MOTOR H.P. Three phase motor data for 60 Hz, 1800 RPM standard squirrel cage motors. 200 VOLTS Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)**** 509- Starter 505- Reversing Starter 512- Fusible Combination Starter 513- Circuit Breaker Combination Starter 592- Solid-State Overload Relay 230 VOLTS Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)**** 509- Starter 505- Reversing Starter 512- Fusible Combination Starter 513- Circuit Breaker Combination Starter 592- Solid-State Overload Relay 460 VOLTS Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)**** 509- Starter 505- Reversing Starter 512- Fusible Combination Starter 513- Circuit Breaker Combination Starter 592- Solid-State Overload Relay 575 VOLTS Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)**** 509- Starter 505- Reversing Starter 512- Fusible Combination Starter 513- Circuit Breaker Combination Starter 592- Solid-State Overload Relay Example of 509-COD - A2E - - 17 - 90 Catalog Number: INSTRUCTIONS: 1. Place Bulletin No. and NEMA Size in same color window. 2. Read Rules 3. Select Heater Element. RULES: Motors rated for continuous duty: Motors with marked service factor of not less than 1.15, or motors with marked temperature rise not over 40 °C 1. The Same Temperature at the Controller and the Motor – Select the “Heater Type No.” with the listed “Full Load Amps.” nearest the full load value shown on the motor nameplate. This will provide integral horsepower motors with protection between 110 and 120% of the nameplate full load currents. 2. Higher Temperature at the Controller than at the Motor † – If the full load current value shown on the motor nameplate is between the listed “Full Load Amps.”, select the “Heater Type No.” with the higher value. This will provide integral horsepower motors with protection between 115 and 125% of the nameplate full load currents. © 2004 Rockwell Automation, Inc. HEATER TYPE NUMBER FULL LOAD AMPS FULL LOAD AMPS FULL LOAD AMPS HEATER TYPE NUMBER HEATER TYPE NUMBER BULLETIN NO: NEMA SIZE 0, 1, 2 BULLETIN NO: NEMA SIZE 3, 4 RULES Continued: 3. Lower Temperature at the Controller than at the Motor† – If the full load current value shown on the motor nameplate is between the listed “Full Load Amps.”, select the “Heater Type No.” with the lower value. This will provide integral horsepower motors with protection between105 and 115% of the nameplate full load currents. Rules 2 and 3 apply when the temperature difference does not exceed 10°C (18°F). Consult Local Allen-Bradley Distributor when the temperature difference is greater. All other motors rated for continuous duty (includes motors marked with service factor of 1.0): Select the “Heater Type No.” one rating smaller than determined by the rules in paragraphs 1, 2 and 3. This will provide protection at current levels 10% lower than indicated above. Motors rated for intermittent duty: Consult local Allen-Bradley Distributor Heater Element Selector For Starters With Bulletin 592 Eutectic Overload Relays, Class 20 Overload Protection Publication 592-QR001B-EN-P – July 2013 Copyright © 2013 Rockwell Automation, Inc. All rights reserved. Printed in USA. MOTOR DATA CALCULATOR BULLETIN NO: NEMA SIZE 0, 1, 2 MOTOR DATA CALCULATOR BULLETIN 509 STARTER CALCULATOR Control Voltage: 24V 50 Hz / 24V 60 Hz Control Voltage: 110V 50 Hz / 120V 60 Hz Control Voltage: 208V 60 Hz Control Voltage: 220V 50 Hz / 240V 60 Hz a a a a NEMA Size NEMA Size NEMA Size NEMA Size Modular Kit # Modular Kit # Modular Kit # Modular Kit # Components Components Components Components Contactor Contactor Contactor Contactor Eutec. OLR # Eutec. OLR # Eutec. OLR # Eutec. OLR # Coil Coil Coil Coil Control Voltage: 440V 50 Hz / 480V 60 Hz Control Voltage: 380V 50 Hz Control Voltage: 550V 50 Hz / 600V 60 Hz DC Control Voltage: 24V DC a a a a NEMA Size NEMA Size NEMA Size NEMA Size Modular Kit # Modular Kit # Modular Kit # Modular Kit # Components Components Components Components Contactor Contactor Contactor Contactor Eutec. OLR # Eutec. OLR # Eutec. OLR # Eutec. OLR # Coil Coil Coil Coil Auxiliary Contact On Eutectic Relay c Cont. Type Modular Kit Code Component NEMA Sz. 0-2 NEMA Sz. 3-4 1N.O. -9 595-A02 595-A34 1N.C -9A 595-B02 595-B34 Auxiliary Contact on Starter e All NEMA Sizes Cont. Type Mod. Kit Code Component 1N.O. -90 595-A 1N.C -91 595-B 2N.O. -900 595-AA 2N.C. -911 595-BB 1N.O & 1N.C. -901 595-AB Surge Suppressor d All NEMA Sizes Component Voltage Mod. Kit Code 120V AC -17 599-KO4 240V AC -17 599-KA04 Additional Options a b c d e Control Voltage: 24V 50 Hz / 24V 60 Hz Control Voltage: 110V 50 Hz / 120V 60 Hz Control Voltage: 208V 60 Hz Control Voltage: 220V 50 Hz / 240V 60 Hz a a a a NEMA Size NEMA Size NEMA Size NEMA Size Modular Kit # Modular Kit # Modular Kit # Modular Kit # Components Components Components Components Contactor Contactor Contactor Contactor Top Wire Kit Top Wire Kit Top Wire Kit Top Wire Kit Terminal Shield Terminal Shield Terminal Shield Terminal Shield Coil Coil Coil Coil Control Voltage: 440V 50 Hz / 480V 60 Hz Control Voltage: 380V 50 Hz Control Voltage: 550V 50 Hz / 600V 60 Hz DC Control Voltage: 24V DC a a a a NEMA Size NEMA Size NEMA Size NEMA Size Modular Kit # Modular Kit # Modular Kit # Modular Kit # Components Components Components Components Contactor Contactor Contactor Contactor Top Wire Kit Top Wire Kit Top Wire Kit Top Wire Kit Terminal Shield Terminal Shield Terminal Shield Terminal Shield Coil Coil Coil Coil Power Poles b NEMA Size Number of Poles Mod. Kit Code Component Standard (3) 930 4 940 5 950 Surge Suppressor c All NEMA Sizes Voltage Mod. Kit Code Component 120V AC -17 599-KO4 240V AC -17 599-KA04 Auxiliary Contact on Starter d All NEMA Sizes Cont. Type Mod. Kit Code Component 1N.O. -90 595-A 1N.C -91 595-B 2N.O. -900 595-AA 2N.C. -911 595-BB 1N.O & 1N.C. -901 595-AB Additional Options a b c Example of 500-BOD - 940 - 17 - 90 Catalog Number: d BULLETIN 500 TOP-WIRED CONTACTOR Solid-State Overload b NEMA Size Component Adjus. Range Mod. Kit Code 0.2-1.0 A 592-EEBC 1-5 A 592-EECC 3.2-16 A 592-EEDC 5.4-27 A 592-EEEC 9-45 A 592-EEFC 9-45 A 592-EEFD 18-90 A 592-EEGD 30-150 A 592-EEHE NEMA STARTER SELECTOR - EUTECTIC For Starters with Bulletin 592 Eutectic Overload Relays Class 20 Overload Protection – (“W” Heater Elements) Manual Reset INSTRUCTIONS: 1. Slide insert to select appropriate motor horsepower. 2. Read motor, wire and conduit data from window according to motor voltage. * Full Load Currents are from Table 430-150 of the 2002 NEC Code. ** Wire sizes were selected using the 2002 NEC Code (60 °C THW wire for motor full load currents less than 100 Amps and 75 °C THW wire for full load currents of 100 Amps and above). *** Conduit sizes were selected using the 2002 NEC Code. **** Fuse sizes were selected using Table 430-52 of the 2002 NEC Code for Dual Element Time Delay fuses. NEMA STARTER SELECTOR – E1 PLUS (Replaces SMP-1) For Starters with Bulletin 592 Solid State Overload Relays Self Powered Phase Loss Protection Wide Adjustment Range (5:1) Ambient Temperature Compensation Visible Trip Indication Selectable Trip Class (10, 15, 20 or 30) Selectable Manual/Auto-Manual Reset INSTRUCTIONS: 1. Slide insert to select appropriate motor horsepower. 2. Read motor, wire and conduit data from window according to motor voltage. * Full Load Currents are from Table 430-150 of the 2002 NEC Code). ** Wire sizes were selected using the 2002 NEC Code (60 °C THW wire for motor full load currents less than 100 Amps and 75 °C THW wire for full load currents of 100 Amps and above). *** Conduit sizes were selected using the 2002 NEC Code. **** Fuse sizes were selected using Table 430-52 of the 2002 NEC Code for Dual Element Time Delay fuses. MOTOR H.P. Three phase motor data for 60 Hz, 1800 RPM standard squirrel cage motors. 200 VOLTS Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)**** 509- Starter 505- Reversing Starter 512- Fusible Combination Starter 513- Circuit Breaker Combination Starter 230 VOLTS Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)**** 509- Starter 505- Reversing Starter 512- Fusible Combination Starter 513- Circuit Breaker Combination Starter 460 VOLTS Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)**** 509- Starter 505- Reversing Starter 512- Fusible Combination Starter 513- Circuit Breaker Combination Starter 575 VOLTS Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)**** 509- Starter 505- Reversing Starter 512- Fusible Combination Starter 513- Circuit Breaker Combination Starter W10 W11 W12 W13 W14 W15 W16 W17 W18 W19 W20 W21 W22 W23 W24 W25 W26 W27 W28 W29 W30 W31 W32 W33 W34 W35 W36 W37 W38 W39 W40 W41 W42 W43 W44 W45 W46 W47 W48 W49 W50 W51 W52 W53 W54 W55 W56 W57 W58 W59 W60 W61 W62 W63 W64 W65 W66 W67 W68 W69 W70 W52 W53 W54 W55 W56 W57 W58 W59 W60 W61 W62 W63 W64 W65 W66 W67 W68 W69 W70 W71 W72 W73 W74 W75 W76 W77 W78 W79 W80 W81 W82 W83 W84 Control Voltage: 24V 50 Hz / 24V 60 Hz Control Voltage: 110V 50 Hz / 120V 60 Hz Control Voltage: 208V 60 Hz Control Voltage: 220V 50 Hz / 240V 60 Hz a a a a NEMA Size NEMA Size NEMA Size NEMA Size Modular Kit # Modular Kit # Modular Kit # Modular Kit # Components Components Components Components Contactor Contactor Contactor Contactor Coil Coil Coil Coil Control Voltage: 440V 50 Hz / 480V 60 Hz Control Voltage: 380V 50 Hz Control Voltage: 550V 50 Hz / 600V 60 Hz DC Control Voltage: 24V DC a a a a NEMA Size NEMA Size NEMA Size NEMA Size Modular Kit # Modular Kit # Modular Kit # Modular Kit # Components Components Components Components Contactor Contactor Contactor Contactor Coil Coil Coil Coil Surge Suppressor b All NEMA Sizes Voltage Mod. Kit Code Component 120V AC -17 599-K04 240V AC -17 599-KA04 Auxiliary Contact On Eutectic Relay c All NEMA Sizes Cont. Type Mod Kit Sizes Component 1N.O. -90 595-A 1N.C -91 595-B 2N.O. -900 595-AA 2N.C. -911 595-BB 1N.0. & 1N.C. -901 595-AB Additional Options a b c Example of 500F-BOD - 17 - 90 Catalog Number: BULLETIN 500F FEED-THROUGH CONTACTOR

Upload: others

Post on 01-Sep-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Heater Element Selector - Rockwell Automation · 2019. 8. 15. · MOTOR DATA CALCULATOR BULLETIN NO: NEMA SIZE 0, 1, 2 MOTOR DATA CALCULATOR BULLETIN 509 STARTER CALCULATOR Control

MOTOR H.P. Three phase motor data for 60 Hz,1800 RPM standard squirrel cage motors.

200 VOLTS

Full Load Current*/NEMA SizeWire Size**/Conduit Size***Fuse Size (Amps)****

509- Starter505- Reversing Starter512- Fusible Combination Starter513- Circuit Breaker Combination Starter592- Solid-State Overload Relay

230 VOLTS

Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)****509- Starter505- Reversing Starter512- Fusible Combination Starter513- Circuit Breaker Combination Starter592- Solid-State Overload Relay

460 VOLTS

Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)****509- Starter505- Reversing Starter512- Fusible Combination Starter513- Circuit Breaker Combination Starter592- Solid-State Overload Relay

575 VOLTS

Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)****509- Starter505- Reversing Starter512- Fusible Combination Starter513- Circuit Breaker Combination Starter592- Solid-State Overload Relay

Example of 509-COD - A2E - - 17 - 90 Catalog Number:

INSTRUCTIONS:1. Place Bulletin No. and NEMA Size in same color window.2. Read Rules3. Select Heater Element. RULES: Motors rated for continuous duty: Motors with marked service factor of not less than 1.15,

or motors with marked temperature rise not over 40 °C1. The Same Temperature at the Controller and the

Motor – Select the “Heater Type No.” with the listed “Full Load Amps.” nearest the full load value shown on the motor nameplate. This will provide integral horsepower motors with protection between 110 and 120% of the nameplate full load currents.

2. Higher Temperature at the Controller than at the Motor † – If the full load current value shown on the motor nameplate is between the listed “Full Load Amps.”, select the “Heater Type No.” with the higher value. This will provide integral horsepower motors with protection between 115 and 125% of the nameplate full load currents.

© 2004 Rockwell Automation, Inc.

HEAT

ER TY

PE N

UMBE

R

FULL

LOAD

AM

PS

FULL

LOAD

AM

PS

FULL

LOAD

AM

PS

HEAT

ER TY

PE N

UMBE

R

HEAT

ER TY

PE N

UMBE

R

BULLETIN NO:NEMA SIZE 0, 1, 2

BULLETIN NO:NEMA SIZE 3, 4RULES Continued:

3. Lower Temperature at the Controller than at the Motor† – If the full load current value shown on the motor nameplate is between the listed “Full Load Amps.”, select the “Heater Type No.” with the lower value. This will provide integral horsepower motors with protection between105 and 115% of the nameplate full load currents.

† Rules 2 and 3 apply when the temperature difference does not exceed 10°C (18°F). Consult Local Allen-Bradley Distributor when the temperature difference is greater.

All other motors rated for continuous duty (includes motors marked with service factor of 1.0):

Select the “Heater Type No.” one rating smaller than determined by the rules in paragraphs 1, 2 and 3. This will provide protection at current levels 10% lower than indicated above.

Motors rated for intermittent duty:Consult local Allen-Bradley Distributor

Heater Element SelectorFor Starters With Bulletin 592 Eutectic Overload Relays, Class 20 Overload ProtectionPublication 592-QR001B-EN-P – July 2013

Copyright © 2013 Rockwell Automation, Inc. All rights reserved. Printed in USA.

MOTOR DATA CALCULATOR

BULLETIN NO:NEMA SIZE 0, 1, 2

MOTOR DATA CALCULATOR

BULLETIN 509 STARTER CALCULATOR

Control Voltage: 24V 50 Hz / 24V 60 Hz

Control Voltage: 110V 50 Hz / 120V 60 Hz

Control Voltage: 208V 60 Hz

Control Voltage: 220V 50 Hz / 240V 60 Hz

a a a aNEMA Size NEMA Size NEMA Size NEMA Size

Modular Kit # Modular Kit # Modular Kit # Modular Kit #Components Components Components Components

Contactor Contactor Contactor ContactorEutec. OLR # Eutec. OLR # Eutec. OLR # Eutec. OLR #

Coil Coil Coil CoilControl Voltage:

440V 50 Hz / 480V 60 Hz Control Voltage:

380V 50 Hz Control Voltage:

550V 50 Hz / 600V 60 HzDC Control Voltage:

24V DCa a a a

NEMA Size NEMA Size NEMA Size NEMA SizeModular Kit # Modular Kit # Modular Kit # Modular Kit #

Components Components Components ComponentsContactor Contactor Contactor Contactor

Eutec. OLR # Eutec. OLR # Eutec. OLR # Eutec. OLR #Coil Coil Coil Coil

Auxiliary Contact On Eutectic Relayc

Cont. Type Modular Kit Code ComponentNEMA Sz. 0-2 NEMA Sz. 3-4

1N.O. -9 595-A02 595-A341N.C -9A 595-B02 595-B34

Auxiliary Contact on Startere

All NEMA SizesCont. Type Mod. Kit Code Component

1N.O. -90 595-A1N.C -91 595-B2N.O. -900 595-AA2N.C. -911 595-BB

1N.O & 1N.C. -901 595-AB

Surge Suppressord

All NEMA SizesComponent

Voltage Mod. Kit Code120V AC -17 599-KO4240V AC -17 599-KA04

Additional Options

a b c d e

Control Voltage: 24V 50 Hz / 24V 60 Hz

Control Voltage: 110V 50 Hz / 120V 60 Hz

Control Voltage: 208V 60 Hz

Control Voltage: 220V 50 Hz / 240V 60 Hz

a a a aNEMA Size NEMA Size NEMA Size NEMA Size

Modular Kit # Modular Kit # Modular Kit # Modular Kit #Components Components Components Components

Contactor Contactor Contactor ContactorTop Wire Kit Top Wire Kit Top Wire Kit Top Wire Kit

Terminal Shield Terminal Shield Terminal Shield Terminal ShieldCoil Coil Coil Coil

Control Voltage: 440V 50 Hz / 480V 60 Hz

Control Voltage: 380V 50 Hz

Control Voltage: 550V 50 Hz / 600V 60 Hz

DC Control Voltage: 24V DC

a a a aNEMA Size NEMA Size NEMA Size NEMA Size

Modular Kit # Modular Kit # Modular Kit # Modular Kit #Components Components Components Components

Contactor Contactor Contactor ContactorTop Wire Kit Top Wire Kit Top Wire Kit Top Wire Kit

Terminal Shield Terminal Shield Terminal Shield Terminal ShieldCoil Coil Coil Coil

Power Polesb

NEMA SizeNumber of Poles Mod. Kit Code Component

Standard (3) 9304 9405 950

Surge Suppressorc

All NEMA SizesVoltage Mod. Kit Code Component120V AC -17 599-KO4240V AC -17 599-KA04

Auxiliary Contact on Starterd

All NEMA SizesCont. Type Mod. Kit Code Component

1N.O. -90 595-A1N.C -91 595-B2N.O. -900 595-AA2N.C. -911 595-BB

1N.O & 1N.C. -901 595-AB

Additional Options

a b cExample of 500-BOD - 940 - 17 - 90 Catalog Number: d

BULLETIN 500 TOP-WIRED CONTACTOR

Solid-State Overloadb

NEMA Size ComponentAdjus. Range Mod. Kit Code0.2-1.0 A 592-EEBC

1-5 A 592-EECC3.2-16 A 592-EEDC5.4-27 A 592-EEEC9-45 A 592-EEFC9-45 A 592-EEFD

18-90 A 592-EEGD30-150 A 592-EEHE

NEMA STARTER SELECTOR - EUTECTICFor Starters with Bulletin 592 Eutectic Overload Relays Class 20 Overload Protection – (“W” Heater Elements) Manual Reset

INSTRUCTIONS:1. Slide insert to select appropriate motor horsepower.2. Read motor, wire and conduit data from window according to motor voltage.

* Full Load Currents are from Table 430-150 of the 2002 NEC Code. ** Wire sizes were selected using the 2002 NEC Code (60 °C THW wire for motor full load currents less than 100 Amps and 75 °C THW wire for full load currents of 100 Amps and above). *** Conduit sizes were selected using the 2002 NEC Code. **** Fuse sizes were selected using Table 430-52 of the 2002 NEC Code for Dual Element Time Delay fuses.

NEMA STARTER SELECTOR – E1 PLUS (Replaces SMP-1)For Starters with Bulletin 592 Solid State Overload Relays Self Powered Phase Loss Protection Wide Adjustment Range (5:1) Ambient Temperature Compensation Visible Trip Indication Selectable Trip Class (10, 15, 20 or 30) Selectable Manual/Auto-Manual Reset

INSTRUCTIONS:1. Slide insert to select appropriate motor horsepower.2. Read motor, wire and conduit data from window according to motor voltage.

* Full Load Currents are from Table 430-150 of the 2002 NEC Code). ** Wire sizes were selected using the 2002 NEC Code (60 °C THW wire for motor full load currents less than 100 Amps and 75 °C THW wire for full load currents of 100 Amps and above). *** Conduit sizes were selected using the 2002 NEC Code.**** Fuse sizes were selected using Table 430-52 of the 2002 NEC Code for Dual Element Time Delay fuses.

MOTOR H.P. Three phase motor data for 60 Hz,1800 RPM standard squirrel cage motors.

200 VOLTS

Full Load Current*/NEMA SizeWire Size**/Conduit Size***Fuse Size (Amps)****

509- Starter505- Reversing Starter512- Fusible Combination Starter513- Circuit Breaker Combination Starter

230 VOLTS

Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)****509- Starter505- Reversing Starter512- Fusible Combination Starter513- Circuit Breaker Combination Starter

460 VOLTS

Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)****509- Starter505- Reversing Starter512- Fusible Combination Starter513- Circuit Breaker Combination Starter

575 VOLTS

Full Load Current*/NEMA Size Wire Size**/Conduit Size*** Fuse Size (Amps)****509- Starter505- Reversing Starter512- Fusible Combination Starter513- Circuit Breaker Combination Starter

W10W11W12W13W14W15W16W17W18W19W20W21W22W23W24W25W26W27W28W29W30W31W32W33W34W35W36W37W38W39W40

W41W42W43W44W45W46W47W48W49W50W51W52W53W54W55W56W57W58W59W60W61W62W63W64W65W66W67W68W69W70

W52W53W54W55W56W57W58W59W60W61W62W63W64W65W66W67W68W69W70W71W72W73W74W75W76W77W78W79W80W81W82W83W84

Control Voltage: 24V 50 Hz / 24V 60 Hz

Control Voltage: 110V 50 Hz / 120V 60 Hz

Control Voltage: 208V 60 Hz

Control Voltage: 220V 50 Hz / 240V 60 Hz

a a a aNEMA Size NEMA Size NEMA Size NEMA Size

Modular Kit # Modular Kit # Modular Kit # Modular Kit #Components Components Components Components

Contactor Contactor Contactor ContactorCoil Coil Coil Coil

Control Voltage: 440V 50 Hz / 480V 60 Hz

Control Voltage: 380V 50 Hz

Control Voltage: 550V 50 Hz / 600V 60 Hz

DC Control Voltage: 24V DC

a a a aNEMA Size NEMA Size NEMA Size NEMA Size

Modular Kit # Modular Kit # Modular Kit # Modular Kit #Components Components Components Components

Contactor Contactor Contactor ContactorCoil Coil Coil Coil

Surge Suppressorb

All NEMA SizesVoltage Mod. Kit Code Component120V AC -17 599-K04240V AC -17 599-KA04

Auxiliary Contact On Eutectic Relayc

All NEMA SizesCont. Type Mod Kit Sizes Component

1N.O. -90 595-A1N.C -91 595-B2N.O. -900 595-AA2N.C. -911 595-BB

1N.0. & 1N.C. -901 595-AB

Additional Options

a b cExample of 500F-BOD - 17 - 90Catalog Number:

BULLETIN 500F FEED-THROUGH CONTACTOR