EFFECT OF VARIOUS LOAD ON POWER SYSTEM PROTECTION SUN RUIHAO A project report submitted in partial fulfilment of the requirements for the award of the degree of Master of Engineering (Electrical-Power) Faculty of Electrical Engineering Universiti Teknologi Malaysia JANUARY 2012

Upload: phungtruc

Post on 09-Aug-2019

215 views

Category:

Documents


0 download

TRANSCRIPT

i

EFFECT OF VARIOUS LOAD ON POWER SYSTEM PROTECTION

SUN RUIHAO

A project report submitted in partial fulfilment of the

requirements for the award of the degree of

Master of Engineering (Electrical-Power)

Faculty of Electrical Engineering

Universiti Teknologi Malaysia

JANUARY 2012

iii

DEDICATION

To my beloved mother and father

谨此献给含辛茹苦的,我所爱的父母

iv

ACKNOWLEDGEMENTS

ACKNOWLEDGEMENTS

I would like to express my sincere gratitude to my supervisor Prof. Ir. Dr.

Abdullah Asuhaimi bin Mohd Zin for him continuous guidance, advice and support.

Besides, I would like to thank some of my local friends. Thanks for them give me

lots of ideas and help in my study, and give me a wonderful life in UTM.

Finally, I would like to extend special word of appreciation to the most important

person in my life: my dear father SUN JUN, and my lovely mother YAN YU, for

their endless love and selfless support to allow me further study in Malaysia.

v

ABSTRACT

ABSTRACT

This project established a reclosing simulation mode on 161kv line with

bilateral power source of regional network based on PSCAD, and to do the

simulation when the different types of fault occur on the various load condition. On

this basis, analysis for the different types of fault occur is done, and effect of various

loads of the protection devices in the power system is studied. The key point analysis

focused on the effect of residue voltage produced from the induction motor load in

case of the transient fault and permanent fault occurred on the transmission line

separately.

This thesis has analyzed the changing rule of the residual voltage produced

from the induction motor when the faults occurred. Hence, a proper reclosing time

was identified, and a better control system, which able to improve the residual

voltage on the power system protection, was proposed.

vi

ABSTRAK

ABSTRAK

Projek ini bertujuan untuk mensimulasikan sumber kuasa elektrik rangkaian

serantau dua hala 161kV dengan menggunakan PSCAD. Kajian ini adalah hasil

simulasi mod “reclosing” pada sistem talian penghantaran 161kV ke atas jenis

keadaan beban yang berlainan. Simulasi ini juga mengesahkan pelbagai kesilapan

atau kegagalan yang mungkin boleh berlaku kepada sistem. Oleh itu, analisis ini

dibuat berdasarkan pelbagai kesan beban peranti perlindungan dalam sistem kuasa.

Analisis tertumpu kepada kesan voltan yang dihasilkan daripada beban yang

berdasarkan motor induksi dalam kes kesalahan fana dan kerosakan tetap yang

berlaku dalam talian penghantaran secara berasingan.

Tesis ini telah menganalisis perubahan peraturan voltan yang dihasilkan

daripada motor induksi apabila kesalahan berlaku. Oleh itu, masa yang sesuai untuk

“reclosing” telah dikenal pastikan. Selain itu, sistem kawalan yang lebih baik, di

mana dapat meningkatkan voltan baki perlindungan sistem kuasa, telah dicadangkan.

vii

TABLE OF CONTENTS

1 INTRODUCTION 1

1.1 Background

1.2 Problem Statement

1.3 Objectives

1.4 Scope

1.5 Thesis Outline

1

3

4

4

4

2 LITERATURE REVIEW 6

2.1 Introduction

2.2 Faults on Power System

2.3 Acuter Event

6

6

8

CHAPTER TITLE PAGE

DECLARATION

DEDICATION

ACKNOWLEDGEMENT

ABSTRACT

ABSTRAK

TABLE OF CONTENTS

LIST OF TABLES

LIST OF FIGURES

LIST OF ABBREVIATIONS

LIST OF APPENDICES

ii

iii

iv

v

vi

vii

x

xi

xiii

xiv

viii

2.3.1 Fault Arc Path and Effect on Motor

2.4 Distance Relay

2.5 Auto-Recloser

2.5.1 Setting Reclosing Time

2.6 Induction Motor and Residue Voltage

2.6.1 The Theory Analysis of Induction Motor

Residue Voltage

2.6.2 Research on Residue Voltage

2.7 Summary

9

10

11

13

16

19

20

23

3 METHODOLOGY 24

3.1 Introduction

3.2 Process Analysis

3.3 Circuit Construction

3.4 Components

3.4.1 Source

3.4.2 Multimeter

3.4.3 Transmission Line

3.4.4 Circuit Breaker

3.4.5 Fault Component

3.4.6 Induction Motor

3.4.7 Online Frequency Scanner

3.4.8 Distance Relay

3.5 Summary

24

25

25

26

27

28

28

30

31

32

33

34

38

4 RESULTS AND DISCUSSIONS 39

4.1 Introduction

4.2 No Fault Condition

4.3 Transient Fault Condition

39

39

41

ix

4.3.1 Transient Fault without Motor Load

Condition

4.3.2 Transient Fault with Induction Motor

Load Condition

4.4 Permanent Fault Condition

4.4.1 Permanent Fault without Motor

Load Condition

4.4.2 Permanent Fault with Motor Load

Condition

4.5 Summary

42

46

56

56

59

67

5 CONCLUSIONS AND RECOMMENDATIONS 68

5.1 Conclusions

5.2 Recommendation

68

69

REFERENCES 70

APPENDIX A 72

x

LIST OF TABLE

TABLE NO.

2.1

TITLE

Main Parameter of Induction Motor

PAGE

22

3.1 Configuration of Voltage Source

27

xi

LIST OF FIGURES

FIGURE NO. TITLE PAGE

1.1 The typical load on transmission line network 3

2.1 The Photo of the fault type on transmission line 7

2.2 One-line of Monsanto-Johnsonville 161kv line 8

2.3 Power Quality data captured during unsuccessful

high-speed reclose.

8

2.4 3-Zone distance protection scheme 11

2.5 The typical operational settings of auto-recloser 12

2.6 Principle diagram of synchronous reclosing 14

2.7 Diagram of ΔU and δ on synchronism check relay 16

2.8 Auto-reclosing on lines with motors 17

2.9 Induction motor equivalent circuit. 21

2.10 Residual voltage and rotor current oscillogram in single

motor

21

2.11 Simulating model of reclosing for induction machine 22

2.12 Result of simulating 22

3.1 The schematic diagram of project flow 25

3.2 Establishment of 161 kV line reclosing on without

motor load

26

3.3 Establishment of 161 kV line reclosing on induction

motor load.

26

3.4 Three Phase Voltage Source 27

3.5 Multimeter 28

3.6 Transmission Line 28

3.7 The Type of Transmission Tower 30

3.8 Parameters of Line Model 30

3.9 Circuit Breaker 30

xii

3.10 Three Phase Fault 31

3.11 The Fault Type 31

3.12 Squirrel Cage Induction Machine 32

3.13 The induction motor definition by CSMF 32

3.14 Online Fast Fourier Transform (FFT) 33

3.15 Distance relay design by PSCAD 34

3.16

3.17

3.18

3.19

3.20

3.21

4.1

4.2

4.3

4.4

4.5

4.6

4.7

4.8

4.9

4.10

4.11

4.12

4.13

The control part of Distance relay

The Distance relay definition by CSMF

Line to Ground Impedance Component

The Distance relay definition by CSMF

Line to Line Impedance Component

MHO Circle Component

No Fault Condition

Without motor load condition model by PSCAD

Signal Phase Fault without Motor Load Condition

Signal Phase Fault without Motor Load Condition

Induction motor load condition model by PSCAD

Three Phase Fault without Motor Load Condition

Three Phase Fault with Induction Motor Load

Condition

Three Phase Fault with Induction Motor Load

Condition

Three Phase Fault with Induction Motor Load

Condition

Permanent Fault without Motor Load Condition

Permanent Fault without Motor Load Condition

Permanent Fault without Motor Load Condition

Permanent Fault with Motor Load Condition

35

35

36

36

37

37

40

42

44

46

46

49

51

53

56

58

61

62

64

4.14 Permanent Fault with Motor Load Condition 66

xiii

LIST OF ABBREVIATIONS

Ea - Voltage Source

Ia - Current phase a

UV - Under-Voltage

OV - Over-Voltage

TEF - Transient Energy Function

KV - Low Voltage Element

KY - Synchronous Element

AAR - Auto-Recloser

MATLAB - Math Lab

W - Motor Speed

CSMF - Continuous System Model Function

FFT - Fast Fourier Transform

MAG - Magnitude

PH - Phase

PSCAD - Power System CAD

xiv

LIST OF APPENDICES

APPENDIX PAGE

A Output of Channels 72

1

CHAPTER 1

1 INTRODUCTION

INTRODUCTION

1.1 Background

Electrical energy is the most popular form of energy due to it can be

transported easily at high efficiency and reasonable cost [1]. The modern power of

engineering consists of three main subsystems, which are generation, transmission

and distribution. In order to provide the electrical energy to consumer in usable form,

the transmission and distribution system have to be satisfying some of the basic

requirements, which are shown as below [2]:

i. Provide the power consumers needed for all the time.

ii. Maintain a stable and nominal voltage that does not vary by more than

+10%.

iii. Maintain a stable frequency that does not vary by more than +0.1 Hz.

iv. Supply energy at an acceptable price.

v. Meet the standard of safety.

vi. Follow the environmental standards.

Transmission line in power system is an important component, where it is

used to transmit the power. The operation experiences the power of system shows

that the faults occurred on transmission lines are mostly transient; hence the

automatic recloser is widely used in transmission line. It is a very important

equipment to guarantee the security of operation power line and improve the

2

reliability of power supply. Besides, it is an effective method to improve the stability

and reliability of power systems. However, the present auto-recloser technique

normally employs a prescribed reclosing time, which is the breaker will be re-closed

after a fixed period following a tripping operation.

In the industrial production sectors, medium and large induction motors have

been widely used, often used as an important auxiliary production. Its capacity can

reach up to thousands of kilowatts, no matter the operations can reclose or cannot; all

the consequence can affect the entire production process. Once the electrical outage

for any reason, it will cause great loss of production [1-2].

In practice, when the transient fault occurred, the produce of the short-term

depression on power supply, which led to the protection device tripped, and make the

loss of motor power is a common phenomenon. Luckily, this failure is usually

temporary, and let the motor rapidly recover the power supply after short-term outage;

hence the production loss can be reduced. This requires a temporary reclose after

troubleshooting operations to ensure the normal operation of the motor [3-5].

The various components constitute in the power system, the transmission

lines have a wide working area and can support a variety of natural conditions and

the rate of failure is the highest in all electrical equipment. Therefore, the protection

of normal transmission line operation is an important task in the power system. The

installation of auto-recloser is to ensure the rapid restoration if necessary, and to

protect the circuit during normal operation.

3

1.2 Problem Statement

Weak

SourceE F

A D

BC

Pulp and

paper mill

(motor)

Utility

161 kV

Utility

161 kV

Strong

Source

Figure 1.1: The typical load on transmission line network

With reference to Figure 1.1, points E and F are circuit breakers which are

installed with protective device, first to assume there without motor load, when faults

occur on the transmission line the utility protective relays at each end detect the fault

and initiate tripping of their respective breaker. Breakers E and F will trip. Protection

device at E will operate in the dead line live bus condition, followed by F. After the

protective device E operates, the transmission line become live, the protective device

F will be reclose during this condition.

In reality, there are large motor loads connected to transmission line. When

the faults occur in the transmission line, the supply is removed from an induction

machine, flux is trapped in its rotor. This flux decays with time and produces a

residual voltage in the machine windings until its rotation ceases. Residual voltage

can decay in a few cycles in small machines but may require up to five seconds in

larger machines. Higher inertia machines will tend to act as generators feeding the

lower inertia machines on the bus such that the entire group decays together. Means

that the motor load will become generator which supply power to grid. The power

will be supplied from strong source to weak source, so the problem is to optimize the

protective device setting in the system, which can work normal conduction in live

line live bus condition.

4

1.3 Objective

The objectives of this study are:

(i) To study the performances of protective device operate safely and

successfully during various load condition.

(ii) To study the residual voltage generated by induction motor.

(iii) To propose some protection elements to decrease the effect of residual

voltage on power system.

1.4 Scope

The two main goals of a transmission line protection scheme are to

successfully clear faults and to successfully reclose the circuit once when fault has

been cleared. The chances of success are greatly reduced in the presence of

significant induction motor load. The presence of motor load, can affect the system

protection, so must proper scheme adjustments could be made.

The scopes of the project are as below:

(i) The various load condition effect on the transmission line reclosing

will be studied.

(ii) In this project, the protection elements setting will be considered.

(iii) The modeling and simulation using power system CAD software.

1.5 Thesis Outline

First chapter is briefly introducing protective devices which are used in

transmission line and a general idea about the project. This chapter discusses about

the main objectives, scope, problem statement and describes the project methodology

that will be used.

5

Second chapter is written based on the finding from literature review. This

chapter elaborates about protective device used related with induction motor of

transmission line, and the residue voltage generated by induction motor. It is about

the basic theory or general topic related this project.

Third chapter is mainly discussed the methodology and the background of the

project.

Fourth chapter is to describe the simulation and results of the design using

PSCAD consist of the components.

Fifth chapter is the conclusion and also the last chapter concludes the project

and highlights some of the recommendation to improve the project.

70

REFERENCE

REFERENCE

1. Abdullah Asuhaimi Bin Mohd. Zin, “Power system protection” 2010.

2. Hadi Saadat, “Power System Analysis” McGraw Hill, 2004.

3. Les Hewitson, “Practical Power Systems Protection” Pearson Prentice Hall,

2004.

4. Russell W. Patterson George T. Pitts, “Reclosing and Tapped Motor Load”

61st Annual Georgia Tech Protective Relaying Conference May 2-4, NY,

2007

5. LI Yi feng, “Discussions for Setting Reclosing Time of Transmission Lines”

The Information College of Guangdong Ocean University, Journal of

Guangdong University, Zhanjiang 524088, China, 2007.

6. Kuo-HsiungTseng, Wen-ShiowKao, and Jia-Renn Lin, “Load Model Effects

on Distance Relay Settings”, IEEE transactions on power delivery, VOL. 18,

NO. 4, October 2003, 13(1):21-24.

7. Shaltout A, Al-omoush M, “Reclosing torques of large motors with stator

trapped flux”, IEEE Transactions on Energy Conversion, 1996, 11(1):84-90.

8. Deng Jianguo, “Transient analysis on reclosing of three-phase motor”,

Electric power Automation Equipment, 2004, 24(1):37-41.

9. J. Berdy and P. G. Brown, “High-Speed Reclosing Systemand Machine

Considerations” IEEE Transactions on Energy Conversion, NY. 2009, 42(2).

10. Meyer Kao Tennessee Valley, “Analysis of Underfrequency Load Shedding

and Reclosing into a Motor Load on a TVA 161 kV Transmission Line”.

Authority Presented to the Georgia Tech Fault and Disturbance Analysis

Conference May 1-2, 2006.

11. Ma Hongzhong, Hu Qiansheng, Zhang Lim in, Han Jingdong, “Research on

Residua l Voltage of AC Motor after Dump” S&M Electric Machines, 2005,32

(5):3-5.

12. Line Protection Subcommittee Working Group D5 of the IEEE Power

71

Engineering Society, “Summary of C37.230-2007, IEEE Guide for Protective

Relay Applications to Distribution Lines”, Power System Relaying

Committee. 2006, 17(1).

13. Zhang baohui, “Optimal reclosing time and its setting calculation” IEEE

Transactions on Energy Conversion, China. 2009.

14. Xie Kefu, “Transient Analysis of Three -phase Induction Motor with

Momentary Voltage Dips”, Journal of Zhejiang University ( Engineering

Science), China. 2003.

15. G.E Alexander and J.G Andrichak, “Ground Distance Relaying: Problems

and Principles”, General Electric Company Malvern, PA, 1991

16. Yu Ji Akiyama, member, IEEE, “Induction Motor Residual Voltage”

Kanagawa Institute of Technology, JAPAN, 2002.

17. Aiyuan Wang, Zhihao Ling, Wenbo Liu,“ Residual Voltages Analysis in

Reclosing Process for Induction Machine”, Proceedings of the 7th

World

Congress on Intelligent Control and utomation June 25 - 27, Chongqing,

China, 2008,