14-bus system as follows:
subject to:
14
Minimize I Xi i=1
F\: X/+X2+Xj � 1
F2: X/+X2+X3+X4+Xj � 1
F3: X2+X3+X4 � 1
F4: X2+X3+X4+Xj+X7+X9 � 1
Fs: X/+X2+X4+Xj+X6� 1
F6: Xj+X6+XI/+XI2+X/3 � 1
F7: X4+X7+X8+X9 � 1
Fg: X7+X8 � 1
F9: X4+X7+X9+X/O+XI4 � 1
F\O: X9+X/O+XI/ � 1
Fll: X6+X/O+XI/ � 1 F 12: X6+X I2+X /3 � 1
F\3: X6+XI2+X/3+XI4� 1
F\4: X9+X/3+XI4 � 1
The locations found by the ILP method where the PMUs
can be placed are at buses 2, 6, 7 and 9.
B. New England 39-bus system
The 39-bus system is as shown in Fig 3. The OPP formulation can be done for this system in the same manner as shown for IEEE 14- bus system. There are 13 PMU locations obtained for this system after simulation. The places where the PMUs are to be located are the buses 2, 6, 9, 10, 13, 14, 17, 19, 20, 22, 23, 25 and 28.
C. 400/220/ 132 kV Practical Network
The practical network consists of 77 buses comprising of Nagaland, Manipur, South Assam, Mizoram, Tripura, Meghalaya and Palatana. The OPP technique has been implemented, in a similar way as shown in the previous two cases, on this network without considering the lines which are currently under construction and under long outage. The buses where the PMUs are to be located have been highlighted in dark blue as shown in Fig 4. A total of 25 PMUs are required to be placed for complete observability of the system. The places where the PMUs are to be located are the buses 3, 7, 9, 13, 17, 20, 24, 25, 26, 27, 3 1, 34, 37, 41, 44, 47, 48, 50, 53, 59, 61, 65, 70, 71 and 72.
144
The number of PMUs required for each of the systems is given in Table I.
TABLE I No OF PMUS REQUIRED
SYSTEM No. of PMUs
IEEE 14-bus system 4
New England 39-bus system 13 400/220/132 kV Practical system 25
GI
C3
7
l-+-I--+-'-3
f\; G2
Fig. 2. IEEE 14- bus system
@ 30 --L
37 26 29
2
.,L-,---..L 23
Fig. 3. New England 39-bus system
2013 International Conference on Circuits, Power and Computing Technologies [ICCPCT-2013]
rml (TR)
-+-.. " I
- -400kV - -220kV - -132kV - -66kV - - PMU placed bus
J,a:-... ,,----�
Fig. 4. 400/220/ 132 kV network of the NER Grid and its 77- bus structure
145
2013 International Conference on Circuits, Power and Computing Technologies [ICCPCT-2013]
VI. CONCLUS10N
The practical implementation of the technique used for the optirnal location of PMUs has been successfully shown in this paper for a part of the practical network of the NER Grid of India. The entire network can be observed by placing the PMUs in few of the locations. The synchrophasor technology has not yet been introduced in India. However, it is recommended that PMUs should very soon be adopted in the grid with the view of irnproving the security, monitoring and protection of the system, thus making the Grid more reliable.
ACKNOWLEDGMENT
The authors would like to thank the Electrical Engineering
Department of National Institute of Technology, Silchar for
believing in them and allowing them to work in the Research
Lab of the college.
References [ I] A. G. Phadke and J. S. Thorp, Synchronized Phasor Measurements and
Their Applications. New York: Springer, 2008. [2] S. Chakrabarti and E. Kyriakides, "Optimal placement for phasor
measurement units for power system observability", iEEE Transactions
on Power Systems, Vol. 23, No. 3, pp. 1433-1440, August 2008. [3] S. Chakrabarti, E. Kyriakides and G. K. Venayagamoorthy, "PMU
placement for power system observability using binary particle swarm optimization" in Proceedings 0/ Australian Universities Power
Engineering Conference, Sydney, Australia, December 2008. [4] H. Mori and Y. Sone, 'Tabu search based meter placement for
topological observability in power system state estimation", in Proceedings 0/ iEEE Transmission and Distribution Conference, New Orleans, Louisiana, 1999, pp. 172-177.
[5] M. Farsadi, H. Golahmadi, and H. Shojaei, "Phasor measurement unit (PMU) allocation in power system with different algorithms," in int. Conf on Electrical and Electronics Engineering, 2009, pp. 396-400.
[6] G. Venugopal, R. Veilumuthu, and P. Avila Theresa, "Optimal PMU placement and observability of power system using PSA T," in int. Joint Journal Conf on Engineering and Technology, 2010, pp. 67-71.
[7] R. F. Nuqui, "Phasor Measurement Unit placement Based on 1ncomplete Observability," Power Engineering Society, Summer Meeting, 2002, IEEE, Vol 2, pp. 883-893.
146
[8] R. F. Nuqui and A. G. Phadke, "Phasor measurement unit placement techniques for complete and incomplete observability," iEEE Trans. Power Dei., vol. 20, no.4, pp. 2381-2388, Oe!. 2005.
[9] K.S. Cho, J. R. Shin, and S. H. Hyun, "Optimal placement of phasor measurement units with GPS receiver," in Proc. IEEE Power Eng. Soc. Winter Meet., Jan.lFeb. 2001, vol. I, pp. 258-262.
[10] K. Mazlumi, and H. Vahedi, "Optimal placement of PMUs in power systems based on bacterial foraging algorithm," in Froc. 0/ iCEE, 20 I O.
[11] T. L. Baldwin, L. Mili, M. B. Boisen, Jr., and R. Adapa, "Power system observability with minimal phasor measurement placement", iEEE
Trans. Power Syst., vol. 8, no. 2, pp. 707-715, May 1993. [12] F. Aminifar, C. Lucas, A. Khodaei and M. Fotuhi-Firuzabad "Optimal
placement of phasor measurement units using immunity genetic algorithm," iEEE Trans. Power Dei., vol. 24, no. 3, pp. 1014-1020, Jul 2009.
[13] B. Xu and A. Abur, "Observability analysis and measurement placement for system with PMUs," in Proc. iEEE Power Syst. Conf Expo., Oe!. 2004, vol. 2, pp. 943-946.
[14] B. Gou, "Generalized integer linear programming formulation for optimal PMU placement," iEEE Trans. Power Syst., vol. 23, no. 3, pp. 1099-1104, Aug. 2008.
[15] Power System Operation Corp. Ltd., Black start and restoration
procedures 0/ NER grid, 8th revision, Nov. 2012.
Dr. A. K. Sinha had received his B.E. and M. Tech. from VNlT, Nagpur in 1978 and 1981. Dr Sinha had received his Ph. D. from lIT, Kharagpur, India in 1990. His field of work is Multiprocessor based digital relays, Power Quality Monitoring and Signal processing.
Chaynika Saikia was born on 10th July, 1991. She is currently pursuing her B. Tech in Electrical Engineering from National Institute of Technology, Silchar, 1ndia. Her areas of interest are Power System Monitoring and Control.
Satyabrata Rudra Paul is currently in the final year of B. Tech (Electrical Engineering) in National Institute of Technlogy, Silchar, 1ndia. His areas of interest include Power System monitoring, protection and control.
Bristi Saikia was born on 17th April, 1991. She is presently pursuing her B. Tech in Electrical Engineering from National Institute of Technology, Silchar, India. Her areas of interest include Power System protection and Electric Vehicles.