i-tec i36z-i60z 2-stage compressor high efficiency air ...page 1 of 12 the bard i-tec indoor heat...
TRANSCRIPT
Form No S3460-820Supersedes S3460-120Page 1 of 12
The Bard I-TEC Indoor Heat Pump system is designed for classrooms and other similar applications demanding high efficiency and the lowest possible sound levels that are practical and achievable, and also accommodates the over-the-window sill requirement for many replacement projects on older school buildings. The I-TEC Series meets that challenge with many innovative design features resulting in a highly refined appearance while at the same time improving on the very important maintenance and serviceability features needed by the facilities maintenance and service staffs.
I-TEC® I36Z-I60Z 2-Stage CompressorHigh Efficiency Air Source Heat Pumps
Ventilation Option:CRV has ECM motor, filter system, and positive shut-off.Commercial Room Ventilator (CRV) is a fan powered ventilation package to manage intake & exhaust air at fixed rates but without energy recovery capability. • The rates are: 300-375-450, are independently selectable, and has positive shutoff on intake and exhaust sides when unoccupied. • Requires control system that has a dedicated ventilation control output to be ON during Occupied and OFF during Unoccupied. CO2 controller with ON/OFF output relay can be used. • Factory setting is 375 CFM balanced to meet pressurization requirements of ASHRAE.
I-TEC Optional Features & Accessories
I-TEC Standard Features
Accessories: • Outdoor louver grilles: Clear, Medium Bronze, Dark Bronze • Telescoping Wall Sleeves • Wall Sleeve Ranges (wall thickness): 5.5" to 8.5", 8" to 13.5", 13" to 23.5" • 3" and 6" Riser Platforms available if required • Electric heat packages factory installed within the basic unit cabinet • Accessories for Duct-Free and Ducted installations
Other Options: • Low Ampacity Models available
• Installation flexibility. Can be installed in corner applications with one side against a wall. • Condensate overflow detection system with diagnostics monitors equipment and shuts down compressor to prevent condensate overflow. • Freezestat on indoor coil safeguards against indoor coil freeze up by shutting down the compressor.
• Double wall construction, 20-ga. exterior skin, no visible fasteners • Non fiberglass insulation • Hinged, lockable, removable doors • Removable sides and modularized construction for transporting through standard doors or in elevators allows installation on second and third floor • Can be installed in left or right corners with no modifications • Non-corrosive drainpans with no standing water • 2-Stage scroll compressors with discharge muffler, double floating isolation mounting system, and sound muffling cover • R-410A Green Refrigerant • Heating and cooling thermostatic expansion valves • Extra large full width control panel for easy access to all controls • All 230/208V units with or without electric heat have circuit breaker. All 460V units have Toggle Disconnect. Option for 460V circuit breaker on 0KW models only. • Evaporator coils constructed with hydrophilic fin stock w/the following advantages: Acrylic coating Wettable surface with low contact angle – no bead-up condensate, lower wet-coil air-side pressure drop, improved draining & lower re-entrainment of moisture back into the air stream in continuous blower operating modes Antimicrobial properties provide microbial resistance to fungicidal growth Resistant to Mold and Mildew, ASTM D3273 – no growth Seals fin surface against aluminum oxide formation • 24VAC 75VA control transformer with circuit breaker • 24VAC low-voltage terminal strip for thermostat or DDC control • ECM indoor and outdoor motors • Modulating outdoor fan motor and low ambient control • Modulating indoor fan motor for constant CFM in different operating modes up to 0.50" ESP • High and Low Pressure switches with lockout circuit • Electronic heat pump control board with diagnostics • Liquid line filter/drier • Readily accessible service ports located behind locking hinged doors • Pleated 2" MERV 8 filter • Designed for over-the-window sill wall penetration and has 3" vertical adjustment for wall sleeve attachment • Units designed to be flush to a smooth interior wall and not require trim kits by use of adjustable wall sleeves; Trim Kits available where required • Low sound levels are achieved by numerous system design innovations including special acoustical insulation
Cooling Capacities: 25,000 to 54,000 Btuh Heating Capacities: 22,800 to 54,000 Btuh
Form No S3460-820Supersedes S3460-120 Page 2 of 12
Motor will deliver consistent CFM through voltage supply range with no deterioration. Continous fan CFM is the total air being circulated during continuous fan mode. Will operate @ rated Full Load Airflow when operating with Heat Pump. Will occur automatically with a call for "W3" or "Emergency Heat" signal from thermostat (Heat Pump Operation is terminated @ this condition).
Specifications - 3, 4 & 5 Ton
Indoor Blower Performance
ModelRatedESP
Max.ESP
Continuous
CFM
Rated2nd Stage
CFM
Rated1st Stage
CFM
4-10 KW
CFM
15-20 KW
CFM
I36Z1 0.15 0.50 600 1150 850 700 1050
I48Z1 0.20 0.50 700 1400 1050 700 1400
I60Z1 0.20 0.50 800 1600 1100 700 1400
+ CFM @ rating points, will modulate based upon O.D. ambient.
• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2013.• Certified to ARI Standard 390-2003 for SPVU (Single Package Vertical Units).• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05, Fourth Edition.• Commercial Product - Not intended for Residential application.
* The AHRI Certified® mark indicates Bard Manufacturing Company participation in the AHRI
Certification program. For verification of individual certified products, go to www.ahridirectory.org.
MODELS I36Z1-A I36Z1-B I36Z1-C I48Z1-A I48Z1-B I48Z1-C I60Z1-A I60Z1-B I60Z1-CELECTRICAL RATING--60 HZ 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 414-506 197-253 414-506 197-253 414-506
COMPRESSOR
Volts 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Rated Load Amps (230/208) 11.1/13 8.5/9.9 4.9 15.6/17.5 10.4/11.6 5.4 22/23.4 13.4/14.3 6.3
Branch Circuit Selection Current 15.3 11.7 5.8 19.9 11.6 6.4 27.2 16.6 7.2
Locked Rotor Amps 83 73 38 104.0 83.1 41 152.9 110.0 52.0
ENERGY RECOVERY VENTILATOR
Volts 230/208-60-1 230/208-60-1 230/208-60-1
Full Load Amps (3-motors) 2.2 2.2 2.2
FAN MOTOR – ECM
Horsepower 1/3 1/2 1/2
Volts 230/208-60-1 230/208-60-1 230/208-60-1
Full Load Amps 2.6 3.2 3.2
+ CFM 2300 2600 2600
BLOWER MOTOR – ECM
Horsepower 1/2 1/2 3/4
Volts 230/208-60-1 230/208-60-1 230/208-60-1
Full Load Amps 2.5 3.2 4.4
Form No S3460-820Supersedes S3460-120Page 3 of 12
Capacity & Efficiency Ratings (Stage 1) Part Load Operation
EER = Energy Efficiency Ratio - BTU/WATT efficiency IPLV = Integrated Part Load Value - BTU/WATT efficiency (combines full and part load performance) COP = Coefficient of Performance - BTU/WATT efficiency
Capacity & Efficiency Ratings (Stage 2) Full Load Operation
Unit Weights
Deduct 65# from all values for installed weight.
MODELS I36Z1 I48Z1 I60Z1 Cooling BTUH, Full Load Capacity, 95-80/67 EER Rated CFM
35,00012.01150
47,00011.81400
54,00011.01600
IPLV (Integrated Full & Part Load) 80-80/67 16.5 16.1 15.2
Heating BTUH, Full Load Capacity 47/43-70 COP Rated CFM
31,8003.7
1150
44,5003.7
1400
54,0003.5
1600
MODELS I36Z1 I48Z1 I60Z1 Cooling BTUH, Part Load Capacity, 95-80/67 EER Rated CFM
25,00012.7850
32,50012.01050
37,00011.01200
Heating BTUH, Part Load Capacity 47/43-70 COP Rated CFM
23,1003.6850
30,5003.6
1050
36,5003.4
1200
MODELS NO VENT CRV
I36Z1-A 990 1080
I36Z1-B 990 1080
I36Z1-C 1025 1115
I48Z1-A 1030 1120
I48Z1-B 1030 1120
I48Z1-C 1065 1155
I60Z1-A 1075 1165
I60Z1-B 1075 1165
I60Z1-C 1110 1200
Unit Charge Rates
UNIT Std. Unit - Lbs.
Dehum. Units - Lbs.
I36Z1 - High Efficiency Step Capacity Indoor HP
10.5625 N/A
I48Z1 - High Efficiency Step Capacity Indoor HP
14.1875 N/A
I60Z1 - High Efficiency Step Capacity Indoor HP
12.8750 N/A
Form No S3460-820Supersedes S3460-120 Page 4 of 12
Factory Built-in Electric Heat Table
NOTE: Not all KW's available in all models. See Minimum Circuit Ampacity and Maximum Overcurrent Protection table on following page.
Model Voltage PhaseKW Amps BTUH
240V 208V 240V 208V 240V 208V
-A04 240/208 1 4 3 16.7 14.4 13,652 10,239
-A05 240/208 1 5.00 3.75 20.8 18.0 17,065 12,799
-A10 240/208 1 10.00 7.50 41.7 36.1 34,130 25,598
-A15 240/208 1 15.00 11.25 62.5 54.1 51,195 38,396
-A20 240/208 1 20.00 15.00 83.3 72.1 68,260 51,195
-B06 240/208 3 6.00 4.50 14.4 12.5 20,478 15,359
-B09 240/208 3 9.00 6.75 21.7 18.7 30,717 23,038
-B15 240/208 3 15.00 11.25 36.1 31.2 51,195 38,396
-B18 240/208 3 18.00 13.50 43.3 37.5 61,434 46,076
Model Voltage PhaseKW Amps BTUH
480V 460V 480V 460V 480V 460V
-C06 480 3 6.00 5.52 7.2 6.9 20,478 18,840
-C09 480 3 9.00 8.28 10.8 10.4 30,717 28,260
-C15 480 3 15.00 13.80 18.0 17.3 51,195 47,099
-C18 480 3 18.00 16.56 21.7 20.8 61,434 56,519
Form No S3460-820Supersedes S3460-120Page 5 of 12
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power conductor sizing.
Caution: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
Maximum size of the time delay fuse or HVAC type circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
Maximum KW that can operate with the heat pump is 10KW for 1-Phase and 9KW for 3-Phase.
Represents Electric Heat only. Electric Control Circuit will lock-out Heat Pump Operation. These models have Toggle Disconnect switch. This Model has 460V Circuit Breaker. Available for 0KW only.
Minimum Circuit Ampacity & Maximum Overcurrent Protection – Standard
MODEL
Rated Volts,
Hertz & Phase
Single Circuit Dual Circuit
No. Field Power
Circuits
Minimum Circuit
Ampacity
Maximum External Fuse or
Ckt. Brkr.
Field Power
Wire Size
Ground Wire
Minimum Circuit
Ampacity
MaximumExternal Fuse or Ckt. Breaker
Field Power Wire Size
Ground Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
I36Z1-A0Z A05 A10
A15
230/208-1
11
1 or 21 or 2
26527884
40608090
8644
101088
2626
5252
4040
6060
88
66
1010
1010
I36Z1-B0Z B06 B09
B15
230/208-3
1111
22404951
30455060
10886
10101010
I36Z1-C0Z C06 C09
C15
460-3
1111
11202428
15202530
14121010
14121010
I36Z1-C0C 460-3 1 11 15 14 14
I48Z1-A0Z A04 A05 A10
A15 A20
230/208-1
11
1 or 21 or 21 or 21 or 2
3454598585
110
5060709090
110
866332
10108886
35353559
26525252
45454560
30606060
8886
10666
10101010
10101010
I48Z1-B0Z B06 B09
B15 B18
230/208-3
11111
2644535353
3550606060
88666
1010101010
I48Z1-C0Z C06 C09
C15 C18
460-3
11111
1221262833
1530303035
141010108
1410101010
I48Z1-C0C 460-3 1 15 20 12 12
I60Z1-A0Z A05 A10
A15 A20
230/208-1
11 or 21 or 21 or 21 or 2
44709696
112
6080
100100120
84332
108886
44444460
26525252
60606060
30606060
8886
10666
10101010
10101010
I60Z1-B0Z B06 B09
B15 B18
230/208-3
1111
1 or 2
3149585863
4560606070
88666
101010108 31 54 45 60 8 6 10 10
I60Z1-C0Z C06 C09
C15 C18
460-3
11111
1525292933
2030303035
121010108
1210101010
I60Z1-C0C 460-3 1 15 20 12 12
Form No S3460-820Supersedes S3460-120 Page 6 of 12
Model D.B. / W.B.
COOLING CAPACITY 60°F 65°F 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F 125°F
I36Z1
75/62Total CoolingSensible Cooling
37,05028,631
36,40028,388
35,75028,144
35,10027,900
34,45027,656
33,80027,413
33,15027,169
32,50026,925
31,28126,418
30,06325,911
28,84425,404
27,62524,897
26,40624,390
25,18823,883
80/67Total CoolingSensible Cooling
41,95630,444
40,96329,888
39,96929,331
38,97528,775
37,98128,219
36,98827,663
35,99427,106
35,00026,550
33,68826,050
32,37525,550
31,06325,050
29,75024,550
28,43824,050
27,12523,550
85/72Total CoolingSensible Cooling
45,10030,219
44,35029,613
43,60029,006
42,85028,400
42,10027,794
41,35027,188
40,60026,581
39,85025,975
38,35625,486
36,86124,997
35,36724,507
33,87324,018
32,37823,529
30,88423,040
I48Z1
75/62Total CoolingSensible Cooling
50,98238,895
49,77338,266
48,56437,636
47,35537,007
46,14536,378
44,93635,748
43,72735,119
42,51834,490
40,90133,804
39,28433,119
37,66732,434
36,04931,748
34,43231,063
32,81530,378
80/67Total CoolingSensible Cooling
55,96938,188
54,68837,675
53,40637,163
52,12536,650
51,00035,875
49,71935,363
48,28135,113
47,00034,600
45,21333,913
43,42533,225
41,63832,538
39,85031,850
38,06331,163
36,27530,475
85/72Total CoolingSensible Cooling
51,87737,889
51,69937,293
51,52236,697
51,34436,101
51,16735,505
50,98934,909
50,81134,312
50,63433,716
48,70833,046
46,78232,376
44,85731,706
42,93131,036
41,00530,367
39,08029,697
I60Z1
75/62Total CoolingSensible Cooling
40,23129,706
41,46331,038
42,69432,369
43,92533,700
45,15635,031
46,38836,363
47,61937,694
48,85039,025
47,06338,215
45,27737,405
43,49036,595
41,70335,785
39,91734,975
38,13034,166
80/67Total CoolingSensible Cooling
44,11329,044
45,52530,488
46,938 31,931
48,35033,375
49,76334,819
51,17536,263
52,58837,706
54,00039,150
52,02538,338
50,05037,525
48,07536,713
46,10035,900
44,12535,088
42,15034,275
85/72Total CoolingSensible Cooling
47,98128,919
49,43830,238
50,894 31,556
52,35032,875
53,80634,194
55,26335,513
56,71936,831
58,17538,150
56,04737,358
53,92036,567
51,79235,775
49,66434,983
47,53734,191
45,40933,400
Model D.B. / W.B.
COOLING CAPACITY 60°F 65°F 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F 125°F
I36Z1
75/62Total CoolingSensible Cooling
28,50022,794
27,70022,388
26,90021,981
26,10021,575
25,30021,169
24,50020,763
23,70020,356
22,90019,950
21,97319,502
21,04519,054
20,11818,607
19,19018,159
18,26317,711
17,33517,263
80/67Total CoolingSensible Cooling
30,73122,456
29,91322,113
29,09421,769
28,27521,425
27,45621,081
26,63820,738
25,81920,394
25,00020,050
23,98819,600
22,975 19,150
21,96318,700
20,95018,250
19,938 17,800
18,92517,350
85/72Total CoolingSensible Cooling
32,11921,500
31,61321,300
31,10621,100
30,60020,900
30,09420,700
29,58820,500
29,08120,300
28,57520,100
27,41819,649
26,26019,198
25,10318,747
23,94618,296
22,78917,844
21,63117,393
I48Z1
75/62Total CoolingSensible Cooling
36,48927,440
35,47726,922
34,46526,404
33,45325,886
32,44125,369
31,42924,851
30,41724,333
29,40523,815
28,40423,512
27,40323,210
26,40222,907
25,40122,604
24,40022,302
23,39921,999
80/67Total CoolingSensible Cooling
40,38027,189
39,25526,712
38,12926,234
37,00325,756
36,00025,241
34,87424,763
33,62624,323
32,50023,845
31,39423,542
30,28823,239
29,18122,936
28,07522,633
26,96922,330
25,86322,027
85/72Total CoolingSensible Cooling
37,19426,876
36,98726,403
36,78025,930
36,57325,457
36,36624,984
36,15924,511
35,95224,038
35,74523,565
34,52923,265
33,31222,966
32,09522,666
30,87922,367
29,66222,067
28,44521,768
I60Z1
75/62Total CoolingSensible Cooling
42,00630,931
40,78830,363
39,56929,794
38,35029,225
37,13128,656
35,91328,088
34,69427,519
33,47526,950
32,20326,339
30,93025,727
29,65825,116
28,38624,505
27,11423,893
25,84123,282
80/67Total CoolingSensible Cooling
46,49430,631
45,13830,113
43,78129,594
42,42529,075
41,00028,500
39,64427,981
38,35627,519
37,00027,000
35,59426,388
34,18825,775
32,78125,163
31,37524,550
29,96923,938
28,56323,325
85/72Total CoolingSensible Cooling
50,98130,306
49,51329,788
48,04429,269
46,57528,750
45,10628,231
43,63827,713
42,16927,194
40,70026,675
39,15326,070
37,60625,465
36,05924,860
34,51324,254
32,96623,649
31,41923,044
Below 50°F, unit requires a factory or field installed low ambient control. Return air temp. °F Rated CFM.
Heating Full Load Application Data
Heating Part Load Application Data
Cooling Part Load Application Data
Cooling Full Load Application Data
70°F DB indoor return air at rated CFM includes defrost operation below 45°.
Model Indoor 0° 5° 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60°F
I36Z1
70°F
BTUHWATTS
COP
13,52522331.78
15,45022632.00
17,37522882.23
19,30023082.45
21,22523252.68
23,15023392.90
25,07523513.13
27,00023613.35
29,20024623.48
31,40025563.60
33,36025793.79
35,32026003.98
37,28026194.17
I48Z1BTUH
WATTSCOP
24,45030652.34
25,80031172.43
27,15031662.51
28,50032122.60
29,85032542.69
31,20032942.78
32,55033322.86
33,90033672.95
38,90034543.30
43,90035243.65
46,88035963.82
49,86036613.99
52,84037224.16
I60Z1BTUH
WATTSCOP
30,11338152.31
31,07538342.38
32,03838512.44
33,00038682.50
33,96338832.56
34,92538982.63
35,88839132.69
36,85039262.75
45,42542933.10
52,80044843.45
56,36046183.58
59,92047423.70
63,48048593.83
Model Indoor 0° 5° 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60°F
I36Z1
70°F
BTUHWATTS
COP
9,12519991.34
10,55019631.58
11,97519361.81
13,40019152.05
14,82518992.29
16,25018862.53
17,67518752.76
19,10018653.00
21,10019173.23
21,40018173.45
23,35018423.71
25,30018643.98
27,25018834.24
I48Z1BTUH
WATTSCOP
15,96324781.89
17,22524922.03
18,48825052.16
19,75025162.30
21,01325262.44
22,27525352.58
23,53825422.71
24,80025502.85
27,65025123.23
29,1002,368
3.60
31,76024683.77
34,42025603.94
37,08026434.11
I60Z1BTUH
WATTSCOP
20,32529662.01
21,65029852.13
22,97530022.24
24,30030172.36
25,62530302.48
26,95030432.60
28,27530542.71
29,60030652.83
32,70031013.09
35,80031313.35
38,81532773.47
41,83034143.59
44,84535423.71
Form No S3460-820Supersedes S3460-120Page 7 of 12
1. dBA @ 10 feet, Values recorded in Bard Manufacturing Company, Inc. Sound Lab Facility.2. Actual field results may vary with classroom design and construction.3. Integrated values calculated per ANSI/ASA S12.60-2009 / Part 2, Section 5.2.2.1, Table 2 Triple Mode
Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17%4. Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1. Integrated Sound
Values are also applicable for use in learning spaces for LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBa. Results referenced were recorded in The Bard Manufactur-ing Company, Inc. Sound Lab Facility. Actual field application results may vary with classroom design and construction methods.
Vent: CRV IPBDFZ-12 Duct Free12" Plenum Box
IPBDFZ-18 Duct Free18" Plenum Box
Ducted @ 0.20" ESP at Full Load Rated CFM
Model Operation CRV Off CRV @ 300
CRV @ 375
CRV @ 450 CRV Off CRV @
300CRV @ 375
CRV @ 450
CRV Off
CRV @ 300
CRV @ 375
CRV @ 450
I36Z Integrated 37.5 36.8 37.2 37.3 35.3 35.9 36.0 36.3 36.1 36.5 36.6 36.9
I48Z Integrated 36.9 37.0 37.0 37.4 36.7 36.9 37.2 37.1 37.4 37.5 37.4 37.8
I60Z Integrated 39.0 39.3 39.2 39.4 39.0 39.0 39.1 39.2 38.0 38.4 38.3 38.5
I36Z, I48Z, I60Z Indoor Sound Data at 10 Feet
ModelI36Z I48Z I60Z
66.6 67.9 67.8
Outdoor Sound Data at 10 Feet
Factory Setting(s) shaded in Gray
Form No S3460-820Supersedes S3460-120 Page 8 of 12
I-TEC Accessory Model NumbersWall Sleeves (Required Option – Select One)Model #: Description:
IWS-A Wall Sleeve adjustable 5.5 to 8.5" total depth of wall system
IWS-B Wall Sleeve adjustable 8.0 to 13.5" total depth of wall system
IWS-C Wall Sleeve adjustable 13.0 to 23.5" total depth of wall system
Outdoor Louver Grilles (Required Option – Select One)Model #: Description:
ILG-10 Clear anodized aluminum
ILG-20 Medium bronze anodized aluminum
ILG-30 Dark bronze anodized aluminum
Duct-Free Plenum BoxesModel #: Description:
IPBDFZ12-X 12" high — Beige. White linear slot grilles, side w/shutoff damper
IPBDFZ12-1 12" high — White. White linear slot grilles, side w/shutoff damper
IPBDFZ12-4 12" high — Gray. White linear slot grilles, side w/shutoff damper
IPBDFZ18-X 18" high — Beige. White linear slot grilles, side w/shutoff damper
IPBDFZ18-1 18" high — White. White linear slot grilles, side w/shutoff damper
IPBDFZ18-4 18" high — Gray. White linear slot grilles, side w/shutoff damper
Cabinet ExtensionsModel #: Description:
ICXZ28-X 28" extension for ceilings up to 10'2", beige paint
ICXZ28-1 28" extension for ceilings up to 10'2", white paint
ICXZ28-4 28" extension for ceilings up to 10'2", gray paint
NOTE 1: Use of Riser Platforms will increase maximum ceiling height by riser height.
NOTE 2: Cabinet Extensions can be used with ducted systems to enclose ductwork or piping, and can also be used with Duct-Free Plenum Boxes to enclose to ceiling if desired. Extensions can be trimmed to height as needed.
Riser PlatformsModel #: Description:
IRPZA-3-X Riser platform 3" with trim kit, beige paint
IRPZA-3-1 Riser platform 3" with trim kit, white paint
IRPZA-3-4 Riser platform 3" with trim kit, gray paint
IRPZA-6-X Riser platform 6" with trim kit, beige paint
IRPZA-6-1 Riser platform 6" with trim kit, white paint
IRPZA-6-4 Riser platform 6" with trim kit, gray paint
NOTE: Use of Riser Platforms will increase maximum ceiling height by riser height.
Wall Curbs
Model #: Description:
ICURB740 7" Deep Curb to allow sleeve installation with a 40" window sill height
Side Trim KitModel #: Description:
ISTZ4-X 4" Side Trim Kit, beige paint, adaptable for up to 12' ceilings
ISTZ4-1 4" Side Trim Kit, white paint, adaptable for up to 12' ceilings
ISTZ4-4 4" Side Trim Kit, gray paint, adaptable for up to 12' ceilings
Other Optional AccessoriesModel #: Description:
AHCK-2 Anti-Huffing Locking Refrigerant Caps (2) with Key
SK111 Hard Start Kit for 1-Phase Models (I36Z1-A) OnlySK118 Hard Start Kit for 1-Phase Models (I48Z1-A & I60Z1-A) Only
I-TEC Accessories — Optional per Job Requirement
Form No S3460-820Supersedes S3460-120Page 9 of 12
_ 21
1 8_
3 4_
33 4"
22
"
Secti
on
25"
Lowe
r"Up
per
Secti
on
713 4
_ 21
3 4_
Fron
t Vie
w
Uni
t Spe
cific
atio
n Sh
eet
Top
View
Rig
htSi
deVi
ew
(2) U
nitDr
ains
Back
View
MIS-
3114
B
Vent
Exha
ust
Air F
ilters
(2) 1
6"x 2
5"
Retur
n Air
Elec
tricHe
at
Lock
ingDo
orLa
tch
Contr
ol Pa
nel
Filter
s
Disc
onne
ct
(4) L
ift-Of
fHi
nges
Elec
trical
Door
Latch
Lock
ing
Wire
Chan
nel
(2) 2
"x24"
x30"
Fron
t For
klift H
oles
(Rem
ove F
ront
Trim
)
58"
16 "
94 "
Entra
nce
High
Volt
age
Entra
nce
Low
Volta
ge
20" x
24" S
upply
Fram
e
"To
talDe
pth
3 887
"
" With
Side
s Rem
oved
"
26"
2"
4
41
2
31
161
" Tota
l Widt
h
318
20"
" 428
1
9"1
4
18"
346
1 8
24"
Open
ings
(2) R
eturn
Side
Forkl
iftHo
les(R
emov
e Side
s)
(2) S
ideHa
ndles
30" W
ithDo
ors a
nd
"
Side
s Rem
oved
501 4
22 "
Supp
lyAi
r
Retur
nAi
r
Outer
Slee
ve
Air
Retur
n
Slee
veInn
er
Slee
veOu
ter
Slee
veInn
er
PART
#545
1-02
7RU
BBER
MATT
(2) O
pt.Un
it Dra
inEn
tranc
es
WIR
E TI
ESPA
RT#7
950-
031
" 1
43
8 "
13 4"
RUBB
ERMA
TT &
FRON
T TR
IMLO
CATI
ON
Form No S3460-820Supersedes S3460-120 Page 10 of 12
73 8"
183 4"
35"
171 2"
Rig
ht S
ide
View
Fron
t (W
all O
nly)
Vie
w
Wal
l Sec
tion
View MI
S-31
76 B
C LC L
IRPZ
RIS
ER K
ITDI
M A
DIM
BDI
M C
NONE
31 1/
2" - 3
4 1/2"
MAX
30 1/
32"
94 5/
8"
IRPZ
A-3 (
3")
34 1/
2" -
37" M
AX33
1/32
"97
5/8"
IRPZ
A-6 (
6")
37 1/
2" - 4
0 1/2"
MAX
36 1/
32"
100 5
/8"
IRPZ
RIS
ER K
ITDI
M A
DIM
BDI
M C
NONE
31 1/
2" - 3
4 1/2"
MAX
30 1/
32"
94 5/
8"
IRPZ
A-3 (
3")
34 1/
2" -
37" M
AX33
1/32
"97
5/8"
IRPZ
A-6 (
6")
37 1/
2" - 4
0 1/2"
MAX
36 1/
32"
100 5
/8"
Optio
nal
Duct
Floor
Wall Grille
Wall
Slee
ve**
Ceilin
g
Teles
copin
g
Outsi
de
Unit
Optio
nal
Trim
orSu
pply
Duct
Box
31 1/
2" M
in. 34
1/2"
Max
.
Moun
ting h
oles
(4) op
tiona
l Unit
C LC L
Optio
nal T
opBr
acke
t
** Se
parat
e tele
scop
ing sl
eeve
s ava
ilable
for d
ifferen
t wall
thick
ness
es.
Cente
red on
* Hi
gher
Sill H
eights
Ach
eivab
le W
ith B
ase K
it.
*
Wall
Open
ingOu
tside
Room
Floo
r Lev
el
(4) op
tiona
l Unit
Moun
ting h
oles
Slee
ve M
ounti
ngHo
le Lo
catio
ns
FLOO
R MO
UNTIN
G HO
LE&
CENT
ERLIN
ES
8 20
DIM
C
3 "
20"
DIM
A
8 49
Cen
tered
8
Cen
tered
43-1
/4" M
ax.
20"
"
48-1
/2" M
ax.
6"
48" M
in.
7
"
20" 43
42-3
/4" M
in.
158
8" 1
16"
8"7
20
3"3 "
438
7"
20"
" 20
87
DIM
B
561 2"
Form No S3460-820Supersedes S3460-120Page 11 of 12
DIMENSIONAL CHARTMODEL NO. DIM. A DIM B.IPBDFZ12 12" 106.5" (8'-10.5")IPBDFZ18 18" 112.5" (9'-4.5") MIS-3168 A
IPBDFZ12 AND IPBDFZ18DUCT-FREE PLENUM BOX
DIMENSIONS
MIS-3168 A
IPBDFZ12 AND IPBDFZ18DUCT-FREE PLENUM BOX
DIMENSIONS
7' - 10.5"
A
94.5"
B
ROUTE HIGH VOLTAGEUNIT POWER THROUGH
BOX IN CONDUIT
ROUTE LOW VOLTAGEUNIT POWER THROUGH
BOX IN CONDUIT
Form No S3460-820Supersedes S3460-120 Page 12 of 12
Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com
Due to our continuous product improvement policy, all specifications subject to change without notice.
I-TEC 2-Stage Air Source Heat Pumps Model Number Nomenclature
Form No. S3460
August 2020
Supersedes: S3460-120
CompleteStat™ Selection Guide
Vent Type Type ofVent Control
BACnet Communication
Ethernet Connection
ControlCode Description CompleteStat
Part Number
NoneN/A Yes No 1 CompleteStat THO (Temp, Humidity & Occupancy) CS9B-THO
N/A Yes Yes 3 CompleteStat THO w/Ethernet CS9BE-THO
CRV
On/Off Yes No 1 CompleteStat THO (Temp, Humidity & Occupancy) CS9B-THO
Demand Yes No 2 CompleteStat THO w/CO2 CS9B-THOC
On/Off Yes Yes 3 CompleteStat THO w/Ethernet CS9BE-THO
Demand Yes Yes 4 CompleteStat THO w/CO2 & Ethernet CS9BE-THOC
I 36 Z 1 – A 0Z M P 4 X X 2
Controls:X = 24v terminal block Only w/o CompleteStat1 = CompleteStat THO (Temp, Humidity & Occupancy)2 = CompleteStat THO w/CO23 = CompleteStat THO w/ Ethernet4 = CompleteStat THO w/CO2 & EthernetNote: CompleteStat must be field installed & wired. All units have 24V terminal block. See Selection Guide.
Coil Treatment:X = Std. Hydrophilic Fin Evap. & Uncoated Alum. Cond. Coil1 = Phenolic Coated ID coil2 = Phenolic Coated OD coil3 = Phenolic Coated ID & OD coil
Door Vinyl Graphics OptionsX = No GraphicsA = Stacked Books (Color Code 1 - White Only)B = Paint Brush (Color Code 1 - White Only)
Color:X = Beige, Painted Steel1 = White, Painted Steel4 = Gray, Painted Steel
Filter:P = 2 inch pleated MERV 8M = 2 inch pleated MERV 11N = 2 inch pleated MERV 13
Vent Option:B = Blank Off PlateM = Multi-Speed CRV
Electric Heat 1-Phase 230/208 3-Phase 230/208 3-Phase 4600Z=No heat w/Breaker 0Z=No heat w/Breaker 0C=No heat w/Circuit Breaker04 = 4KW 06 = 6KW 0Z=No heat w/Toggle Disconnect05 = 5KW 09 = 9KW 06 = 6KW10 = 10KW 15 = 15KW 09 = 9KW15 = 15KW 18 = 18KW 15 = 15KW20 = 20KW 18 = 18KW
Electrical Rating:A = 230/208, 60-1B = 230/208, 60-3C = 460-60-3
Revision Level
System Type:Z = Heat Pump
Nominal Capacity: 30 = 30,000 BTUH36 = 36,00048 = 48,00060 = 60,000
Model Series
Note All 230/208V units with KW have circuit breaker. All 460V units with KW have Toggle Disconnect.
BACnet is standard - all versions, shielded twisted pair.
These models also have CAT 5 port for ease of networking in addition to twisted pair terminals.
Demand control for ventilation is ON/OFF based on CO2 set-point.