  • Hydraulic SeparationMoving Beyond Priamry / Secondary Piping...

    presented by:John Siegenthaler, P.E.Appropriate DesignsHolland Patent, NYwww.hydronicpros.com Copyright 2012, J. Siegenthaler, all rights reserved. The contents of this file shall not be copied or transmitted in any form without written permission of the author. All diagrams shown in this file on conceptual and not intended as fully detailed installation drawings. No warranty is made as the the suitability of any drawings or data for a particular application.

    primary!circulator

    closely!spaced!

    tees

    parallel!primary!circuit

    load!#1

    load!#2

    load!#3

    balancing valves

    crossover!bridge

  • Hydraulic SeparationIts not just about hydraulic separators...

    Todays topics... What is common piping? Whats the relationship b/w common piping & hydraulic separation? It doesnt have to be perfect What is the ideal hydronic header? Achieving hydraulic separation using low resistance heat souce Achieving hydraulic separation using closely spaced tees Achieving hydraulic separation using a buffer tank Achieving hydraulic separation using a hydraulic separator Divide & Conquer Examples of systems using hydraulic separation

  • What is COMMON PIPING?

    The degree to which two or more operating circulators interact with each other depends on the head loss of the common piping.The lower the head loss of the common piping the less the circulators will interfere with each other.

    common piping

    circulator 1

    circuit 1

    circuit 2 circulator 2

    Its the piping components shared by two or more circuits.

    When the head loss of the common piping is very low, there is hydraulic separation between the circuits.

  • Very little head loss occurs!in this portion of the circuits.

    common piping circulator 1

    circuit 1

    circuit 2 circulator 2

    When the head loss of the common piping is very low, there is hydraulic separation between the circuits.

  • Very little head loss occurs!in this portion of the circuits.

    common piping circulator 1

    circuit 1

    circuit 2 circulator 2

    Assume that circulator 1 is operating, but that circulator 2 is off. The lower (blue) system head loss curve in figure 2 applies to this situation.

    flow ratehe

    ad lo

    ss (f

    eet o

    f hea

    d)00

    pump curve!(circulator 1)

    circuit 1 head loss curve including !common piping (both circulators on)

    circuit 1 head loss curve including !common piping (1 circulator on)

    VERY small decrease in!circuit 1 flow rate!

    when circuit 2 is on

    very small change in!head loss across!common piping!when both circuits are on

    flow rate in circuit 1 when it is the only circuit operating

    flow rate in circuit 1 when BOTH circuits!

    are operating

    Next, assume circulator 2 is turned on, and circulator 1 continues to operate.

    The flow rate through the common piping increases, and so does the head loss across it.

    However, because of its spacious geometry, the increase in head loss across the common piping will be very slight. The system head loss curve that is now seen by circulator 1 has very slightly steepened. It is the upper, (green) curve shown in figure 2.

    The operating point of circuit 1 has moved very slightly to the left, and as a result, the flow rate through circuit 1 has decreased very slightly.

  • Very little head loss occurs!in this portion of the circuits.

    common piping circulator 1

    circuit 1

    circuit 2 circulator 2

    Imagine a hypothetical situation in which the head loss across the common piping was zero, even with both circuits operating.

    Because NO head loss occurs across the common piping, it would be impossible for either circulator to influence the other circulator.

    This would be perfect hydraulic separation.Fortunately, perfect hydraulic separation is not required to ensure that the flow rates through independently operated circuits remain reasonably stable.

    Almost Perfect Is Good Enough:

  • The higher the flow resistance of the common piping, the more each circulator will influence flow in the other circuit (e.g. the lower the hydraulic separation of the circuits.

    common piping (with HIGH FLOW RESISTANCE)

    circulator 1

    circuit 1

    circuit 2 circulator 2

    Common piping with high flow resistance is NOT good:

  • common piping and !heat source have!

    HIGH FLOW RESISTANCE

    ON ONlarger

    circulatorsmaller

    circulator

    P=22 psibackseated!flow checkP=17psi

    common piping and !heat source have!

    high flow resistance

    large circulator

    small circulator

    ON

    P p

    rodu

    ced"

    by c

    ircula

    tor"

    @ 0

    flow

    = 4

    psi

    P= 5 psi

    P =

    5 p

    si

    no flow

    P=12 psi

    P=17 psi

    P=13

    psi

    P=16

    psi

    ONP= 10 psi

    High flow resistance common piping - something to avoid

    5

    10

    15

    0

    head

    add

    ed (f

    eet)

    0

    6

    4

    2

    02 4 6 8 10

    flow rate (gpm)

    pump curve!for small circulator

    !P=Head

    ()

    D 144

    " #$% &'

    4 psi P at 0 flow

  • Multi-zone system - using zone circulators

    low flow resistance headers

    other zone circuits

    low flow resistance heat source

    zone circulators with spring-loaded

    check valves

    purging!valves

    OK

    other zone circuits

    zone circulators with spring-loaded

    check valves

    purging!valves

    compact mod/con

    boiler

    NOT OK

    Always keep the flow resistance of the common piping as low as possible. This provides hydraulic separation between circulators. Always provide a check valve on each zone circuit.

    high flow resistance of compact boiler creates flow bottleneck

  • circuit 2 circulator 2

    common!piping

    circulator 1

    circuit 1

    common!piping

    circulator 1

    circuit 1

    circuit 2 circulator 2

    common!piping

    Divide & Conquer:Hydraulic separation allows designers to think of an overall system as a collection of independent (hydraulically isolated) circuits.

    From the standpoint of hydraulics, each circuit can be designed as if its a stand-along circuit.

    More on this later...

  • load!#1

    load!#2

    load!#3

    closely!spaced!

    tees!(typical)

    primary!circulator

    secondary!circuit

    secondary!circuit

    secondary!circuit

    secondary circuit

    primary!circuit!

    (series)

    Primary / Secondary piping - where it all began...

    Primary / secondary piping, using closely spaced tees, is now well known and often used in North America.

    But primary / secondary piping is not the ONLY way to create hydraulic separation...

    Primary / secondary piping, is one way to achieve hydraulic separation between circulators.

  • Both series and parallel primary/secondary systems require a primary circulator.

    This adds to the installed cost of the system AND adds hundreds, even thousands of dollars in operating cost over a typical system life.

    load!#1

    load!#2

    load!#3

    closely!spaced!

    tees!(typical)

    primary!circulator

    secondary!circuit

    secondary!circuit

    secondary!circuit

    secondary circuit

    primary!circuit!

    (series)

    SERIES primary loop

    primary!circulator

    closely!spaced!

    tees

    parallel!primary!circuit

    load!#1

    load!#2

    load!#3

    balancing valves

    crossover!bridge

    PARALLEL primary loop

    Series and parallel primary/secondary systems

  • An example of primary loop circulator operating cost:

    Consider a system that supplies 500,000 Btu/hr at design load. Flow in the primary loop is 50 gpm with a corresponding head loss of 15 feet (6.35 psi pressure drop). Assume a wet rotor circulator with wire-to-water efficiency of 25 is used as the primary circulator.

    The input wattage to the circulator can be estimated as follows:

    W = 0.4344 f P0.25 =0.4344 50 6.35

    0.25 = 552watts

    Assuming this primary circulator runs for 3000 hours per year its first year operating cost would be:

    1st year cost = 3000hryr

    552w1

    1kwhr1000whr

    $0.10kwhr

    = $165.60

  • Assuming electrical cost escalates at 4% per year the total operating cost over a 20-year design life is:

    This, combined with eliminating the multi-hundred dollar installation cost of the primary circulator obviously results in significant savings.

    cT = c1 1+ i( )N 1

    i

    = $165.60

    1+ 0.04( )20 10.04

    = $4,931

    An example of primary loop circulator operating cost:

  • Question: What is the ideal header in a hydronic system?Answer: One that splits up the flow without creating head loss Think about a copper basketball with pipes sticking out of it in all directions.

    very low head loss!

    inside header

    Wouldnt this be pretty close to an ideal header???

  • So why dont we build headers like this???

    very low head loss!

    inside header

    Short / fat headers are GOOD!

    Instead, we approximate the ideal header by making it short & fat

    shortfat

    Long / skinny headers are BAD!

  • So whats EXACTLY is a short / fat header???

    shortfat

    max (design) flow rate

    select pipe size that yields a flow velocity no higher than 2 feet per second

  • very low flow resistance!

    common piping!

    size headers for max flow velocity of 2 ft/sec

    low flow resistance

    heat!source

    The short / fat headers hydraulically separate the distribution circulators from each other.

    The low flow resistance heat source maintains low flow resistance of common piping

    Hydraulic separation achieved by low flow resistance heat source & short / fat headers.

  • The short / fat headers hydraulically separate the distribution circulators from each other.

    closely spaced tees

    very low flow resistance!common piping!

    high flow ! resistance boiler

    size headers for max flow velocity of 2 ft/sec

    Hydraulic separation achieved by closely spaced tees & short / fat headers.

    The closely spaced tees hydraulically separate the heat source from the header system.

  • multiple!boiler!

    controller

    ouside!sensor

    closely!space!tees

    zone circulators!(w/ check valves)

    air!vent

    drain!valve

    purge!valves

    "short/fat" header

    supply !temperature!sensor

    A

    B

    The short & fat header and close spacing between supply and return connections results in a low pressure drop between points A and B. Each load circuit is hydraulically separated from the others.

    Header should be sized for max. flow velocity of 2 feet per second Each circuit must include a check valve.

    The supply temperature sensor must be downstream of the point of hydraulic separation.

    The header can be vertical (as shown) or horizontal.

    Hydraulic separation achieved by closely spaced tees & short / fat headers.

  • The short / fat headers hydraulically separate the distribution circulators from each other.

    buffer!tank

    very low flow resistance!common piping!

    size headers for max flow velocity of 2 ft/sec

    boiler!circulator

    high flow resistance boiler

    Hydraulic separation achieved by buffer tank (piped as shown ) & short / fat headers.

    The buffer tank hydraulically separate the heat source from the header system.

  • to / from other heating

    zones

    wood gasification boiler

    VENT

    ThermoCon tank

    Hydraulic separation achieved by buffer tank

  • earth loop circuits

    purging!valves

    VENT

    temperature!sensor

    chilled water

    cool

    ing m

    ode

    reversing!valve

    cond

    ense

    r

    evap

    orat

    or

    insula

    te a

    ll chil

    led w

    ater

    pipi

    ng!

    to p

    reve

    nt c

    onde

    nsat

    ion

    chilled water air handlers

    ThermoCon tank

    zoned chilled water cooling

    Only tanks with sprayed foam insulation should be used for chilled water storage.

    Hydraulic separation achieved by buffer tank

  • Hydraulic Separation in Micro-load systems:The small insulated tank provides: Thermal buffering Hydraulic separation Air separation and collection Sediment separation and collection

    indirect water heater

    thermostatic!radiator valves!(TRV) on each!

    radiator

    TRV

    TRV

    TRV

    TRV

    TRV

    manifold!station

    TRV

    variable speed!pressure-regulated!

    circulator

    outdoor!temperatue!

    sensor

    buffer tank, also serves as hydraulic separator,!air separator, dirt separator

  • hydraulic separator

    very low flow resistance!common piping!

    high flow ! resistance boiler

    size headers for max flow velocity of 2 ft/sec

    The short / fat headers hydraulically separate the distribution circulators from each other.

    Hydraulic separation achieved by hydraulic separator.The hydraulic separator hydraulically separates the heat source from the header system.

  • diam

    eter

    = 1

    "

    flow velocity = 4 ft/secdiameter = 3"

    flow rate = 6.5 gpm

    flow velocity = 0.44 ft/secflow rate = 6.5 gpm

    area = A

    area = 9Aalmost zero

    pressure drop b/w!upper and lower

    connections

    air bubbles can rise faster than the downward water flow

    dirt particle drop into lower bowl

    drain valve

    air ventWhats going on inside a hydraulic separator?

    The low vertical velocity inside the separator produces minimal pressure drop top to bottom. Thus there is very little tendency to induce flow on the load side of the separator.

  • drain valve

    air vent

    "STANDARD"!hydraulic !separator

    What does the coalescing media do inside a hydraulic separator?

    The coalescing media creates tiny vortices that cause gas molecules (mostly oxygen and nitrogen) to form microbubbles. The media also helps microbubble merge together and rise upward out of the active flow zone.

    upper coalescing media encourages!air bubbles to form

    drain valve

    air vent

    air bubbles "ride" up the vertical filaments of the coalescing media - out of the active flow zone

    lower coalescing media encourages!dirt particle to drop!out of active flow zone

    HIGH PERFORMANCE!(air & dirt removal)!hydraulic separator

  • drain valve

    air vent

    high performance!(low velocity zone)!

    dirt separator

    high performance!(microbubble)!air separator

    drain valve

    air vent

    WELD

    WELD

    drain valve

    air vent

    CUT

    CUT

    Why companies that offer air and dirt separators also offer hydraulic separators...

    drain valve

    air vent

  • heating!load(s)

    boiler circuit

    distribution system

    air!separator

    sediment!strainer

    closely!spaced!tees

    heating!load(s)

    boiler circuitdistribution

    system

    Hydraulic!Separator

    High performance hydraulic separators provide three functions:1. hydraulic separation2. air separation 3. dirt separation

  • 1. Flow in the distribution system is equal to the flow in the boiler circuit.

    2. Flow in the distribution system is greater than flow in the boiler circuit.

    3. Flow in the distribution system is less than flow in the boiler circuit.

    Each case is governed by basic thermodynamic...

    As the flow rates of the boiler circuit and distribution system change there are three possible scenarios:

  • T4T3

    T2T1f1 f2

    f3 f4

    NOTE:=f1 f3

    (always!)f2 f4=

    NOTE:

    (always!)

    In this case only:!

    T1 T2T3 T4

    ==

    Case #1: Distribution flow equals boiler flow:

    Very little mixing occurs because the flows are balanced.

  • T4T3

    T2T1f1 f2

    f3 f4

    NOTE:=f1 f3

    (always!)f2 f4=

    NOTE:

    (always!)

    Case #2: Distribution flow is greater than boiler flow:

    Mixing occurs within the hydraulic separator.

    T2 =f4 f1( )T4 + f1( )T1

    f4

    The mixed temperature (T2) supplied to the distribution system can be calculated with:

    Where:f4 = flow rate returning from distribution system (gpm)f1 = flow rate entering from boiler(s) (gpm)T4 = temperature of fluid returning from distribution system (F)T1 = temperature of fluid entering from boiler (F)

  • Case #3: Distribution flow is less than boiler flow:

    T2 =f4 f1( )T4 + f1( )T1

    f4

    The temperature returning to the boiler (T3) can be calculated with:

    Where:T3 = temperature of fluid returned to boiler(s) (F)f1 = flow rate entering from boiler(s) (gpm)f2, f4 = flow rate of distribution system (gpm)T1 = temperature of fluid entering from boiler (F)T4 = temperature of fluid returning from distribution system (F)

    Heat output is temporarily higher than current system load.

    Heat is being injected faster than the load is removing heat.

    T4T3

    T2T1f1 f2

    f3 f4

    NOTE:=f1 f3

    (always!)f2 f4=

    NOTE:

    (always!)

    Mixing occurs within the hydraulic separator.

  • Sizing of Hydraulic Separators:Hydraulic separators must be properly sized to provide proper hydraulic, air, and dirt separation. Excessively high flow rates will impede these functions.

    The piping connecting to the distribution side of the Hydro Separator should be sized for a flow of 4 feet per second or less under maximum flow rate conditions.

    The size of a hydraulic separator refers to the nominal piping size of the 4 side connections (not the diameter of the vertical barrel).

    Pipe sizeof

    hydraulicseparator

    1 1.25 1.5 2 2.5 3 4 6

    Max flowrate

    (GPM)11 18 26 40 80 124 247 485

    union connections

    flange connections

  • Typical European concepts for multiple mod/con installation:

  • Typical European concepts for multiple mod/con installation:

  • Boiler manifold with integral hydraulic separator (courtesy Sinus North America).

    Form fitting insulation is supplied with all manifolds.

    Flexible piping connects each boiler to low manifold. (Boilers have integral circulators and check valves.)

    Notice that two additional boilers can be added to the front side of lower manifold.

  • Here's what the real products look like

  • How about 8 mod/cons with integral hydraulic separator (courtesy Sinus North America).

    Think of the output per unit of mechanical room floor area

    Each boiler can be independently serviced .

    Flexible piping connects each boiler to low manifold. (Boilers have integral circulators and check valves.)

  • Example of Hydro Separator Installation in New System:Magna Steel Corporation - Connecticut

    Photos courtesy of Peter Gasperini - Northeast Radiant

  • Example of Hydro Separator Installation in Old System:

    Because hydraulic separators remove sediment fromsystems theyre ideal for applications where new boilers are retrofit to old distribution systems.

  • Example of Hydro Separator Installation in Old System:Because hydraulic separators remove sediment from systems theyre ideal for applications where new boilers are retrofit to old distribution systems.

    hydraulic!separator

    supply!temp.!sensor

    from existing system

    sediment capture!and removal

    multiple!boiler!

    controller outdoor!temperature!sensor

  • existing cast-iron radiators (converted from steam)

    existing piping

    mod/con boiler!w/ compact heat exchanger

    supply!temperature!

    sensor

    ECM!pressure!regulated!circulator

    vent

    hydraulic!separator

    A hydraulic separator is a great way to interface a new mod/con boiler to a older steam conversion system.

    WHY?

    Dirt separation is especially important in older systems with iron components.

  • fluid feeder

    earth loop circuits

    purging!valves

    purge

    variable-speed!pressure-regulated!

    circulator

    geothermal manifolds

    hydro!separator

    to / from!other heat pumps

    heat

    ing m

    ode

    reversing!valve

    cond

    ense

    r

    evap

    orat

    or

    water-to-water!heat pump

    zone!valve

    balancing!valve

    Hydraulic Separators will likely become a key component in multiple ground source heat pump applications.

    The will allow the flow rate in the earth loop to be different than the flow rate through the heat pump array - more on this later...

  • temperature!sensor

    VENT

    fluid feeder!(optional)

    earth loop circuits

    purging!valves

    purge

    to / from other heating zones

    variable-speed!pressure-regulated!

    circulator

    geothermal manifolds

    hydro!separator

    water-to-water!heat pump

    chilled water buffer tank

    temperature!sensor

    warm water buffer tank

    circulator!w/ check

    3-way!diverter!

    valve

    insula

    te a

    ll chil

    led w

    ater

    pipi

    ng!

    to p

    reve

    nt c

    onde

    nsat

    ion

    chilled water air handlers

    varia

    ble-

    spee

    d!pr

    essu

    re-re

    gulat

    ed!

    circu

    lator

    insula

    te a

    ll chil

    led w

    ater

    pipi

    ng!

    to p

    reve

    nt c

    onde

    nsat

    ion

    reversing!valve

    cond

    ense

    r

    evap

    orat

    or

    compressor

    TXV

    heat

    ing m

    ode

    size all header piping for maximum flow velocity of 2 ft/sec to provide hydraulic separation

    fixed speed!or!

    variable-speed!circulator

    12D AAB

    B

    AAB

    B

    circulator!w/ check

    reversing!valve

    cond

    ense

    r

    evap

    orat

    or

    compressor

    TXV

    heat

    ing m

    ode

    12D AAB

    B

    AAB

    B

    circulator!w/ check

    reversing!valve

    cond

    ense

    r

    evap

    orat

    or

    compressor

    TXV

    heat

    ing m

    ode

    12D AAB

    B

    AAB

    B

    3-way!diverter!

    valve

    Hydraulic Separators will likely become a key component in multiple ground source heat pump applications.

  • circuit 2 circulator 2

    common!piping

    circulator 1

    circuit 1

    common!piping

    circulator 1

    circuit 1

    circuit 2 circulator 2

    common!piping

    Divide & Conquer:Hydraulic separation allows designers to think of an overall system as a collection of independent (hydraulically isolated) circuits.

    From the standpoint of hydraulics, each circuit can be designed as if its a stand-along circuit.

  • Simplifying system analysis Preventing flow interference

    Divide & Conquer:

  • LWCO

    cast-iron sectional boiler!with oil burner

    brass unions!(typical)

    PRV

    closely spaced tees

    3/4"

    cop

    per

    Webstone!purging!valves

    variable speed!pressure regulated!

    circulator!set for Pc

    !mix supply!sensor

    1.25" copper 12D

    3/4"

    cop

    per

    1" c

    oppe

    r

    3/4"

    cop

    per

    3/4"

    cop

    per

    1" c

    oppe

    r

    3/4"

    cop

    per

    3/4"

    cop

    per

    3/4"

    cop

    per

    outdoor!sensor

    TRV

    TRV

    TRV

    TRV

    TRV

    TRV

    thermostatic radiator valves!on each panel radiator

    12- circuit manifold distribution system

    using PEX or PEX-AL-PEX tubing

    panel radiator

    MRH

    L

    12D

    356 injection mixing controller

    closely spaced tees3/4"

    cop

    per

    balancing!valve

    outdoor!sensor

    purging!valves

    1" c

    oppe

    r

    !mix supply!sensor

    1" c

    oppe

    r

    1" c

    oppe

    r

    1" c

    oppe

    r

    1.25" copper 12D

    manifold B

    manifold A

    2" copper supply!and return headers!

    keep as short as possible

    2" copper

    2" copper

    1.25" copper

    3/4" copper

    12D

    1" copper

    12D 12D

    3/4"

    cop

    per

    return temperature!sensor for 356!

    mixing controllers

    !indirect water heater

    12D

    2" air separator3/4" fast fill piping

    3/4" cold water supply

    12D

    manifold G!(garage)

    strap-on!aquastat!contacts!

    close at 100F!open at 50F

    P1

    P2

    P3

    P4

    P5

    P6

    P7

    P8These panel radiators are representative!of second floor heating distribution system!exact size and number of panels may vary,!but all are supplied with 1/2" PEX-AL-PEX tubing, and controlled by individual thermstatic radiator valves.

    30 psi!PRV

    fill/purgesupply sensor

    3/4"

    cop

    per

    12DHW

    CW

    P&TRV

    tank acqustat

    floor!drain

    1.25" copper

    swing!check

    manifold C

    manifold D

    manifold E

    manifold F

    !brazed plate SS!heat exchanger

    to / from other!radiators

    This portion of system filled with 40% solution of inhibited

    propylene glycol

    3/4"

    cop

    per

    3/4" copper

    manifold H (2nd floor)

    manifold I (2nd floor)3/

    4" c

    oppe

    r

    3/4"

    cop

    per

    3/4"

    cop

    per

    variable speed!pressure regulated!

    circulator!set for Pc

    356 injection mixing controller

    356 injection mixing controller

    balancing!valve

    zone valves

    all three injection pumps!equipped with internal!

    check valves

    Divide & Conquer:

    In a complex system like this...

    How does the water know where to go???

  • P1

    cast-iron sectional boiler

    P2

    P3

    P4

    P5

    manifold H (2nd floor)

    manifold I (2nd floor)

    P7

    P8

    TRV

    TRV

    TRV

    TRV

    TRV

    TRV

    P6

    low flow resistance heat source!+ short / fat headers

    In this system, hydraulic separation was achieved using short / fat header in combination with low flow resistance heat source.

    Hydraulic separation allows designers to think of an overall system as a collection of independent (hydraulically isolated) circuits.

    Divide & Conquer:

  • You find it: Where is the hydraulic separation in this system?

    reversing!valve

    cond

    ense

    r

    evap

    orat

    or

    TXV

    cool

    ing m

    ode

    VENT

    temperature!sensor

    insula

    te a

    ll chil

    led w

    ater

    pipi

    ng!

    to p

    reve

    nt c

    onde

    nsat

    ion

    chilled water air handlers

    to / from other heating

    zones

    buffer tank

    heating is off

    chilled water

    variable-speed!pressure-regulated!

    circulator

    electric!heating!element

    DHW P&TRV

    water heater

    geothermal manifolds

    earth loop circuits

    purging!valves

  • You find it: Where is the hydraulic separation in this system?

    closely!spaced!

    tees

    air handler w/ drip pan

    indoor unit

    INSI

    DE

    OUTS

    IDE

    !outdoor unit

    thermostatic tempering valve

    indiret water heater with auxiliary electric element

    motorized diverter

    valve

    make-up!water &

    supllemental!expansion

    tank

    variable speed!pressure regulated!

    circulators

    purge!valve

    flow setterzone valve

    low flow resistance headers

    chilled water cooling

    low temperature space heating

  • Hydraulic Separators now available in North America

    Sinus North AmericaPrecision Hydronic

    Products

    Bell & Gossett

    Taco

    SpirothermCaleffi