hv2
TRANSCRIPT
-
CHAPTER 6HIGH VOLTAGE GENERATION,
MEASUREMENT AND TESTING TECHNIQUE
byAssoc. Prof. Dr. Mohd Muhridza YaacobInstitute of High Voltage & High Current
Faculty of Electrical EngineeringUniversiti Teknologi Malaysia
Dr. MMY 2005 1
-
Dr. MMY 2005 2
Introduction
Generation of high voltage and current are required for testing of power equipment Simulating the stresses on the insulation
to overvoltages to determine the insulation strengthVoltage stresses such as the power
frequency and high frequency voltages, lightning impulse, and switching impulse.
-
Introduction In high voltage testing, the current under
failure conditions is limited to small value (less than 1 A for d.c. or a.c. voltages and few amperes for impulse or transient voltages).
High currents are required when testing surge arresters or short-circuit testing of switchgear (several kA)
Dr. MMY 2012 3
-
Dr. MMY 2012 4
Classification1. High Voltage Direct Current
(HVDC)2. High Voltage Alternating Current
(HVAC) 3. High Impulse Voltage Lightning
& Switching4. High Current AC, DC & Impulse
-
Dr. MMY 2012 5
HVDC Generation Required for insulation testing on
cables and capacitors Used also as impulse generator
charging unit Generation circuits are;1. Half Wave and Full Wave Rectifier2. Voltage Multiplier Circuits3. Voltage Doubler Circuits
-
Dr. MMY 2012 6
HVDC Generation
1. Electron Tube rectifier up to 250 kV
Solid state or semiconductor rectifier up to 20 kV. For higher voltage several units are used in series
-
Dr. MMY 2005 7
HVDC GenerationIn modern high voltage lab semiconductor (solid state) rectifier stacks are usedCommonly prefered are silicon diodes with PIV of 1 to 2 kV or selenium element with PIV up to 500 V
-
Dr. MMY 2012 8
HVDC GenerationHalf Wave Rectifier
+ve half-cycle: C is charged to Vmax-ve half-cycle: C is discharged to loadCRL = 10 times the ac supply periodRectifier valve have peak rating of 2VmaxR is connected in series with transformer output to limit current
-
HVDC Generation
Dr. MMY 2005 9
Output Without smoothing C
Output Withsmoothing C
-
Dr. MMY 2012 10
HVDC Generation
Full Wave Rectifier+ half-cycle: A conducts
and charged up C (smoothing capacitor)
-ve half-cycle: B conducts and charged up C Centre-tap source transformer of 2V
-
Dr. MMY 2012 11
HVDC Generation(a) Sine wave input(b) Output of half-wave(c) Output of full-wave V is the fluctuation
in output dc duringon-load (ripple)
V is larger for half-wave Ripple is kept low by
proper choice ofcapacitor and transformer reactance
-
Dr. MMY 2005 12
TransformerRectifier
HV Arm Resistive DividerLV Arm
Ground
-
Dr. MMY 2012 13
HVDC Control Panel
-
Dr. MMY 201214
HVDC GenerationVoltage Doubler Circuit - C1 is charged through
R1 to Vmax (-ve cycle)- transformer voltage rise to Vmax and C1potential rises to 2Vmax(+ve cycle)
- C2 in turn charged to 2Vmax thro R2
- Cascaded voltagedoubler for larger output voltage
-
Dr. MMY 2012 15
HVDC GenerationVoltage Multiplier Circuits (Cockcroft-
Walton) 1st stage same as
doubler circuit (D1,D2,C1,C2)
For higher voltage the circuit is repeated with cascade or series connection (4,6,..2n)
C4 charged to 4Vmax and C2n to 2nVmax
-
Dr. MMY 2012 16
HVDC GenerationD1,D3,D2n-1 conduct during +ve half-cyclesD2,D4,D2n conduct during -ve half-cyclesVC2 = Vac + VC1The voltage across othercapacitors (C2 C2n) is the difference between voltage across theprevious capacitor and charging voltage
-
Dr. MMY 2012 17
HVDC Measurement
Essential to measure voltage & current accurately to ensure safety to personnel and equipment
Method or technique;1. Series resistance microammeter2. Resistance potential divider3. Generating voltmeter4. Sphere and other spark gap
-
Dr. MMY 2012 18
HVDC Measurement
High Ohmic Series Resistance with Microammeter
- A very high resistance (hundreds of M) connected in series with microammeter
Vsource = IR - Voltage drop in meter is
negligible since meter impedance is small
-
Dr. MMY 2012 19
HVDC Measurement
- Protective device as protection against high voltage if R fails
- Resistor constructed from wire wound
- Ohmic resistor value is chosen such that 1 10 A is allowed for full scale defelction
-
Dr. MMY 2012 20
HVDC MeasurementLimitations:1. Power dissipation and source loading2. Temperature effect and long time stability3. Voltage dependence of resistive elements4. Sensitivity to mechanical stress
-
Dr. MMY 2012 21
HVDC Measurement
Resistance Potential Divider
Resistance connected to electrostatic or high impedance voltmeter
High voltage magnitude
= [(R1 + R2)/R2]V2
-
Dr. MMY 2012 22
HVDC Measurement
Generating VoltmetersA variable capacitor electrostatic
voltage generator which generates current proportional to the applied voltage
No direct connection to high voltage electrode
eg. Van de Graaff Generator
-
Dr. MMY 2012 23
HVAC Generation
- Single transformer for voltage < 300 kV
- Used for routine test of service equipment such as transformers, switchgears and cables
- Cascade & Resonant Transformers
-
Dr. MMY 2012 24
HVAC GenerationCascade Transformer
- 1st Tx. at ground potential- 2nd Tx. kept on insulators
and maintained at V2- HV winding of 1st unit
connected to tank of 2ndunit
- LV winding of 2nd unit is supplied from excitation winding of 1st unit
-
Dr. MMY 2012 25
HVAC GenerationCascade Transformer
- 3nd Tx. kept on insulators above ground at ground potential of 2V2 and is supplied from the 2ndunit.
- Supply 230 400 V for up to 100 kVA
- Supply 3.3 11 kV for larger units
-
Dr. MMY 2012 26
HVAC GenerationCascade Transformer
- 2nd scheme using isolating transformer (IS1, IS2, IS3) to excite 2nd& 3rd stage and are insulated to tank potentials
- Supply from same ac input
- Expensive , spacing but natural cooling, light & compact
-
Dr. MMY 2005 27
HVAC GenerationCascade Transformer
- Testing of hv apparatus involves supplying of capacitive loads with low power dissipation
- Transformer Rating, P = kV2C (k>1.0)k to account extra capacitanceV nominal output voltage of TxC test object capacitance - angular frequency
-
Dr. MMY 2012 28
HVAC Generation
Cascade Transformer- Typical Capacitance values of test object;
Test Object CapacitanceP. Tx (< 1 MVA) 1000 pF
(> 1 MVA) 1000 10 000 pFP. Cables (solid) 250 300 pF/m
(gas) 50 80 pF/mGIS s/station 100 10 000 pF
-
Dr. MMY 2012 29
HVAC GenerationResonant Transformer- Eqv. Cct: windings leakage
reactance & resistance, magnetizing reactance and shunt capacitance across the output terminal due to bushing of hv terminal and test object
- Utilised in testing at very high voltage and on occasion requiring large current such as cable test, dielectric loss and pd measurement
-
Dr. MMY 2012 30
HVAC GenerationSeries Resonant Transformer
To have series resonance at power frequency, L1 + L2 = 1/CVc = -jVXc/[R + j(XL-XC)]
= VXC/R = V/CRThe factor XC/R is the Q factor which gives the magnitude of the voltage multiplication across the test object under resonanceTest Condition; (Le + L) = 1/ C
Le eqv. Leakage inductance
-
Dr. MMY 2012 31
HVAC GenerationParallel ResonantHv reactor connected asauto transformerMore stable output andhigh rate of rise of testvoltageBuilt for 500 kV single unitCascaded unit for 3000kV
-
Dr. MMY 2012 32
HVAC GenerationPrinciple of operation- Voltage regulator (auto-transf or induction
reg.) is connected to main supply- 2ndary winding at exciter transf. is connected
across hv reactor L & C- Inductance of reactor is varied by varying air
gap- C is the test object, divider, bushing
capacitances- Q factor = 50
-
Dr. MMY 1205 33
HVAC GenerationAdvantages;1. Pure output sine wave2. Less power requirement3. No high-power arcing and high current surges
if test object fails as resonance ceases at failure4. Possible for cascading5. Simple & compact6. No repeated flashoverDisadv. requirements of additional variable
chokes
-
Dr. MMY 2012 34
HVAC Measurement
1. Series Impedance Voltmeter2. Series Capacitance Voltmeter3. Capacitance Potential Divider4. Voltage Transformer5. Electrostatic Voltmeter6. Peak Reading AC Voltmeter7. Spark Gap
-
Dr. MMY 2012 35
HVAC MeasurementSeries Impedance Voltmeter
- for power frequency by using pure resistance or reactance- capacitor often used as series reactance sinceresistance involves power loss problem in variation of resistance with temperature
-
Dr. MMY 2012 36
HVAC Measurement
Series Impedance Voltmeter -residual inductance of the
resistance give rise to impedance which is different from its ohmic value
- Z = R + jL(1 - 2LC) + j CR)
= R[1 + j(L/R - CR)]
-
Dr. MMY 2012 37
HVAC MeasurementSeries Capacitance
VoltmeterIc = jCVV = (V12 + V22 + ..+Vn2)- not recommended when
ac voltages are not purely sinusoidal but contains harmonics
- used with cascade transf. For measuring rms up to 1 MV
-
Dr. MMY 2012 38
HVAC Measurement
Series Capacitance Voltmeter
- series capacitance formed as a parallel plate capacitor between hv terminal and ground plate
- rectifier ammeter as indicating instrument and directly calibrated in hv rms value ( 0 100 A)
-
Dr. MMY 2012 39
HVAC MeasurementCapacitance Voltage Divider
- eliminate errors due to harmonic voltages
- C1 : Std compressed air or gas capacitor as C1
- C2 : large capacitor (mica @ paper)
- C1 is connected to C2 thro shielded cable
- C2 is completely shielded in a box to avoid stray capacitances
-
Dr. MMY 2012 40
HVAC MeasurementCapacitance Voltage Divider
V1 = V2 C1 + C2 + CmC1
Cm capacitor of the meter & connecting cableV2 meter reading
-
Dr. MMY 2012 41
HVAC Measurement
-
Dr. MMY 2005 42
HVAC Measurement Capacitance Voltage
Transformer (CVT)- Capacitance divider with suitable matching or isolating potential transformer tuned for resonance condition- C1 made up of few units of hvcapacitors - Transf. ratio : hv:10 to 30 kV,
lv:100 to 500 V- Value of L (tuning choke) is chosen to make eqv. cct. of CVT purely resistive
(L + LT) = 1/(C1 + C2)
-
Dr. MMY 2005 43
HVAC MeasurementCapacitance Voltage Transformer (CVT)Advantage;- Simple design and easy installation- Frequency independent- Used as voltage measuring device for coupling
condenser- Provides isolation between hv terminal dan lv meterDisadvantage;- Voltage ratio is susceptible to temperature variation- Ferro-resonance
-
Dr. MMY 2005 44
HVAC Measurement
CT/PT
-
Dr. MMY 2005 45
HVAC MeasurementElectrostatic Voltmeter- Made with parallel plateconfiguration using guardring to avoid corona- Force on the plate measured by controlling it by a spring or balancing with counter weight- Small displacement of the electrode is sufficientfor voltage measurement
-
Dr. MMY 2005 46
HVAC MeasurementPeak Reading AC Voltmeter- To obtain the maximum dielectric strength of insulating solids- Rd permit variation of Vm when V2 is reduced- Cs charged to peak value to be measured by C2- CsRd is 1 to 10 s
-
Dr. MMY 2012 47
HVAC Measurement
Sphere Gap
-
48
HVAC Measurement- Uniform field spark gap have a sparkover
voltage within a known tolerance- Can measure peak value of voltage if gap
distance is known- Vs = 30 kV peak at 1 cm spacing in air at
20C and 760 torr- Arrangement : vertically with lower gap
grounded or horizontally
Dr. MMY 2012
-
49
HVAC Measurement
- Rseries connected between source and gap to limit Ib/d and suppress unwanted oscillations in the source voltage when b/d occurs
- Factors affecting sparkover voltage of gap:1. Nearby earthed objects2. Atmospheric conditions & humidity3. Irradiation4. Polarity & rise time of voltage waveforms
Dr. MMY 2012
-
Dr. MMY 2005 50
HVAC Measurement
-
51
HVAC Measurement
Dr. MMY 2012
-
52
HVAC Measurement
High Voltage ProbeHigh Voltage Divider Dr. MMY 2012
-
Impulse Voltage Generation & Measurement
Dr. MMY 2012 53
Impulse voltages are required in high-voltage tests to simulatethe stresses due to external and internal overvoltages,
They are generated by discharging high voltage capacitorsthrough switching gaps onto a network of resistors andcapacitors
-
54
Generation of Impulse VoltageWaveform to be generated - Risetime of 0.5 to 10 s, Decay time 30 to
200 s - Unidirectional & double exponential;
v(t) = V0[exp(-t) exp(-t)] where, & time constant
- The equation represents a wave with rapid rise to peak and slowly falls to zero
- During waveshape recording the initial portion may not clearly defined or missing due to disturbances
Dr. MMY 2012
-
55
Generation of Impulse Voltagetf or t1 = 1.25(t90 t10) 30%tt or t2 = T3 20%Std. Waveshape = 1.2/50 s
Dr. MMY 2012
-
Dr. MMY 201256
Generation of Impulse Voltage Circuit to produce impulse wave Series R-L-C under overdamped or R-C
combination. C is charged to a particular dc voltage and discharged thro waveshaping network. Rd and Re control the front and tail time
-
57
Generation of Impulse Voltage
Circuit Analysis of Impulse GeneratorCircuit (a); Vo(t) = Vc [exp(-t) exp(-t)]
R1C2( - )Circuit (b); Vo(t) = VcC1R2 [exp(-t) exp(-t)]
( - )where;
= 1/(R1C2) and = 1/(R2C1)
Vo(t) - output voltageVc - charging voltage
Dr. MMY 2012
-
58
Generation of Impulse Voltage
Calculation of front time and tail time;
t1 = 3R1 C1C2 = 3R1CeC1 + C2
t2 = 0.7(R1 + R2)(C1 + C2)
Energy rating of generator = C1V02
Dr. MMY 2012
-
59
Generation of Impulse Voltage
Multi-stage Impulse Generator is used to generate higher impulse voltage output
Dr. MMY 2012
-
Multi-stage Impulse Generator
60Dr. MMY 2012
-
Multi-stage Impulse Generator
61Dr. MMY 2012
-
62
Generation of Impulse Voltage
Components of Multistage IG1. DC Charging Set2. Charging Resistor3. Charging Capacitors4. Spark Gaps5. Waveshaping Resistors6. Voltage Dividers
Dr. MMY 2012
-
Dr. MMY 2005 63
Corona Rings
Dividers
Chopping Gap
Impulse Generator
-
Impulse Generator Output
64Dr. MMY 2012
-
Impulse Generator Output
65Dr. MMY 2012
-
66
Generation of Impulse Voltage
Dr. MMY 2012
-
67
Measurement of Impulse Voltage
1. Potential Dividers Either resistive,
capacitive or mixed element type
Low voltage arm is connected to fast recording oscillograph or peak reading intsrument
Z1 & Z2 series resistors or capacitors
Dr. MMY 2012
-
68
Measurement of Impulse Voltage Errors and distortion in output waveshape due
to: 1. Residual inductance in the elements 2. Stray capacitance between element, elements terminal to ground, high voltage lead to element 3. Impedance errors due to connecting leads between dividers and test object and ground return leads 4. Parasitic oscillations due to lead and cable inductances and capacitance
Dr. MMY 2012
-
69
Measurement of Impulse Voltage
2. Sphere Gap
Dr. MMY 2012
-
70
Multiple Impulse Generator (MIGe)
Dr. MMY 2012
-
MIGe Achievements
1. 1. Silver Medal at INATEX 20082. 2. Silver Medal at Malaysia Technology Exposition
(MTE) 20083. 3. Gold Medal at Seoul Int. Invention Fair 20084. 4. Special Award at Seoul Int. Invention Fair 20085. 5. Patent Filing PI 2008 12726. 6. Nine Technical Journal and Conference papers7. 7. One monograph and one book chapter8. 8. One PhD and nine Master tesis9. 9. Nominated for Anugerah Harta Intelek Negara 2009
71Dr. MMY 2012
-
72
EXAMPLE 1An impulse generator has been designed to generate an impulse voltage of 1.2/200 s waveshape. Find the waveshaping resistors R1 and R2 when C1 = 0.125 F and C2 = 1 nF.
Soln.tf = 3R1 [C1C2/(C1 + C2)] 1.2 x 10-6 = 3R1 [(0.125 x 10-6 x 1 x 10-9)/ (0.125 x 10-6 + 1 x 10-9)] R1 = 400
tt = 0.7(R1 + R2)(C1 + C2)200 x 10-6 = 0.7(R1 + R2)(0.125 x 10-6 + 1 x 10-9) R2 = 1868
Dr. MMY 2012
-
73
EXAMPLE 2An impulse generator having charging capacitor of 0.01 F. The wave front and wave tail resistances connected are 800 and 5000 respectively. If the load capacitor is 1000 pF, find the front and tail times of the impulse wave produced. Comment on the answer as compared to the standard waveshape of 1.2/50 s.
Dr. MMY 2012
-
74
Soln.tf = 3R1 [C1C2/(C1 + C2)]
= 3 x 800[0.01 x 10-6 x 0.001 x 10-6][0.01 x 10-6 + 0.001 x 10-6]
tf = 2.19 s
tt = 0.7(R1 + R2)(C1 + C2)= 0.7(800 + 5000)(0.01 x 10-6 + 0.001 x 10-6)
tt = 46.7 s
Front time is outside the range of 1.2 s 30% (0.84 to 1.56 s)
Dr. MMY 2012
-
75
EXAMPLE 3A ten stage impulse generator have C1 = 0.2 F per stage and an external load capacitor C2 = 1 nF. Determine the values of waveshaping resistors at each stage to generate standard lightning impulse of 1.2/50 s waveshape. If the DC charging voltage is 100 kV, determine also the output voltage and generator energy rating.
Dr. MMY 2012
-
76
Soln.n = 10, thus for 10 stage; nV0 = 10 x 100 kV = 1000 kV, C1/n = 0.02 F, C2 = 1 nF, front resistor = 10R1, tail
resistor = 10R2tf = 3R1 [C1C2/(C1 + C2)]
1.2 s = 3 x (10R1) [0.02 x 10-6 x 1 x 10-9][0.02 x 10-6 + 1 x 10-9]
R1 = 42
tt = 0.7(R1 + R2)(C1 + C2)50 s = 0.7 x 10(42 + R2)(0.02 x 10-6 + 1 x 10-9)
R2 = 300 Dr. MMY 2012
-
77
1. INTRODUCTION
Purpose of the testing: To ensure that the electricalequipments are capable of withstanding the overvoltagesthat are met with in service.
Covers basic requirements procedures for testing on severalelectrical apparatus. Normally, high voltage (HV) testing is toinvestigate the insulation performance.
International/national specifications for testing are outlined(details of test, specific equipment, procedure andacceptable limits) to meet the users and manufacturersrequirements
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATUTMUTM
Dr. MMY 2012
-
Dr. MMY 2005 78
2.1 CLASSIFICATION OF HIGH VOLTAGE TESTS
Destructive Test
Normally the equipment underwent destructive test cannot beused in the service.
Test voltage is higher than its normal working voltage.
Breakdown test.
Non-Destructive Test
Mainly done to assess the electrical properties, eg. Resistivity,dielectric constant and loss factor.
The apparatus is not destroyed during the test and can be usedagain
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATUTMUTM
-
Dr. MMY 2005 79
2.2 TYPES OF TESTS
Routine Tests
Made by the manufacturer on every finished piece ofproduct.
To fulfills the specifications
Type Tests
Performed on each type of equipment before their supplyon a general commercial scale demonstrateperformance characteristics.
No need to repeat the test unless changes are made inthe design of the product.
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATUTMUTM
-
80
TYPES OF TESTS (Cont.)
Special Test other than routine or type
Maintenance Tests
Usually carried out after maintenance/repair ofthe equipment.
Conducted according to schedule provided.
Purpose of the test : To ensure the equipmentlifetime is achieved.
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATUTMUTM
Dr. MMY 2012
-
Dr. MMY 2005 81
3. TEST VOLTAGES
Can be divided into three, eg. Direct voltages (DC),power-frequency alternating voltages (AC) andimpulse voltages.
Test with Direct Voltage (DC).Mainly to test equipment used in HVDC transmission systems.Insulation testing, fundamental investigations in discharge physics and dielectric behaviour. Rate of voltage rise above 75% of its estimated final value should be about 2% per second.
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATUTMUTM
-
Dr. MMY 2005 82
TEST VOLTAGES (Cont.)
Test with Alternating Voltage (AC).
Frequency range : 40-60 Hz, sinusoidal shape.
Dry withstand test : Most common routine test for alltypes of electrical equipment especially insulators,bushing, rod gaps etc.
Applied voltage between two to three times of the normalworking voltage.
Wet withstand test : To simulate the effect of natural rainon external insulation. Recommended for tests onapparatus which are designed for outdoor used.Useartificial rain.Applied for 30-60 seconds.
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATUTMUTM
-
Dr. MMY 2005 83
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
Test with Impulse Voltage. Is designed to investigate
the insulation performancedue to the lightning strokeor switching operation.
3 types of impulse voltages,ie;
1) Full wave
2) Chopped wave
3) Switching wave
BS 923: Part 2: 1980
Full lightning impulse
Lightning impulse choppedon the front
-
Dr. MMY 2005 84
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
Lightning impulse choppedon the tail
Full switching impulse
BS 923: Part 2: 1980
-
Dr. MMY 2005 85
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
Rated impulse withstand test
For test on non-self-restoring insulation, 3 impulses areapplied.
For withstand tests on self-restoring insulation, 2 proceduresare use:
1) 15 impulses (rated withstand voltage) with the specifiedshape and polarity are applied
2) Test procedure for determining 50% disruptive dischargevoltage is applied
The method used for determining the levels of appliedvoltage is up-and-down methods.
-
86
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
Atmospheric Correction Factors
By applying correction factors, a measured flashover voltage that influenced by the atmospheric conditions can be determined.
Tpk
kkkVV
d
o
273293
760
by,given ,density air offunction a is where d
kd 0.70 0.75 0.80 0.85 0.90 0.95 1.0 1.05 1.10 1.15
k 0.72 0.77 0.82 0.86 0.91 0.95 1.0 1.05 1.09 1.12
Dr. MMY 2012
-
87
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
4.0 DIAGNOSTIC TESTING OF INSULATION
The purpose of diagnostic testing is to estimate the importance of any deterioration.
Diagnostic testing can use measurements of;
Non-electrical properties
Breakdown strength
Conductivity/Resistivity
Loss tangent
Partial dischargesDr. MMY 2012
-
88
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
Loss Tangent (tan )
Figure 1.1
V
I
I
V
I
VRp Cp
IR IC ICI
IRV
Figure 1.2 : Parallel model
tan = I I
R
C tan =
V / RV C
p
p
tan = 1
C Rp p
Dr. MMY 2012
-
89
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
I
VR
VC
Rs
Cs
V
VR
VC
I
V
Figure 1.3: Series model
R = R
1 + C Rsp
2p2
p2
C = C + 1C Rs p 2 p p2
tan = V V
= I R
I 1C
R
C
s
s
tan = CsRs
Dr. MMY 2012
-
90
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
Measurement of tan (dissipation factor), resistance and capacitance ofthe sample are often made using a.c. bridges.
The common bridge circuits used in power frequency high voltages are:
Schering Bridge
Transformer ratio-arm
AC
A
BD
C
detector
Z1 Z2
Z3 Z4
Figure 2.1
At balanced condition
Z1 Z4 = Z2 Z3
Dr. MMY 2012
-
91
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
The Schering Bridge
AC
C
r
R3
C2
R4 C4
Figure 2.2: Schering Bridge
(r - j / C) R 1
j C
R + 1j C
= Rj C
44
44
3
2
r = R CC
and C = C RR3
4
22
4
3
tan = C4R4
Dr. MMY 2012
-
92
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
The Transformer Ratio-arm Bridge
AC
A
B
C
D
N1
N2
I1
I2
detector
Z1
Z2
Figure 2.3: Transformer Ratio-Arm Bridge
ZZ
= NN
1
2
1
2
Dr. MMY 2012
-
93
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
5.0 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS
Impulse testing on transformer
According to BS 171: Part 3. Carried out at room temperature with the transformer not energized.
Used standard impulse waveshapes. Full and chopped waves. During the tests, impulse voltage and current are recorded.
Failure detection (Insulation failure) A change in the waveshape of the voltage and current both before and
after the chopped waves have been applied. The existing of acoustic noise. Visual signs of flashoverFailure location : Voltage waveform propagation may provide clue to the
position of a breakdown.Dr. MMY 2012
-
94
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
Testing on switchgear or circuit breaker
According to BS 5227: Part 2, IEC 56. Conducted in two conditions:
Circuit breaker closed (ON position) Circuit breaker opened (OFF position)
15 negative and positive standard lightning impulse are applied. Test on one phase, the other two phases and structure of the panel is
connected to earth.
Routine and Type test on cables
According to BS 923: Part 2, IEC 60-2, IEC 55-1, IEC 230 and BS 6480. PD, Power frequency, conductor resistance, direct current and impulse
voltage tests.
Dr. MMY 2012
-
95
TRANSFORMER STANDARD TESTING PROCEDURE
Routine Tests Tests required for each individual transformer such as resistance measurements, voltage ratio and loss measurement.
Dr. MMY 2012
-
96
TRANSFORMER STANDARD TESTING PROCEDUREType- or design tests :
Conducted on a transformer which is representative of other transformers to demonstrate that these transformers comply with specified requirements not covered by routine tests, eg. temperature rise test and lightning impulse test.
-
97
TRANSFORMER STANDARD TRANSFORMER STANDARD TESTING PROCEDURETESTING PROCEDURE
Special- or other tests : Tests other than type- or routine tests agreed to by the manufacturer and the purchaser, eg.measurement of zero-sequence impedance and sound level measurement.
Dr. MMY 2012
-
98
Lightning Impulse Test
LowLow--frequency tests alone are not frequency tests alone are not adequate to demonstrate the dielectric adequate to demonstrate the dielectric strength of transformers. strength of transformers.
The impulse voltage stress imposed on The impulse voltage stress imposed on windings by lightning phenomena can be windings by lightning phenomena can be very different from the low frequency very different from the low frequency voltage distribution. voltage distribution.
The lightning impulse test is performed The lightning impulse test is performed to prove the transformers ability to to prove the transformers ability to withstand transient voltages withstand transient voltages
Dr. MMY 2012
-
99
Lightning Impulse TestThe basic waveshapes have been defined The basic waveshapes have been defined
and the impulse voltage levels, referred to and the impulse voltage levels, referred to as the basic lightning impulse insulation as the basic lightning impulse insulation level (BIL), have been established for level (BIL), have been established for respective standardized voltage classes. respective standardized voltage classes.
By defining amplitudes and waveshapes, By defining amplitudes and waveshapes, however, a minimum impulse dielectric however, a minimum impulse dielectric strength is established which the strength is established which the transformer should meet.transformer should meet.
Dr. MMY 2012
-
Dr. MMY 2005 100
Lightning Impulse Test-Test Waveshape
-
101
Lightning Impulse Test- Test Connection
The voltage is applied to each The voltage is applied to each line terminal in succession. line terminal in succession.
All other terminals shall All other terminals shall nominally be earthed directly or nominally be earthed directly or through lowthrough low--ohmic current ohmic current shunts. shunts.
Dr. MMY 2012
-
102
Lightning Impulse Test- Test Connection
Dr. MMY 2012
-
103
Lightning Impulse Test- Test Sequence
The test sequence consists of one reference impulse(RW) at 60% of full amplitude (FW):1RW 50 -70% amplitude 1 FW 100 amplitude1RCW 50-70% amplitude2 CW 100% amplitude2 FW 100% amplitude
Dr. MMY 2012
-
104
Lightning Impulse Test- Failure Indications
Detection of faults at impulse testing is based on comparison of voltage and current records obtained at reduced and full amplitudes
The two traces should have a perfect match to constitute evidence that the insulation has passed the test
Dr. MMY 2012
-
Dr. MMY 2005 105
HIGH VOLTAGE TESTING TECHNIQUESHIGH VOLTAGE TESTING TECHNIQUES
IVATIVATIVATUTMUTM
-
Dr. MMY 2005 106
TESTING ACTIVITIES AT IVATTESTING ACTIVITIES AT IVAT
High voltage AC withstand test on 11 kV XLPE single core cable
(TOPLINK SDN BHD)
High voltage lightning impulse test on cast resin transformer
(LKH POWER TRANSFORMER SDN BHD)
High voltage lightning impulse test on 11 kV switchgear(MAHKOTA MANUFACTURING SDN BHD)
-
Dr. MMY 2005 107
TESTING ACTIVITIES AT IVATTESTING ACTIVITIES AT IVAT
Impulse Withstand Test on 630 kVA, 11/0.433 kV (top) and
20 MVA, 33/11.5 kV (bottom) Three Phase Power Transformer
(MALAYSIAN TRANSFORMER MANUFACTURING SDN BHD)
Cable jointing works for preparation of high voltage withstand test
(TOPLINK SDN BHD)