hinljr00bua-ed00002a dc cable sizing calculation
TRANSCRIPT
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
1/18
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
2/18
POWER SYSTEMS abcd
TABLE DES MODIFICATIONS / MODIFICATIONS TABLE
REVETABLI
ESTABLISHED
VERIFIE
CHECKED
APPROUVE
APPROVED DATE MODIFICATIONS STAT.
A MURUGIAH DHS VIKAS 19.7.10 FIRST ISSUE. GFE
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
3/18
POWER SYSTEMS abcd
CONTENTS
1 PURPOSE 4
2 REFERENCE DOCUMENT 4
2.1 REFERENCE STANDARDS 4
3 BASIC DATA 5
3.1 ENVIRONMENTAL CONDITIONS AND DESIGN CRITERIA 53.2 ELECTRICAL NETWORK DATA 5
4 TECHNICAL SPECIFICATION: 5
4.1 TYPE OF CABLE 5
4.2 INSTALLATION METHOD 6
5 CABLE SIZING METHOD 6
5.1 CURRENT CARRYING CAPACITY CRITERIA 6
5.2 SHORT CIRCUIT CRITERIA 8
5.3 VOLTAGE DROP CRITERIA 9
6 CIRCUIT BREAKER SELECTION 9
7 CALCULATION SHEET 9
8 ANNEXURE-I : CURRENT RATING, RESISTANCE & REACTANCE 10
9 ANNEUXRE-II : TEMPERATURE CORRECTION FACTOR 11
10 ANNEUXRE-III : GROUP RATING FACTORS 12
ATTACHMENT 1: CALCULATION SHEETS (220V DC SYSTEM)
ATTACHMENT 2: CALCULATION SHEETS (48V DC SYSTEM)
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
4/18
POWER SYSTEMS abcd
1 PURPOSE
The purpose of the document is to define the basis of calculation of 220V & 48V DC Power Cable
Sizes for all the DC Distribution boards.
2 REFERENCE DOCUMENT
1 HINLJR20BUA-FD00001: 220 V DC System Single Line Diagram
2 HINLJR20BUA-FE00001: 220 V DC System Design memorandum
3 HINLJR20BUA-ED00001: 220 V DC System Power Balance
4 HINLJR20BUD-FD00001: 48 V DC System Single Line Diagram
5 HINLJR20BUD-FE00001: 48 V DC System Design memorandum
6 HINLJR20BUD-ED00001: 48 V DC System Power Balance
2.1 REFERENCE STANDARDS
1 IEC 60364-4-43 Electrical Instalations of Building – Protection Against Over Current
2 IEC 60364-5-52Electrical Instalations of Building – Selection and Erection of
Electrical Equipment Wiring System
3 IEC 60364-5-54
Selection and Erection of Electrical Equipment Earthing
Arrangements, Protective Conductors and Protective Bonding
Conductors
4 IEEE Std 241Recommended Practice For Electrical Power System In Commercial
Building
5 IS 1554 - Part 1PVC insulated (heavy duty) electric cables specification: For working
voltages upto and including 1 100 V
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
5/18
POWER SYSTEMS abcd
3 BASIC DATA
3.1 ENVIRONMENTAL CONDITIONS AND DESIGN CRITERIA
In particular, the electrical and control equipment will be designed for the following ambient
conditions:
1 Pollution level Level III as per IS
2 Altitude
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
6/18
POWER SYSTEMS abcd
4.2 INSTALLATION METHOD
Cable ..........................................................................Perforated Tray / Ladder Type
Single core cables ...............................................................Single layer laying with trefoil formation
[Refer Doc. HINLJR000BB FE00001]
Multi core cables.................................................................Multi layer laying (without exceeding the90% height of cable tray) and Cable
surfaces are touching [Refer Doc.
HINLJR000BB FE00001]
Buried cables ......................................................................Multi layer laying and Cable surfaces are
touching
5 CABLE SIZING METHOD
Cable sizing and selection is based on the following criteria:-
• Current carrying capacity under normal operating condition
• Current carrying capacity under short-circuit condition and
• Voltage drop
5.1 CURRENT CARRYING CAPACITY CRITERIA
The current carrying capacity of a cable de-rates due to
a) ambient temperature
b) accumulation of cable/installation of cable)
Such adaptation is done considering de-rating factors for ambient temperature and cable installation
d ib d h d
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
7/18
POWER SYSTEMS abcd
Where, K θ = correction factor for ambient temperature (Annexure-III)
K 2 = Sun exposition factor which is
= 1 For cable screened from sun rays
= 0.8 For cable exposed to air with black sheath
= 0.9 For cable exposed to air with light colour sheath
K g = Cable installation de-rating factor (Annexure-IV)
The maximum permanent current (In) of a feeder is given as
In = SnU
Where Sn = Nominal apparent power of the feeder
U = System voltage (220V for 220V DC System)
Size of the cable selected shall ensure Id ≤ Iz
Where Iz is the rated current carrying capacity of the cable (Refer Annexure-I).
5.1.1 AMBIENT TEMPERATURE CORRECTION FACTOR
Temperature correction factor for an ambient temperature equal to 50
0
C, will be
K t = 0.9 (Annexure-III)
5.1.2 SUN EXPOSITION FACTOR
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
8/18
POWER SYSTEMS abcd
5.1.3 GROUPING FACTOR
Multi core cables
As per the installation method adopted for multi core cables as per IEC 60364-5-52 (Annexure-IV),
the installation group rating factor shall be suitably selected.
Perforated trays, Laying configuration of 6 cables and 3 trays, K g = 0.71
5.2 SHORT CIRCUIT CRITERIA
The minimum cable cross-sectional area S is selected such that the maximum thermal stress in the
cable during short circuit does not reach the maximum permissible limit. The selection criteria is
given as (IEC 60364-4-43)
K 2 S2 ≥ I ² t
Where
i² t :- Energy let-through of the associated circuit breaker (As per
breaker manufacturer data)
K : - Cable constant which is given as
= ))()(1(ln)20(
20 i
i f cQθ β θ θ
θ β
+
−+×+× (IS 3043)
Where
Qc = Volumetric heat capacity of the conductor material in J/oC mm3
(See Annexure IV)
20θ = Electrical resistivity of conducting material at 20oC in Ω. mm. (See Annexure IV)
β = Reciprocal of temperature coefficient of resistivity of the conducting material at
0oC
iθ = Initial temperature of conductor inoC
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
9/18
POWER SYSTEMS abcd
5.3 VOLTAGE DROP CRITERIA
The minimum cable cross-sectional area, S (in mm2) is calculated in such a way that the voltage drop
from the station service board / unit auxiliary board up to the consumer is less than or equal to 4%.
(IEC 60364-5-52)
Voltage drop
Δ V = (2 x In x R x L) / 1000
Where R = Resistance of the cable in Ω / Km, (Annexure-II)
In = Current in the feeder current A,
L = Length of cable in meter.
6 CIRCUIT BREAKER SELECTION
Circuit breakers rating is selected as per the connected load (i.e. maximum current in the feeder, I n)
so as to confirm that the rated current of the circuit breaker is greater than the maximum permanent
load in the feeder.
1. Thermal setting (Ith) of the circuit breaker/ current rating of CB is greater than or equal toconnected load, In.
2. Icu with or without association with upstream breaker ≥ Icu Upstream Board.
7 CALCULATION SHEET
Please refer to Attachment 1.
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
10/18
POWER SYSTEMS abcd
8 ANNEXURE-I : CURRENT RATING, RESISTANCE & REACTANCE
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
11/18
POWER SYSTEMS abcd
9 ANNEUXRE-II : TEMPERATURE CORRECTION FACTOR
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
12/18
POWER SYSTEMS abcd
10 ANNEUXRE-III : GROUP RATING FACTORS
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
13/18
POWER SYSTEMS abcd
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
14/18
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
15/18
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
16/18
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
17/18
-
8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation
18/18
ATTACHMENT 2 : CALCULATION SHEET (48V DC POWER CABLES)
FROM EQUIPMENT TO EQUIPMENTLOAD CURRENT
IN Amp
CABLE
TYPE
No. OF
RUNS
SELECTED
CABLE SIZE
RATED
CAPACITY OF
CABLE
CABLE
RESISTANCE
( Ω/Km)
LENGTH
(m)Kt Ks Kg
REQUIRED
CAPACITY OF
FEEDER (A)
PROTECTIVE
DEVICE RATING
(A)
DESIGNATION DESIGNATION (In) mm2 (Iz) R L (In / Kd) (Ir)
BATTERY BANK 1
48 V BATTERY BANK 48 V DCDB 48 - 15 XLPE-AL 1 2Cx35 1.11 0.0783 20 0.9 1 0.71 0.639 23.47 80 10.82 0.51 0.92 0.68
48 V BATTERY BANK 48 V DCDB 48 - 15 XLPE-AL 1 2Cx35 1.11 0.0783 20 0.9 1 0.71 0.639 23.47 80 10.82 0.51 0.92 0.68
48 V BATTERY BANK 48 V DCDB 48 - 15 XLPE-AL 1 2Cx35 1.11 0.0783 20 0.9 1 0.71 0.639 23.47 80 10.82 0.51 0.92 0.68
48V DCDB
48 V DCDB PLCC-1 48 - 2.7 XLPE-AL 1 2Cx2.5 9.5 0.0985 16 0.9 1 0.71 0.639 4.23 16 10.82 0.099 1 0.84
48 V DCDB PLCC-2 48 - 2.7 XLPE-AL 1 2Cx2.5 9.5 0.0985 16 0.9 1 0.71 0.639 4.23 16 10.82 0.099 1 0.84
48 V DCDB PLCC-3 48 - 2.7 XLPE-AL 1 2Cx2.5 9.5 0.0985 16 0.9 1 0.71 0.639 4.23 16 10.82 0.099 1 0.84
48 V DCDB PLCC4-Future 48 -
Kd = (Kt x
Ks x Kg)
Voltage
[V]
Consumption/O
utput Power
[W]
PERMISSIBLE
VOLTAGE
DROP (Vr)
RUNNING
VOLTAGE
DROP (Vpr)
K2S2
(kA2s)
LET-
THROUGH
(kA2s)
sheet 1 of 1