hinljr00bua-ed00002a dc cable sizing calculation

Upload: badri-venkatesh

Post on 07-Jul-2018

263 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    1/18

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    2/18

    POWER SYSTEMS abcd 

    TABLE DES MODIFICATIONS / MODIFICATIONS TABLE  

    REVETABLI

    ESTABLISHED  

    VERIFIE

    CHECKED  

    APPROUVE

    APPROVED  DATE MODIFICATIONS STAT.

    A MURUGIAH DHS VIKAS 19.7.10 FIRST ISSUE. GFE

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    3/18

    POWER SYSTEMS abcd 

    CONTENTS

    1  PURPOSE 4 

    2  REFERENCE DOCUMENT 4 

    2.1 REFERENCE STANDARDS 4

    3  BASIC DATA 5 

    3.1 ENVIRONMENTAL CONDITIONS AND DESIGN CRITERIA 53.2 ELECTRICAL NETWORK DATA 5

    4  TECHNICAL SPECIFICATION: 5 

    4.1 TYPE OF CABLE 5

    4.2 INSTALLATION METHOD 6

    5  CABLE SIZING METHOD 6 

    5.1 CURRENT CARRYING CAPACITY CRITERIA 6

    5.2 SHORT CIRCUIT CRITERIA 8

    5.3 VOLTAGE DROP CRITERIA 9

    6  CIRCUIT BREAKER SELECTION 9 

    7  CALCULATION SHEET 9 

    8   ANNEXURE-I : CURRENT RATING, RESISTANCE & REACTANCE 10 

    9   ANNEUXRE-II : TEMPERATURE CORRECTION FACTOR 11 

    10   ANNEUXRE-III : GROUP RATING FACTORS 12 

     ATTACHMENT 1: CALCULATION SHEETS (220V DC SYSTEM) 

     ATTACHMENT 2: CALCULATION SHEETS (48V DC SYSTEM) 

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    4/18

    POWER SYSTEMS abcd 

    1 PURPOSE

    The purpose of the document is to define the basis of calculation of 220V & 48V DC Power Cable

    Sizes for all the DC Distribution boards. 

    2 REFERENCE DOCUMENT

    1 HINLJR20BUA-FD00001: 220 V DC System Single Line Diagram

    2 HINLJR20BUA-FE00001: 220 V DC System Design memorandum

    3 HINLJR20BUA-ED00001: 220 V DC System Power Balance

    4 HINLJR20BUD-FD00001: 48 V DC System Single Line Diagram

    5 HINLJR20BUD-FE00001: 48 V DC System Design memorandum

    6 HINLJR20BUD-ED00001: 48 V DC System Power Balance

    2.1 REFERENCE STANDARDS

    1 IEC 60364-4-43 Electrical Instalations of Building – Protection Against Over Current

    2 IEC 60364-5-52Electrical Instalations of Building – Selection and Erection of

    Electrical Equipment Wiring System

    3 IEC 60364-5-54

    Selection and Erection of Electrical Equipment Earthing

    Arrangements, Protective Conductors and Protective Bonding

    Conductors

    4 IEEE Std 241Recommended Practice For Electrical Power System In Commercial

    Building

    5 IS 1554 - Part 1PVC insulated (heavy duty) electric cables specification: For working

    voltages upto and including 1 100 V

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    5/18

    POWER SYSTEMS abcd 

    3 BASIC DATA

    3.1 ENVIRONMENTAL CONDITIONS AND DESIGN CRITERIA

    In particular, the electrical and control equipment will be designed for the following ambient

    conditions:

    1 Pollution level Level III as per IS

    2 Altitude

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    6/18

    POWER SYSTEMS abcd 

    4.2 INSTALLATION METHOD

    Cable ..........................................................................Perforated Tray / Ladder Type

    Single core cables ...............................................................Single layer laying with trefoil formation

    [Refer Doc. HINLJR000BB FE00001]

    Multi core cables.................................................................Multi layer laying (without exceeding the90% height of cable tray) and Cable

    surfaces are touching [Refer Doc.

    HINLJR000BB FE00001]

    Buried cables ......................................................................Multi layer laying and Cable surfaces are

    touching

    5 CABLE SIZING METHOD

    Cable sizing and selection is based on the following criteria:-

    • Current carrying capacity under normal operating condition

    • Current carrying capacity under short-circuit condition and

    • Voltage drop

    5.1 CURRENT CARRYING CAPACITY CRITERIA

    The current carrying capacity of a cable de-rates due to

    a) ambient temperature

    b) accumulation of cable/installation of cable)

    Such adaptation is done considering de-rating factors for ambient temperature and cable installation

    d ib d h d

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    7/18

    POWER SYSTEMS abcd 

    Where, K θ = correction factor for ambient temperature (Annexure-III)

    K 2  = Sun exposition factor which is

    = 1 For cable screened from sun rays

    = 0.8 For cable exposed to air with black sheath

    = 0.9 For cable exposed to air with light colour sheath

    K g  = Cable installation de-rating factor (Annexure-IV)

    The maximum permanent current (In) of a feeder is given as

    In  = SnU

    Where Sn  = Nominal apparent power of the feeder

    U = System voltage (220V for 220V DC System)

    Size of the cable selected shall ensure Id ≤  Iz

    Where Iz is the rated current carrying capacity of the cable (Refer Annexure-I).

    5.1.1 AMBIENT TEMPERATURE CORRECTION FACTOR

    Temperature correction factor for an ambient temperature equal to 50

    0

     C, will be

    K t  = 0.9 (Annexure-III)

    5.1.2 SUN EXPOSITION FACTOR

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    8/18

    POWER SYSTEMS abcd 

    5.1.3 GROUPING FACTOR

    Multi core cables

    As per the installation method adopted for multi core cables as per IEC 60364-5-52 (Annexure-IV),

    the installation group rating factor shall be suitably selected.

    Perforated trays, Laying configuration of 6 cables and 3 trays, K g = 0.71

    5.2 SHORT CIRCUIT CRITERIA

    The minimum cable cross-sectional area S is selected such that the maximum thermal stress in the

    cable during short circuit does not reach the maximum permissible limit. The selection criteria is

    given as (IEC 60364-4-43)

    K 2 S2  ≥  I ² t

    Where

    i² t  :- Energy let-through of the associated circuit breaker (As per

    breaker manufacturer data)

    K : - Cable constant which is given as

    = ))()(1(ln)20(

    20   i

    i f cQθ  β θ θ 

    θ  β 

    +

    −+×+×   (IS 3043)

    Where

    Qc = Volumetric heat capacity of the conductor material in J/oC mm3

    (See Annexure IV)

    20θ    = Electrical resistivity of conducting material at 20oC in Ω. mm. (See Annexure IV)

     β    = Reciprocal of temperature coefficient of resistivity of the conducting material at

    0oC

    iθ    = Initial temperature of conductor inoC

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    9/18

    POWER SYSTEMS abcd 

    5.3 VOLTAGE DROP CRITERIA

    The minimum cable cross-sectional area, S (in mm2) is calculated in such a way that the voltage drop

    from the station service board / unit auxiliary board up to the consumer is less than or equal to 4%.

    (IEC 60364-5-52)

    Voltage drop

     Δ V = (2 x In x R x L) / 1000

    Where R = Resistance of the cable in Ω / Km, (Annexure-II)

    In  = Current in the feeder current A,

    L = Length of cable in meter.

    6 CIRCUIT BREAKER SELECTION

    Circuit breakers rating is selected as per the connected load (i.e. maximum current in the feeder, I n)

    so as to confirm that the rated current of the circuit breaker is greater than the maximum permanent

    load in the feeder.

    1. Thermal setting (Ith) of the circuit breaker/ current rating of CB is greater than or equal toconnected load, In.

    2. Icu with or without association with upstream breaker ≥  Icu Upstream Board.

    7 CALCULATION SHEET

    Please refer to Attachment 1.

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    10/18

    POWER SYSTEMS abcd 

    8 ANNEXURE-I : CURRENT RATING, RESISTANCE & REACTANCE

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    11/18

    POWER SYSTEMS abcd 

    9 ANNEUXRE-II : TEMPERATURE CORRECTION FACTOR

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    12/18

    POWER SYSTEMS abcd 

    10 ANNEUXRE-III : GROUP RATING FACTORS

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    13/18

    POWER SYSTEMS abcd 

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    14/18

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    15/18

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    16/18

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    17/18

  • 8/19/2019 HINLJR00BUA-ED00002a Dc Cable Sizing Calculation

    18/18

     ATTACHMENT 2 : CALCULATION SHEET (48V DC POWER CABLES)

    FROM EQUIPMENT TO EQUIPMENTLOAD CURRENT

    IN Amp

    CABLE

    TYPE

    No. OF

    RUNS

    SELECTED

    CABLE SIZE

    RATED

    CAPACITY OF

    CABLE

    CABLE

    RESISTANCE

    ( Ω/Km)

    LENGTH

    (m)Kt Ks Kg

    REQUIRED

    CAPACITY OF

    FEEDER (A)

    PROTECTIVE

    DEVICE RATING

    (A)

    DESIGNATION DESIGNATION (In) mm2 (Iz) R L (In / Kd) (Ir)

    BATTERY BANK 1

    48 V BATTERY BANK 48 V DCDB 48 - 15 XLPE-AL 1 2Cx35 1.11 0.0783 20 0.9 1 0.71 0.639 23.47 80 10.82 0.51 0.92 0.68

    48 V BATTERY BANK 48 V DCDB 48 - 15 XLPE-AL 1 2Cx35 1.11 0.0783 20 0.9 1 0.71 0.639 23.47 80 10.82 0.51 0.92 0.68

    48 V BATTERY BANK 48 V DCDB 48 - 15 XLPE-AL 1 2Cx35 1.11 0.0783 20 0.9 1 0.71 0.639 23.47 80 10.82 0.51 0.92 0.68

    48V DCDB

    48 V DCDB PLCC-1 48 - 2.7 XLPE-AL 1 2Cx2.5 9.5 0.0985 16 0.9 1 0.71 0.639 4.23 16 10.82 0.099 1 0.84

    48 V DCDB PLCC-2 48 - 2.7 XLPE-AL 1 2Cx2.5 9.5 0.0985 16 0.9 1 0.71 0.639 4.23 16 10.82 0.099 1 0.84

    48 V DCDB PLCC-3 48 - 2.7 XLPE-AL 1 2Cx2.5 9.5 0.0985 16 0.9 1 0.71 0.639 4.23 16 10.82 0.099 1 0.84

    48 V DCDB PLCC4-Future 48 -

    Kd = (Kt x

    Ks x Kg)

    Voltage

    [V]

    Consumption/O

    utput Power

    [W]

    PERMISSIBLE

    VOLTAGE

    DROP (Vr)

    RUNNING

    VOLTAGE

    DROP (Vpr)

    K2S2

    (kA2s)

    LET-

    THROUGH

    (kA2s)

    sheet 1 of 1