DC Distribution Panels (DCDB)DC power systems are usually centrally located. A distribution system is needed to distribute the DC power safely among
various load centres. DC distribution board serve this purpose.
Depending on customer’s requirement, HBL offers integrated DC distribution boards with chargers or standalone DC
distribution boards. Each DCDB is equipped with several load circuits, each of which is protected by an appropriate circuit
breaker. Earth leakage monitoring devices are also offered as an option. DCDBs are delivered fully equipped & pre-wired,
to terminate load connections directly after installation.
DC systems need protection – and the DC distribution panel ensures that each circuit has that protection. In the event of an
overload or short circuit, the panel is designed to disconnect the fault safely.
HBL panels are type tested in independent labs to give you the confidence you need that your systems will be protected.
HBL’s DC distribution boards are type tested at IPH Labs, Germany per IEC 61439-1 & - 2.
Our panels perfectly match our DC systems to offer you an attractive panel array in your equipment room.
®
HBL
Applicable Standards
Input voltage
Parameter
Switchgear
Alarm indication by LED
Metering
Operating Temperature
Incoming : MCB / MCCB / SFU / SWITCH +FUSEOutgoing : MCB / MCCB / SFU / SWITCH +FUSE(Number of Feeders and their ratings will be based on customer requirements)
Standard:• DC Under / Over voltage• Earth Fault
Optional:• Feeder trip
Digital DC Voltmeter & Ammeter
0 to 50 °C
IEC 61439
24V / 48V / 110V / 220V DC
Type of Construction
Mounting
Ingress Protection
Enclosure Construction
Cable entry
Service Support
Standard: Non-compartmentalized, Form 2b Type 1 (IEC 61439)Optional: Compartmentalized
Standard: Floor mounted
Optional: Wall mounted
Standard: IP42 Optional: IP20 to IP65
Standard: Mild steel, RAL 7032 epoxy powder coatingOptional: Stainless steel / Galvanised Electro plating enclosures with different paint shades
Support of qualied factory trained service personnelField assistance & annual maintenance contracts
Gland plate (top and / or bottom)
Specication
System Specications
Mechanical Specications
Applications
Feeding D.C. Motor Loads
Fire Alarm Systems
Control &
inst
rum
enta
tion
Loads
DC Power supply &Cathodic Protection
LV & HV Switch Gear
Tele-communications
Battery Isolation Switch
To facilitate ease of maintenance and protection of
battery against short circuit currents, HBL offers
battery isolation switches that can be installed close to
the batteries. These isolation switches can also be
delivered in explosion-proof panels for installation in
hazardous areas.
®
HBL
SPECIFICATIONS
Input voltage
Switchgear
Remote alarm indication
Operating Temperature
Mounting
Ingress Protection
Cable entry
Enclosure Construction
Service Support
24V / 48V / 110V / 220V DC
System Specications
MCB / MCCB / SFU / SWITCH +FUSE
Potential-free contact to indicate Isolator open / trip
0 to 50 °C
Mechanical Specications
Wall Mounted type
Standard: IP42 Optional: IP20 to IP65, Ex-d
Gland plate (top and / or bottom)
Standard: Mild steel, RAL 7032 epoxy powder coatingOptional: Stainless steel / Galvanised Electro plating enclosures with different paint shades
Support of qualied factory trained service personnel
Field assistance & annual maintenance contracts
Parameter Specication
®
HBLCell BoosterIn a stationary battery system there are often hundreds of cells. It is not unusual for one or two cells
to display lower voltages than the average or recommended level – over time on float voltage,
cells can “drift” apart. HBL’s Cell Booster is a simple charger to selectively revive low voltage cells
and boost charge replacement cells before they enter service. Up to 6 Cells (Lead acid or Nickel-
cadmium) can be charged at one time. Potentiometers are provided to adjust the output voltage
and current to the levels required by the cells on charge.
The Cell Booster is portable for ease of use at site – powered from normal AC socket power. It is a
tool that every battery service team should have available.
SPECIFICATIONS
Charger Characteristics
Input Voltage
Input Frequency
Bridge Conguration
Output Voltage
Ripple Voltage
Current Rating
Current Limit
Line Regulation
Protections
Metering
Indications
Operating Temperature
Description Specification
Constant voltage/constant current with current limit
230V±10%, Single Phase
50Hz ± 5%
Single phase full wave half controlled bridge rectier
2 – 14V, adjustable through front-panel potentiometer
1% RMS, with battery connected
Different models covering 10 to 300A range, custom designed
Adjustable 50% to 100% of rating through front-panel potentiometer
± 10% input voltage variation2 to 5V output voltage: ± 1%5.1 to 14V output voltage: ± 5%
Input: •MCB/MCCB
Output: •Primary: Electronic current limit•Secondary: MCB / MCCB
I/P VoltageO/P Voltage & Current
I/P POWER ON LED O/P ON LED
0 to 50 °C
Type of cooling
Enclosure Construction
Ingress Protection
Cable entry
Service Support
Natural air cooling
Optional: Stainless steel / Galvanised Electro plating enclosures with different paint shades
Support of qualied factory trained service personnel
Gland plate (top and / or bottom)
Standard: Mild steel, RAL 7032 epoxy powder coating
Standard: IP21Optional: As per Customer Requirements
Field assistance & annual maintenance contracts
Mechanical Specications
Applications
Battery Charging
Feeding D.C. Motor Loads
Control & instrumentation
Loads
Fire Alarm Systems
Tele-communications
DC Power supply &Cathodic Protection
LV & HV Switch Gear
Earth Leakage MonitorsUndiagnosed faults in the electricity supply can produce very high economic
losses. Monitoring and signalling of unwanted earth faults helps the utility
minimize outages.
HBL’s ELM in DC power systems enables quick detection of earth faults and
prompts the operator to take corrective action.
It works on the principle of residual or differential magnetising current
induced in a current transformer. Our ELM is used in DC power systems such
as battery chargers, AC-DC converter systems, DC-DC converter systems
and DC Distribution Boards. It provides the customer an ability to install
earth leakage protection systems in their installations at a reasonable cost.
®
HBL
SPECIFICATIONS
Parameter Specication
DC system voltage 24V, 48V, 110V
Current rating 25A / 32A / 40A / 63A
Sensitivity Please see ordering codes below
Power consumption 2.5W
Operating temperature -25°C to +60°C
Relay output Potential free SPDT Contacts rated 24V, 12A DC 250V, 10A AC
Annunciation Local – LED Remote - PFC
Fault Reset Manual reset, by front-panel push button
Mounting DIN rail and screw xing
Dimensions (Height, Width, Depth in mm)
70 X 60 X 112 for 25A & 32A 73 X 75 X 112 for 40A & 63A
System voltage, V System current, A Earth leakage sensitivity, mA Part Number
25 5 60000 17009
25 20 60000 17008
32 5 60000 17012
40 20 60000 17006
63 10 60000 17007
25 5 60000 17010
32 5 60000 17011
24 / 32 / 48
110
Note: Please contact HBL with your requirements, if not covered in the above standard list.
Ordering codes
All specications are subject to change to ensure constant up gradation of technology
Applications
Feeding D.C. Motor Loads
Fire Alarm Systems
Control &
inst
rum
enta
tion
Loads
DC Power supply &Cathodic Protection
LV & HV Switch Gear
Tele-communications
corp
.comms\N
ov-2
019
Road No. 10, Banjara Hills,
www.hbl.in
712, Brook Street, Suite 107 Rocky Hill, CT 06067 USA
E-mail:[email protected]
HBL America Inc.HBL Power Systems Ltd.
Hyderabad 500034, T S, INDIA
Emilienstraße 24A
E-mail:[email protected]
08056 Zwickau, Germany
HBL Germany GmbH
www.hblpower.de
®
HBL
E-mail:[email protected] www.hblelectronics.com