higher ground source heat pump cop in a residential

14
Higher ground source heat pump COP in a residential building through the use of solar thermal collectors Aymeric Girard a, * , Eulalia Jadraque Gago b , Tariq Muneer c , Gustavo Caceres d a Faculty of Engineering and Sciences, Adolfo Ib a~ nez University, Av. Padre Hurtado 750, Altos del Sporting, Vi~ na del Mar, Chile b School of Civil Engineering, University of Granada, Av. Severo Ochoa s/n,18071, Granada, Spain c School of Engineering and Built Environment, Edinburgh Napier University,10 Colinton Road, Edinburgh EH10 5DT, Scotland, UK d Faculty of Engineering and Sciences, Adolfo Ib a~ nez University, Diagonal Las Torres 2640, Pe~ nalol en, Santiago, Chile article info Article history: Received 4 October 2014 Accepted 27 January 2015 Available online 14 February 2015 Keywords: Ground-source heat pump Solar-assisted ground-source heat pump Building space heating Energy efciency Model simulation abstract This article investigates the feasibility of achieving higher performance from ground-source heat-pumps (GSHP) in space heating mode through the use of solar thermal collectors. A novel simulation tool for solar-assisted ground-source heat-pumps (SGSHP) is presented with an analysis of the inuence of solar collectors on the improvement of heat pump performance. Solar radiation and climate temperature data of 19 European cities were used to perform simulations of SGSHP and GSHP systems considering a typical residential house. Overall performance coefcients (COP sys ) varied from northern to southern locations between 4.4 and 5.8 for SGSHP and between 4.3 and 5.1 for GSHP. Results show that solar collectors coupling has more impact on performance improvement in regions that benet from higher irradiance. However, greater running cost savings are achieved in milder climate conditions. Both heat-pump systems are able to effectively contribute to carbon footprint reductions for residential buildings, especially in countries where fossil fuels are the primary source of electricity generation. SGSHP payback periods are found between 8.5 and 23 years from northern to southern localities, making such heating system an economic heating option. SGSHPs are best suited for high irradiance and cool climate locations such as the mountainous regions in southern Europe. © 2015 Elsevier Ltd. All rights reserved. 1. Introduction Energy from fossil fuels (oil, gas, and coal) has been identied as the major cause of the increase of greenhouse gas concentrations in the atmosphere; a leading contributor to climate change. Energy efciency is seen as the cheapest, fastest and cleanest energy resource, which can be used in response to the growing concerns about climate change. Space heating for buildings in residential, commercial and public sectors has a major impact on worldwide energy consumption. Globally, buildings are responsible for approximately 40% of total world annual energy consumption [1e5], with space heating accounting for a majority of this energy, requiring between 61 and 70% of home energy use [6]. Fossil fuels and electricity account for 37.6% (gas 22.3%; oil 12.9%; coal 2.4%) and 27%, respectively of energy consumption in buildings [7], with a high fossil fuel share for electricity generation (World gures in 2010: coal 41%, gas 22%, oil 5% and nuclear 13% [8]). Thus, there are great opportunities for energy efcient equipment to reduce fossil fuel consumption and space heating demand in buildings. Heat pumps are one option among available energy efcient equipment [2,9,10] and their combination with solar thermal en- ergy is promising. Solar thermal assisted heat pump systems (SAHPS) are usually powered by electricity and indirectly by fossil fuel. Such hybrid systems allow a reduction in the consumption of nonrenewable fuel. SAHPS can help improve the economic and environmental sustainability of renewable energy systems, and they also contribute to fullling the energy demand [11]. In the past 30 years, several studies concerning SAHPS have been performed [12e21] [22e31], some of which show promising results for the design or sizing of real solar-driven heat pump systems [32e39]. In recent years, several companies started offering SAHPS on the European Market; and in 2009 an overview was given by Zorner W. et al. [40]. Also, several reviews on existing SAHPS installations were presented in the Task 44 solar and heat pump systemsby * Corresponding author. E-mail addresses: [email protected] (A. Girard), [email protected] (E.J. Gago), [email protected] (T. Muneer), [email protected] (G. Caceres). Contents lists available at ScienceDirect Renewable Energy journal homepage: www.elsevier.com/locate/renene http://dx.doi.org/10.1016/j.renene.2015.01.063 0960-1481/© 2015 Elsevier Ltd. All rights reserved. Renewable Energy 80 (2015) 26e39

Upload: others

Post on 11-May-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Higher ground source heat pump COP in a residential

lable at ScienceDirect

Renewable Energy 80 (2015) 26e39

Contents lists avai

Renewable Energy

journal homepage: www.elsevier .com/locate/renene

Higher ground source heat pump COP in a residential buildingthrough the use of solar thermal collectors

Aymeric Girard a, *, Eulalia Jadraque Gago b, Tariq Muneer c, Gustavo Caceres d

a Faculty of Engineering and Sciences, Adolfo Ib�a~nez University, Av. Padre Hurtado 750, Altos del Sporting, Vi~na del Mar, Chileb School of Civil Engineering, University of Granada, Av. Severo Ochoa s/n, 18071, Granada, Spainc School of Engineering and Built Environment, Edinburgh Napier University, 10 Colinton Road, Edinburgh EH10 5DT, Scotland, UKd Faculty of Engineering and Sciences, Adolfo Ib�a~nez University, Diagonal Las Torres 2640, Pe~nalol�en, Santiago, Chile

a r t i c l e i n f o

Article history:Received 4 October 2014Accepted 27 January 2015Available online 14 February 2015

Keywords:Ground-source heat pumpSolar-assisted ground-source heat pumpBuilding space heatingEnergy efficiencyModel simulation

* Corresponding author.E-mail addresses: [email protected] (A

(E.J. Gago), [email protected] (T. Muneer), gustav

http://dx.doi.org/10.1016/j.renene.2015.01.0630960-1481/© 2015 Elsevier Ltd. All rights reserved.

a b s t r a c t

This article investigates the feasibility of achieving higher performance from ground-source heat-pumps(GSHP) in space heating mode through the use of solar thermal collectors. A novel simulation tool forsolar-assisted ground-source heat-pumps (SGSHP) is presented with an analysis of the influence of solarcollectors on the improvement of heat pump performance. Solar radiation and climate temperature dataof 19 European cities were used to perform simulations of SGSHP and GSHP systems considering a typicalresidential house. Overall performance coefficients (COPsys) varied from northern to southern locationsbetween 4.4 and 5.8 for SGSHP and between 4.3 and 5.1 for GSHP. Results show that solar collectorscoupling has more impact on performance improvement in regions that benefit from higher irradiance.However, greater running cost savings are achieved in milder climate conditions. Both heat-pumpsystems are able to effectively contribute to carbon footprint reductions for residential buildings,especially in countries where fossil fuels are the primary source of electricity generation. SGSHP paybackperiods are found between 8.5 and 23 years from northern to southern localities, making such heatingsystem an economic heating option. SGSHPs are best suited for high irradiance and cool climate locationssuch as the mountainous regions in southern Europe.

© 2015 Elsevier Ltd. All rights reserved.

1. Introduction

Energy from fossil fuels (oil, gas, and coal) has been identified asthe major cause of the increase of greenhouse gas concentrations inthe atmosphere; a leading contributor to climate change. Energyefficiency is seen as the cheapest, fastest and cleanest energyresource, which can be used in response to the growing concernsabout climate change.

Space heating for buildings in residential, commercial andpublic sectors has a major impact on worldwide energyconsumption. Globally, buildings are responsible for approximately40% of total world annual energy consumption [1e5], with spaceheating accounting for a majority of this energy, requiring between61 and 70% of home energy use [6]. Fossil fuels and electricityaccount for 37.6% (gas 22.3%; oil 12.9%; coal 2.4%) and 27%,

. Girard), [email protected]@uai.cl (G. Caceres).

respectively of energy consumption in buildings [7], with a highfossil fuel share for electricity generation (World figures in 2010:coal 41%, gas 22%, oil 5% and nuclear 13% [8]). Thus, there are greatopportunities for energy efficient equipment to reduce fossil fuelconsumption and space heating demand in buildings.

Heat pumps are one option among available energy efficientequipment [2,9,10] and their combination with solar thermal en-ergy is promising. Solar thermal assisted heat pump systems(SAHPS) are usually powered by electricity and indirectly by fossilfuel. Such hybrid systems allow a reduction in the consumption ofnonrenewable fuel. SAHPS can help improve the economic andenvironmental sustainability of renewable energy systems, andthey also contribute to fulfilling the energy demand [11]. In the past30 years, several studies concerning SAHPS have been performed[12e21] [22e31], some of which show promising results for thedesign or sizing of real solar-driven heat pump systems [32e39].In recent years, several companies started offering SAHPS onthe EuropeanMarket; and in 2009 an overviewwas given by Z€ornerW. et al. [40]. Also, several reviews on existing SAHPS installationswere presented in the Task 44 “solar and heat pump systems” by

Page 2: Higher ground source heat pump COP in a residential

Nomenclature

a1 solar collector heat loss coefficient (W/m2.�C)A surface area (m2)Cp specific heat (kJ/kg.�C)COP coefficient of performancehc convective heat transfer coefficient (W/m2.�C)HDD heating degree day (�C day)k thermal conductivity (W/m.�C)L length (m)_m mass flow rate (kg/s)Ncount number of iterationn ventilation rate (air change/h)Pr Prandtl numberQ heat energy (kW)r radius (m)R thermal resistance (m2.�C/W)SG slope global radiation (W/m2)T temperature (�C)U overall heat transfer coefficient (W/m2.�C)V volume (m3)v velocity (m/s)W work energy (kW)x interest rate (%)

y service life (years)

Greek symbolsa ground reflectance (albedo) coefficientDP pressure loss (kPa)h efficiency (%)m dynamic viscosity (Pa.s)r density (kg/m3)

Subscriptsai internal ambientao outside ambientc or cond condensercol collectorconv convectioncomp compressore or evap evaporatorG ground collectori inleto outletp pipes soilS solar collectorw water or antifreeze solution

Fig. 1. Global geothermal installed capacity 1995e2010 (direct use). Source: Ref. [50].

A. Girard et al. / Renewable Energy 80 (2015) 26e39 27

the International Energy Agency Solar Heating and Cooling (IEASHC) program [41,42] show the potential of this combination oftechnologies.

The energy performance improvement in ground-source heatpumps (GSHP) has been identified as a way to promote a widerintroduction of GSHP for residential use in the space heating mar-ket. Yet, studies by Esen et al. [43], Pulat et al. [44] both in Turkeyand by Healy and Ugursal [45] in Canada have demonstrated thatthe horizontal-loop GSHP system offers economic advantages overconventional heating methods such as liquid petrol gas heating,coal fired heating and diesel oil heating. However it is clear thatthere is a lack of in-situ measured data that is available on COP ofsolar-assisted ground-source heat-pumps (SGSHP) and their per-formance. This research investigated the performance of a SGSHPsystem at different latitudes in space heating mode of operation forresidential use, and to evaluate the influence of roof-top thermalsolar collectors in achieving higher heat-pump COP compared toGSHPs alone.

2. Overview of GSHP

A GSHP system extracts heat from the ground through a groundheat exchanger (GHE). A buried coil with circulating fluid in a closedloop is used to transfer thermal energy from the ground. The closedloop can be deposited in vertical boreholes or horizontal trenches.Boreholes are drilled approximately 45 me150 m deep and4.5me6m apart to allowminimum interference between the pipes[46]. The GHE of the horizontal mode consists of using a series ofparallel pipe arrangements laid in trenches. Due to temperatureinterference issues, pipes are buried in trenches spaced a minimumof 1.5m apart and from 1.2m to 1.8m deep. Pipe diameter generallyranges from 20 mm to 40 mm and their length is about 35 me50 mper kilowatt (kW) of heating and cooling capacity [46]. Trench andborehole length greatly depends on soil conditions includingtemperature, moisture content, particle size and shape [47].

The principle of GSHP relies on the near stability of the tem-perature of ground source. At depths of less than 2 m, the ground

temperature showsmarked seasonal variation above and below theannual average ambient air temperature. As the depth increases,the seasonal swing in temperature is reduced and the maximumandminimum soil temperatures begin to lag the temperature at thesurface. At a depth of about 1.5 m, the time lag is approximately onemonth. Below 10 m, ground temperature remains effectively con-stant at approximately the annual average air temperature [48].

Electric plug-in heaters, air-source heat pumps, oil and woodstoves, and gas-boilers largely dominate themarket of space heatingsystems. GSHP have been used for space heating for over 50 years[49], but GSHP market penetration is still in its infancy. However,direct use of geothermal energy (i.e. excluding centralizedgeothermal plants for electricity generation) presents a constantgrowth of installed capacity at a global level [50], as shown in Fig. 1.

3. Study objectives

This study aims to explore the potential increase in COP of a heatpump by using roof-top thermal solar collectors. The objective ofthe research was to develop a novel simulation tool allowing the

Page 3: Higher ground source heat pump COP in a residential

A. Girard et al. / Renewable Energy 80 (2015) 26e3928

assessment of SGSHP performance for the space heating scenario ofa residential building. Furthermore, the performance of three sys-tems, i.e. electrical radiant heaters, electrically-operated GSHPs andSGSHPs are compared with respect to energy use, emissions andfinancial costs.

The schematic diagram of the SGSHP process is presented inFig. 2. The mathematical model used in the simulation tool isdeveloped considering the following working requirements of theSGSHP system. The heat harvested in the solar collectors is usedwith priority to provide the heat-pump evaporator with themaximum operating temperature. The fluid in the ground/solarcircuit is considered as a 35% propylene glycol solution (water-based liquid mixture) to prevent from the risk of freezing. A highconcentration of propylene glycol increases the electricity con-sumption of circulation pumps but has very little impact on theheat-pump performance [51]. The antifreeze liquid at the evapo-rator outlet is injected into the ground via pipes buried in trenchesat a depth of 2 m. The fluid then reaches solar panels again only ifthe radiation is sufficient. Otherwise, heat extracted from theground directly enters the heat-pump evaporator without circu-lating through the solar loop. In that condition, the solar collectorby-pass is used. The buffer tank serves to store the extra solar heatharvested during the day, which cannot be used instantly due tooperating temperature limits of the heat-pump. The advantage ofthis operation is that it contributes to balance the fluid temperatureentering the evaporator, optimizing the use of solar heat providedby solar collectors and preventing overheating problems. When thetemperature of the antifreeze liquid has reached the maximumallowed by the heat-pump, and the solar radiation is still high, theextra solar heat is stored in the buffer tank so that it can be usedwhen solar radiation decreases at the end of the day. In that con-dition, the fluid coming out of the ground coil directly enters the

Fig. 2. Schematic of th

buffer tank (cold side), so no fluid circulates through the solarcollector circuit, which avoids heat losses during low solar radiationor at night.

When space heating is not required, the hot water produced canbe used as domestic hot water and the heat-pump can be reversedfor space cooling if necessary.

For comparison purposes, the study also provides performancesimulations of the GSHP only. In this case, the simulation modelconsiders that the outlet of the ground circuit is directly connectedto the inlet of the heat pump evaporator. Different numericalsimulations of the proposed model are performed for 19 Europeancities at different latitudes for both SGHSP and GSHP systems. Themodel integrates identical heat-pump, soil, building characteristicsfor each simulation, in order to evaluate the influence of solar ra-diation, ground and ambient temperatures on the heat-pump en-ergy performance.

4. Parameters assumption

4.1. Characteristics of the installation

The energy model developed in this study was used to simulatethe working performance of the selected SGSHP for differentclimate conditions. The SGSHP technical characteristics wereidentical for each simulation, as well as the building's technicalfeatures. It was important to maintain the same installation char-acteristics for each city simulation in order to compare the effect ofclimate conditions on SGSHP performance.

The article is based on a commercially available ground-sourceheat-pump [52], and solar system [53]. Table 1 provides the man-ufacturer's specifications for the selected heat-pump, showing itsworking performance for the given evaporator and condenser mass

e studied SGSHP.

Page 4: Higher ground source heat pump COP in a residential

Table 1Manufacturer's specification for the selected heat pump (Dimplex SIH6ME). Source:Ref. [52].

Heat capacity, Qcond (kW) 5.82COP 3.9Wcomp (kW) 1.49Qevap (kW) 4.342Evaporator mass flow rate, ṁwe (kg/s) 0.27Twei (�C) 10Tweo (�C) 6.06DPevap (kPa) 20Area evaporator, Aevap (m2) 0.8Heat transfer coefficient evaporator, Uevap (W/m2 �C) 1500Condenser mass flow rate, ṁwc (kg/s) 0.394Twci (�C) 37.8Twco (�C) 41.3Area condenser, Acond (m2) 0.456DPcond (kPa) 30.3

Table 3Antifreeze solution characteristics at 10 �C. Source: Ref. [64].

Composition 65% water e 35% propylene glycol(mass fraction)

Density rw (kg/m3) 1032Heat capacity Cpw (kJ/kg �C) 3.8Thermal conductivity kw (W/m �C) 0.42Dynamic viscosity mw (Pa s) 5.25 � 10�3

Prandtl Number Prw 47.5

A. Girard et al. / Renewable Energy 80 (2015) 26e39 29

flow rates, the antifreeze solution temperature at the evaporatorinlet (Twei), and the water temperature of the heating radiator cir-cuit at the inlet of the heat pump condenser (Twci). The selectedheat-pump has temperature operating limits for the antifreezesolution at the inlet of the evaporator comprised between �5 �Cand 25 �C.

The principal components of the soil are mineral substances(solid state), organic matter (solid state), water (liquid state) and air(gas state), which all have different thermal properties [54,55]. It isnecessary to study soil properties in a detailed site survey to accu-rately predict the thermal behavior of GHEs. Soil component pro-portions can vary from one site to another, and so can their thermalproperties. Comprehensive research shows that soil thermal con-ductivity is greatly related to moisture content, density and tem-perature [56e58]. In this study, the soil type was assumed identicalfor all locations and of ordinary density and moisture content. Alsoassumed was that the soil was homogeneous of constant density rsand thermal conductivity ks, as presented in Table 2.

The GHE will be considered as a collector coil horizontallyburied into trenches at 2 m depth. Because the soil is a solid ma-terial, the ground loop design must consider the building's heatingload, the heat pump running hours and the ground thermal prop-erties [59e61]. Specific software programs using the InternationalGround-Source Heat Pump Association (IGSHPA) method aregenerally used to determine the length of the ground collector coil,such as for instance GLGS, EED, GLD, GLHEPRO and GchpCalc [62,63].For the purpose of the study, ground collector parameters areassumed the same for each location (Table 2). Antifreeze solutioncharacteristics are presented in Table 3.

4.2. Building characteristics

Simulations presented in this study were performed for eachlocation considering the same two-bedroom one-story residential

Table 2Ground collector parameters.

Parameter Characteristics

Configuration type Horizontal 2-pipes systemPipe material Polyethylene high densityLength of pipe L (m) 240Pipe inner radius r1 (m) 0.008Pipe outer radius r2 (m) 0.010Piping depth (m) 2Pipe distance (m) 0.3Pipe thermal conductivity kp (W/m �C) 0.4Soil density rs (kg/m3) 2200Soil thermal conductivity ks (W/m �C) 1.6

property, whose characteristics are shown in Table 4. This type ofbuilding, with such envelope characteristics (overall heat transfercoefficient and ventilation rate) has low energy efficiencycompared to modern houses, but represents most individualhouses built in the 1970s and 1980s, which remain very common inEurope. Heating is assumed to be delivered by the heat-pump to thebuilding through hot water radiators. The heating schedule used formodel simulations is 6e10 am and 3e9 pm from 1st of October to30th of April.

4.3. Solar thermal system

To predict energy performance of the SGSHP during the heatingseason, the optimum tilt angle at each locationwas chosen in orderto maximize the solar collectors' capacity during winter. There arevarious correlations available in the literature to determine thefixed optimum tilt angle [65]. The study assumes solar collectorswith a fixed tilt angle that is equal to the site latitude plus 15�, asdemonstrated by Duffie et al. [66].

The orientation of the solar panel is southern. For the calcu-lation of the ground reflection, a ground reflectance (or albedo)value a of 0.24 was used. Typical ground reflectance values fordifferent ground surfaces can be found in numerous literaturesources. In Europe, for example, tabulated values for groundreflectance are included in the European Solar Radiation Atlas[67,68]. The value taken here is slightly above the average valueof 0.2 given by Liu and Jordan [69] for dry bare ground, free ofsnow [70,71].

For each simulation, three high efficiency flat-plate solar col-lectors of 2 m2 were used, connected in series, Table 5 [53]. Thebuffer tank used in the simulation model has 100 L capacity. Thetank is assumed to bewell-insulatedwith a heat transfer coefficientof 2 W/m2.�C and located at 19 �C air temperature.

4.4. Locations

This article is based on climate data for 19 European cities madeavailable by the Office of Energy Efficiency and Renewable Energyof the US Department of Energy [72]. The data files were converted

Table 4Building characteristics.

Components Characteristics

Building Total heated floor surface: Afloor ¼ 108 m2 (12 m � 9 m);Total heated volume: Vheated ¼ 302 m3 (108 m2 � 2.8 m);Total envelope surface: Aenvelope ¼ 330 m2;Building overall heat transfer coefficient (Ubat) equalsto 0.9 W/m2 �C;Natural ventilation: air change per hour n ¼ 1;Air pressure: 1 atm.Design internal ambient temperature Tai set to 19 �C

Heating system Hot water radiator heaters of 14 kW nominal capacitySupplied temperature to radiators Twco set to 47 �C

Heating period 6 to 10 am and 3e9 pm from 1st of October to 30th of April

Page 5: Higher ground source heat pump COP in a residential

Table 5Technical characteristics of the solar system. Source: Ref. [53].

Number of solar collectors 3 (6 m2)Zero loss collector efficiency h0 0.82Collector heat loss coefficient a1 3.31Buffer tank capacity (L) 100Buffer tank heat transfer capacity (W/m2 �C) 2Solar system total pressure loss (kPa) 20

A. Girard et al. / Renewable Energy 80 (2015) 26e3930

in EnergyPlus format by Crawley et al. [73] to ease their use inbuilding simulation programs. The weather data used in the articleare derived from two different sources: SWEC (SpanishWeather forEnergy Calculations) for Albacete, Murcia and Granada; IWEC (In-ternational Weather for Energy Calculations) for the other 16 cities.Hourly data of global and diffuse solar radiation and dry bulbtemperature were collected from SWEC and IWEC database, whileannual average air temperature, heating degree day (HDD)numbers, and ground temperatures for all locations were collectedfrom ASHRAE database [74]. Table 6 presents the 19 cities and theirmain climate conditions. Global solar radiation is represented asthe yearly sum of direct and diffuse radiations incident per unit areaon horizontal surface.

Table 7 shows ground temperatures at 2 m depth for a sampleof the studied locations (Bergen, Hamburg, Nantes, Madridand Granada) [72,75].

Table 6Climate conditions of the 19 locations. Source: Refs. [72e74].

Latitude Longitude Altitude(m)

Annualaveragetemperature(�C)

HDD at15.5 �C(�C day)

Global solarradiation(kWh/m2/year)

Bergen 60.30�N

5.22 �E 50 7.1 3191 747

Aberdeen/Dyce

57.20�N

2.22 �W 65 8.4 2758 856

Edinburgh 56.00�N

3.20 �W 41 9.4 2540 928

Belfast 54.65�N

6.22 �W 81 9.1 2468 888

Hamburg 53.63�N

10.00 �E 16 9.0 2752 955

Amsterdam 52.30 �N 4.77 �E �2 10.0 2310 982London/

Gatwick51.15�N

0.18 �W 62 10.2 2230 1010

FrankfurtAm Main

50.05�N

8.60 �E 113 10.1 2458 1035

Paris/Orly 48.73�N

2.40 �E 96 11.1 2003 1068

Nantes 47.17�N

1.60 �W 27 12.2 1723 1184

Lyon 45.73�N

5.08 �E 240 11.9 1989 1203

Bordeaux 44.83�N

0.70 �W 61 13.2 1482 1265

Marseille 43.45�N

5.23 �E 36 14.8 1228 1545

Rome 41.80�N

12.23 �E 3 15.8 1077 1462

Madrid 40.45�N

3.55 �W 582 14.3 1494 1617

Valencia 39.50�N

0.47 �W 62 17.3 747 1634

Albacete 38.95�N

1.85 �W 704 13.5 1512 1666

Murcia 37.79�N

0.80 �W 62 16.9 604 1599

Granada 37.18�N

3.78 �W 559 14.9 1233 1777

4.5. Financial and environmental assumptions

Analysis of the results was based on the financial sustainabilityof the studied installation. Electricity prices are different accordingto each European country. Thus, an identical electricity price wasassumed of 0.17 V/kWh for each of the locations. At the time of thestudy, this was the average price of electricity in the EuropeanUnion (EU27) in May 2013 [76]. It included the market price, thetransmission through main and local networks, administrativecharges and all taxes. The study assumed a CO2 emission forelectricity consumption of 0.42 kgCO2/kWh,which is amedian value[77e80].

According to the manufacturer price list, a total fully installedcost of 8980 V was found for the selected GSHP (Dimplex SIH6ME)[81]. This cost included all GSHP components, accessories, trench-ing costs, as well as delivery, installation, and commission. Table 8presents the GSHP cost breakdown. Accessories included theground coil, circulating pump, antifreeze solution, control andregulation instruments and sensors, valves and connectionaccessories.

An extra cost was calculated of 3800V for the fully installed rooftop 6 m2 solar system and the buffer tank [82]. This cost includedthe three solar collector panels, the roof installation kit, expansionvessel, 3-way valves, pipes and connections, and the installationcost. A cost of 450 V was used for the buffer tank including itsinstallation.

The financial analysis took into account the installed cost of thesystem components, but also maintenance costs as well asreplacement costs. The yearly replacement cost is calculated fromEquations (1) and (2) as follows.

Interest factor ¼ ð1 þ xÞy � 1ð1 þ xÞy � x

(1)

Yearly replacement cost ¼ Installed cost=Interest factor (2)

where x represents the interest rate (%) and y is the service life ofthe heating system (years).

SGSHP system costs are given as the sum of GSHP and solarsystem costs. Table 9 presents the financial data. System compo-nents, installation and service costs may vary according to marketdifferences between countries. However, for the purpose of thestudy, all costs are assumed identical for each location.

The electricity running cost of a heat pump is directly related toits coefficient of performance (COP). At equivalent heatingdemands, the electricity consumption of a heat pump drops whenCOP increases. Table 10 presents the evolution of space heatingcosts for the GSHP as a function of heat pump COP using as anexample an annual space heating consumption of 10,000 kWh. Itincludes the GSHP maintenance cost, and assumes an electricityprice of 0.17 V/kWh.

5. Mathematical model

Simulations were performed by means of a detailed, novelmodel developed by the authors, aimed at predicting performanceof solar-assisted ground-source heat pumps. The mathematicalmodel was built with Microsoft Excel software. The simulation ofeach location provided a generic mechanism for managing inputdata sets via a specific worksheet. Microsoft Visual Basic for Ap-plications (VBA) code was used to for data processing.

Initial research focused on the estimation of the heat-pumpCOP depending on evaporating and condensing temperaturesgiven by manufacturer. Secondary analysis focused on the

Page 6: Higher ground source heat pump COP in a residential

Table 9

Table 7Ground temperatures at 2 m depth (�C) for Bergen, Hamburg, Nantes, Madrid and Granada. Source: Refs. [72,75].

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Year

Bergen 5.6 3.7 2.8 2.8 4.2 6.3 8.5 10.4 11.4 11.2 9.9 7.9 7.0Hamburg 6.9 4.4 3.3 3.2 5.1 7.9 10.8 13.4 14.7 14.4 12.7 10.0 8.9Nantes 7.6 7.9 9.2 10.6 13.8 15.8 16.8 16.6 15.1 13.0 10.5 8.6 12.1Madrid 9.1 7.6 7.9 9.1 13.0 16.6 19.4 20.9 20.6 18.6 15.4 12.0 14.2Granada 10.2 8.9 9.2 10.2 13.7 16.9 19.4 20.8 20.5 18.7 15.8 12.8 14.7

A. Girard et al. / Renewable Energy 80 (2015) 26e39 31

estimation of each point of the refrigerant cycle. Fig. 3 showsR410a refrigerant flows on the P-h chart. The COP of the selectedheat pump was obtained for different combinations of evaporatorand condenser temperatures of the R410a using the P-h chart andEquation (3).

COP ¼ Qcond

Wcomp¼ ðh2a � h3Þ

ðh2a � h1Þ(3)

Different combinations of temperatures at the evaporator (from2 �C to 20 �C) and condenser (from 30 �C to 60 �C) temperatureswere used to calculate different values of COP from the R410avaporecompression cycle plotted in the P-h diagram and Equation(3). The COP variations obtained are reported in Table 11 and in agraphical format in Fig. 4. Such COP variations were modeled intoEquation (4) as follows.

COP ¼�a0 þ a1Tevap þ a2T

2evap

�$exp

h��b0 þ b1Tevap

þ b2T2evap

�Tcond

i(4)

where the coefficients a0, a1, a2, b0, b1 and b2 calculated from the P-hchart are as follows: a0 ¼ 11.929, a1 ¼ 1.5964, a2 ¼ 0.07526,b0 ¼ 0.019235, b1 ¼ 0.002291 and b2 ¼ �5.29$10�5.

Building characteristics are crucial to determine the heatingload (Qheating load). Both heat loss through the building envelope andheat loss due to ventilation should be considered. Building heatingload was calculated using Equation (5), Tai representing the designinternal ambient temperature and Tao the outside ambient airtemperature (dry bulb temperature).

Qheating load ¼�Ubat$Aenvelope þ 0:34$n$Vbuilding

�$

ðTai � TaoÞ ½kW�(5)

The building heating load (Qheating load) is the first variable to beevaluated. It represents the heat energy that needs to be deliveredby the heat pump to the building according to the outside ambienttemperature, and so the thermal capacity of the heat pump (Qcond)in that condition:

Qcond ¼ Qheating load ½kW� (6)

The heat extracted from the ground is calculated using Equa-tion (7).

Qground ¼ Uground$Acoil$DTLM ½kW� (7)

Table 8Cost breakdown for GSHP Dimplex SIH6ME.

Modelno.

Heatingcapacity(kW)

Priceincl.VAT (V)

Accessories(V)

Delivery,installation, andcommissioning (V)

Trenching(V)

Totalcost (V)

SIH6ME 6 3484 2381 1436 1678 8980

where Uground and Acoil are the overall heat transfer coefficient andthe surface area of the ground coil, respectively. DTLM is the logmean temperature difference calculated using Equation (8).

DTLM ¼ ðTwGo � TwGiÞLn ðTwGo � TgroundÞ

ðTwGi � TgroundÞ½�C� (8)

where TwGi and TwGo are respectively the temperature of the anti-freeze solution at the inlet and outlet of the ground collector, andTwGi the soil temperature in the ground. The overall heat transfercoefficient Uground should be determined using the following threethermal resistance values:

Rconv ¼ 12pr1Lhc

½�C=W� (9)

Rp ¼ 12pLkp

lnr2r1

½�C=W� (10)

Rs ¼ 12pLks

lnr2 þ r3

r2½�C=W� (11)

where Rconv is thermal resistance due to convection heat transferbetween the antifreeze liquid in the ground pipe and the pipe innersurface, Rp the thermal resistance due to conduction heat transferbetween the pipe's inner and outer surface. Rs is the thermalresistance due to conduction heat transfer between the coil outersurface and the undisturbed soil; r1 is the inner pipe radius, r2 is theouter pipe radius, and r3 the distance between the pipe outer sur-face and undisturbed soil, which is assumed to be equal to theradius of the pipe; L is the coil length; and kp and ks are the thermalconductivity of the pipe material and the soil respectively.

The convective heat transfer coefficient at the inner pipe surfacein Equation (9), hconv, is a function of Nusselt number, Nu, andthermal conductivity of the antifreeze solution kw, which can beexpressed by the following expression:

hconv ¼ Nukw2r1

½W=m�C� (12)

The Nusselt number Nu, determined using fluid mechanicscorrelations for forced convection in pipes (the appropriate formulaapplies for each laminar or turbulent flow condition), is function of

Details of costs for the selected installation.

GSHP Solar collectors þ buffer tank

Installed cost (V) 8980 4250Maintenance cost (V/year) 120 60Bank loan (years) 10 10Loan interest rate (%) 5 5Yearly replacement cost (V/year) 1163 550Service life (years) 30 30

Page 7: Higher ground source heat pump COP in a residential

Table 10Cost of electricity for space heating/annum as a function of COP.

Heat pump COP 1.5 2.5 3.5 4.5 5.5 6.5 7.5 8.5 9.5 10.5Cost (V/year) 1253 800 606 498 429 382 347 320 299 282

A. Girard et al. / Renewable Energy 80 (2015) 26e3932

the antifreeze solution Prandtl number Prw and its Reynoldsnumber Rew are calculated as follows:

Rew ¼ rwvwLmw

(13)

where rw and mw are the antifreeze liquid density and dynamicviscosity respectively, L is the coil length and vw is the fluid velocitycalculated using its flow rate and the pipe section.

Using the three thermal resistance values, Rconv, Rp and Rs, theoverall heat transfer coefficient of ground coil can be estimatedusing Equations (14) and (15):

Uground ¼ 1Rt

½W=�C� (14)

Rt ¼ Rconv þ Rp þ Rs ½�C=W� (15)

The values of the heat pump COP as a function of Tevap and Tcondcalculated in Equation (4) are used to determine the heat providedto the heat pump evaporator (Qevap), the heat delivered to the house(Qcond), the temperature changes of antifreeze solution in theevaporator (Twei and Tweo) and the temperature changes of thewater of the radiator circuit in the condenser (Twci and Twco) usingthe following equations. Fig. 5 shows the temperature evolutions inthe different heat exchangers.

The heat absorbed at the heat pump evaporator (i.e. source),which is the accumulation of the heat extracted from the groundand the heat harvested from the solar panels is calculated using thefollowing Equation (16).

Qevap ¼ QcondðCOP � 1Þ=COP ½kW� (16)

where Qcond, calculated using Equations (5) and (6) is the heatrejected to the house (i.e. load).

The heat source of the heat pump can be written such asEquation (17), which allows evaluating the inlet and outlet tem-peratures of the ground/solar circuit antifreeze solution at the heatpump evaporator (Twei and Tweo). The heat load of the heat pump,written in Equation (18) is used to evaluate the inlet and outlettemperatures of radiator circuit water at the condenser (Twci andTwco).

Qevap ¼ _mewCpwðTwei � TweoÞ ½kW� (17)

Fig. 3. Pressureeenthalpy chart for the heat pump cycle using the refrigerant R410a.

Qcond ¼ _mcwCpwaðTwco � TwciÞ ½kW� (18)

The variable _mew represents the mass flow rate of the antifreezesolution at the evaporator, _mcw the mass flow rate of the radiatorwater at the condenser, while Cpw is the antifreeze solution specificheat (3.8 kJ/kg.�C at 10 �C for the 35% propylene glycol solution) andCpwa the specific heat of the water in the radiator circuit (4.2 kJ/kg.�C at 45 �C).

The useful heat produced by the solar collector is estimated bythe following Equation (19).

Quseful ¼ Acol$SG$B ½kW� (19)

where Acol is the solar collector area, SG is the slope global radiationcalculated from the hourly global and diffuse solar radiation datasets, site longitude and latitude, collector orientation and tilt, whichgoverning equations are described in detail in previous work by theauthors [83e85], and B the solar collector efficiency, calculated asfollows:

B ¼ h0 � a1 � ðTwGo � TaoÞSG

(20)

The solar collector technical specifications h0 and a1 are the zeroloss collector efficiency and the collector heat loss coefficient bothgiven by the product manufacturer, while TwGo represents thetemperature of the antifreeze solution at the exit of the ground coil,and Tao the ambient air temperature.

The temperature at the exit of the solar collector (TwSo) can becalculated using Equation (21):

Quseful ¼ _mewCpwðTwSo � TwSiÞ ½kW� (21)

where TwSi is the temperature of the antifreeze solution at the inletof the solar collector. It is worth noting that TwSi ¼ TwGo assumingthat connection pipes are well insulated and that no heat is lostbetween system components.

The selected heat-pump allows a maximum inlet fluid temper-ature of 25 �C at the evaporator due to temperature operating limitsset by the manufacturer. When the antifreeze solution at the solarcollector outlet reaches temperatures above 25 �C, the extra heatenergy is stored in the buffer tank so that it can be delivered in latertimes when solar radiation lowers. This operation is made possiblethrough the use of a 3-way valve, that regulates the temperature of

Table 11Heat pump COP as a function of temperature of evaporator and condenser.

COP Temperature condenser Tcond (�C)

30 35 40 45 50 55 60

TemperatureevaporatorTevap (�C)

2 8.238 6.955 5.999 5.256 4.658 4.163 3.7434 8.922 7.443 6.366 5.541 4.886 4.348 3.8976 9.713 7.999 6.776 5.856 5.135 4.550 4.0628 10.653 8.638 7.239 6.206 5.408 4.768 4.241

10 11.810 9.398 7.776 6.606 5.716 5.013 4.43812 13.161 10.250 8.363 7.034 6.042 5.268 4.64314 14.888 11.288 9.056 7.530 6.413 5.556 4.87216 17.115 12.550 9.868 8.096 6.830 5.875 5.12318 20.078 14.104 10.825 8.744 7.298 6.227 5.39620 24.231 16.076 11.977 9.498 7.829 6.621 5.699

Page 8: Higher ground source heat pump COP in a residential

Fig. 4. Evolution of COP versus condensing (a) and evaporative (b) temperatures.

A. Girard et al. / Renewable Energy 80 (2015) 26e39 33

the solution at the inlet of the evaporator. The temperature of thetank (Ttank) is calculated as follows.

Quseful ¼ VtankrwCpwðTtank � TwSoÞ�3600 ½kW� (22)

When the temperature of the propylene glycol in the tank (Ttank)is below 25 �C, we assume that the temperature of the solutionentering the heat-pump evaporator Twei equals to Ttank. Otherwise,Twei remains equal to 25 �C until the heat stored in the buffer tank isused.

The energy balance on the evaporator heat exchanger can bewritten as Equation (23), which is be used to calculate the tem-perature of the refrigerant fluid in the evaporator (Tevap).

Tweo � TevapTwei � Tevap

¼ exp�� Uevap Aevap

_mew Cpw

�(23)

where Uevap is the heat transfer coefficient of the evaporator heatexchanger and Aevap is its surface heat exchange area.

The power input to the compressor,Wcomp is calculated from thefollowing Equation (24).

Wcomp ¼ Qcond=COP ½kW� (24)

The power input to the ground/solar circuit pump, Wpump iscalculated using Equation (25).

Wpump ¼ ð _m$DPÞ� (25)

where _m is the mass flow rate of the pumped fluid (antifreeze so-lution in the ground/solar loop, water in the radiator circuit), DP isthe pressure loss through the pump circuit (accordingly to the

Fig. 5. Evolution of temperatures through each heat exchanger of the SGS

corresponding pump, it includes pressure loss through heat ex-changers, through ground coil and solar collectors, as well as linearand local pressure losses through circuit pipes, fittings and valves),r is the fluid density, and hpump is the pump efficiency.

The computer model integrates a loop process for the calcula-tions of temperatures and energy rates of the evaporator andcondenser. Firstly, Tevap is assumed to be equal to Tweie 8 (step 1), inorder to set an approximate but plausible starting point of the loopprocess. Then Qevap is calculated from the P- h chart (Equation (4)),using Tevap and assuming Tcond ¼ 52 �C (step 2). The temperature atthe heat pump condenser Tcond is chosen so that the temperature ofthe circulating water in the radiator heating circuit can be suffi-ciently warm. Then the temperature of the antifreeze solution atthe outlet of the heat pump evaporator (Tweo) is calculated fromEquation (17) (step 3), which is used to calculate the new Tevapfrom Equation (23) (step 4). Finally the loop process introduced inthe computer model consists of repeating steps 2 to 4 until Tevapconvergence is achieved. The flowchart of the complete computermodel is shown in Fig. 6.

Using hourly weather data, the energy model calculates hourlyperformance values of the selected SGSHP during its working time.Therefore, power values of Qcond, Qevap, Wcomp and Wpump in kW areconverted as energy values in kWh.

The overall heat pump performance coefficient of the system(COPsys) is calculated using the sum for eachworking hours over thestudied year of the energy delivered by the heat pump (Qcond), thework energy spent by the heat pump compressor to deliver thatamount of energy (Wcomp) and the work energy consumed by theground/solar circuit pump and heating radiator pump (Wpump), asshown in Equation (26).

COPsys ¼X

Qcond

.�XWcomp þ

XWpump

�(26)

HP (From left to right: ground coil (GC), evaporator, and condenser).

Page 9: Higher ground source heat pump COP in a residential

Fig. 6. Flowchart for the computer model.

A. Girard et al. / Renewable Energy 80 (2015) 26e3934

6. Results and discussion

Sample simulation results for one day each, in January and Aprilare shown in Tables 12 and 13 for SGSHP system at the location ofEdinburgh. It is shown that the SGSHP systemworks slightly betterin spring/autumn when more solar heat is available. This is espe-cially true in northern regions, where solar radiation is less avail-able during winter days than in southern locations. In Table 13, theheat-pump COP increases considerably as the temperature of theantifreeze solution in the storage tank (Ttank) rises, when incidentslope global radiation (SG) reaches significant levels.

Considering identical housing, solar system, heat-pump and soilcharacteristics, the effects of different climates in Europe wereinvestigated from a total of 19 European cities in different regions.Overall COPsys obtained for both SGSHP and GSHP systems at eachof the 19 locations are presented in Fig. 6.

Southern localities, which benefit from higher outdoor ambientair temperature throughout the winter obtained higher heat pump

COPsys for both heat-pump systems. Two trend lines of COPsys, onefor each system, are drawn in Fig. 6. Results located above the trendline were obtained for milder climate locations, while those plottedbelow were obtained for cooler climate cities in their respectiverange of latitude. This statement is verified considering the loca-tions HDD values given in Table 6, and confirmed by space heatingdemand figures calculated in themodel simulations as presented inTable 14.

Results given in Fig. 6 show that coupling the selected roof-topsolar collectors and buffer tank to the GSHP had the effect ofincreasing the overall heat-pump performance. The color gradientbars for each location represent the difference of overall perfor-mance coefficient between SGSHP and GSHP systems. It is clear thatthe increase of COPsys between both systems is much higher forsouthern localities than for northern ones. Indeed the gradientslope of the SGSHP COPsys trend line is greater than the one of theGSHP system. Also, the greater COPsys difference are obtained forregions that benefit from the mildest climate and the highest solar

Page 10: Higher ground source heat pump COP in a residential

Table 12SGSHP simulation results for the first day of January in Edinburgh.

Hour SG (W/m2) Tao (�C) Ttank (�C) Twei (�C) Tevap (�C) Qevap (kWh) Tweo (�C) Ncount COP Qcond (kWh) Wcomp (kWh) Wpumps (Wh)

1 0.0 2.3 5.82 0.0 2.5 5.83 0.0 2.6 5.84 0.0 2.7 5.85 0.0 2.5 5.86 0.0 2.5 5.8 5.8 �1.1 5.06 1.3 2 4.32 6.58 1.52 18.47 0.0 2.5 5.8 5.8 �1.1 5.06 1.3 2 4.32 6.58 1.52 18.48 0.0 1.9 5.8 5.8 �1.3 5.24 1.1 2 4.30 6.82 1.59 19.19 0.8 2.6 5.8 5.8 �1.0 5.03 1.3 2 4.32 6.54 1.51 18.310 14.6 2.9 5.8 5.8 �0.9 4.94 1.4 2 4.33 6.42 1.48 18.011 48.5 2.9 7.312 38.9 3.5 7.013 29.4 3.7 6.714 27.2 3.7 6.615 4.9 3.7 5.8 5.8 �0.6 4.70 1.6 2 4.35 6.10 1.40 17.116 0.0 3.5 5.8 5.8 �0.7 4.76 1.5 2 4.35 6.18 1.42 17.317 0.0 3.4 5.8 5.8 �0.7 4.79 1.5 2 4.34 6.22 1.43 17.418 0.0 3.4 5.8 5.8 �0.7 4.79 1.5 2 4.34 6.22 1.43 17.419 0.0 2.9 5.8 5.8 �0.9 4.94 1.4 2 4.33 6.42 1.48 18.020 0.0 3.2 5.8 5.8 �0.8 4.85 1.5 2 4.34 6.30 1.45 17.721 0.0 2.5 5.8 5.8 �1.1 5.06 1.3 2 4.32 6.58 1.52 18.422 0.0 2.8 5.823 0.0 3.0 5.824 0.0 3.3 5.8

A. Girard et al. / Renewable Energy 80 (2015) 26e39 35

radiation, such as Marseille, Rome, Valencia, or Murcia, which aresituated around the Mediterranean Sea (Fig. 7).

Table 14 compares the performance of three systems for theselected building (i.e. electrically-operated SGSHP, GSHP andradiant electrical heater) following three parameters such as en-ergy use, relative CO2 emissions and payback period. The electricityconsumption field for both heat-pump systems represents the sumof electrical consumptions of the compressor and circulatingpumps. Payback periods are calculated taking in account replace-ment costs and maintenance costs given in Table 9.

It is shown that the SGSHP annual electricity consumption isinferior to that of GSHP in all locations. The relative savings onbilling cost that would be obtained with the SGSHP instead of theGSHP system are the weakest for the northern localities, where

Table 13SGSHP simulation results for the first day of April in Edinburgh.

Hour SG (W/m2) Tao (�C) Ttank (�C) Twei (�C) Tevap (�C) Qevap (kWh)

1 0.0 6.4 6.62 0.0 5.9 6.63 0.0 6.2 6.64 0.0 5.8 6.65 0.0 4.0 6.66 9.8 3.7 6.6 6.6 0.2 4.727 59.9 4.0 8.7 8.7 2.4 4.678 107.1 5.0 10.8 10.8 4.9 4.389 155.8 6.9 13.6 13.6 8.3 3.8710 281.7 9.4 21.4 21.4 17.0 3.2511 445.3 11.5 30.412 734.9 13.6 44.813 543.3 13.5 36.614 193.2 13.6 21.915 271.3 14.5 26.1 25.0 22.8 1.6016 154.8 14.6 21.2 25.0 22.9 1.5617 94.9 14.1 18.2 25.0 22.7 1.7318 27.4 11.3 12.5 25.0 21.4 2.6919 0.8 9.7 9.8 9.8 5.8 2.9420 0.0 9.7 9.8 9.8 5.8 2.9421 0.0 9.4 9.5 9.5 5.4 3.0322 0.0 8.9 9.023 0.0 9.2 9.324 0.0 9.0 9.1

solar radiation is the lowest and climate the coolest. For example, a13 V/year saving between SGSHP and GSHP in Bergen represents a2% relative savings on total billing cost. Therefore, only 5% savingsare obtained from SGSHP compared to GSHP in Aberdeen, Belfast,Hamburg and Frankfurt. Milder climates present the greatestrelative savings, up to a 13% billing cost savings for the SGSHPcompared to the GSHP in Marseille and Rome; and 12% in Valencia,Albacete, Murcia and Granada.

Shorter payback periods are obtained for cooler regions, in lo-cations presenting higher space heating demands. This is also thereason why the difference of payback periods between the twoheat-pump systems is the shortest for northern cities.

In comparison with the electrical radiant heating system (ERH),both heat-pump systems ensure important savings on energy

Tweo (�C) Ncount COP Qcond (kWh) Wcomp (kWh) Wpumps (Wh)

2.4 2 4.40 6.10 1.39 17.14.5 2 4.54 5.99 1.32 16.87.0 1 4.65 5.59 1.20 15.7

10.2 2 5.03 4.83 0.96 13.518.5 2 6.56 3.83 0.58 10.7

23.6 2 8.96 1.80 0.20 5.023.6 2 8.99 1.76 0.20 4.923.5 2 8.85 1.96 0.22 5.522.6 3 8.14 3.07 0.38 8.67.2 2 4.80 3.71 0.77 10.47.2 2 4.80 3.71 0.77 10.46.8 2 4.77 3.83 0.80 10.7

Page 11: Higher ground source heat pump COP in a residential

Table 14Comparison between the three sources of heating.

Space heatingdemand (kWh/year)

Heating system COPsys Electricity consumption(kWh/year)

Space heating cost(V/year)

Payback period(years)

Bergen 15,461 SGSHP 4.430 3490 593 8.5GSHP 4.338 3565 606 5.8ERH e 15,461 2628 e

Aberdeen/Dyce 13,486 SGSHP 4.618 2921 497 9.7GSHP 4.388 3073 522 6.6ERH e 13,486 2293 e

Edinburgh 12,426 SGSHP 4.822 2577 438 10.4GSHP 4.490 2768 470 7.2ERH e 12,426 2112 e

Belfast 12,789 SGSHP 4.762 2686 457 10.1GSHP 4.511 2835 482 7.0ERH e 12,789 2174 e

Hamburg 14,490 SGSHP 4.648 3117 530 9.0GSHP 4.428 3272 556 6.2ERH e 14,490 2463 e

Amsterdam 12,865 SGSHP 4.906 2622 446 10.0GSHP 4.536 2837 482 6.9ERH e 12,865 2187 e

London/Gatwick 12,264 SGSHP 4.814 2547 433 10.5GSHP 4.484 2735 465 7.3ERH e 12,264 2085 e

Frankfurt 13,693 SGSHP 4.756 2879 489 9.4GSHP 4.503 3041 517 6.5ERH e 13,693 2328 e

Paris/Orly 12,173 SGSHP 4.759 2558 435 10.6GSHP 4.486 2714 461 7.3ERH e 12,173 2069 e

Nantes 10,345 SGSHP 5.086 2034 346 12.3GSHP 4.627 2236 380 8.5ERH e 10,345 1759 e

Lyon 11,885 SGSHP 4.977 2388 406 10.8GSHP 4.653 2555 434 7.4ERH e 11,885 2020 e

Bordeaux 9614 SGSHP 5.221 1841 313 13.2GSHP 4.687 2051 349 9.2ERH e 9614 1634 e

Marseille 8748 SGSHP 5.583 1567 266 14.2GSHP 4.829 1811 308 10.0ERH e 8748 1487 e

Rome 7375 SGSHP 5.692 1295 220 16.8GSHP 4.968 1485 252 11.8ERH e 7375 1254 e

Madrid 9544 SGSHP 5.288 1805 307 13.2GSHP 4.726 2020 343 9.2ERH e 9544 1622 e

Valencia 5679 SGSHP 5.764 985 168 21.8GSHP 5.059 1123 191 15.2ERH e 5679 965 e

Albacete 10,044 SGSHP 5.308 1893 322 12.5GSHP 4.665 2153 366 8.8ERH e 10,044 1707 e

Murcia 5394 SGSHP 5.777 934 159 23.0GSHP 5.096 1059 180 16.0ERH e 5394 917 e

Granada 8252 SGSHP 5.424 1521 259 15.2GSHP 4.797 1720 292 10.6ERH e 8252 1403 e

A. Girard et al. / Renewable Energy 80 (2015) 26e3936

consumption. In locations where the space heating demand is high,the absolute saving (V/year) is substantial. For instance, Comparingan SGSHP to an ERH system in Bergen, the absolute savings is2035V/year, while it is only 758V/year inMurcia. However relativesavings (%) is more important in southern locations, i.e. cities fromBordeaux to Granada present relative savings from 81 to 83% for theSGSHP compared to the ERH system, while northern localities fromBergen toLyonshowrelative savings from77 to80%. Considering theGSHP, relative savings compared to the ERH system are just underthose obtained by the SGSHP but are also considerable (79e80%from Lyon to Granada, and 77e78% from Bergen to Nantes).

The same analysis can be done for relative CO2 emission savings.Identical relative savings (percentage) on CO2 emissions are ob-tained because electricity consumption and emission factor valuesare directly linked. The absolute CO2 savings (mass) depends oneach country's source fuel mix for electricity generation.

7. Conclusion

The present study introduces a novel simulation tool for theheating mode of operation of SGSHPs. Having assumed identicalheat-pump systems, building and soil characteristics for all

Page 12: Higher ground source heat pump COP in a residential

Fig. 7. COPsys comparison for SGSHP (in red) and GSHP (in blue) systems for the 19 studied cities. (For interpretation of the references to color in this figure legend, the reader isreferred to the web version of this article.)

A. Girard et al. / Renewable Energy 80 (2015) 26e39 37

locations, the analysis focused on the influence of solar radiationand climate factors in the evaluation of heat-pump performance.Site survey for soil characteristics would be required for more ac-curate results for each specific location, as well as a market inves-tigation for systems costs in each country to obtain a more precisefinancial analysis.

The results of this feasibility study demonstrate that the use ofsolar collectors combined with a ground-source heat-pump helpsin achieving higher overall COP, especially in locations where theclimate is mild and the solar radiation high. In higher latituderegions, the overall COP improvement is only marginal comparedto expected, however such results are explained by the fact thatsolar radiation in northern localities does not give as much heatenergy as it gives in southern ones [86]. Also in cooler climates,the heat-pump requires more electrical energy input to cover ahigher space heating demand, but in this case payback periods areshorter.

The SGSHP and the GSHP allow an average reduction of 5.1 and4.6 times, respectively the building dependence on electricity forspace heating compared to a conventional electrical radiant heatingsystem. Thus, considering CO2 emission factors from electricitygeneration, it has the potential to lower building carbon footprints,especially in countries where fossil fuel is a major part of the sourcefuel mix for electricity generation. For this reason heat pumps canplay a key role in the response to growing environmental concernsand can efficiently help in decarburizing the grid.

The studied SGSHP and GSHP are then respectively 5.1 and 4.6times cheaper to run than a conventional electrical radiant heatingsystem. SGSHPs, which are more efficient than GSHPs alone,represent an economically attractive low carbon solution comparedto other popular electrical heating systems.

When counting total lifetime costs of each system, paybackperiods for both heat pump systems were found in an acceptablerange of time (8.5e23 years for the SGSHP and 5.8e16 years for theGSHP). In all cases, payback periods remain under the entire systemlifetime, which makes both heat pump systems economic options.

Although the solar-assisted ground-source heat pump haslonger payback periods, such system achieves greater savings inbilling cost and CO2 emission on the long term than the GSHP alone.

The SGSHP system is best suited for cold regions with highirradiance, in order to obtain the greatest absolute electricity sav-ings compared to conventional systems, and to allow the mostreasonable and shortest payback time.

Further study investigating the potential of SGSHPs for bothcooling and heating modes and for domestic hot water productionshould be included in future research.

Acknowledgments

The authors are grateful to CIC Start Online for providingfunding to this project. CIC Start Online is funded by EuropeanRegional Development Fund and Scottish Government SEEKITprogramme that is managed by Scottish Funding Council. Thanksalso due to Mr Paolo Buoni of the European Energy Centre Ltd. forhis support.

This work was supported in Chile by the projects CONICYT/FONDAP/15110019 (SERC-CHILE) and by the Center for the Inno-vation in Energy of UAI.

References

[1] Juan YK, Gao P, Wang J. A hybrid decision support system for sustainable officebuilding renovation and energy performance improvement. Energy Build2010;42:290e7.

[2] Omer AM. Energy environment and sustainable development. Renew SustainEnergy Rev 2008;12:2265e300.

[3] Bolattürk A. Determination of optimum insulation thickness for building wallswith respect to various fuels and climate zones in Turkey. Appl Therm Eng2006;26(11):1301e9. 12.

[4] Yildiz A, Güng€or A. Energy and exergy analyses of space heating in buildings.Appl Energy 2009;86:1939e48.

[5] Hepbasli A. Low exergy (LowEx) heating and cooling systems for sustainablebuildings and societies. Renew Sustain Energy Rev 2012;16:73e104.

Page 13: Higher ground source heat pump COP in a residential

A. Girard et al. / Renewable Energy 80 (2015) 26e3938

[6] Papathanasopoulou E. Household consumption: associated fossil fuel demandand carbon dioxide emissions: the case of Greece between 1990 and 2006.Energy Policy 2010;38:4152e62.

[7] International Energy Agency (IEA). CO2 emissions from fuel combustion high-lights (2012 Edition). In: IEA Statistics, Paris, France, IEA/OECD; 2012. p. 1e138.

[8] International Energy Agency (IEA). Key world energy statistics. Paris, France:International Energy Agency, IEA; 2012. p. 1e82.

[9] Zogou O, Stamatelos A. Optimization of thermal performance of a buildingwith ground source heat pump system. Energy Convers Manage 2007;48:2853e63.

[10] Desideri U, Sorbi N, Arcioni L, Leonardi D. Feasibility study and numericalsimulation of a ground source heat pump plant, applied to a residentialbuilding. Appl Therm Eng 2011;31:3500e11.

[11] Dagdougui H, Minciardi R, Ouammi A, Robba M, Sacile R. Modelling andoptimization of a hybrid system for the energy supply of a “Green” building.Energy Convers Manage 2012;64:351e63.

[12] Sporn P, Ambrose ER. The heat pump and solar energy. In: The World Sym-posium on Applied Solar Energy, Phoenix, Arizona; 1955.

[13] Freeman TL, Mitchell JW, Audit TE. Performance of combined solareheatpump systems. Sol Energy 1979;22(2):125e35.

[14] Kush EA. Performance of heat pumps at elevated evaporating temper-aturesdwith application to solar input. Sol Energy Eng 1980;102:203.

[15] Chaturvedi SK, Chiang YF, Roberts Jr AS. Analysis of two phase flow collectorswith applications to heat pumps. Sol Energy Eng 1982;104:358.

[16] Chaturvedi SK, Shen YJ. Thermal performance aspects of direct expansionsolar assisted heat pump. Sol Energy 1984;33:155.

[17] Matsuki K, Shinobu Y, Yoshikawa M. A prototype direct-expansion solar heatpump system. ASHRAE Trans 1987;93:615.

[18] Nicolas J, Poncelet JP. Solar-assisted heat pump system and in-ground energystorage in a school building. Sol Energy 1988;40(2):117e25.

[19] Kaygusuz K, Ayhan T. Exergy analysis of solar-assisted heat-pump systems fordomestic heating. Energy 1993;18(10):1077e85.

[20] Kaygusuz K, Ayhan T. Experimental and theoretical investigation of combinedsolar heat pump system for residential heating. Energy Convers Manag1999;40:1377e96.

[21] Hawlader MNA, Chou SK, Ullah MZ. The performance of a solar heat pumpwater heating system. Appl Therm Eng 2001;21:1049e65.

[22] Badescu V. Model of a space heating system integrating a heat pump, pho-tothermal collectors and solar cells. Renew Energy 2002;27:489e505.

[23] Badescu V. Model of a thermal energy storage device integrated into a solarassisted heat pump system for space heating. Energy Convers Manage2003;44:1589e604.

[24] Huang BJ, Lee CP. Long-term performance of solar-assisted heat pump waterheater. Renew Energy 2004;29(4):633e9.

[25] Ozgener O, Hepbasli A. Exergoeconomic analysis of a solar assisted ground-source heat pump greenhouse heating system. Appl Therm Eng 2005;25:1459e71.

[26] Yang WB, Shi MH, Dong H. Numerical simulation of the performance of asolar-earth source heat pump system. Appl Therm Eng 2006;26:2367e76.

[27] Georgiev A. Testing solar collectors as an energy source for a heat pump.Renew Energy 2008;33:832e8.

[28] Wang H, Qi C, Wang E, Zhao J. A case study of underground thermal storage ina solar-ground coupled heat pump system for residential buildings. RenewEnergy 2009;34:307e14.

[29] Chow TT, Pei G, Fong KF, Lin Z, Chan ALS, He M. Modeling and application ofdirect-expansion solar-assisted heat pump for water heating in subtropicalHong Kong. Appl Energy 2010;87(2):643e9.

[30] Chow TT, Bai Y, Fong KF, Lin Z. Analysis of a solar assisted heat pump systemfor indoor swimming pool water and space heating. Appl Energy 2012;100:309e17.

[31] Kim W, Choi J, Cho H. Performance analysis of hybrid solar-geothermal CO2heat pump system for residential heating. Renew Energy 2013;50:596e604.

[32] Wu C, Chen L, Sun F, Cao S. Optimal collector temperature for solar-drivenheat pumps. Energy Convers Manage 1998;39:143e7.

[33] Chiasson A, Yavuzturk C. Assessment of the viability of hybrid geothermalheat pump systems with solar thermal collectors. ASHRAE Trans 2003;109(2):487e500.

[34] Bi Y, Guo T, Zhang L, Chen L. Solar and ground source heat-pump system. ApplEnergy 2004;78:231e45.

[35] Gorozabel Chata FB, Chaturvedi SK, Almogbel A. Analysis of a direct expansionsolar assisted heat pump using different refrigerants. Energy Convers Manage2005;46:2614e24.

[36] Trillat-Berdal V, Souyri B, Fraisse G. Experimental study of a ground-coupledheat pump combined with thermal solar collectors. Energy Build 2006;38:1477e84.

[37] Huang BJ, Wu JH, Hsu HY, Wang JH. Development of hybrid solar-assistedcooling/heating system. Energy Convers Manage 2010;51:1643e50.

[38] Chen X, Yang H. Performance analysis of a proposed solar assisted groundcoupled heat pump system. Appl Energy 2012;97:888e96.

[39] Choi J, Kang B, Cho H. Performance comparison between R22 and R744 solar-geothermal hybrid heat pumps according to heat source conditions. RenewEnergy 2014;71:414e24.

[40] Z€orner W, Holger M, Trinkl C. Domestic solar/heat pump heating systems:market overview, systems and components technologies. In: ESTEC Confer-ence, Munich, Germany; 2009.

[41] Sparber W, Vajen K, Herkel S, Ruschenburg J, Thür A, Fedrizzi R, et al. Over-view on solar thermal plus heat pump systems and review of monitoringresults. In: IAE SHC programme, Task 44; 2011.

[42] Haller MY, Frank E. On the potential of using heat from solar thermal col-lectors for heat pump evaporators. In: ISES Solar Word Congress, Kassel,Germany; 2011.

[43] Esen H, Inalli M, Esen M. Technoeconomic appraisal of a ground source heatpump system for a heating season in eastern Turkey. Energy Convers Manage2006;47:1281e97.

[44] Pulat E, Coskun S, Unlu K, Yamankaradeniz N. Experimental study of hori-zontal ground source heat pump performance for mild climate in Turkey.Energy 2009;34:1284e95.

[45] Healy PF, Ugursal VI. Performance and economic feasibility of ground sourceheat pumps in cold climate. Int J Energy Res 1997;21:857e70.

[46] ASHRAE. Guide to fundamentals. Atlanta, USA: American Society for HeatingRefrigerating and Air Conditioning Engineers; 2009.

[47] Energy Saving Trust. Energy efficiency best practice in housing. Domesticground source heat pumps: design and installation of closed-loop systems.Energy Saving Trust; 2004 [Online]. Available from: http://gshp.org.uk/documents/CE82-DomesticGroundSourceHeatPumps.pdf [accessed 02.12.13].

[48] Omer AM. Soil Thermal properties and the effects of groundwater on closedloops. Int J Sustain Energy Environ Res 2014;3(1):34e52.

[49] Bloomquist RG. Geothermal heat pumps, four plus decades of experience.Geo-Heat Cent Q Bull 1999;20. ISSN: 0276-1084:13e8.

[50] Lund JW, Freeston DH, Boyd TL. Direct utilization of geothermal energy 2010worldwide review. Geothermics 2011;40:159e80.

[51] Bernier M, Ladang O, Hulot J. �Etude du choix du fluide caloporteur sur�l�energiede pompage des syst�emes de pompes �a chaleurs g�eothermiques. In: 7e Col-loque Interuniversitaire Franco-qu�eb�ecois sur la thermique des syst�emes, IUTde St Malo; 2005.

[52] Dimplex renewable. Project planning manual: heating and cooling with heatpumps. 2011 [Online]. Available from: http://www.dimplex.de/fileadmin/dimplex/downloads/planungshandbuecher/en/dimplex_phb_kuehlen_gb_122008.pdf.

[53] CSTB. Avis technique 14þ5/05-996-TopSon F3-1 flat plate collector WOLFGmbH. Marne la Vall�ee: CSTB - Commission charg�ee de formuler des AvisTechniques; 2006.

[54] Song Y, Yao Y, Na W. Impacts of soil and pipe Thermal conductivity on per-formance of horizontal pipe in a ground-source heat pump. In: Proceedings ofthe Sixth International Conference for Enhanced Building Operations,Shenzhen, China; 2006.

[55] Naili N, Attar I, Hazami M, Farhat A. Experimental analysis of horizontalground heat exchanger for northern Tunisia. J Electron Cool Therm Control2012;2:44e51.

[56] Bose JE, Parker JD. Ground-coupled heat pump research. ASHRAE Trans1983;89(2):375e90.

[57] Sabau SS, Tao YX, Liu G, Vidhuvalavan G. Effective thermal conductivity foranisotropic granular porous media using fractal concepts. In: ASME Pro-ceedings of 32nd National Heat Transfer Conference, New York; 1997.

[58] Kavanaugh SP, Rafferty K. Ground-source heat pumps: design of geothermalsystems for commercial and institutional buildings. American Society ofHeating, Refrigerating and Air-Conditioning Engineers; 1997.

[59] Garcia Gonzalez R, Verhoef A, Vidale PL, Main B, Gan G, Wu Y. Interactionsbetween the physical soil environment and a horizontal ground coupled heatpump, for a domestic site in the UK. Renew Energy 2012;44:141e53.

[60] Cho H, Choi JM. The quantitative evaluation of design parameter's effects on aground source heat pump system. Renew Energy 2014;65:2e6.

[61] Chung JT, Choi JM. Design and performance study of the ground-coupled heatpump system with an operating parameter. Renew Energy 2012;42:118e24.

[62] Nagano K, Katsura T, Takeda S. Development of a design and performanceprediction tool for the ground source heat pump system. Appl Therm Eng2006;26:1578e92.

[63] Chiasson A. Geothermal heat pump systems: closed-loop design consider-ations. Geo-Heat Center, Oregon Institute of Technology; 2006.

[64] M. Conde Engineering. Properties of working fluids e brines. 2011. Zurich.[65] Stanciu C, Stanciu D. Optimum tilt angle for flat plate collectors all over the

world e a declination dependence formula and comparisons of three solarradiation models. Energy Convers Manage 2014;81:133e43.

[66] Duffie J, Beckman W. Solar engineering of thermal processes. John Wiley &Sons Inc; 2006.

[67] Aguiar R, Page J. ESRA handbook. In: Palz W, Greif J, Scharmer J, editors. Eu-ropean solar radiation atlas. 3rd ed. 1999 [Chapter 3]., Brussels, Belgium.

[68] Scharmer K, Greif J. European solar radiation atlas: fundamentals and maps.Paris: Ecole des Mines de Paris; 2000.

[69] Liu BYH, Jordan RC. The long term average performance of flat plate solarenergy collectors. Sol Energy 1963;7:53e74.

[70] Enriquez R, Zarzalejo L, Jim�enez MJ, Heras MR. Ground reflectance estimationby means of horizontal and vertical radiation measurements. Sol Energy2012;86:3216e26.

[71] Psiloglou BE, Kambezidis HD. Estimation of the ground albedo for the Athensarea, Greece. J Atmos Solar-Terr Phys 2009;71:943e54.

[72] US Department of Energy. Weather data, EnergyPlus energy simulation soft-ware. U.S. Department of Energy, Office of Energy Efficiency and RenewableEnergy; 2013 [Online]. Available from: http://apps1.eere.energy.gov/buildings/energyplus/weatherdata_about.cfm.

Page 14: Higher ground source heat pump COP in a residential

A. Girard et al. / Renewable Energy 80 (2015) 26e39 39

[73] Crawley DB, Lawrie LK, Pedersen CO, Liesen RJ, Fisher DE, Strand RK, et al.EnergyPlus, a new-generation building energy simulation program. In:Building Simulation '99, vol. I. Kyoto, Japan: IBPSA; September 1999. p. 81e8.

[74] ASHRAE (a). Chapter 14, climatic design information. In: 2009 ASHRAEhandbook fundamental. ASHRAE; January 2009.

[75] ASHRAE (c). International weather for energy calculations (IWEC weatherfiles) users manual and CD-ROM. Atlanta: ASHRAE; 2001.

[76] Europe's energy portal. 2013. [Online]. Available from: http://www.energy.eu/, [accessed 23.10.13].

[77] Garber D, Choudhary R, Soga K. Risk based lifetime costs assessment of aground source heat pump (GSHP) system design: methodology and casestudy. Build Environ 2013;60:66e80.

[78] Barrett M, Lowe R, Oreszczyn T, Steadman P. How to support growth with lessenergy. Energy Policy 2008;36:4592e9.

[79] UK Department of Energy and Climate Change (DECC). Guidelines to Defra/DECC's GHG conversion factors for company reporting. July 2013.

[80] UK Carbon Trust. Conversion factors, energy and carbon conversion factors,2013 update. 2013. p. 1e10.

[81] Dimplex Renewables Ltd. Renewables list prices,” Dimplex renewables.Southampton: GDC Group; October 2013.

[82] Wolf GmbH. Price list heating systems. Wolf GmbH; February 2013 [Online].Available from: http://www.wolf-heiztechnik.de/en/pkp/service/downloads/preislisten.html.

[83] Muneer T. Solar radiation and daylight models, Oxford. Butterworth-Heine-mann; 2004.

[84] Muneer T. Windows in buildings: thermal, acoustic, visual & solar perfor-mance. Oxford: Architectural Press; 2000.

[85] Girard A, Muneer M, Caceres G. A validated design simulation tool for passivesolar space heating: results from a monitored house in West Lothian, Scot-land. Indoor Built Environ 2013. http://dx.doi.org/10.1177/1420326X13480057.

[86] Citherlet S, Bony J, Nguyen B. SOL-PAC e analyse des performances ducouplage d'une pompe �a chaleur avec une installation solaire thermiquepour la r�enovation. Rapport final. Swiss Federal Office of Energy (SFOE);2008.