High‐Rise Fire ProtectiongStandpipe and Sprinkler Systems

By:Douglas Nadeau, PE

PresidentRAN Fire Protection Engineering, PC

Tel: 518‐275‐0791Email: dnadeau@ranfpe comEmail: [email protected]

Page 2: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

IntroductionIntroduction

Why talk about high-rise buildings?y g g

Focus on the Building Code applicationg pp

Purpose of the presentation

My experience

Question

Page 3: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

First Interstate BankFirst Interstate Bank

62 Stories – process of62 Stories process of sprinkler retrofitStarted on 12th floorDelayed call to Fire DepartmentpSprinkler System disabledFire Pumps shut downpFire Damage – 12th-16th

1 Dead (Building Engineer)1 Dead (Building Engineer)

Page 4: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

AgendaAgenda

Overview of High-Rise Buildingsg g

Standpipe Systems

Sprinkler Systems

Water Supply

Design Issues

Key Points

Page 5: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Overview of High‐Rise Buildings

Page 6: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Building Occupancy CharacteristicsBuilding Occupancy Characteristics

ResidentialResidential

Commercial

Mixed occupancy

Page 7: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Building Occupancy Characteristics dContinued

Residential buildings may contain senior citizens g yor people with special needs.

Residential buildings often have similar floor plans.

Commercial building floor plans often differ from floor to floorfloor to floor.

Building core usually remains consistentBuilding core usually remains consistent.

Page 8: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Characteristic FeaturesHigh Rise Characteristic Features

Occupants above reach of rescue ladders.Occupants above reach of rescue ladders.

The only effective means of fire control is byThe only effective means of fire control is by internal attack.

A fire fighting team working from a riser are unlikely to control a fully involved 100 ft x 200 ft y yfloor area.

Page 9: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Characteristic Features dContinued

Fire Department response times will be increasedFire Department response times will be increased in inner city areas.

High-rises are closed buildings – causing a rapid build up of heat and smoke.p

Page 10: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Building Code SectionsHigh Rise Building Code Sections

Chapter 4 – Special Detailed Requirements p p qBased on Use and Occupancy

Sprinkler Protection §903 2 10 3 BuildingsSprinkler Protection - §903.2.10.3 Buildings over 30 feet in height.

Standpipe Protection - §905.3.1 Building height. Class III standpipe systems shall be installed throughout buildings where the floorinstalled throughout buildings where the floor level of the highest story is located more than 30 feet…

Page 11: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Building Code provisions lapplies to

Buildings having occupied floors located more than 75 feet (22 860 mm) above the lowestthan 75 feet (22 860 mm) above the lowestlevel of fire department vehicle access

Some exceptions such as air traffic control towers.towers.

Page 12: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Building CodehChapter 4

Standby and Emergency Power RequiredStandby and Emergency Power RequiredThere is a difference!

Standby required for fire pumps, fire command centercenter …

E i f li hti fi lEmergency is for egress lighting, fire alarm…

Page 13: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Standpipe SystemsStandpipe Systems

Page 14: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Standpipe SystemHigh Rise Standpipe System

Purpose – installed to provide d t t fl f h tadequate water flow for hose streams

used to extinguish the fire.

Page 15: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Standpipe SystemHigh Rise Standpipe System

Design BasisDesign Basis

Building Code and Fire Code

NFPA 14

Page 16: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Standpipe System ld dBuilding Code 

Chapter 9 requires that standpipes be installed p q p pper NFPA 14

Required installationsClass III standpipe systems shall be installed throughout buildings where the floor level of thethroughout buildings where the floor level of the highest story is located more than 30 feet above the lowest level of the fire department vehicle access …

But wait there is an Exception

Page 17: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Standpipe System dContinued

Building Code Exception!!!g pClass I standpipes are allowed in buildings equipped throughout with an automatic

i kl t i t ll d i d ithsprinkler system installed in accordance with §903.3.1.1 or §903.3.1.2.

Note throughout

Page 18: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Types of High‐Rise Standpipe SystemsTypes of High Rise Standpipe Systems

Wet Automatic – most commonWet Automatic most common

Wet Manual parking garages <150 ftWet Manual – parking garages <150 ft

D A t ti bj t t f iDry Automatic - areas subject to freezing

Dry Manual - open parking garages

Page 19: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Standpipe System NFPA 14 Overview

Standpipes located in required stairwell.Standpipes located in required stairwell.

At least 4” for Class IIIAt least 4 for Class III.

6” risers required for combined system 4” if full6 risers required for combined system – 4 if full sprinkler protection.

Determine hose valve locations – max travel distance have to be in compliancedistance have to be in compliance.

Page 20: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Standpipe SystemNFPA 14 Overview

Class I StandpipeClass I Standpipe

100 psi at the outlet of the hydraulically most100 psi at the outlet of the hydraulically most remote 2½ in. hose connection

Generally 500 gpm at hydraulically most remote standpipe + 250 gpm for eachremote standpipe + 250 gpm for each additional (max 1250 gpm)

Page 21: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Standpipe System NFPA 14 Overview

Class I StandpipeClass I StandpipeRemote standpipe 100 psi requirement

Generally all new buildings.Possible pressure problemPossible pressure problem.3 in. drain rise for PRV’s

Page 22: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Sprinkler SystemsSprinkler Systems

Page 23: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

General Sprinkler FactsGeneral Sprinkler Facts

Usually 1 or 2 sprinklers will control a fire:Usually 1 or 2 sprinklers will control a fire:

85% of the time in a wet pipe system85% of the time in a wet pipe system.

67% f th ti i d i t67% of the time in a dry pipe system.

Page 24: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Why Sprinkler System FailWhy Sprinkler System Fail

NFPA, June 2007

Page 25: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Sprinkler SystemHigh Rise Sprinkler System

Purpose – installed to provide d t t t ti tadequate property protection to

control the fire.

Page 26: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Sprinkler SystemHigh Rise Sprinkler System

Design BasisDesign Basis

Building Code and Fire Code

NFPA 13

Page 27: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Sprinkler Systemld dBuilding Code Requirements 

Section §403 2 Automatic sprinkler systemSection §403.2 Automatic sprinkler system.Buildings shall be equipped throughout with an automatic sprinkler system inwith an automatic sprinkler system in accordance with NFPA 13.

A secondary water supply where required.

Page 28: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Sprinkler System ““equipped equipped h hh h ””throughoutthroughout””

§903.3.1.1 NFPA 13 sprinkler systems. -provisions of this code require that a building orprovisions of this code require that a building or portion thereof be equipped throughout …Important wording – why?Important wording why?Exempt locations – where water is badAlternate protection allowed?Alternate protection allowed?

Page 29: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Sprinkler System lAlternative protection

Section §903 1 1 states alternateSection §903.1.1 states alternate protection is permitted in lieu of automatic sprinkler protection where:sprinkler protection where:

1. recognized by the applicable standard andand

2. Such installations shall be approved by the code enforcement official.the code enforcement official.

Page 30: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Sprinkler System ld d hBuilding Code Chapter 9

Floor control valves need to be supervised atFloor control valves need to be supervised at point of connection to riser.

Rubbish chutes need to have sprinkler protection.protection.

NFPA 13D and NFPA 13R do NOT applyNFPA 13D and NFPA 13R do NOT apply.

Page 31: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Sprinkler SystemNFPA 13 Overview

Floor control valves shall be supervised byFloor control valves shall be supervised by constantly attended signaling service

Additional alarm apparatusWaterflow device per floor for the sprinkler systemsp p yCentral station service is required if a constant

supervision by qualified personnel is not providedDistinct trouble signal to indicate impairment of the

sprinkler system

Page 32: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Water SupplyWater Supply

Page 33: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Water Supply hCharacteristics

Primary Water SupplyPrimary Water Supply

Secondary Water Supply

Fire Pump

Page 34: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Secondary Water SupplyHigh Rise Secondary Water Supply

On-site water supplypp y

Equal to the hydraulically calculated sprinkler demand including the hose stream requirementdemand, including the hose stream requirement

In Seismic Design Category C, D, E or F areasIn Seismic Design Category C, D, E or F areas

Duration of not less than 30 minutes

Exception for existing buildings

Page 35: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Fire PumpHigh Rise Fire Pump

Series and Parallel PumpsSeries and Parallel Pumps

Zoning - Pressure

Break Tanks

Page 36: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Series and ParallelFire Pumps

Series Fire PumpsSeries Fire PumpsMeant to boost the pressure from a lower

zonezone.The design is dependent on both operating

Parallel Fire PumpsPrimary and secondaryMeant to boost flow volume

Page 37: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise ZoningHigh Rise Zoning

R id l BuildingResidual Pressure

Building Height (feet)

Zones Remarks

65 psi 200 1 max 175 psi rating100 psi 120 1p

65 psi 350 1 PRV’s required100 psi 270 1 q100 psi 270 1

65 psi 580 2 Design limit of 350 psi100 psi 500 2 of 350 psi100 psi 500 2

Page 38: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Break TanksBreak Tanks

No NFPA standards for sizing break tanksNo NFPA standards for sizing break tanks

Generally the size for 3 to 5 minutes of full flowGenerally the size for 3 to 5 minutes of full flow

M it i f th t l l i d dMonitoring of the water level is recommended

Page 39: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

Page 40: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

What is the biggest issue?

PPressure

Page 41: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

Standpipe system pressure limit is 350 psip p y p p

Generally (product specific, safety factor of 8)S h d l 10 t 300 iSchedule 10 maxes at 300 psiSchedule 40 minimum at 350 psiSchedule 80 minimum at 650 psiSchedule 80 minimum at 650 psi

Reduction to 65 psi may be allowed by the p y yAuthority Having Jurisdiction. Generally used for existing buildings.

Page 42: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

When system pressure exceeds 175 psiWhen system pressure exceeds 175 psi there may be listing problems.

Sprinkler listing are limited to 175 psi l i l li tiunless a special listing.

Page 43: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

Make sure that water supply will meet system pp y ydemand.

Combined Standpipe/Sprinkler systems required additional coordination between NFPA 13 and 14

Generally the standpipe will be the most demanding on the water supply NOT ALWAYSdemanding on the water supply. NOT ALWAYS THE CASE.

Page 44: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

If building is existing need to watchIf building is existing need to watch out for applying current code sections di tl t th b ildidirectly to the building.

Due Diligence is required to identify the required level of protectionthe required level of protection.

Page 45: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

Existing buildingExisting building

AddiAdding new preaction systems

Jockey pump y p psetting

Page 46: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign IssuesExisting building and systems

Upgrading to meet current codecurrent code requirements.

Listing pressure tiratings

Page 47: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

New Construction

Water Supply

Greatest DemandGreatest Demand

Page 48: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

Existing buildingExisting building

G t R h bilit tiGut Rehabilitation

Preparing for the future tenant renovation.

Page 49: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Design IssuesDesign Issues

Page 50: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

QuestionsQuestions

What is the most effective means of fire control in high-rise buildings?

What is the pressure requirement for the hydraulically most remote hose connection for a Class I standpipe system?Class I standpipe system?

What is one of the most critical design issues forWhat is one of the most critical design issues for high-rise building standpipe systems?

Page 51: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Key Points To RememberKey Points To Remember

Analyze the Codey

Plan early – communicate with CEOy

Address existing buildings uniquely

Address exceptions

PRESSURE!

Page 52: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

Key Points To RememberKey Points To Remember

Page 53: High Rise Fire Protection 2013 - C&S · PDF fileThe only effective means of fire control is byThe only effective means of fire ... A fire fighting team working from a ... High‐Rise

High‐Rise Fire ProtectiongStandpipe and Sprinkler Systems