hydronic engineering handbook engineering great solutions...hydronic resistance, all the available...

56
Engineering GREAT Solutions Hydronic Engineering Handbook Balancing of Radiator Systems Thermostatic Control & Balancing

Upload: others

Post on 03-Oct-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

EngineeringGREAT Solutions

Hydronic Engineering Handbook

Balancing of Radiator Systems

Thermostatic Control & Balancing

Page 2: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

2

Page 3: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

3

Balancing of Radiator Systems

Contents

Why balance? ......................................................................................................................... 5

1- Balancing of radiator systems ......................................................................................... 7

1.1- Overflowscauseunderflows .................................................................................... 7

1.2- Overflowsindistribution ........................................................................................... 9

2 Radiator valves .................................................................................................................. 11

2.1- General .................................................................................................................... 11

2.1.1-Whentheinletvalveisusedonlytoisolate

2.1.2-Whentheinletvalveisusedtoisolateandadjusttheflow

2.2- Whatisathermostaticvalve? .................................................................................. 12

2.3- Thermostaticvalvesandthesupplywatertemperature........................................... 13

2.4- Isthethermostaticvalveaproportionalcontroller? ................................................. 14

2.5- Shouldaplantbehydraulicallybalancedwithallthermostaticvalvesfullyopen? .... 17

2.6- Accuracytobeobtainedontheflow ........................................................................ 18

3 Radiators .......................................................................................................................... 20

3.1- Nominalanddesignconditions .............................................................................. 20

3.2- Selectionofaradiatornotworkinginnominalconditions ....................................... 20

3.3- Emissionofaradiatorasafunctionofthewaterflow .............................................. 21

3.4- Selectionofthedesignwatertemperaturedrop ...................................................... 22

3.5- Existingplants ......................................................................................................... 23

4 Two-pipe distribution ....................................................................................................... 24

4.1- Balancingofradiatorsbasedonaconstant∆p ....................................................... 24

4.1.1-Choosingthedesigndifferentialpressure

4.1.2-Presettingthethermostaticvalve

4.1.3-Non-presettablethermostaticvalves

4.1.4-Limitationsofchoicewiththesame∆pforallradiators

4.2- Presettingbasedoncalculated∆p......................................................................... 29

4.3- Constantorvariableprimaryflow ............................................................................ 30

4.3.1-Aboutnoise

4.3.2-Constantprimaryflow

4.3.2.1-Abypassandasecondarypumpminimisethe∆ponthebranch

4.3.2.2-ABPVstabilisesthe∆ponthebranch.

4.3.3-Variableprimaryflow

4.3.3.1- A plant with balancing valves

4.3.3.2-A∆pcontrollerkeepsthe∆pconstantacrossabranch

Page 4: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

4

5 One-pipe distribution ...................................................................................................... 39

5.1- General .................................................................................................................. 39

5.1.1-Advantages

5.1.2-Disadvantagesandlimitations

5.1.3-Emissionfrompipes

5.2- One-pipevalves ..................................................................................................... 44

5.2.1-Constantbypass–variableKv

5.2.2-Variablebypass–constantKv

5.2.3-Protectionagainstdoublecirculation

5.3- Proportionoftheloopflowintheradiator(λcoefficient) ......................................... 45

5.3.1-50%flowintheradiator(λ=0.5)

5.3.2-Choiceofanotherflowintheradiator

5.4- Theloopflow ........................................................................................................... 47

5.4.1-Basedonagiven∆T

5.4.2-Basedonthelargestradiatorintheloop

5.4.3-Finalchoiceoftheloopflow

5.5- Pressurelossesintheloop ..................................................................................... 48

Appendices

A- Calculation of radiators in several conditions ............................................................ 49

B- Pressure losses in pipes ............................................................................................... 52

Furtherinformationisavailableinourgeneralbookonbalancing“Totalhydronicbalancing”.

Page 5: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

5

Balancing of Radiator Systems > Why balance?

Why balance?

Manypropertymanagersspendfortunesdealingwithcomplaintsabouttheindoorclimate.Thismaybethecaseeveninnewbuildingsusingthemostrecentcontroltechnology.Theseproblemsarewidespread:

• Someroomsneverreachthedesiredtemperatures.

• Roomtemperaturesoscillate,particularlyatlowandmediumloads,eventhoughtheterminalshavesophisticatedcontrollers.

• Althoughtheratedpoweroftheproductionunitsmaybesufficient,designpowercan’tbetransmitted,particularlyduringstart-upafterweekendornightsetback.

Theseproblemsfrequentlyoccurbecauseincorrectflowskeepcontrollersfromdoingtheirjob.Controllerscancontrolefficientlyonlyifdesignflowsprevailintheplantwhenoperatingatdesigncondition.

Theonlywaytogetdesignflowswhenrequiredistobalancetheplant.Balancingmeansadjustingtheflowsatcorrectvaluesatdesigncondition.Avoidingunderflowsatdesignconditionmakessurethatunderflowswillbeavoidedinallothernormalconditions.Balancingisnecessaryforthreereasons:

1. The production units must be balanced to obtain design flow in each boiler or chiller.Furthermore, inmostcases,theflowineachunithastobekeptconstantwhenrequired.Fluctuationsreducetheproductionefficiency,shortenthelifeoftheproductionunitsandmakeeffectivecontroldifficult.

2. Thedistributionsystemmustbebalancedtomakesureallterminalscanreceiveatleastdesignflow,regardlessofthetotalaverageloadontheplant.

3. Thecontrolloopsmustbebalancedtobringabouttheproperworkingconditionsforthecontrolvalvesandtomakeprimaryandsecondaryflowscompatible.

Thishandbookdealswiththebalancingofradiatordistributionsystems.

Otherhandbooksavailableare:

Handbook1:Balancingofcontrolloops.

Handbook2:Balancingofdistributionsystems.

Handbook4:Balancingwithdifferentialpressurecontrollers.

Page 6: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

6

CoolingHeating%45

35

25

15

5

20 21 22 23˚C

35

25

15

5

20 21 22 23˚C

%45

Why is the average temperature higher in a plant that is not balanced? During cold weather it wouldbetoohotclosetotheboilerandtoocoldonthetopfloors.Peoplewouldincreasethesupplytemperatureinthebuilding.Peopleonthetopfloorswouldstopcomplaningandpeopleclose to the boiler would open the windows. During hot weather the same applies. It is just that itwouldbetoocoldclosetothechiller,andtoohotonthetopfloors.Onedegreemoreorlessin a single room rarely makes any difference to human comfort or to energy costs. But when the average temperature in the building is wrong, it becomes costly.

Onedegreeabove20°Cincreasesheatingcostsbyatleast8percentinmidEurope(12percentinthesouthofEurope).Onedegreebelow23°Cincreasescoolingcostsby15percentinEurope.

Percentage increase in energy costs for every degree C too high, or too low, relative to average building temperature.

Page 7: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

7

Balancing of Radiator Systems > 1. Balancing of radiator systems

1. Balancing of radiator systems

1.1 Overflowscauseunderflows

The design flow must pass through each radiator at design condition, which requires individual local adjustment.

Atfirstsight,therewouldappeartobenoadvantageinbalancingaheatingplantequippedwiththermostaticvalvesastheirfunctionistoadjusttheflowtothecorrectvalue.Hydronicbalancingshouldthereforebeobtainedautomatically.

Thiswouldbemoreorlesstrueinnormaloperationprovidedthatallcontrolloopsarestable.However,unbalancedradiatorscreatemajordistortionsbetweenflows.Letusconsidertworadiatorsonthesamebranch,one500Wandtheother2500W.Theinstallerusuallyinstallsthesamethermostaticvalvesonallradiators.Theradiatorheadlossisnormallynegligibleandtheflowislimitedmainlybythethermostaticvalve.Flowswillthereforebethesameforbothradiators.Ifthisflowisrightforthe2500Wradiator,itisfivetimesthedesignvalueforthe500Wradiator.

Asifthatwerenotenoughtocreateproblemsinaplant,otherdistortionsareadded.Forexample,thermostaticvalvesleftatthemaximumsetpoint,willkeepthemopenpermanently.Ifthemaximumflowisnotlimited,theseoverflowscreateunderflowsinotherpartsoftheplantwheretherequiredroomtemperaturecannotbeobtained.

Restartingtheplant,everymorningafternightsetback,isaseriousproblemasmostthermostaticvalvesareopen.Thiscreatesoverflowsgettingunpredictedpressuredropsinsomepipes,consequentlyreducingtheflowsinunfavouredcircuits.Thesecircuitsdonotreceivesufficientwateruntilthefavouredthermostaticvalvesareattheirnominallift.Thiscausestheplanttohaveanonuniformstart-up,whichmakesmanagementbyacentralcontrollerdifficultandalsomakesanyformofoptimisationpracticallyimpossible.

Figure1.1representsabranchwithfourradiators.ThepressuredropsinthepipesbetweeneachradiatorareonekPaatdesignflow.Theavailabledifferentialpressureis9kPaforthefirstradiatorand6kPaforthelastone.

30 kPa

80 °C 1 2 3 4

Fig 1.1. Branch with four radiators.

Thepresettingsofthethermostaticvalveshavebeenchosentoobtainthedesignflowineachradiator.Thebranchesandrisersarealsobalanced.

Page 8: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

8

Theresultsareintable1.1.

Branchesandrisersbalanced-Thermostaticvalvesbalanced Totalflow

Radiators 1 2 3 4 l/h

Kvthermostaticvalve 0.04 0.15 0.25 0.14

152Flow(l/h) 11 43 65 33

Heatoutput(W) 255 1000 1512 765

Roomt°in°C 20 20 20 20

Table 1.1. Results obtained when the plant is fully balanced.

Now,letusconsiderthecaseofaplantwheretherisersandbranchesarebalanced,buttheradiatorvalvesarenotpreset.Thetotalflowinthebranchiscorrect,buttheradiatorsarenotworkingatdesignflow.Theresultsareshownintable1.2.

Branchesandrisersbalanced Thermostaticvalvesnotbalancedandfullyopen

Totalflow

Radiators 1 2 3 4 l/h

Kvthermostaticvalve 0.8 0.8 0.8 0.8

152

Flow(l/h) 66 45 30 11

Flow(%) 600 105 46 33

Heatoutput(W) 290 1006 1270 573

Heatoutput(%) 114 101 84 75

Roomt°in°C 24.1 20.2 15.2 12.4

Table 1.2. Risers and branches are balanced, but not the thermostatic valves.

Thefirstradiatorreceives6timesitsdesignflow.Thisincreasestheheatoutputbyonly14%.Thatmeansthatthenecessarytimetoreachthedesignroomtemperature,afteranightsetback,isnotreducedsignificantly.Ifthethermostaticvalve1issetatthecorrectvalue,theflowinthefirstradiatorwillbereducedafteracertaintimeallowingthetwolastradiatorstofinallyreceivetheirdesignflow.Start-upisthenmuchlongerthanexpected.

Ifthethermostaticvalveofthefirstradiatorismaintainedfullyopen,radiators3and4willneverobtaintheirdesignflowandtheroomtemperaturesobtainedatdesignconditionaregivenintable1.2(12.4°Cforroom4).

Anotherpossibilityistopresetallthermostaticvalveswithoutanybalancingvalvesinthebranchesandrisers.Inthiscase,thebalancingprocedureisverydifficultasallcircuitsareinteractive.Therefore,alltheexcessofdifferentialpressurehastobetakenawaybythethermostaticvalves,whichcanbenoisy.Moreover,thevalve’smaximumKvissosmallthattheriskofcloggingishigh.

Page 9: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

9

Balancing of Radiator Systems > 1. Balancing of radiator systems

1.2 Overflowsindistribution

An overflow in the distribution creates one or several undesired mixing points and the actual supply water temperature is lower than expected.

Anoverflowinthedistribution,particularlyduringthemorningstart-up,createsanincompatibilityproblembetweenproductionanddistribution.Letusconsidertwotypicalexamples.

A

qs

B

M

qs

tr

qg

tgs

tgr

trqb

qd ts

tr

qc

Fig 1.2. Several circuits are connected to the heating plant through a decoupling bypass.

InFig1.2,ifthedistributionflowqdisgreaterthantheproductionflowqg,thedifferencecirculatesinthebypassinthedirectionBM.AmixingpointisthereforecreatedatMcausingadropinthesupplywatertemperature.Themaximumsupplywatertemperatureinthedistributionislowerthanthemaximumtemperatureobtainedintheboilers.Theplantthereforehasdifficultiesatstart-upastheinstalledpowercannotbetransmitted.Insomeplants,theproblemissolvedbyinstallingadditionalboilers,whichcanincreasetheproductionflowqg,makingitcompatiblewiththedistributionflowqd.Thistypeofsolutionisveryexpensivebothincapitalcostandinoperationastheseasonalefficiencydrops.

Page 10: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

10

qsqs

tr

qg

tgs

tgr

tr

qp

ts

tr

qc

E

F

D

Fig 1.3. Distribution through a closed loop.

InFig1.3,circuitoverflowscausecirculationinpipeFEfromEtowardsFwithamixingpointcreatedinD.Thelastcircuitisthensuppliedfromitsownreturn.Thiscircuitworksunderparticularlybadconditionsandbecomestheplant’s“nightmare”circuit.

Placinganon-returnvalveinpipeEFwouldappeartosolvetheproblem,butitactuallycreatesanotherproblemastheloopisopenandboilerpumpsgointoserieswithcircuitpumps,makingsomecontrolloopsunstable.

Inconclusion,themostefficientandeasiestsolutionistocorrectlybalanceproductionanddistributionensuringtheirflowcompatibility.

Page 11: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

11

Balancing of Radiator Systems > 2. Radiator valves

2. Radiator valves

2.1 General

Fig 2.1. Radiator valves on the inlet and the outlet.

Radiatorvalveshaveseveralfunctions.Oneofthemistoisolatetheradiatorontheinletandtheoutlet.Animportantfunctionisalsotoadjusttheflowtotherequiredvalue.Thisfunctioncanbeachievedeitherbythevalveontheinletorbythereturnvalve.

2.1.1 When the inlet valve is used only to isolate

Whenthemanualvalveon the inlet isonlyused forshut-off function, itsoversizing isnotsoimportant.Thelimitationoftheflowatdesignvalueisobtainedwiththevalveonthereturn,whichtakesthemajorityofthedifferentialpressureavailable.Thisreturnvalvemusthaveaprofiledconetogetadequateauthorityontheflowintherangeofadjustment.Thepresettingofthereturnvalveismadeaccordingtotheexpectedavailabledifferentialpressureandtherequireddesignflow.

ThewaterflowdependsonthedifferentialpressureacrossthevalveanditsKvaccordingtotheequation:

q=100Kv√∆p(qinl/hand∆pinkPa)

TheKvvaluedependsonthedegreeofopeningofthevalve.WhenthevalveisfullyopenthespecificKvobtainediscalledtheKvs.

Thecorrectvalvecanbedeterminedwiththehelpofanomogram,(seee.g.,Fig4.2).

2.1.2 Whentheinletvalveisusedtoisolateandadjusttheflow

Thismanualvalvemustbeprovidedwithaprofiledplugtoobtainaprogressiverestrictionoftheflowwhenshuttingthevalve.Thisprogressivenessonlyworksifthevalveisnotoversizedandthushasasufficientauthority.

TheKvsofthevalveintheinletischosentoobtainapproximatelythedesignflowforthevalve75%open.WhentheavailableKvsistoohigh,onesolutionistolimitthedegreeofopeningofthisvalvetothecorrectKv.Anotherpossibilityistoinstallintheinletadoubleregulatingvalvewheretheshut-offandregulatingfunctionsareindependent.

Page 12: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

12

2.2 What is a thermostatic valve?

Athermostaticvalveisaself-actingautomaticvalvecontrolledbyanexpandingelement.Dependingonthedifferencebetweenthetemperaturesetpointandtheroomtemperature,thevalvegraduallyopensorcloses.

Allthethermostaticvalvesonthemarkethaveatotalliftofseveralmillimetres.However,startingfromthevalveinshutposition,adecreaseintheroomtemperatureof2Kwillopenthevalveabout0.5mm.Thispartofthelift,wherethecontrolvalvenormallyworks,iscalledthenominallift.

Fig2.2showstworelationsbetweenthewaterflowandtheroomtemperature.Curveaisforanunlimitedflowthermostaticvalve.Curvebisforathermostaticvalvewithflowlimitation.Thislimitationisobtainedwithanadjustableresistanceinserieswiththeactiveportofthevalve.

a

b - TA

Room temperatur e

200

100

150

50

014 16 18 20 22

Set point

Nominal liftof 0.5 mm

Fig 2.2. Relation between the water flow and the room temperature for a thermostatic valve supplied at constant differential pressure. a - unlimited flow valve.

b - valve with flow limitation.

Inpractice,thethermostaticvalvereactsgraduallytothechangesintheroomtemperature,unlessthetemperaturestartstodevelopintheotherdirection.Inthiscasetheplugofthevalvedoesnotmoveuntiltheroomtemperaturevariesbyavaluethatexceedsthehysteresis(normallyaround0.5K).Thisphenomenonsometimesgivestheimpressionofastableheattransferfromtheradiatorwhereasthecontrolloopcanbecomeunstableinthelongerterm.

Thermostaticvalvesallowtheachievementofthecorrecttemperatureineachroomindividually.Theycompensateapossibleoversizingoftheradiatorandreduceheatoutputwhenothersourcesofheating(lamps,people,sun,etc.)compensateforpartoftheheatlosses.Inthisrespect,thermostaticvalvesprovidetheuserwithmoreflexibility,improvethecomfortandsaveenergy.

Page 13: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

13

Balancing of Radiator Systems > 2. Radiator valves

2.3 Thermostatic valves and the supply water temperature

Controlling the heat output from a radiator with a thermostatic valve is

quite difficult when the supply water temperature is maintained constant during the whole heating season. For this reason, the supply water temperature is

normally variable and depends, for instance, on outdoor conditions.

Asanexample,wecan takea radiatorpermanentlysuppliedat80°C throughout theentireheating season. The thermostatic valve is assumed to be correctly sized to give designflow at nominal opening (80/60 conditions). The minimum outdoor design temperature is –10°C.

0

10

20

30

40

50

60

70

80

90

100

10 20 30 40 50 60 70 80 90 1000

22° C

20° C

18° C

20° C –10° C5° C

Outdoor temperature

Water flow in %

Heat losses in %

Fig 2.3. The necessary water flow to maintain the room temperature constant as a function of outdoor conditions. The supply water temperature is assumed to be constant and equal to 80 °C.

Fig2.3showsthenecessarywaterflowintheradiatorasafunctionofoutdoorconditions,inordertoobtainroomtemperaturesof18,20and22°C.

Aroundthemeanwintertemperature(te=5°C),awaterflowvariationof4%willchangetheroomtemperatureby2K.Toobtainapreciseroomtemperaturewithin±0.5K,thewaterflowmustbecontrolledwithanaccuracyof±1%.As50%oftheloadcorrespondsto20%oftheflow,theliftofthevalvehastobesetatanopeningof0.1mm(20%ofthenominalliftof0.5mm),withaprecisionof±0.005mm(1%ofnominallift)!Obviouslythisisimpossible,andthethermostaticvalvecannotfindastabledegreeofopening.Itthenworksinon-offmodewithoscillationsintheroomtemperature.Whenthethermostaticvalveisopen,theheatoutputismuchhigherthannecessary,creatingatransitoryincreaseofroomtemperaturebeforethethermostaticvalvereacts.

Page 14: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

14

This iswhythethermostaticvalve isnormallyusedwithacentralcontroller thatmodifiesthesupplywatertemperaturetosuitrequirements.Thesearedeterminedbyanoutdoorsensororbyatemperaturesensorlocatedinareferenceroom(notfittedwiththermostaticvalves)orbyacombinationofthetwo.Thethermostaticvalvecorrectsresidualvariationsasafunctionoftheconditionsspecifictoeachroom.

Inconclusion,theheatoutputofaradiatorcannotbecontrolledonlybyvaryingtheflow.Basiccontrolisobtainedbycontrollingthesupplywatertemperatureaccordingtogeneralneeds.

2.4 Is the thermostatic valve a proportional controller?

The thermostatic valve theoretically behaves like a proportional controller. In practice, working conditions are not always favourable and the thermostatic valve often works as a

temperature limiter. In this case a small proportional band gives better results. Even then, it may sometimes give the impression of behaving proportionally as it moves into intermediate,

temporarily stable positions, as a function of its hysteresis.

Aproportionalcontrollergraduallyopensorclosesthecontrolvalveinproportiontothedeviationbetweenthecontrolledvalueanditssetpoint.

Fig2.4showsalevelcontroller.Theoperationobtainedissimilartothatofathermostaticvalveifitisassumedthatthewaterlevelrepresentstheroomtemperature.TheflowZcorrespondstotheheatlosses,andthesupplyflowYcorrespondstotheradiator’sheatoutput.

Y = radiator heat output

PB proportional band

Z = heat losses

Y

B

V

Ho

Hm

Z

H = room temperature

Fig 2.4. Analogue representation of a thermostatic valve. Whentheleveldecreases,thefloatBgoesdownandopensvalveVproportionallytothelevelreduction.AbalanceisobtainedwhenthesupplywaterflowYequalstheflowZ.

WhenZ=0,thelevelrisestoHoatwhichvalveVisclosed.WhenZreachesitsmaximumvalue,astablesituationisobtainedwhenvalveVisfullyopen.ThefloatisthenintheHmposition.ThelevelthereforetakesonstablevaluesbetweenHo and Hmdependingontheamplitudeofdisturbances.

Page 15: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

15

Balancing of Radiator Systems > 2. Radiator valves

ThisdifferenceHo–Hmiscalledtheproportionalband.Itisthelevelvariationnecessarytochangethecontrolvalvefrommaximumopeningtoclosing.

Ifthisproportionalbandisreducedtoincreasethecontrolaccuracy,thereisariskofreachingacriticalvalueatwhichthecontrolloopbecomesunstable.AsmallproportionalbandresultsinalargevariationoftheflowYforasmallchangeinthelevel.Thisflowvariationmaythenbelargerthanthedisturbancethatcausedthechangeinlevel,thuscreatingareversedisturbancelargerthantheinitialdisturbance.Thelevelthenoscillatescontinuously.

ReconsiderFig2.2.Thevalveisfullyclosedforaroomtemperatureof22°C,andfullyopenforti=14°C.Theproportionalbandistherefore8K.However,forathermostaticvalvewithpresetting,thedesignflowisobtainedinpracticeforaroomtemperaturevariationof2Kanditisnormalpracticetoarbitrarilyassumethattheproportionalbandofthethermostaticvalveis2K.Wewouldliketoclarifythatthis2Kisnotreallytheproportionalbandofathermostaticvalve.Theproportionalbandhastorepresenttherangeofroomtemperaturemodificationswherelinearityisobtainedbetweentheroomtemperatureandthewaterflow.Thiscontrolisexpressedintermsof%offlowperKoftheroomtemperaturedeviation.Therefore, we have adopted, for thermostatic valves, a specific definition for the proportional band: it’s the double of the deviation in room temperature which changes the water flow from 0 to 50% of the design value (100% being obtained for a deviation of 2K). This definition concerns the assembly consisting of thermostatic valve + radiator + return valve (if there is one).

Ifweconsidernowthatareturnvalveoraninternalrestrictioninthethermostaticvalveisusedtoobtainthecorrectflowatnominallift,theresultingcurvesforsomesettingsareshowninFig2.5.

Thesetpointischosensothattheflowislessthan100%whentheroomtemperatureexceeds20°C.

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

18 19 20 21 22

1.60 K

0.50 K

1.30 K

Proportional band

Total Kv

Room temperature °C

Set points

Fig 2.5. A regulating valve or an internal restriction in the thermostatic valve modifies the resulting Kv = f (ti) curve and the practical proportional band

Page 16: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

16

Table2.1showsthevariationoftheproportionalband,forthreesettingexamples,whenarestrictionreducesthemaximumflow.

Kv2 0.65 0.50 0.20

Kvmax 0.80 0.56 0.20

PB 1.60 1.30 0.50

SP 20.00 19.7 18.90

ST 22.00 21.7 20.90

Kv2 = (Kvat∆T2K)Kvatnominalliftcorrespondingtoadeviationof2K,

thisKvcorrespondstothedesignKv.

Kvmax =Kvobtainedwiththevalvefullyopen.

PB = Proportionalband

SP = Setpointadoptedforarequiredroomtemperatureof20°C.

ST = Roomtemperatureatwhichthevalveiscompletelyshut.

Table 2.1. Variation of the proportional band of one thermostatic valve

under the effect of a restriction in series.

TherealcurvebetweenKvandroomtemperaturealsodependsonthehysteresisofthevalveaswellasthevariationofthemicroclimatearoundthethermostatichead.

Inanycase,aproportionalbandoflessthan1Kwillalmostcertainlymakethevalveworkinon-offmode.Thisisnotaseriousproblemifoscillationsoftheroomtemperaturearepracticallynotperceivable,whichisthecaseinbalancedplantswherethewatertemperatureiscontrolledasafunctionofoutdoorconditions.Inwell-insulatedbuildingsanarrowproportionalbandgivesmoreaccuratecontrolofroomtemperaturedespitetheon-offbehaviourofthecontrolloop,whichalsocontributestoreducedenergyconsumption.Whenworkingwithwideproportionalbands,wemaygetastablecontrol.However,asthetemperatureisslowlymovingwithinalargespan,wedon’tsaveasmuchenergyaspossible.Effectively,wedon’ttakeallthebenefitofinternalheatorsunenergy.

Thequestionisthefollowing:whenathermostaticvalveworkstocompensateforaninternalemission,isitbettertohaveasmalloralargeproportionalband?

Letusconsidertwodifferentthermostaticvalves,setat20°C,withthesameKvbutwithaproportionalbandof2and1Krespectively.

Withaproportionalbandof2K,theroomtemperaturecanincreaseto22°Cbeforetheradiatoremissionwillbestopped.Iftheproportionalbandisonly1Ktheradiatorwillbealreadyisolatedforaroomtemperatureof21°C.Itisthenpossibletosavemoreenergywhenworkingwithsmallproportionalbands.

Page 17: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

17

Balancing of Radiator Systems > 2. Radiator valves

2.5 Should a plant be hydraulically balanced with all thermostatic valves fully open?

The answer is yes and the thermostatic valves must have a saturated characteristic.

Balancingtheradiatorsinacircuitresultsinobtainingcorrectflowsineachradiatoratdesigncondition.At intermediate loads, flowsandpressuredrops inpipesare reduced,differentialpressuresincreaseandeachradiatorcanatleastobtainitsdesignflow.

Someconsiderthatallthermostaticvalvesshouldbesettotheirnominalopeningbeforebalancingaplant.Thisappearslogicalasflowsarenormallydeterminedintheseconditions.Thethermostaticheadsshouldthenbereplacedbygraduatedcapsforsettingthevalvesattheirnominallift.

Whenevertheplantisstartedup,afterthenightsetback,thermostaticvalvesareopenedbeyondtheirnominalopeningandwillbeinoverflow,creatingunderflowsinotherpartsoftheplant.Thepurposeofbalancingisthusnotachieved.

ThissituationisdifficultinthecaseofanunlimitedflowthermostaticvalvesuchasthatshowninFig2.2a.Moreover,overflowsarepermanentonvalvesforwhichthethermostaticheadhasbeenremoved.

Thermostaticvalveswithaninterchangeableplug,allowingtheachievementoftherightKv,normallydon’thaveaflatenoughcurvetosolvetheproblem.

Theproblemisrelatedtothebigdifferenceinflowsbetweenthevalvefullyopenandthevalveatnominallift(Fig2.2a).Solvingthisproblemisquitesimple:thevalvecharacteristichastobesaturated.Itmeansthattheflowwillnotsignificantlyincreasebeyondthenominalopening(Fig2.2b).Thisisobtainedwitharesistanceinserieswiththethermostaticvalve(Fig2.5).Inthiscase,theflow/openingcurvebeyondthenominalliftissoflatthattheplantcanbebalancedwithallthermostaticheadsremoved.

Thisdiscussiondemonstratesthenecessitytobalancetheplantwithallthermostaticheadsremovedandtousethermostaticvalveswithasmalldifferencebetweenthedesignandthemaximumflows,thismeanswithasaturatedcharacteristicasshownonFig2.5.

However,inthecaseofanoccupiedbuilding,theoperationofremovingallthermostaticheadsandreplacingthemafterbalancingisadifficultoperation.Sendingcircularsaskingoccupantstocarryoutthisoperationisnotaparticularlyreliablemethod.Someinstallersprefertodothebalancingduringtheheatingseason;theyreducethehotwatertemperaturesignificantlythedaybefore,incitingoccupantstofullyopentheirthermostaticvalves.

Page 18: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

18

2.6Accuracytobeobtainedontheflow

In most cases the flow has to be adjusted with an accuracy of ± 10%.

Insection1weconsideredthedisadvantagesofhydronicunbalancesinplants.Beforestudyingbalancingprocedures,wemustdefinetheprecisionwithwhichflowshavetobeadjusted.

Inpractice,flowadjustmentprecisiondependsontherequiredroomtemperatureprecision.Thisprecisionalsodependsonotherfactorssuchascontrolofthesupplywatertemperatureandtherelationbetweentherequiredandinstalledcapacity.Thereisnopointinimposingaveryhighaccuracyontheflowifthesupplywatertemperatureisnotcontrolledwithanaccuracyproducingequivalenteffectsontheroomtemperature.

Anunderflowcannotbecompensatedbythecontrolloop,andhasadirecteffectontheroomtemperatureundermaximumloadconditions;itmustthereforebelimited.Anoverflowhasnodirectconsequenceontheroomtemperaturesinceintheory,thecontrolloopcancompensateforit.However,whenthecontrolvalveisfullyopen,forexample,whenstartinguptheplant,thisoverflowproducesunderflowsinotherunitsandmakesdistributionincompatiblewithproduction.Overflowsmustthereforealsobelimited.

Table2.2comparestheinfluenceoftheflowontheroomtemperatureunderwell-defineddesignconditions.

Design Allowabledeviationin%ofdesignwaterflow,foraroomtemperature

accuracyof0.5K

tec tsc trc -0.5K +0.5K

0 90 70 -15 +2182 71 -24 +44

-10 93 82 -21 +3490 70 -12 +1590 40 -4 +480 60 -10 +1380 50 -7 +780 40 -4 +560 40 -8 +955 45 -15 +20

-20 90 70 -10 +1380 60 -9 +1080 40 -4 +475 45 -5 +670 45 -6 +760 40 -7 +855 45 -13 +17

Table 2.2. Variations of the flow q in the radiator to modify the room temperature by 0.5K at full load.

Page 19: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

19

Balancing of Radiator Systems > 2. Radiator valves

Letustakeanexampleforaheatingplantworkingwiththefollowingdesignconditions:Supplywatertemperaturetsc=80°C,returntrc=60°Candroomtemperaturetic=20°C.Thedesignoutdoortemperatureistec=–10°C.Aroomtemperaturevariationof0.5Kcanbeobtainedbyreducingthewaterflowby∆q=10%.

ThewaterflowadjustmentaccuracymustbebetterwhentheplantisworkingwitharelativelyhighthermaleffectivenessΦ.

Foraroughconclusion,wecanseethatwaterflowshavetobecontrolledwithanaccuracyof±10to±15%.Concurrently,thewatertemperaturehastobecontrolledwithanaccuracyof±1to±1.5K.

Wemaybetemptedtoacceptoverflows,especiallywhentheyhavelittleeffectontheroomtemperature.Thiswouldneglecttheperniciouseffectsofoverflowswhichcreateunderflowselsewheremakingitimpossibletoobtaintherequiredwatertemperatureathighloads,duetoincompatibilitybetweenproductionanddistributionflows(seesection1.2).

Page 20: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

20

3. Radiators

3.1 Nominal and design conditions

Aradiatorheatoutputistobedefinedforagivenroomtemperature(20°C),watersupplyandreturntemperatures,forexample75and65°C.Thetemperaturesof20,65and75°Carenominalvaluesoftheroomtemperatureandwatertemperatures.Theyareidentifiedbythesubscript“n”(forexampletin=nominalroomtemperature).Nominalvaluesareactuallycataloguevaluesusedbymanufacturers;theydeterminetheconditionsunderwhichthepowerofaunitisdefined.AccordingtoEuropeannormsEN442,thenominalpowerofaradiatorisvalidforasupplywatertemperatureof75°C,areturnwatertemperatureof65°Candaroomtemperatureof20°C.But,normally,aradiatordoesnotworkintheseconditions.Then,therequireddesignwaterflowintheradiatormustbedeterminedineachparticularcase.Itisobviouslymeaninglesstotrytoadjustthewaterflowinaradiatorifthisflowisnotcorrectlydetermined.

Theplantiscalculatedincertainconditionswithspecificvaluesforthecontrolledvariables,outdoorconditions,supplyandreturnwatertemperatures.Thosevalues,usedtocalculatetheplant,arethedesignvalues;theyareidentifiedbyasubscript“c”(valuesusedforcalculations).

3.2 Selection of a radiator not working in nominal conditions

Radiator heat output in catalogues refers to nominal conditions, for example,water supplytemperaturetsn=75°C,returntemperaturetrn=65°Candaroomtemperaturetin=20°C.Howisaradiatorselectedifitdoesnotworkintheseconditions?

TherealtransferredpowerPisrelatedtothenominalpowerPnasfollows:

P = Pn × n/2

(ts-ti) (tr-ti)

(tsn-tin) (trn-tin)( )

Nosubscript:presentconditions Subscriptn:nominalconditions.

ts= Supplywatertemperature.

tr= Returnwatertemperature.

ti = Roomtemperature.

n= Thisexponentforradiatorsisnormallytaken=1.3

Thisformulaexpressestheinfluenceofthetemperaturegeometricaveragebetweentheradiatorandtheroom.ThisformulaistranslatedintoagraphonfigureA1inappendixAwheresomespecificexamplesareexplained.

Page 21: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

21

BalancingofRadiatorSystems>3.Radiators

Example:What is the nominal power 75/65of a radiatorwhich has todeliver 1000Wina roomat22 °Cwhen theactual supply and returnwater temperature are respectively 72and60°Crespectively?

In Fig A1 (Appendix A), join ts – ti = 72 – 22 = 50 to tr – ti = 60 – 22 = 38 to find Sp=Pn/P=1.18.Thenominalpowertoinstallis1000x1.18=1180W.

Thisformulaistheoreticalasitassumesthatthewaterflowisdistributeduniformlyintheradiator.

Heatoutputisalsoaffectedbyawindowsillabovetheradiatorthatmayreduceheatoutputby35%.Aradiatorclosetoawindowgenerateshotaircirculationandsupplementaryheatlossesthroughthewindow,reducingtheenergyreallytransmittedintheroom.Thenominalpowerofaradiatorisdeterminedinfavourableconditions,whicharenotalwaysreproducedinpractice.Acoefficientofsecurityremainsnecessarywhenaradiatorisselected.

3.3Emissionofaradiatorasafunctionofthewaterflow

Therequiredwaterflowintheradiatorcanbecalculatedusingthefollowingequation:

∆T0.86 × P

q=

q:flowinl/h P:heatoutputinW ∆T:temperaturedropinK

For a 1000 W radiator and a design temperature drop of 20K, the required water flow is0.86× 1000 / 20 = 43 l/h.

However,whentheflowvaries,thewatertemperaturedropalsovarieswhichmakestherelationbetweentheflowandheatoutputnon-linear.

Fig3.1showsthisrelationforasupplywatertemperatureof80°Candvarioustemperaturedrops∆Tc.

Φ = 0.17

Φ = 0.33

Φ = 0.50

P%

q% 0

10

20

30

40

50

60

70

80

90

100

11

120

130

50 100 150 200 250 300

80/5

80/6

80/7

Fig 3.1. Heat output, in a room at 20 °C, as a function of the water flow, for a radiator (n = 1.3) and for different water ∆Tc values. tsc = 80 °C.

Page 22: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

22

Attheorigin,thegradientofthe“heatemission/flow”curveistheinverseofthethermaleffectiveness“Φ”oftheradiator.Thisthermaleffectivenessisdefinedasfollows:

∆Tc

∆To

φ =

∆Tc=designwatertemperaturedrop.

∆To=watertemperaturedropatzeroload=tsc–tic

For80/60designconditions,thethermaleffectivenessΦis:(80–60)/(80–20)=0.33andtheincreasedpowerattheoriginis1/0.33=3%powerper%offlow.

Atdesigncondition,anoverflowintheradiatordoesnotsignificantlyincreasetheemittedheat,particularlywhenthethermaleffectivenessislow.

3.4 Selection of the design water temperature drop

For a supply water temperature between 70 and 90 °C, it’s quite common to design the plants for a ∆T = 20. This magic value has been adopted for many years and translated

into local units (20 °C in continental Europe and 20 °F (11 °C) in the UK and USA, for instance). However, to reduce the return water temperature in district heating or when using condensing boilers, a higher ∆T is adopted. The design ∆T depends mainly on the habits in

each country, but it can be optimised according to each specific plant. Radiatorsworkingwithalowwatertemperaturedrop∆TchaveastronglysaturatedresponsecurveP%=f(q%).Flowvariationsthereforehavelittleinfluenceonthemaximumemission.However,theseradiatorsbecomedifficulttocontrolatlowloadssincetheemissionisverydependentontheflowinthiszone.

Theuseofahigh∆Tccanreducewaterflows,pumpingcosts,pipediametersandlosses.Controloftheradiatorisalsoimproved.However,themaximumpowerbecomesmoresensitivetothewaterflow,requiringaprecisehydronicbalancingoftheplant.

Ahighvalueof∆Tcreducesheatexchanges,thusrequiringtheuseofradiatorswithlargersurfaceareas.Forexample,theuseofa∆Tcof30Kinsteadof20Kreducestheheatexchangeapproximatelyby 16%.

Theoptimum∆Tdependsoneachplant.Increasingthe∆Treducesthewaterflows,thesizesofthepipesandaccessories,thepumpingcostsandtheheatlossesinpipesbutradiatorsurfaceshavetobeincreased.Theoptimum∆Tcanthereforebecalculatedforeachplant.

Page 23: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

23

BalancingofRadiatorSystems>3.Radiators

10

200

133

100

66

30252015

Flow %

∆T

Pn / Pc = Relative radiator oversizing

∆T

0.87

0.93

1.00

1.10

1.20

10 30252015

ts = 80 ° C ts = 80 °C

Fig 3.2. When the designed ∆T is increased, the water flow decreases but the required radiator surfaces increase (ts = 80 °C ).

3.5 Existing plants

How to compensate for oversized radiators after an improvement of the insulation of the building.

Existingplantscanbetreatedinthesamewayasnewplants.However,improvementsmayhavebeenmadetothebuilding,considerablyreducingheatlosses.Radiatorswillthenbeoversizedwithrespecttotheinitialconditions.

Ifthethermalinsulationwasimproveduniformly,theheatoutputoftheradiatorsisadjustedtonewconditionsbyreducingthewatersupplytemperature.

An example of a calculation: Take,forinstance,aradiatorwithanominalpowerof1200Winconditions75/65.Thedesignpowerrequiredis,forinstance,1000Wforasupplywatertemperatureofts=80°Cinaroomtemperatureofti=20°C.Whatflowshouldtheradiatorhave?

ThenominaloversizingfactorisSpn = Pn /P = 1200/1000 = 1.2.

Referring to Fig A1 in appendix A, join ts – ti = 80 – 20 = 60 °C to Pn/P = 1.2 to find tr – ti = 31.2 °C. Then tr = 51.2 and ∆T = 80 – 51.2 = 28.8 K. Finally, q=0.86× 1000/ 28.8 = 30 l/h.

Fig A2 can also be used. Join ts – ti = 80 – 20 = 60 °C to Pn /P = 1.2 to find q=30l/hper1000W.

Inmostplants,thermalinsulationisnotimproveduniformlyandeachradiatorhastobetreatedindependentlyasinsection3.2.

Page 24: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

24

4. Two-pipe distribution

4.1 Balancingofradiatorsbasedonaconstant∆p

To set the Kv of the thermostatic valves, the differential pressure

is considered to be of ∆Ho = 10 kPa, for instance. This differential pressure is automatically obtained after balancing the distribution.

4.1.1 Choosing the design differential pressure

Ifaflowmeasurementdeviceisavailableateachradiator,astandardbalancingprocedurecanbeusedandabalancingvalveonthecircuitactsasapartnervalve.Thiscankeeppreviouslyadjustedradiatorflowsconstantwhileothersarebeingadjusted(thecompensatedmethod).However,thermostaticvalvesaregenerallypresetaccordingtocalculatedvalues.

STAD

∆Ho

Fig 4.1. Each radiator valve is adjusted as if it were subject to the same differential pressure ∆Ho.

ThemainpressuredropisinthethermostaticvalvewithadjustableKvasthepressuredropintheradiatorisnormallylow.Sincesomeinaccuracyisacceptableonflows,wecanassumethateachradiatorinabranchissubjecttothesamedifferentialpressure∆Ho.Thisdifferentialpressuremustnotbetoohightomaintainanadequatecross-sectionatthevalve,thusreducingrisksofcloggingandnoises.Thisdifferentialpressuremustnotbetooloweither,inwhichcasetherelativeinfluenceofpressuredropsincircuitpipescannotbeneglected.Therefore,thedifferentialpressure∆Hoisgenerallychosentobe10kPa.

Page 25: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

25

BalancingofRadiatorSystems>4.Two-pipedistribution

Eachadjustablethermostaticvalveisthenpresetbasedonthisselecteddifferentialpressure∆Ho. WhenthebalancingvalveSTADonthebranchisadjustedtoobtainatotalflowcorrespondingtothesumoftheflowsintheradiators,thepreliminarysettingsmadearejustified.Theselecteddifferentialpressure∆Hoisthenappliedacrossthehydrauliccentreofthecircuit.Inpractice,thefirstradiatorwillbeinslightoverflowandthelastradiatorwillbeinslightunderflow.Thesedifferencesdependonthecircuitlengthandonthepressuredropsinthepipesandaccessories.

Example:Acircuitwithradiators,eachhavingadesignflowof50l/h.Thepressuredropinthepipesis2kPa.Consider∆Ho = 10 kPa.

Flowinthefirstradiatoris=50× √ =52.4l/h,andinthelast=50 × √ = 47.4 l/h

Thedeviationis±5%. Considernow∆Ho=2kPaandthesamepressuredropinthepipes.

Flowinthefirstradiatoris=50× √=61l/h,andinthelast=

50 × √ = 35 l/h

Thedeviationis–30to+20%. Thisexampleconfirmsthat∆Hoshouldbearound10kPa.

10 + 11110

10–111011

2 + 111211

2–111 2

Page 26: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

26

4.1.2 Presetting the thermostatic valve

Table4.1givestheKvvaluestobetakenaccordingtothe∆Hoadopted.

WorkingconditionsKvvalvefor∆Ho = 10

kPa

Heatoutputin(W) Waterflow

∆T = 10 ∆T = 20 l/h l/s Kv

250 500 21.5 0.006 0.068

300 600 25.8 0.007 0.082

350 700 30.1 0.008 0.095

400 800 34.4 0.010 0.109

450 900 38.7 0.011 0.122

500 1000 43.0 0.012 0.136

600 1200 51.6 0.014 0.163

700 1400 60.2 0.017 0.190

750 1500 64.5 0.018 0.204

800 1600 68.8 0.019 0.218

900 1800 77.4 0.022 0.245

1000 2000 86.0 0.024 0.272

1100 2200 94.6 0.026 0.299

1200 2400 103.2 0.029 0.326

1250 2500 107.5 0.030 0.340

1300 2600 111.8 0.031 0.354

1400 2800 120.4 0.033 0.381

1500 3000 129.0 0.036 0.408

1750 3500 150.5 0.042 0.476

2000 4000 172.0 0.048 0.544

2250 4500 193.5 0.054 0.612

Table 4.1. Determining the Kv of a thermostatic valve.

Example:Fora1500Wradiatorworkingwitha∆Tof20Kandadifferentialpressureof10kPa,theKvvalueofthethermostaticvalvemustbe0.2.UsethechartinFig4.2tofindtheKvvaluegraphically.

Page 27: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

27

BalancingofRadiatorSystems>4.Two-pipedistribution

qP Kv

mm WGkPaKvl/hl/sWatt (∆T = 20K)

Kv ˘p

kPa mm WG

P q Kv ∆p

Kvl/s l/hWatt (∆T= 20K)

Foraradiatorof1500W,thewaterflow=64.5l/h.Fora∆pof10kPa,Kv=0.2

Page 28: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

28

4.1.3 Non-presettable thermostatic valves

Whenathermostaticvalveisnon-presettable,theadjustmentwillbemadeonthereturnvalve.Asthethermostaticvalvealreadycreatessomepressuredropatnominalopening,onlytherestoftheavailable∆pisappliedacrossthereturnvalve.

Example:A2000Wradiatorworkingwitha∆T=20Kissuppliedatadifferentialpressureof10kPa.ThethermostaticvalvehasaKv=0.5.WhatKvshouldbesetatthereturnvalve?

ReferringtoFig4.2,itcanbeseenthattheradiatorflowis86l/h.Atthisflow,thepressuredropinavalvewithKv=0.5is2.96kPa.Therestisforthereturnvalve:10–3=7.Usingthesamediagram,wefind that theKvmustbe0.33 foraflowof86 l/handapressuredropof7kPa.Ifwehadneglectedthepressuredropinthethermostaticvalve,wewouldhave found a Kv of 0.27 for the regulating valve. The flow obtained would have been 75l/hinsteadofthepredicted86,representingadeviationof13%.

Thesameproceduremaybeusedifpressuredropsinotherresistances,suchaselbows,highresistanceradiators,etc.,havetobededucted.

4.1.4 Limitationsofchoicewiththesame∆pforallradiators

Theassumptionthatthesamedifferentialpressure isappliedtoall radiatorshassomelimits,dependingmainlyontherequiredflowaccuracy.

ConsiderthecaseinFig4.3.Valvesarepresetbasedonanaveragedifferentialpressure∆Ho. Theflowwillbehigherthanthedesignflowatthestartofthecircuit,andlowerattheend.Foradeviationof∆qin%ofdesignflow,themaximumallowablelengthforpipesisdeterminedinFig4.3.

Page 29: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

29

BalancingofRadiatorSystems>4.Two-pipedistribution

0

1020

30

40

5060

70

80

0 5 10 15 20 25

?q max %

Lmax in m

∆Ho/R

0.15

0.10

0.08

0.06

0.04

0.02

∆qmax in %

∆Hmax ∆Ho

LmaxSTAD

∆Hmin

Fig 4.3. When all valves are calculated based on the same ∆p = ∆Ho, the circuit length should not exceed a given value (∆Ho in kPa and R (pressure drop in pipes) in Pa/m).

Considerthecaseofaplantdesignedforconditionstsc=80°Candtrc=60°C.Adeviationintheroomtemperatureintheorderof1Kduetotheflowisaccepted,whichimpliesaflowprecisionof∆q=±20%.∆Ho=10kPaisadopted,andthepressuredropinthecircuitconsideredequals100Pa/m(∆Ho/R=0.1).Themethoddescribedmaythereforebeusedifthedistancemeasuredonthepipebetweenthecircuitinletandlastradiatordoesnotexceed44metres(SeeFig4.3).

4.2Presettingbasedoncalculated∆p

Ifpressuredropsinpipesarehigh,themaximumcircuitlengthisquicklyrestricted.Inthiscasethedifferentialpressureappliedtoeachradiatormustbeestimatedusingthefollowingformula:

∆H=∆Hmax–=∆H0 + 2RL

1000

RLmax–2RL1000

∆H: DifferentialpressureinkPaavailableforathermostaticvalve,

R: PressuredropinpipeinPa/m,

L: Distanceinmetresofpipebetweenthebalancingvalveofthebranchandaradiator

This∆Histhencalculated,foreachradiator,todeterminethecorrespondingKv.

Page 30: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

30

4.3 Constantorvariableprimaryflow

Primary distribution can be designed for constant or variable flow. This affects the solutions that can be used to obtain the correct differential

pressure on the secondary distribution.

Localdistributionthroughthermostaticvalvesisnecessarilyavariableflowdistribution.However,theprimarygeneraldistributionmaybedesignedforaconstantoravariablewaterflow.

Theadvantageofaconstantprimaryflowinthemaindistributionisthatitkeepsthepressuredropsinthepipesconstant.Thedifferentialpressureoneachcircuitisadjustedatthecorrectvalueatdesignconditionanddoesnotchangewiththeload.However,thereturnwatertemperatureisnotminimised,whichcanbeadisadvantageinsomedistrictheatingplantsandwhencondensingboilersareinstalled.

Theadvantageofavariableflowinthemaindistributionisthatitminimisesthepumpingcostsandreducesthereturnwatertemperaturewhenrequired.However,atsmallloads,thedifferentialpressureonthecircuitsincreasesaccordingtothereductionofthepressuredropsinthepipesandaccessorieswhentheflowisreduced.

Inallcases,theplanthastobebalancedtoavoidoverflowsthatcreateunderflowsinunfavouredsectionsandincompatibilityproblems.Foravariableflowdistribution,balancingismadefordesignconditions,whichguaranteesthatallcircuitswillobtainatleasttheirdesignflowinallworkingconditions.

4.3.1 About noise

Ahydraulicresistanceinacircuitcreatesapressuredropandapartoftheenergyistransformedintoheatandanotherpartintonoise.Theriskofnoiseincreaseswiththedifferentialpressure.

Somenormsdefinethemaximumnoiselevelacceptableinabedroomtobe30dBAduringthenightand35dBAduringtheday.

Inapresettablethermostaticvalve,thedifferentialpressureistakeninthepresetter,whichlimitstheflowatdesignvalue,andthecontrolportwhichadjuststheflowtoobtaintherequiredroomtemperature.

Duringnightsetback,thesupplywatertemperatureisreducedandthecontrolportisfullyopen.Thenoisecreatedbythevalveintheseconditionscomesfromthepresetter.

Thegeometryofthevalveandparticularlythedesignofthepresetterareimportantinordertoobtaina“silent”valve.

Alltestsrealisedshowthatnoiseincreaseswiththewaterflow.Thisisanotherreasontocarefullybalancetheradiators,avoidingoverflows.

Page 31: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

31

BalancingofRadiatorSystems>4.Two-pipedistribution

Theriskofnoisecouldbereduceddramaticallyduringnight-timebydecreasingthepumphead,simultaneouslyreducingthedifferentialpressureandthewaterflow.Thiscanbeobtained,forinstance,withavariablespeedpumpwithdifferentsettingsduringnightandday.

Duringtheday,whenthethermostaticvalvehastocompensateforinternalheat,thecontrolportpartlyshuts.Thedifferentialpressureappliedonthecontrolportincreaseswhilstthewaterflowdecreases.Theriskofnoiseisatmaximumwhenthevalveisclosetoclosure.Vibrationsoccurwhenthevalveisconnectedthewrongwaywiththeflowofwatergoinginthereversedirection.

Noiseinaplantcanhavemanycauses.Aradiatororconvectorcanamplifynoisegeneratedbythepump.

Noisecanalsoincreasedramaticallywhentheplantisnotwellvented.Lowwatertemperaturesmakeitmoredifficulttovent.Increasingthewatertemperatureduringventingprocedurecanbeasolutionwheneverpossible.

Atoolowstaticpressureinsomepartsoftheplantshouldalsobeavoidedastheairseparatesoutofthewaterinarestrictionbecauseofthelowerlocalpressureresultingfromthehighwatervelocity.

Whenathermostaticvalveshuts,thepressuredropinthepipesandrestrictionsdecrease.Thedifferentialpressureonthethermostaticvalveincreaseswhichincreasestheriskofnoise.Forthisreason,itisnotagoodidea,inbigplants,toadjusttheflowwithjustonerestrictioninserieswiththethermostaticvalve.Ifthisthermostaticvalveshuts,theentirepressuredroptakenpreviouslyintherestrictionistransmittedtothecontrolport.Itismuchbettertotakepartsoftheexcessdifferentialpressureinbalancingvalvesinthebranchesandrisersandtherest,10kPaforexample,inthepresetterassociatedwiththethermostaticvalves.Whenonethermostaticvalveshuts,thewaterflowandthenthepressuredropinthebalancingvalvesinbranchesandrisersdonotchangemuch.Consequently,thedifferentialpressureonthethermostaticvalveincreasesjustalittle.

However,ifallthethermostaticvalvesshutsimultaneously,allpressuredropsinpipesandrestrictionsdisappearandthethermostaticvalvesaresubmittedtothefullpumphead.Ifthishappens,thecontrolofthesupplywatertemperaturehastobereconsidered.Forinstance,thesupplywatertemperaturecanbereducedwhenthetotalwaterflowintheplantdecreases.

Thesituationcanbemoredifficultifthepumpisoversizedandworkswithasteepcurveincreasingthepressureatsmallloads.Forthisreason,anadjustableandcontrolledpumpheadisgenerallymoreconvenient.Thepumpheadcanalsobereducedduringmostofthetimeandjustputatitsmaximumvalueduringcoldseasons.Thereductionofthepumpheadinwarmerseasonsiscompensatedbyasmallincreaseofthewatersupplytemperature.

When,inextremecircumstances,thedifferentialpressureexceedsthelimitdefinedbythethermostaticvalvemanufacturer,thedifferentialpressurehastobelimitedlocally.Thisquestionwillbeexaminedinthenextsections.

Page 32: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

32

4.3.2Constantprimaryflow

Fig4.4showstwodifferentcircuitsapplicabletoanapartment.

Inprinciple,thewatertemperatureofthedistributionismodifiedtosuitoutdoorconditions.AcorrectdistributionofprimaryflowsisobtainedbyadjustmentofbalancingvalvesSTAD.

=

A B

BPV

STADSTAD

a b

Fig 4.4. Two circuits with radiators are designed to give a constant primary flow.

4.3.2.1 Abypassandasecondarypumpminimisethe∆ponthebranch(Fig4.4-circuita).

ThiscircuitiswidelyusedinsomeEuropeancountries.AbypasspipeABmakesthesecondarycircuithydraulicallyindependentoftheprimarydistribution.Thehighdifferentialpressureinthemaindistributionnetworkisnottransmittedtothecircuit.Thiscircuitisprovidedwithacirculatingpumpwhichcanbecontrolledbyathermostatlocatedinareferenceroom.Thermostaticvalvesareonlysubjecttotherelativelylow-pressureheadofthesecondarycirculatingpump,decreasingtheriskofnoiseconsiderably.

Page 33: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

33

BalancingofRadiatorSystems>4.Two-pipedistribution

Itisessentialthatthemaximumsecondaryflowislessthantheconstantprimaryflow.Otherwise,atfullload,thedifferencebetweenthetwoflowswillcirculatefromBtoA,creatingamixingpointatA.Inthiscase,thesupplywatertemperaturewillbelowerthanthedesignvalueandcomfortisnotguaranteed.

ABPV(proportionalreliefvalve)maybeinstalledattheendofthecircuitandsetat10kPaforexample.

TheprincipleapplicationofthisBPVistobeclosedexceptwhentheflowthroughthethermostaticvalvesdropsbelowacertainvalue,therebysecuringthefollowing:

– Alimitationofthemaximum∆ponthethermostaticvalves.

– Aminimumflowforprotectionofthecircuitpump.

– Apreventionoflargewatertemperaturedropsinthepipes.Thisisthemainreason,inthiscase,toinstalltheBPVattheendofthecircuitinsteadofinthebeginning.

4.3.2.2ABPVstabilisesthe∆ponthebranch(Fig4.4circuitb).

AproportionalreliefvalveBPVisplacedatthecircuitinlet.Itgraduallyopenswhenthedifferentialpressureacrossitreachesitssetpoint.Radiatorvalveshavebeensetbasedonagivendifferentialpressure,forexample10kPa.

TheBPViskeptshutthroughoutthebalancingprocedure.

Whenbalancingiscomplete,withthermostaticvalvesopen,theBPVsetvalueisreduceduntilitstartstoopen.Thiscausesanincreaseofflow,whichcanbemeasuredatSTAD.TheBPVsetpointisthenincreaseduntilitclosesagain.Insomeplants,theBPVsaresettoobtainasmallflowatdesigncondition;thisgreatlyreducesthecirculationnoisesintheplant.Theexplanationforthisisrelatedtothepressurewavesgeneratedbythepump,whicharebypassedbytheBPV.

Duringnormaloperation,wheneversomethermostaticvalvesclose,thepressuredropacrossSTADisreducedandthedifferentialpressureappliedtotheBPVincreased.TheBPVthenopenstomaintainthisdifferentialpressureatitssetvalue.Thetotalprimaryflowremainspracticallyconstantforaconstant∆H.

NotethatthisfunctionisobtainedbythecombinationoftheBPVandSTAD.Bothelementsareessentialtokeepthetotalflowandthedifferentialpressureacrossthecircuitconstant.TheBPVallowsacertainsupplementaryflowthroughSTADthatcreatesasupplementarypressuredroptocompensateaneventualincreaseoftheprimarydifferentialpressure∆H.WithouttheSTAD,theBPVisnotoperative.

Thisdistributionmethodismoreefficientthanthemethodthatusesasecondarypumpasshowninthecircuita.Thesecondarypumpiseliminated.Theprotectionagainstlowflowsisnolongernecessaryandthesecondarybalancingvalveiseliminated.Finally,thispumpheadischosenaccordingtoneedandismaintainedconstant.

Page 34: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

34

4.3.3Variableprimaryflow

Inordertominimisereturnwatertemperatures,avariableflowdistributionhastobeadopted.Thisisoftenessentialwhentheplantisconnectedtoadistrictheatingdistribution.TwoexamplesareshowninFig4.5.

=

STAD-0

STAD

a b

∆�

p

STA�STAD

Fig 4.5. Two circuits supplied at variable primary flow.

4.3.3.1Aplantwithbalancingvalves(Fig4.5–circuita).

Thisistheclassiccaseofabranchorasmallriserconnectedtoamainnetwork.Thermostaticvalvesarepresetforagivendifferentialpressure,forexample,10kPa.ThebalancingvalveSTADisusedtoobtainthetotalflowincircuit“a”,whichatdesignconditiongivestheselecteddifferentialpressureof10kPaatthehydrauliccentreofgravityofthecircuit,andmorethan10kPaatotherloads.

STAD

STAD

Fig 4.6 The installation is balanced using the TA method.

Page 35: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

35

BalancingofRadiatorSystems>4.Two-pipedistribution

TheinstallationisbalancedusingtheTAmethod,withallthermostaticvalvesopen.

Excessdifferentialpressuresaremostlyresistedinvalvesontherisers.Whenathermostaticvalveisclosed,thedifferentialpressureacrossthebranchincreasesonlyslightlybecauseproportionallythishaslittleeffectontheflowinthebranchandriserbalancingvalves.Theapplieddifferentialpressurebecomesequaltothepumpheadonlyifallthermostaticvalvesareclosedsimultaneously.Thissituationshouldhowevernotoccurifthesupplywatertemperatureiscontrolledcorrectly.

Ifthedifferentialpressureonthethermostaticvalvesexceeds30kPa,thethermostaticvalvesmaybecomenoisy.ThisproblemcanbesolvedbyusingaBPVattheendofthecircuit.ThisBPVstartstoopenwhenthedifferentialpressureexceeds30kPa,creatingatthesametimetheminimumflowrequiredtoprotectthemainpump.Thisminimumflowisalsorequiredtoavoidtoolargewatertemperaturedropsinpipes,whichoccurbelowacertainflow.

4.3.3.2A∆pcontrollerkeepsthe∆pconstantacrossabranch(Fig4.5circuitbandFig4.7).

a- with presettable radiator valves

Differentialpressuresinlargenetworksareoftenhigh,particularlyclosetothedistributionpump.Thedifferentialpressurehastobereducedandstabilisedtoareasonablevalue,of10kPaforexample,tosupplyeachradiatorcircuit.Thisreductionisobtainedbyaself-actingdifferentialpressurecontroller“STAP”.

ItisnecessarytohaveameasuringvalveSTADtomeasuretheflowand,ifnecessary,adjustthesetpointofthe∆pcontrollertoobtaintherequiredbranchflowatdesigncondition.Furthermore,thismeasuringvalveisusedforisolationandasadiagnostictool.

Themaximumflowineachradiatormustalwaysbeadjustedtoitsdesignvalue.Ifbalancingisnotdone,overflows,especiallyatstart-up,makeitimpossibletoobtainacorrectdistributionofpowerandtherequiredsupplywatertemperature.

With only ∆p controllers, the minimum flow necessary to protect the pump is notgenerated. This minimum flow has to be created close to themost remote circuits toalsoobtain thisminimumflow in thepipes,avoiding toohighawater temperaturedrop.Thisminimumflowmaybecreatedbysomecircuitsworkingwithconstantprimaryflow (Fig4.4).

Page 36: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

36

Thesetpointofthe∆pcontroller.

∆Hmax ∆Ho

Lmax

STAD

STAP

∆Hmin

Fig 4.7. A controller stabilises the differential pressure at the circuit inlet.

Letusconsideraplantwith4identicalradiators,withadistanceof10mbetweeneachone.Pressuredropsinthepipesareof100Pa/m.Presettingshavebeenbasedonauniform∆pof10kPa.Wecancomparetheresultswhenwemaintain10kPaattheinletofthebranch(Fig4.8)orifthesetpointofthe∆pcontrollerisadjustedtoobtainthecorrectdesignflowinthebranch(Fig4.9).

∆p = 8.6 kPaq = 93%

∆p = 7.4 kPaq = 86%

∆p = 6.3 kPaq = 79%

∆p = 5.2 kPaq = 72%

∆p = 10 kPaq = 82.5%

10 m 10 m 10 m

Fig 4.8. ∆p = 10 kPa at the inlet of the branch.

InthecaseofFig4.8,allradiatorsareinunderflow.Thedeviationisthenbetween–7and–28%,whichisnormallynotacceptable.

WiththedifferentialpressurecontrollerSTAP,thesetpointisadjustable.ThemeasuringvalveSTADisusedtomeasureandverifytheflowandissettoobtainapressuredropofapproximately3kPafordesignflow.ThesetvalueofthedifferentialpressurecontrolleristhenchosentoobtaintherequiredflowmeasurableattheSTAD.

Indoingthis,thesetvalueofthedifferentialpressurecontrollercomplieswiththeadoptedpreliminarysettings.

Page 37: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

37

BalancingofRadiatorSystems>4.Two-pipedistribution

∆p = 12.7 kPaq = 113%

∆p = 10.9 kPaq = 104%

∆p =9.2 kPaq =96%

∆p =7.7 kPaq = 87%

∆p = 14.7 kPaq = 100%

10 m 10 m 10 m

Fig 4.9. The set point of the ∆p controller is adjusted to obtain the correct design flow in the branch.

In the example of Fig 4.9, the water flows in the radiators are obtained with a deviation of±13%,whichisnormallyacceptable.

b- with non-presettable radiator valves

Insomeoldbuildings,theradiatorvalvesarenon-presettableandwillnotbereplaced.Inthiscase,itcanbesufficienttolimitthetotalflowforeachbranch.Thisisconceivableiftheradiatorsarenottoodifferentandifthepressuredropsinthepipesaresmall.

Thecircuitadoptedisrepresentedinfigure4.10.

STAD

STAP

Fig 4.10. The pressure drop in the balancing valve is included in the total ∆p controlled by the STAP.

ThesetpointoftheSTAPischosen=14kPa.ThebalancingvalveSTADispresetforapressuredropof11kPaatdesignflow.

Page 38: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

38

Duringstart-up,whenallthermostaticvalvesarefullyopen,thetotalflowinthebranchcannotexceedthedesignflowbymorethan13%.Ifweconsidertheextremecaseofabranchwithoutanyhydronicresistance,alltheavailable∆pof14kPahastobetakenintheSTAD.ThatmeansthattheflowintheSTADwillbe:

q=100 × 14 = 113% √ 11

Ifallthethermostaticvalvesareshut,thepressuredropintheSTAD=0buttheavailable∆ponthethermostaticvalvesislimitedbytheSTAPto14kPa.

Thiscombinationguaranteesthattheflowandthe∆parelimitedtothecorrectvalues.

Whenthethermostaticvalvesareworkingatdesignflow,theavailable∆p=14–11=3kPa.

OthervaluescanbechosenforthesetpointoftheSTAPandthepresettingoftheSTAD.Ifitseemsbettertoobtainanavailable∆pof4kPafordesignflow,theSTAPisseton15 kPainsteadof14kPa,forinstance.Howeverthevaluessuggestedcovermostexistingplants.

Thisisconfirmedbyfigure4.11

80

90

100

Total flow in % with thermostatic valves at nominal lift110

1 2 3 4 5 6 7 8 Required ∆p for design flow

kPa

Fig 4.11. If the required ∆p at design condition is 5 kPa instead of the 3 kPa expected, the deviation in flow is only 7%.

Page 39: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

39

BalancingofRadiatorSystems>5.One-pipedistribution

5. One-pipe distribution

5.1 General

Inaone-pipedistribution,radiatorsareconnectedinseries.Eachradiatorvalvesplitstheflowintoonepartbeingbypassedandonepartgoingthroughtheradiator.ThewaterleavingoneradiatorvalveentersthenextoneasshowninFig5.1.

Fig 5.1. Radiators with one-pipe distribution.

Iftheentireloopflowpassesthroughtheradiators,isolationofasingleradiatorwillstopcirculation

inallradiatorsintheloop.Thisiswhythebypassisinstalledateachone-pipevalveasshownin

Fig 5.2.

qL

λ.qL

t1

tr

t2qL

P

Fig 5.2. A bypass diverts part of the loop flow.

P = HeatemissioninW.q

L = Loopflowinl/h.

λqL=Waterflowintheradiator.

t1 = Inletwatertemperature.tr = Outletwatertemperaturefromtheradiator.t2 = Inletwatertemperatureforthenextradiator.

Thedifferentialpressurecreatedbytherestrictioninthebypassgeneratestheflowthroughthe

radiator.Thisflowislimitedbythethermostaticvalve.

Page 40: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

40

IfP istheheatoutputoftheradiator, thesupplywatertemperaturet2 forthenextradiator iscalculatedasfollows:

0.86 x PqL

t2=t1–

Thewatertemperatureintheloopdecreasesaftereachradiator;thismustbetakenintoaccountwhenchoosingnominalradiatorpower.

5.1.1 Advantages

– Reduced pipe lengths.

Whenradiatorscanbespreadoutthroughouttheentireloop,thepipelengthcanbereducedbyupto50%.Thisalsoreducesheatemissionfrompipes,whichcannotbecontrolledbythermostaticvalves.

– Lower labour cost.

Installationisveryfastwhenpipesarelaidoutinloops.Manyaccessoriessuchasteesandelbowsareeliminated.Thelaboursavingcomparedwithatraditionaltwo-pipeinstallationcanexceed40%.

– More reliable installation.

Pipesareusuallymadeofcopperorsoftsteelandprotectedbyplastic.Theuseofcross-linkedpolyethylenetubesisalsobecomingquitecommon.Allofthesepipesarewellprotectedagainstcorrosionandcanbelaidinasingleoperationwithoutanyconnectionintheconcrete,makingtheinstallationmorereliableinthelongterm.

– Distributionwithpracticallyconstantflow.

Sincetheflowintheloopisalmostconstant,thevariousloopsarenotinteractive.

– The pipes emission can be deducted from the heat losses to calculate the radiators.

Thisadvantagewillbediscussedinsection5.1.3.

Page 41: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

41

BalancingofRadiatorSystems>5.One-pipedistribution

5.1.2 Disadvantages and limitations

– Increased total surface of heating elements.

The radiators at the endof the loopmustbeoversized to compensate for the lowerwatertemperature.Thetotalsurfaceofheatingelementsinstalledinaone-pipedistributionisthereforesometimesgreaterthaninatwo-pipedistributionsystem.

– The return water temperature may be higher than in two-pipe systems.

One-pipeloopshaveapracticallyconstantflow.Whenall thermostaticvalvesareclosed,thetemperatureofthereturnwaterisequaltothesupplytemperature.Districtheatingcompaniesrequirethelowestpossiblereturntemperatures,andthereforedonotlikeone-pipedistributions.Thiscommentshouldbekeptinproportion,sincethesupplywatertemperaturenormallydependsonoutsideconditions.Inthiscaseit isonlyaccidental ifmostthermostaticvalvesareclosed.However,itfrequentlyhappensthatone-pipeloopsworkwithalower∆Tthantwo-pipeloopsinordertoreduceheatingsurfacestobeinstalled.Inthiscasethereturniseffectivelywarmer.

– Interactivity between radiators in the loop.

Letusconsideraloopwithfourradiators.Whenclosingthefirsttwo,thewatertemperatureonthelasttwowillincrease.Thethermostaticvalvesontheseradiatorsthenhavetocompensateforapotentialincreaseinemissionintheregionof10to15%.Howeverclosingthelasttworadiatorsaffectstheloopflowbyreducingthepowerofthefirsttworadiatorsbyaround3to5%.Theseinteractivityphenomenadonotcreatearealproblemanddependonthe∆Tusedintheloopandtheproportionoftheloopflowabsorbedbytheradiators.

Whentheflowintheradiatorsisnotbalanced,thepoweremittedbythefirstradiatorswhentheinstallationstartsupmaybehigherthanplanned.Inthiscase,thesupplywatertemperaturetothelastradiatorsintheloopistoolowtobeabletosupplytherequiredpower.Itisthereforeimportanttobalancetheloopbyprovidingthenecessaryflowtoeachradiator.

Page 42: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

42

5.1.3 Emission from pipes

Connectingpipesemitheatinadditiontoheatemittedbyradiators.Thisemissionisnormallyignoredwhen selecting heating elements, butmust be considered in calculating thewatertemperaturedropintheloop.

Emissionfrompipesintheenvironmentdependsonthewatertemperature,thepipediameter,itsdegreeofinsulation,andthepipelocation(visible,castinconcrete,etc.).

Forawatertemperatureof80°Candaroomtemperatureof20°C,theheatlossesofavisibleplastic

tubeareof30W/m(di=10mm)and60W/mfordi=20mm.Foradiameterdi between10and20

mm,theheatemittedpermetrefromavisiblepipecanbeestimatedusingthefollowingformula:

di15

P=(ts–t i) ×

P = HeatlossesinW/m.

ts = Thesupplywatertemperature.

ti = Theroomtemperature.

di = Pipediameter(mm).

Ifeachradiatorisconnectedwith6metresofpipe(di =15mm),emissionfrompipesat80°Cwouldtheoreticallyreducetherequiredheatoutputforeachradiatorby270W.Thisrelativeeffectisquitesignificantforsmallradiators,butisoftenignoredinthecalculations.Somewell-insulatedinstallationsprovideadequateheatingthroughouttheentireheatingseasonwithallradiatorsclosedasthepipesaloneprovidesufficientheat.Insomecountries,allconnectingpipes,eventhoseinsidetheapartment,mustbethoroughlyinsulated.Thisgivesbettercontroloftheheatingpower.

Whenathermostaticvalvecloses,emissionfromthepipecontinuesandmaymaketheroomtoowarm.Howeverthisislimitedsincethewatertemperaturesupplydependsonoutsideconditions.Insomeverywell-insulatedinstallations,acontrolvalveisplacedintheloopandisolatesthisloopwhenthetemperatureinareferenceroomexceedsalimitingvalue,forexample22°C.

Theproblemofuncontrolledemissionfrompipesisnotinherenttotheone-pipesystem.Inatwo-pipedistributionasshowninFig5.3,thisemissionisevenincreasedbythepresenceoftwodistributionpipesinsteadofone.

Page 43: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

43

BalancingofRadiatorSystems>5.One-pipedistribution

a b

Fig 5.3. Emission from pipes in a two-pipe distribution.

Wheneachradiatorisindividuallyconnectedtothedistributors,theclosureofathermostaticvalvestopsthepipeemissionintotheroomandintotheadjacentroomwherethisactionisinfactadisturbance.

Inatwo-pipedistributionasshowninFig5.4,theemissionofpipesinaroomisvariableanddependsmainlyontheroomtemperaturecontrolinotherrooms.Forthisreason,thepipeemissioncannotbedeductedfromtheheatlosseswhencalculatingtheradiators.However,pipeemissionmustbecalculatedtodeterminetherealsupplywatertemperatureforeachradiator.

100 to 600 W 100 to 300 W

85 ºC

1000 W - 85 ºC - 43 l/h or

777 W - 73 C - 43 l/h?º

Fig 5.4. In a two-pipe system, the pipes emission in a room depends mainly on other rooms.

Theoppositeistrueforaone-pipedistribution(Fig5.5);thepipesemissiondoesnotinfluencethefunctionoftheradiatorsinpractice.Consequently,thisemissioncanbedeductedfromtheheatlossestocalculatetheradiators.

Fig 5.5. In a one-pipe distribution the pipes emission can be deducted from the heat losses to calculate the radiators.

Page 44: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

44

5.2 One-pipe valves

5.2.1Constantbypass–variableKv

Severalmethodsofinstallationarepossible.

qL

λ.qL

t1

tr

t2qL

Fig 5.6. Distributor with fixed bypass.

InthecaseshowninFig5.6,theresistanceofthebypassisfixedandtheproportionoftheloopflowpassingthroughtheradiatorisobtainedbyreducingtheKvmaxofthethermostaticvalve.Forasmallradiator,mostoftheflowpassesthroughthebypass,andthepressurelossinthebypassmaybeunnecessarilyhigh.Inthiscase,theKvofthebypassshouldbeincreased,andthereforeavariablebypassvalveshouldbeused.

5.2.2Variablebypass–constantKv

t1 t2

tr

λ.qL

qL q

Fig 5.7. Distributor with variable bypass.

InFig5.7,athree-waydivertingvalvedistributesflowsbetweentheradiatorandthebypassatconstanttotalKv.Thepressurelossacrossthemoduleonlydependsontheflowintheloop.Theadjustmentoftheflowthrougharadiator,withthebypassthree-wayvalve,hasnoinfluenceontheflowloop.

Page 45: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

45

BalancingofRadiatorSystems>5.One-pipedistribution

5.2.3 Protection against double circulation

Whenthethermostaticvalvecloses,thebottomoftheradiatorremainsindirectcontactwiththehotwaterpipe.Thiscancreatedoublecirculationinthereturnorifice(Fig5.8a)withuncontrollableemissionfromtheradiator.ThisiswhyatubeshouldbeinsertedintheradiatorasshowninFig5.8b,inordertopreventthedoublecirculationphenomenon.Thisinsertedtubecannotbeplacedonallradiators.

a b

Fig 5.8. With the thermostatic valve closed, double circulation can take place in the radiator return connection. An inserted tube can practically eliminate this phenomenon.

5.3Proportionoftheloopflowintheradiator(λcoefficient)

5.3.150%flowintheradiator(λ=0.5)

Inearlyversionsoftheone-pipesystem,50%oftheloopflowwasdesignedfortheradiator.Thismagicfigureresultsfromthefactthatthetemperaturet2ofthewatersupplytothenextradiatorisequaltothearithmeticmeantemperatureofthepreviousradiator.AswesawunderFig5.2,t2isveryeasilycalculated.Basedontheaveragetemperatureoftheradiator,itwasthenpossibletocalculatethenominalpowertobeinstalledtoobtainthenecessaryemission.

Thehighoverflowintheradiatorwasconsideredtoimproveitsemission,andthusmakeitpossibletoreduceheatingsurfaceareastobeinstalled.Thisisnotalwaystrueastoohighavelocityintheinletcreatesasuctioneffect.Coldwaterinthebottomoftheradiatorismixedwiththehotwaterintheinletdecreasing,toacertainextent,theheatoutput.However,passing50%ofaloopflowof500l/hina250Wradiatorisequivalentto23timesitsnominalflow.Reducingtheflowusingthethermostaticvalvehaspracticallynoeffectonemissionfor96%(22/23)ofitsnominallift.Thereforethevalveusuallyworksnearitsclosedposition,withtheriskofbeinginefficient.

Moreover,whenathermostaticvalvecloses,theentireflowmustpassthroughthebypass.Thereforetheflowinthebypassisdoubled,andthepressurelossisquadrupled.Thishighpressurelossaffectsthetotalflowandtheemissionfromtheradiatorsintheloop.Toensurethatthiswillnothappen,alowerproportionoftheflowcanbetakenintheradiator.Flowvariationsinthebypassarethenlowerandtheloopflowismorestable.

Page 46: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

46

5.3.2Choiceofanotherflowintheradiator

Forloopflowsofupto200l/h,theTA-RSD801one-pipevalvehasaKv=1.2andtheflowintheradiatorcanbeadjustedfrom0to50%oftheloopflow.

Forloopflowsofmorethan200l/h,theKvoftheTA-RSD831is2.8andtheflowintheradiatorisadjustablefrom0to20%oftheloopflow.

Inbothcases,theKvoftheTA-RSDone-pipevalveisindependentoftheflowproportionchosenintheradiator.

Inordertoestimateitsrequirednominalpower,themaximumpossibleflowisgenerallyassumedintheradiatorwithaminimumvalueof10Kforthe∆T.

Theradiatorisselectedonthisbasisbut,sincethechoiceislimited,itsrealnominalpowerisgenerallyhigherthanthecalculatedpower.Therealflownecessarytoobtainthecalculatedheatingpoweristhendetermined.

Example:Ina400l/hloop,aradiatorissuppliedatawatertemperaturetsof82°Candmustemit850Wintoanenvironmentof20°C.

Preliminary calculation: 20%of400l/h=80l/h.Fora∆Tof10K,theflowmustbe0.86x850/10=73l/h.Thelowestofthesetwoflowsisused,namely73l/handthe∆Tistherefore10K.

UsingthediagraminFigA1(inappendixA),itisfoundthatthenominal75/65oversizingfactoroftheradiatoris0.84(Joints–ti=82–20=62totr–ti=72–20=52).Thenominalpower75/65oftheradiatortobeinstalledistherefore850× 0.84 = 716 W.

Finalcalculation:Therealnominalpowerofthechosenradiatoris935W.Whatflowshouldbeadjustedattheradiator?

TheoversizingfactorSpistherefore935/850=1.1.

UsingFigA1again,join(ts-ti)=(82–20)=62toSp=1.1togettr–ti=34.5thereforetr = 54.5.

Therequired∆Tistherefore82–54.5=27.5Kandtheflowq=0.86×850/27.5=26.6l/h,namely7%oftheloopflow.

Whenaninstallationisbeingrenovated,thenominalpowerofradiatorsisgiven.TheflowintheradiatoristhereforedeterminedbasedonthediagraminFigA1directly,usingtheoversizingfactorandthesupplywatertemperature.Insomenewbuildings,foraestheticreasons,allradiatorsareidenticalandthecorrectpowerhastobeobtainedbyappropriateadjustmentoftheflowtoeachradiator.

Page 47: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

47

BalancingofRadiatorSystems>5.One-pipedistribution

5.4 Theloopflow

Intheory,itisbettertousethehighestpossibleloopflow.Thisreducesthetemperaturedropintheloopandtherequiredheatingsurfaceareaforthelastradiators.Moreover,whenthermostaticvalvescloseonthefirstradiatorsintheloop,thereisnotahighincreaseinthewatertemperatureforthelastradiators.

Inpractice,theloopflowislimitedbytheavailabledifferentialpressureinrelationtothepipesize,thenumberofradiatorsetc.

The total looppower and the supplywater temperature are the predominant factors todetermine the realistic value for the loop flow (see section 5.4.1). In some cases,when λmax=0.2,alargeradiatorintheloopcanbethepredominantfactor(seesection5.4.2).

5.4.1Basedonagiven∆T

Theloopflowisaresultofthechosen∆Tandthesum ΣPofpowers,emittedbyradiatorsintheloop,accordingtothefollowingformula:

qL > 0.86 × ΣP

∆TL

qL =Loopflowinl/h.

ΣP = SumoftherequiredheatoutputinWoftheradiatorsintheloop.

∆TL = Temperaturedropintheloop(K).

Obviously, the allowable temperature drop reduces with the supply water temperature. Thetemperaturedropintheloopisnormallygivenby∆TL < 0.25 ×(ts–20).Substitutingthisvalueinthepreviousformulagivesanestimationofthelowestrealisticloopflow:

qL > 3.44 × ΣP

(ts-20)

Example:IfΣP=4000Wandts=80°C,qL > 230 l/h.

5.4.2Basedonthelargestradiatorintheloop(whenλmax=0.2)

Thelargestradiatorintheloop,PM,requiresaminimumflowtoavoidunreasonableoversizing.Usinganeffectivenessφ=0,43=∆TR/(ts–ti)forexample:qR=0,2×qL = PM ×0,86/∆TR and

qL > 10 × PM

(ts-20)

5.4.3Finalchoiceoftheloopflow

Thehighestwaterflowfromthetwomethodsofcalculationischosen.

Page 48: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

48

5.5 Pressure losses in the loop

Foraflowof300l/hinapipewithaninsidediameterof14mm,thepressurelossforwaterat20°Cis317Pa/m(32mm/m)and278Pa/mat70°C(NomogramB1inAppendixB)

One-pipevalvesmaybeconvertedintoequivalentmetresofpipeasshownintable5.1below.

dimm 10 11 12 13 14 15 16 17 18

Kv=1.2 3.79 6.23 9.80 14.87 21.88

Kv=2.8 0.69 1.14 1.80 2.73 4.02 5.76 8.06 11.05 14.88

1elbow 0.24 0.26 0.29 0.32 0.35 0.39 0.42 0.45 0.48

Table 5.1. Metres of equivalent pipe for valves with Kv =1.2 and 2.8. Equivalence for a single elbow. Water temperature 70 °C.

Thatmeans,forinstance,thatavalveofKv=2.8withtwoelbowshasapressuredropequivalentto4.72metresofpipe(di=14mm).

Page 49: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

49

BalancingofRadiatorSystems>Appendices

Appendices

A. Calculation of radiators in several conditions

ts=Supplywatertemperaturetr=Returnwatertemperatureti=RommtemperaturerequiredP=HeatoutputrequiredPn=Nominalheatoutputofradiator

Nominal conditionstsn=90°C trn=70°C tin=20°Ctsn=80°C trn=60°C tin=20°C

20

30

40

50

60

70

ts - ti tr - ti

75/65

Pn / P

0.5

1.0

1.5

2.0

3.0

4.0

20

30

40

50

60

70

Fig A1. The power of a radiator not working in nominal condition (n = 1.3).

Page 50: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

50

ts - ti)

Wat

er fl

ow in

l/h

per 1

000

W o

utpu

t

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

40 45 50 55 60 65 70

0.80.911.11.21.31.41.5

SP = Pn/P

30

20

25

1514

13

12

11

10

9

∆T

Fig A2. Water flow in l/h per 1000 W is a function of the oversizing factor Sp = Pn/P and the supply water temperature ts (nominal condition tsn = 75 °C, trn = 65 °C).

Examples:(usingFigA1andnominalconditions75/65)

1. The heat losses in a room are 1000 W. ts = 60 °C and tr = 50 °C. What nominal radiatorpowershouldbeinstallediftherequiredroomtemperatureis20°C?

Join ts – ti = 60 – 20 = 40 to point tr – ti = 50 – 20 = 30, to find Pn/P = 1.6. We therefore need to install a 1000 × 1.6 = 1600W radiator (75/65 conditions) to obtain 1000W(60/50conditions).

TherequiredflowisP×0.86/∆Tc = 1000 × 0.86/10 = 86 l/h.

Thefollowingformulacanalsobeused:

SP = ( ) n/2

= ( ) 1.33/2 = 1.6

2475 (ts– t i ) ( tr– t i )

2475 (60– 20)(50– 20)

2. 750Wmustbetransferredwitharadiatorsuppliedat70°C.Theflowis43l/h.Whatnominalcapacityshouldbeinstallediftheroomtemperaturetobeobtainedis22°C?

∆T = 0.86 x 750/43 = 15K therefore tr = ts – ∆T = 70 – 15 = 55 °C. Join ts – ti = 70 – 22 = 48 to point tr – ti = 55 – 22 = 33, to find Pn/P = 1,33.We therefore have toinstalla750×1.33=948Wradiator.

Page 51: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

51

BalancingofRadiatorSystems>Appendices

3. A radiator has a nominal capacity of 1250 W, whereas losses are only 1000 W. The water supply temperature is 80 °C and the room temperature is 20 °C. What shouldthewaterflowbetocompensateforthisoversizing?

Joints–ti=80–20=60toPn/P=1250/1000=1,25,tofindtr–ti=29.Thereforetr = 29 + 20 =49°C.

Thewatertemperaturedropmustbetr–ts=80–49=31K31Kandthewaterflowtobeset0.86 ×1000/31=28l/h,whereasthenominalflowthrougha1250Wradiatoris0.86× 1250/10 = 108 l/h.

Forcomputer,followingformulacanalsobeused:

2475 q =

0.86 × P

( ts– t i )–(ts– t i )

× SPn - n/2

2475 =

0.86 × 1000

(80– 20)–

(80– 20) × 1.25 -2/1.33

= 48 l/h

ThisformulahasbeentranslatedinthegraphoffigureA2.

4. Onaradiatorwithanominalcapacityof1000W(75/65),wemeasureawaterinlettemperaturetsof55°Candareturntemperaturetr of50°C.Theroomtemperaturetiis22.5°Cforanoutdoortemperaturete=3°C

4.1 Whatisthepresentheattransferoftheradiator. Join(ts–ti)=55–22.5=32.5°Cto(tr–ti)=50–22.5=27.5°C ThenPn/P=1.94.ThereforeP=1000/1.94=515W

4.2 Whatisthepresentflowcomparedwiththenominalflow? Nominalflow=0.86Pn/∆Tn = 0.86 × 1000/10 = 86 l/h. Presentrealflow=0.86×515/(55–50)=88.6l/h.

4.3 Whatwouldtheheatlossesbeforte=3°Ciftheroomtemperaturewas20°C? Presentheatlosses=515=k(ti–te)=k(22.5–3)thereforek=26.4. Lossesforti =20°Cgerk(20–3)=26.4(20–3)=449W.

4.4 What should the return temperature tr and thewater flowq be, to obtain a room temperatureof20°C?

For ti = 20 °C, Pn/P = 1000/449 = 2.23. Join (ts– ti) = (55 – 20) = 35 toPn/P = 2.23.

Tofind(tr–ti)=(tr –20)=20.6°C. Thereforetr=20+20.6=40.6°Cand∆T=55–40.6=14.4K. To obtain these conditions, the water flowmust be: 0.86 P/∆T = 0.86 449/14.4

= 3.2 l/h.

4.5 Whatnominalradiatorcapacitywouldhavebeennecessarytoworkundernominal conditions,iftheoutdoordesigntemperaturetec=–10°C?

Lossesattec=–10°C:k(20–(–10))=26.4×30=792W. Theinstalledradiatorcapacityshouldhavebeen792Wwithaflowof 0.86×792/10=68l/h.

Page 52: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

52

B. Pressure losses in pipes.

0.40

0.50

0.60

0.70

0.80

10

11

12

13

14

15

16

17

18

0.050

0.100

0.150

0.200

100

200

300

400

500

600

700

800

∆p v q di70

C

50

C

m/s l/s l/h mmPa/m

200

500

250

300

350

400

450

600

550

500

450

400

350

300

250

˚ ˚

Fig B1a. Pressure losses in pipes with roughness less than 0.0045 (smooth steel, copper, polyethylene, etc.)- di is the inside diameter of the pipe in mm.

Page 53: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

53

BalancingofRadiatorSystems>Appendices

10

1

12

13

14

15

16

17

18

∆p v q di70

C

50

C

m/s l/s l/h mmPa/m

50

100

150

200

250

300

350

400

450

0.02

0.04

0.06

0.08

0.10

0.12

0.20

0.30

0.40

0.50

200

150

50

100

100

150

200

˚ ˚

Fig B1b. Pressure losses in pipes with roughness less than 0.0045 (smooth steel, copper, polyethylene, etc.)- di is the inside diameter of the pipe in mm.

Page 54: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

54

1

2

∆ pPa/m

750

mmv

m/sq di

l/s m3/h

70 °C

20 °

C - R

e <

3500

5 °C

- R

e <

3500

50

100

150

200

250

300

350

400

450500

600

50

100

150

200

250

300

350

400

450

500

600

750

70 °C

20 °C

5.0

4.0

0.2

0.3

0.4

0.5

1.0

1.5

2.0

2.5

3.0

500

0.1

0.5

1

5

10

50

100

1000

0.1

0.5

1

5

10

50

100

500

DN300300

10

20

30

40

50

60

70

80

90100

120

140

160180200

250

DN10

DN15

DN20

DN25

DN32

DN40

DN50

DN65

DN80

DN100

DN125

DN150

DN200

DN250

Fig B2. Pressure drops and velocities (pipes with a roughness of 0.05 mm) for water at 20 and 70 °C

Example 1: PipeDN80 (di = 82.5mm) andwater flow20m3/h: Velocity = 1m/s and ∆p=140Pa/m(at20°C).

Example 2: PipeDN10(di=12.5mm)andwaterflow0.1m3/h:Reynoldsnumberbeingbelow3500,thisnomogramisnotapplicableinthiscase,asitwasestablishedforturbulentconditions.

Page 55: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD
Page 56: Hydronic Engineering Handbook Engineering GREAT Solutions...hydronic resistance, all the available ∆p of 14 kPa has to be taken in the STAD. T hat means that the flowin the STAD

Find out morewww.imi-hydronic.com

qr

Balancing of Radiator SystemsHydronicEngineeringHandbookN°3

“Balancingofradiatorsystems”isthethirdhandbookinTAHydronicsseriesofpublicationsabouthydronicdesignandbalancing.Thefirsthandbookdealswithbalancingofcontrolloops,thesecondwithbalancingindistributionsystemsandthefourthwithhydronicbalancingwithdifferentialpressurecontrollers.