high rise building air pressure, infiltration & stack...
TRANSCRIPT
© 2012-ESD, Inc.
By: Mehdi Jalayerian, PE, LEED® AP BD+C
Executive Vice President Environmental Systems Design, Inc.
2012 Spring Seminar, June 14, 2012
High Rise Building Air Pressure, Infiltration & Stack Effect
Theory and Impact on Indoor Environment
© 2012-ESD, Inc.
Learning Objectives
• Basic Theory of Air Flow Around and In High Rise Building – Wind – Stack-Effect
• Vertical Compartmentation – Elevators – Stairs – Impact on Energy – Impact on Pressure
• Smoke Management – Pressurization (Stairs/Space) – Smoke Control Considerations
• Example Building Air Movement/Pressure Analysis – 16 Story Hotel – Mixed-use Tall Building
• Summary Guidelines
© 2012-ESD, Inc.
Air Flow in High Rise Buildings
• Forced ventilation – Building supply/exhaust air systems – Fully controlled and distributed
• Natural ventilation – Pressure from wind and/or stack effect – Strategically placed intentional openings
• Infiltration – Uncontrolled air leakage – Unintentional openings in building envelope – Air leakage through floor/wall openings – Driven by wind force, temperature difference (buoyancy), and/or
system/appliance induced • Space Pressurization
– Normal mode pressurization – Fire mode pressurization (fire floor and stairs) for smoke
management
© 2012-ESD, Inc.
• Air movement into/out of a building is caused by wind pressure and stack effect pressure
• Wind pressure causes air to infiltrates into the building, or ex-filtrate out of the building
• Stack effect (air buoyancy) pressure causes air to rise or drop
Cold Weather • Air infiltrates into the lower half of the
building, rises to upper floors due to stack effect and exfiltrates in the upper half of the building.
Hot Weather • Air infiltrates into the upper half of the
building, drops to lower floors due to stack effect and exfiltrates in the lower half of the building.
Basic Theory WIND VELOCITY PROFILE
EXFILTRATION
INFILTRATION
STAC
K E
FFEC
T
NUTRAL PLANE
AVERAGE SURROUNDING ROOF HEIGHT OR 10M ABOVE GRADE
© 2012-ESD, Inc.
Basic Theory – Air Flow Around Building
© 2012-ESD, Inc.
Basic Theory - Wind Pressure
Wind creates a distribution of static pressure on the building envelope, which is dependent on wind direction and location on building envelope. ∆ Pw = C Cp ρ v2/2
∆ Pw = wind pressure difference, inches of water C = unit conversion, 0.0129 Cp = surface pressure coefficient, dimensionless ρ = air density, lbm/ft3 (about 0.075) v = wind speed, mph Note: Wind Pressure at top of 60 Story: Upwind = +1.32 in. of Water Sides = +0.61 in. of Water Downwind = -0.61 in. of Water
2X
X
Wind 15 mph
+0.33 in WG
© 2012-ESD, Inc.
Basic Theory - Stack Effect Pressure
Air density varies with temperature. In cold weather, low density air infiltrated into a building rises and creates stack effect pressure. ∆ Ps = C2 ρi g (h-hNPL)(Ti -To)/To
∆ Ps = pressure difference, inches of water
C2 ρi g = density and gravity constant, 0.01444 h = height of observation, ft NPL = building neutral pressure level T = absolute temperature, oR i & o = inside & outside Note: Stack Pressure is approximately 1 in. of water for a 60-story building and -10oF outside T
+0.95 in WG
© 2012-ESD, Inc.
Basic Theory – Overall Pressure
Natural air movement in a building is due to pressure difference caused by wind and temperature difference between indoor and outdoor air (stack effect). ∆P = (Po - Pi )+ ∆Pw + ∆Ps
∆P = pressure difference Po = outside static pressure Pi = interior static pressure ∆Pw= pressure difference due to wind (depends on orientation) ∆Ps = pressure difference due to stack effect
Wind
Stack Effect
Overall
Adjusted Neutral
© 2012-ESD, Inc.
Basic Theory – Air Flow Through Opening
Dynamic air flow through an opening is proportional to square root of the pressure difference across the flow path.
Q = C x Cf x A x √(2∆P/ρ)
Q = Air flow, CFM C = Unit Conversion, 776 Cf = Flow Coefficient, typically = 0.6-0.7 A = Opening Area, ft2
∆ P = pressure difference, inches of water ρ = air density, lbm/ft3 (about 0.075 at standard conditions)
Operation of building appliances and mechanical ventilation systems impact natural air movement. The impact is included with outside/inside pressure difference
© 2012-ESD, Inc.
Basic Theory - Air Flow Network
AMBIENT NODES
SPACE NODES
STAIR NODES
ELEVATOR NODES
Flow equations are developed between nodes (pressure & mass balance) Q = C x A x √(2∆P)/ρ System of equations are solved for each calculation time period Software: NIST CONTAM LBNL COMIS e-Quest
STAIR/ELEVATOR INTERCONNECTION
SPACE NODES INTERCONNECTION
© 2012-ESD, Inc.
Example High Rise Building Air Infiltration
Assumptions • 60-Story Office • 200 feet x 100 feet floor plate • Average leakage curtain wall • Weather-stripped exterior exist
doors • Revolving doors + swing exit
doors at main lobby • Standard door on typical floor stair • Average leakage elevator doors • Exterior condition at -10oF • Interior condition at 73oF • Wind direction from south (longer
wall) • Wind speed 15 mph (33 feet
above grade)
GROUND FLOOR
LOBBY
TENANT TENANT
N
TYPICAL FLOOR
TENANT
© 2012-ESD, Inc.
Building Air Infiltration – Effect of Elevators
Single Zone Elevators
Two Zones Elevators
Three Zones Elevators
Total Infiltration Heat Load 6,357 KW 2,903 KW 1,652 KW 100% 45.7% 25.9%
60-Story Office BuildingEffect of Elevator Zones
-15000 -10000 -5000 0 5000 10000 15000
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
Floo
r
Infiltration, scfm
Single Zone Two Zones Three Zones
~74% reduction
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
#1 #2ELEVATORS STAIRS
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR HR #1 #2ELEVATORS STAIRS
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR MR HR #1 #2ELEVATORS STAIRS
© 2012-ESD, Inc.
Elevator Shaft Air Flow
60 Story Office BuildingElevator Shaft Air Flow (Winter)
-15000 -10000 -5000 0 5000 10000 15000
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
Floo
r
Air Flow, CFM
Single Zone Two Zones Three Zones
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
#1 #2ELEVATORS STAIRS
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR HR #1 #2ELEVATORS STAIRS
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR MR HR #1 #2ELEVATORS STAIRS
Single Zone Elevators
Two Zones Elevators
Three Zones Elevators
© 2012-ESD, Inc.
Building Air Infiltration – Effect of Stairs
Single Zones Stairs
Three Zones Stairs
Total Infiltration Heat Load 1,652 KW 909 KW
100% 55%
60-Story Office BuildingEffect of Stair Zones (Three Elevator Zones)
-6000 -4000 -2000 0 2000 4000 6000 8000 10000 12000 14000
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
Floo
r
Infiltration, scfm
Three Zones Elevators/Single Zone Stairs Three Zones Elevators/Three Zones Stairs
~45% reduction
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR MR HR #1 #2ELEVATORS STAIRS
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR MR HR #1 #2ELEVATORS STAIRS
© 2012-ESD, Inc.
60 Story Building – Space Pressure
© 2012-ESD, Inc.
Typical Stair Air Separation/Lock
Up
Up
Down
AIR LOCK
2'-6"
2'-6"
2'-6"
Down
2'-6"
TYPICAL FLOOR
TENANT
Alternate B
Alternate A
Up
UpDown
Down
Air S
epar
atio
n
2'-6
"
2'-6
"
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR MR HR #1 #2ELEVATORS STAIRS
© 2012-ESD, Inc.
60 Story Building – Infiltration Load (Energy)
© 2012-ESD, Inc.
High Rise Building - Smoke Management
System Objectives • Reduce occupant death and
injuries – Delay smoke accumulation – Reduce smoke migration – Provide safe escape route – Provide safe refuge area
• Reduce property loss – Purge smoke – Manage fire impact
System Approach • Design/operate system to
prevent smoke entering the unaffected areas
• Integrate Smoke Control with Fire Protection System
• Allow for operational flexibility • Use HVAC system for smoke
control to improve system reliability
• Utilize compartmentation • Pressurization
– Horizontal – Vertical – Stairs – Lobbies
© 2012-ESD, Inc.
Pressurization – Normal Mode of Operation
Floor Pressurization • Main building lobby is pressurized • Each floor is provided with required
supply and exhaust • Each zone of building is pressurized
by maintaining differential air flow between supply/exhaust to minimize infiltration
• Stair pressurization systems are off GROUND FLOOR
TYPICAL FLOOR
LOBBY
TENANT TENANT
100% SUPPLY and 80-90% EXHAUST
© 2012-ESD, Inc.
Pressurization – Normal Mode of Operation
Three Zones Central AHU
Three Zones Elevator Single Zone Stairs
60-Story Office Building InfiltrationEffect of AHU Pressurization (Normal Mode)
-10000 -5000 0 5000 10000 15000
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
Floo
r
Infiltration, scfm
AHU - OFF AHU - ON
Building Infiltration Load Reduces by 70% (1652 kW reduced to 506 kW)
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR MR HR #1 #2ELEVATORS STAIRS
© 2012-ESD, Inc.
Pressurization – Fire Mode of Operation
Floor Pressurization • Main building lobby is pressurized • Fire Floor is provided with full
exhaust • Floors above and below fire floor is
provided with full supply air • All other floors operate normal mode • Stairs not pressurized
GROUND FLOOR
FIRE FLOOR
LOBBY
TENANT TENANT
NO SUPPLY and 100% EXHAUST
ABOVE OR BELOW FIRE FLOOR
100% SUPPLY and NO EXHAUST
© 2012-ESD, Inc.
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
Pressurization – Fire Mode of Operation
Exhaust on Fire Floor & Supply Above/Below
Single Zone Stairs Non-pressurized
60-Story Office Building InfiltrationSmoke Condition (Level 28) - Fire Mode Pressurization
-20000 -15000 -10000 -5000 0 5000 10000 15000
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
Floo
r
Infiltration, scfm
AHU - ON AHU - ON - Smoke Mode
Negative Press. (Exhaust) Positive Press. (Supply)
No Stair Pressurization Provided
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR MR HR #1 #2ELEVATORS STAIRS
© 2012-ESD, Inc.
Pressurization – Fire Mode/Stair Impact
Floor and Stair Pressurization • Main building lobby is pressurized • Fire Floor is provided with full
exhaust • Floors above and below fire floor is
provided with full supply air • All other floors operate normal mode • Stairs are pressurized
GROUND FLOOR
FIRE FLOOR
LOBBY
TENANT TENANT
ABOVE OR BELOW FIRE FLOOR
NO SUPPLY and 100% EXHAUST STAIRS PRESSURIZED
100% SUPPLY and NO EXHAUST STAIRS PRESSURIZED
STAIRS PRESSURIZED
© 2012-ESD, Inc.
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
Pressurization – Fire Mode/Stair Impact
Exhaust on Fire Floor & Supply Above/Below
Single Zone Stairs Pressurized – doors open
Open Exit Door
Open Exit Doors
Stairs Are Pressurized
605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321
LR MR HR #1 #2ELEVATORS STAIRS
© 2012-ESD, Inc.
Elevator Shaft Air Flow – Fire Mode
Open Exit Door
Open Exit Doors
Exhaust on Fire Floor & Supply Above/Below Doors open on fire, above/below and ground floors
60 Story Office Building - Elevator Shaft Air Flow (Winter)Smoke Condition on Level 28 (Building and Stairs Pressurized)
-4000 -2000 0 2000 4000 6000 8000 10000 12000 14000 16000
13579
11131517192123252729313335373941434547495153555759
Floo
r
Air Flow, CFM
Three Zones Three Zones - FireMode/Pressurized
© 2012-ESD, Inc.
Stair Air Flow – Fire Mode
Open Exit Door
Open Exit Doors
60 Story Ofice BuildingEffect of Stair Compartment on Pressurized Stair Air Flow - Smoke Condition (Level 28)
-15000 -12500 -10000 -7500 -5000 -2500 0 2500 5000 7500
13579
11131517192123252729313335373941434547495153555759
Floo
r
Air Flow, CFM
Single Compartment Stair Three Compartment Stair
Exhaust on Fire Floor & Supply Above/Below Doors open on fire, above/below and ground floors
© 2012-ESD, Inc.
Stair Pressure – Fire Mode
Open Exit Door
Open Exit Doors
60 Story Ofice BuildingEffect of Stair Compartment on Stair Pressure - Smoke Condition (Level 28)
-0.10 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80
13579
11131517192123252729313335373941434547495153555759
Floo
r
Pressure, in WG
Single Compartment Stair Three Compartment Stair
MA
XIM
UM
STA
IR P
RES
SUR
E TO
MA
INTA
IN D
OO
R F
OR
CE
Exhaust on Fire Floor Supply Above/Below
Doors open on fire floor, floors above/below fire floor and
ground floors
© 2012-ESD, Inc.
Smoke Control Considerations
• Building envelope design • Compartmentation
– Building occupancy types – Zones
• Elevator shafts – design/construction
• Stair shafts – design/construction
• Air leakage paths (smoke movement)
• Local design temperatures • Local wind velocities:
– Site – Envelope (wind tunnel test)
• HVAC system: – System zoning – Components design – System Activation/Controls
• Fire protection, detection and alarm system – Integration/coordination
• Firefighters Access: – To site – To manual/remote control of
system • Exiting plan
– Refuge areas – Exit duration
• Security and access control (door status/control)
© 2012-ESD, Inc.
16 Story Hotel Example – Space Pressure
© 2012-ESD, Inc.
Tall Building Example – Infiltration Air Flow
© 2012-ESD, Inc.
Tall Building Example – Space Pressure Hot
el S
huttl
e
Pub
lic P
arki
ng S
huttl
e
Res
iden
tial P
arki
ng S
huttl
e
Res
iden
tial L
ow Z
one
Res
iden
tial -
Hig
h Zo
ne
Res
iden
tial F
riegh
t
Bui
ldin
Frie
ght
Hot
el F
riegh
t
Am
eniti
es F
riegh
t
Hot
el
Am
eniti
es -
1
Am
eniti
es -
2
9291908988878685848382818079787776757473727170696867666564636261605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110
98765432
LobbyLL-1LL-2LL-3LL-4LL-5
© 2012-ESD, Inc.
Tall Building Example – Space Pressure
© 2012-ESD, Inc.
Summary
• High rise building infiltration can be significantly reduced by vertical compartmentation of building shafts (elevators, stairs, HVAC risers)
• Vertical compartmentation of building shafts creates more uniform pressure and air flow characteristics
• High rise building’s HVAC system will perform more effectively and more efficiently through a managed plan for stack effect
• Smoke control system configuration and performance must be carefully analyzed for various fire conditions and plan designs
• Integrated design process between architecture, structure and MEP assures an optimized building natural air flow
• High rise building’s natural air flow, air pressures characteristics and stack effect must be reviewed early in the design stage
• Minimum of two air barriers (walls, doors & vestibules) shall separate the internal building shafts (elevator, stairs) from the outside environment on each floor – main lobby, sky lobbies and loading dock levels may require additional layer of separation)
© 2012-ESD, Inc.
Thank you!