hawe prop dir spool valve psl, psm, psv

32
2.1 Proportional directional spool valve type PSL, PSM, and PSV according to the Load-Sensing principle size 5 (valve bank design) D 7700-5 Prop. direct. spool valve PSL(V) May 2003-04 HAWE HYDRAULIK GMBH & CO. KG STREITFELDSTR. 25 • 81673 MÜNCHEN Size 2 (valve bank design) D 7700-2 Size 3 (valve bank design) D 7700-3 Size 3, 5 (manifold mounting design) D 7700-F © 1997 by HAWE Hydraulik, D-81673 München The reproduction, distribution and utilization of this document as well as the communication of its contents to others without explicid authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent or utility model. Pressure p max = 400 bar (6000 psi) Flow Q max = 210 lpm (55 gpm) The directional spool valves types PSL and PSV serve to control both, the direction of movement and the load-independent, stepless velocity of the hydraulic consumers. In this way several consumers may be moved simultaneously, independently from each other at different velocity and pressure ratings, as long as the sum of the partial flows needed for this is within the total delivery supplied by the pump. The proportional spool valves of this pamphlet are designed as valve banks and consist of three func- tional groups: Connection block Selection: Selection: Selection: 4/3-way directional spool valve End plate Connection block sect. 3.1 End plate sect. 3.1.5 Depending on the port size for P and R With or without internal control oil supply With or without pressure limiting valve With or without arbitrary idle pump circulation (safety circuit) Add-on valves, up to 10 sections may be added laterally to the connection block, with consumer ports A and B (select acc. to sect. 3.2) Flow pattern Max. permissible consumer flow at the spool's max. elevation Additional functions on the secondary side, e.g. pressure limiting valves, functional cut-off Actuation mode Completion of the valve bank (select acc. to sect. 3.1.5) With internal rooting or port T for the return flow of the control oil With or without additional inlet port LS Adapter plate for direct mounting of valve sections size 3 or 2 (valve bank design) Directional spool valve sect. 3.2 1. General Pump side with ports for pressurized oil inlet P and return R back to the tank as well as additional control and measurement ports LS, Z, M (select acc. to sect. 3.1) Depending on the nature of the pressur- ized oil supply either by constant delivery pump (open center) or variable displace- ment pump (closed center) / constant pressure system

Upload: cosma-petru-raul

Post on 18-Apr-2015

362 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Hawe Prop Dir Spool Valve Psl, Psm, Psv

2.1

Proportional directional spool valve type PSL, PSM, and PSV

according to the Load-Sensing principle

size 5 (valve bank design)

D 7700-5Prop. direct. spool valve PSL(V)

May 2003-04

HAWE HYDRAULIK GMBH & CO. KGSTREITFELDSTR. 25 • 81673 MÜNCHEN

Size 2 (valve bank design) D 7700-2Size 3 (valve bank design) D 7700-3Size 3, 5 (manifold mounting design) D 7700-F

© 1997 by HAWE Hydraulik, D-81673 München

The reproduction, distribution and utilization of this document as well as the communication of its contents to others without explicid authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent or utility model.

Pressure pmax = 400 bar (6000 psi)Flow Qmax = 210 lpm (55 gpm)

The directional spool valves types PSL and PSVserve to control both, the direction of movement and the load-independent, stepless velocity of thehydraulic consumers. In this way several consumersmay be moved simultaneously, independently fromeach other at different velocity and pressure ratings,as long as the sum of the partial flows needed for thisis within the total delivery supplied by the pump. The proportional spool valves of this pamphlet aredesigned as valve banks and consist of three func-tional groups:

Connection block

Selection:

Selection:

Selection:

4/3-way directional

spool valve

End plate

Connection blocksect. 3.1

End platesect. 3.1.5

• Depending on the port size for P and R

• With or without internal control oil supply

• With or without pressure limiting valve

• With or without arbitrary idle pump circulation (safety circuit)

Add-on valves, up to 10 sections may be added laterally to the connection block, with consumer ports A and B (select acc. to sect. 3.2)

• Flow pattern

• Max. permissible consumer flow at the spool's max. elevation

• Additional functions on the secondary side, e.g. pressure limiting valves,functional cut-off

• Actuation mode

Completion of the valve bank (select acc. to sect. 3.1.5)

• With internal rooting or port T for the return flow of the control oil

• With or without additional inlet port LS

• Adapter plate for direct mounting of valve sections size 3 or 2 (valve bank design)

Directionalspool valvesect. 3.2

1. General

Pump side with ports for pressurized oil inlet P and return R back to the tank as wellas additional control and measurementports LS, Z, M (select acc. to sect. 3.1)

• Depending on the nature of the pressur-ized oil supply either by constant deliverypump (open center) or variable displace-ment pump (closed center) / constantpressure system

Page 2: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 2

Order example: (For additional examples, see also sect. 6)

PSL 6 1F80/400 - 5- 52

- 52

- 52

- A1

J

O

H

L

160

63

120

40

/160

/120

/120

/25

A300

C250

F3

S

/EA1

/EA

/EA

/A /5 AS300 BS300 - E1 - G24

1716151413121110987654321

A total of max. 10 valve sections, in one or more valve bank(s), can be connected in series via the internalLS-duct. External piping is required, if more are requested (see also note at sect. 7.1.f).

2. Type coding, overview

; Basic type code for the connection block

(For detailed information, see sect. 3.1.1 and 3.1.2)PSL Supply with pressurized oil by means of constant delivery pump (open center).PSV Supply with pressurized oil by means of variable displacement pump with a delivery/flow controller (closed center),

as a second, separate unit, or if both valve banks are connected to a constant pressure system.PSM Supply of pressurized fluid either via constant delivery or variable displacement pump. For external circuitry, see

sect. 3.1.3 and 7)

< Tapped ports P and R (conf. DIN ISO 228/1 (BSPP)) at the connection block

5 G 1 (DIN ISO 228/1 (BSPP)) 6 G 1 1/4 (DIN ISO 228/1 (BSPP)) UNF 6 1 5/8-12 UN-2B (SAE-20, SAE J 514)

= Additional elements (see table 2 and 5 in section 3.1)

(no coding) Basic versionS Additional damping device in gallery LS (only with PSV, standard with PSL)B Orifice in gallery LS (PSV only)G only restrictor check valve (type PSL)U Automatic reduction of the pump idle circulation pressure by means of a by-pass valve (only type PSL), see also

note in sect. 7.1 a H Raised circulation pressure of the 3-way flow controller (approx. 14 bar, type PSL)UH Like version U but additional with raised circulation pressure of the 3-way flow controller (approx. 15 bar), only

type PSLY Separate, pressure resistant port for the excess oil from the 3-way flow controller, see also note in sect. 7.1a

> Control oil supply (see table 8, sect. 3.1.4)

(no coding) Without pressure reducing valve, if control oil is supplied externally (min. 20 bar up to max. 40 bar)1 With integrated pressure reducing valve for the internal supply with control oil

? Optional 2/2-way solenoid valve for arbitrary idle pump circulation (see table 9, sect. 3.1.4)

(no coding) Without directional valve, but prepared for retrofittingF De-energized open = Idle pump circulation when valve is de-energizedD De-energized closed = Idle pump circulation when valve is energizedF... or D If a pressure is specified, with pressure limiting valve which can be activated as a second pressure stage (e.g. F80)PA, PB, PC, PD Prop. pressure limiting valve with various pressure ranges

@ Tool adjustable, piloted pressure limiting valve (main pressure limitation) in the connection block (see sect. 3.1.4, table 10)

(no coding) Without pressure limiting valve (type PSV only/... Pressure limiting valve, factory set to ... bar

A Size (dep. on the hole-pattern of the mounting area for the spool valves to be added)

5 Size 5 (for size 3, see D 7700-3)

B Tapped consumer ports A and B at the directional spool valve

5 G 1 (DIN ISO 228/1 (BSPP))

A Suited for mounting of ancillary blocks acc. to Ior

Intermediate plates (see sect. 3.2.2). Positions C ... H are omittedZPL 5 S(V)/H Hydraulically actuated shut-off valve ZPL 5 S(V)/E Solenoid actuated shut-off valve ZPL 5 P6 R6 Additional pump and return port G 1/4ZPL 55/9 Spacer plate 9 mm

C Directional spool valve (see table 13, sect. 3.2)

2 (standard) Spool valve with inflow controller for each consumer 1 Spool valve without inflow controller, suitable for consumers, which are actuated individually and successively but

not simultaneously (no additional functions possible)5 Inflow controller with enforced spring for higher flow 8 4/3-way directional spool valve (pre-selector spool valve)

D Coding for the flow pattern (see sect. 3.2, table 14)

L, M, F, H, J, B, R, O, Y, I, Z

E Flow coding for ports A and B (see table 15, sect. 3.2)

.../... Coding for port A or B (independently selectable)16, 25, 40, 63, 80, 120, 160

Page 3: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 3

F Secondary pressure limitation (deviating from the main pressure setting, lower pressure for the connected consumer) no shock valves

(see sect. 3.2, table 16) (doesn't apply to spool valve types without inflow controller) (no coding) No secondary pressure limitationA... Only for consumer port AB... Only for consumer port BA...B... For consumer ports A and B

C... Joint for consumer port A and B (not in conjunction with G F. or S)

G Functional cut-off (see sect. 3.2, table 17) (doesn't apply to spool valve types without inflow controller)

F1 Electrical cut-off, consumer port AF2 Electrical cut-off, consumer port BF3 Electrical cut-off, consumer port A and BFP1(2, 3) Like F1(2,3), however with electro-proportional pressure limitationFPH1(2, 3) Like FP1(2,3), however with additional pushbutton for manual emergency actuationS, S1 External, hydraulic load signal pick-up from the control signal port U (consumer port A) and W (consumer port B)X External load pressure pick-up via control port X (common for A and B)

H Types of actuation (see sect. 3.2, table 20)

/A(1) Manual actuation (suffix 1 = without hand lever)/E Electro-hydraulic actuation/EA(1) Electro-hydraulic and manual actuation /E0A(1) Like /EA(1, 2), however without actuation solenoid (prepared for retrofitting)/H Hydraulic actuation/H UNF Like /H, however with port thread 7/16-20 UNF-2B SAE-4 (conf. SAE J 514)/HA(1), /HEA, /FA Hydraulic, (solenoid) and manual actuation/HA UNF(1) Like /HA(1), however with port thread 7/16-20 UNF-2B SAE-4 (conf. SAE J 514) /C(1) Detent /P Pneumatic actuation/PA(1) Pneumatic and manual actuation

/... Suffix G Reinforced versionB Solenoid with quarter-turn type plugT Manual emergency actuationTH Manual emergency actuation with pushbutton

I Ancillary blocks (acc. to table 19 in sect. 3.2), into combination with coding A of B/5 Ancillary blocks without additional functions/UNF 5 Like /5, however with port thread 1 5/16-12 UN-2B (SAE-16 conf. SAE J 514)/5 AS.. BS.. Ancillary blocks with shock valves at A and B (routed to the opposing side), with pressure specification (bar)/UNF 5 AS.. BS.. Like /5 AS.. BS.., however with port thread 1 5/16-12 UN-2B (SAE-16 conf. SAE J 514)/5 AN.. BN.. Ancillary blocks with shock and suction valves at A and B, with pressure specification (bar)/UNF 5 AN.. BN.. Like /5 AN.. BN.., however with port thread 1 5/16-12 UN-2B (SAE-16 conf. SAE J 514)/5 AL.. Ancillary blocks with over-center valves at A, with pressure specification (bar)/5 BL.. Ancillary blocks with over-center valves at B, with pressure specification (bar)/5 VV(VX, XV) Ancillary blocks with shut-off valves EM 42 V acc. to D 7490/1 (one or both sided) blocking the consumer with

zero leakage (Qmax approx. 160 lpm)

/5 DRH, /UNF 5 DRH Ancillary blocks with releasable check valves

J End plate (see sect. 3.1.5, table 11)

E1 With T-port for external control oil return to the tank (standard)E1 UNF Like E1, however with port thread 7/16-20 UNF-2B (SAE-4 conf. SAE J 514)E2 Like E1, with additional port Y for connection to the LS-port of a further, separately located PSV spool valve.

(Total number of the sequential add-on valves 10, see note sect. 7.1 f)E3 Like E1, with additional 3/2-way directional solenoid valve for arbitrary shut-off of pump circulation during idle

position of the valve spoolsE4 Like E2, however without T-port (like E4) return, max. pressure 10 bar!E4 UNF Like E4, however with port thread 7/16-20 UNF-2B (SAE-4 conf. SAE J 514)E5 Like E2, however without T-port (like E4)E6 Like E3, however without T-port (like E4)E7 to E16 Variations, see table 11, sect. 3.1.5E13 UNF to E16 UNF Like E13 to E16, however with port thread SAE-16 conf. SAE J 514 (For port size, see sect. 5.2)E7 A1(2) Like E1, however with additionally integrated pressure reducing valve

(control pressure: 1 = approx. 20 bar, 2 = approx. 40 bar) similar connection block, see table 6 in sect. 3.1.3 E8 A1(2) Like E2, however with additionally integrated pressure reducing valve

(control pressure: 1 = approx. 20 bar, 2 = approx. 40 bar) similar connection block, see table 6 in sect. 3.1.3ZPL 53 Adapter plate enables combination with valve sections size 3 acc. to D 7700-3ZPL 52 Adapter plate enables combination with valve sections size 2 acc. to D 7700-2

K Nominal solenoid voltage

G 12 12V DCG 24 24V DCG 24ex 24V DC, Explosion-proof version, conforming EEX m II T4

Page 4: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 4

There are two basic variations of connection blocks ' Connection blocks with integrated 3-way flow controller, suitable for a constant delivery pump system (open-center)

' Connection blocks suited for a variable displacement pump system (closed center), a constant pressure systems, or if a secondor more, separately located directional spool valve banks are fed in parallel

Order coding for a connection block as individual section (examples): PSL 61 F/250 - 5 - G 24

(Attention: Size specification absolutely necessary, here -5) PSV 51 - 5

3.1.1 Connection blocks for constant delivery pump systems (with integrated 3- way flow controller) type PSL

Flow pattern symbols (see also sect. 3.1.4)

PSL 5(6)./..PSL 5(6)H./..PSL UNF 6./..

PSL 5(6)U./..

PSL 5(6)UH./..

PSL 6Y./..PSL 6YH./..

Order example: PSL 5 1F80/350-5 -...- E1 - G 24

PSL 6 UH 1F/300-5 -...- E1 - G 24

PSL..G./..

3. Available versions, main data3.1 Connection blocks

Table 1: Basic type and port size 2)

Coding Tapped ports P and R 1)DIN ISO 228/1 (BSPP) or SAE J 514

Max. pumpdeliveryflow (lpm)

G 1

G 1 1/4

1 5/8-12 UN-2B (SAE-20)

G 1

G 1 1/4

G 1 1/4

250

300

300

250

300

300

Description

Standard, integrated 3-way flow controller

Automatic reduction of the idle pump circu-lation pressure by means of a by-pass valve(see also sect. 7.1a, Qpu ≥ 150 lpm with solenoid actuation )

Separate, pressure resistant port for the ex-cess oil from the 3-way flow controller (seealso sect. 7.1a). This version features thesame by-pass valve, like type PSL 5(6)U

For the data of actuation Esee sect. 4.3. For arbitrary idle pump circulation type PSL(V)..F or ..D see WN1F(D) acc. to D 7470 A/1 (currently notavailable as explosion-proof version)

G 12

G 24

G 24 Ex

12V DC

24V DC

Table 3: Nom. voltage for PSL..F(D) and/or actuation solenoids

Coding for additional elements (for notes and descriptions, see sect. 7.1a)

Coding Description

Standard Featuring a combination of orifice, check valve, pre-load valve (pre-load pressureapprox. 25 bar)

Restrictor check valve (without sequence valve), increased throttling effect

Coding for 3-way flow controller with raised circulation pressure (see sect. 4.2), otherwise sim-ilar flow pattern symbol as the standard version. Intended e.g. for valve spools with increasedflow (coding 5 acc. to table 15)

nocoding

H

G

PSL 5 3)

PSL 6 3)

PSL UNF 6

PSL 5 U 3)

PSL 6 U 3)

PSL 6 Y 3)

Table 2:

1) All other ports LS, M, Z = G 1/4 (DIN ISO 228/1 (BSPP))= 7/16-20 UNF-2B (SAE J 514, SAE-4)

2) Type PSL 5, PSL 6 and PSL UNF 6 can be converted any time foruse with variable displacement pumps (similar to type PSV), seesect. 7.4.

3) Attention: A spacer plate type SL5-ZPL55/9 (see sect. 3.2.2) hasto be installed right after the connection block whenever typePSL 5(6), PSV 5(6) and PSM 6 is combined with a valve sectionwith ancillary block (coding SL5-A.. acc. to table 12 and 19) asotherwise it is not possible to mount a fitting in port R.

Explosion-proof version, protection class EEX m II T4 for actua-tion E or EA, see sect. 4.3

see table 2 see table 3

Page 5: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 5

3.1.2 Connection blocks for variable displacement pump systems / constant pressure system or for other more separately,

parallel connected directional spool valve banks type PSV

PSV 6S 1 - 5 -...- E1

PSV 5 1F/300 - 5 -...- E1 - G 24

Order example:

1) The connection blocks type PSV, fea-turing a pressure limiting valve, may beconverted any time into type PSL(standard).

2) All other ports LS, M, Z = G 1/4 (DIN ISO 228/1 (BSPP))= 7/16-20UNF-2B (SAE-4, SAE 514)

3) Version with arbitrary shut-off of thepump gallery; For complete type cod-ing key, notes, and explanation, seesect. 7.7

4) Attention: A spacer plate type SL5-ZPL55/9 (see sect. 3.2.2) has tobe installed right after the connectionblock whenever type PSL 5(6), PSV 5(6) and PSM 6 is combined witha valve section with ancillary block(coding SL5-A.. acc. to table 12 and19) as otherwise it is not possible tomount a fitting in port R or LS (PSV 5N).

Nominal voltage, see table 3 sect. 3.1.1

For nom. voltage seetable 3 in sect. 3.1.1

5) Other ports LS, M, Z = G 1/4 (DIN ISO 228/1 (BSPP))= 7/16-20 UNF-2B

(SAE 4, SAE J 514)

Coding for 3-way flow controller with raised circulation pres-sure (see sect. 4.2), otherwise similar flow pattern symbol asthe standard version. Intended e.g. for valve spools with increased flow (coding 5 acc. to table 15)

3.1.3 Connection block type PSM

Order example: PSM 6.1F/200 - 5 -...- E5 - G 24

The connection block can be used either for a constant delivery pump or for variable displacement pump system by appropriate external connection. This connection is to be customer furnished. The required pipes and fittings are not part of the delivery.

Table 6: Basic type and port size

Table 7: Coding for additional elements

Symbols (see also sect. 3.1.4)

Circuitry for con-stant deliverypump systems

Circuitry for vari-able displacementpump system

Coding

PSM 6 4)

PSM UNF 6

Tapped ports P, R 5)DIN ISO 228/1 (BSPP)or SAE J 514

Max. pumpdelivery flow(lpm)

G 1 1/4

1 5/8-12 UN-2B(SAE-20)

approx. 300

approx. 300

Coding

no coding

H

Description

Standard (dampening like type PSL)6) 6)

Table 4: Basic type and port size

Coding 1) Tapped ports P and R 2),conf. DIN ISO 228/1 (BSPP)or SAE J 514

Max. pumpdelivery flow(lpm)

G 1

G 1

G 1 1/4

1 5/8-12 UN-2B(SAE-20)

approx. 250

approx. 300

approx. 300

approx. 300

PSV 5 4)

PSV 5 N 3) 4)

PSV 6 4)

PSV UNF 6

PSV 5(6).-5 PSV 5(6)./..-5 PSV..S.-5 PSV..B./..-5 PSV 5N..-PSV UNF6../..-5

Symbols (see also sect. 3.1.3)

6) 3/2-way directional valve is notscope of delivery

Codings for features within the LS-signal duct to dampen thepump flow controllers (For notes and explanation, see sect. 7.1.a).Additional features only suitable where variable displacementpumps are used (limitation of the control oil flow).

Coding Description

S

Standard, no additional feature

Integrated combination of orifice, check valve, pre-load valve (pre-load pressure approx. 25 bar);like standard with type PSL

nocoding

B Orifice # 0.8 mm within LS-duct (to limit control oil flow).

Table 5:

Page 6: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 6

PSL 5(6).1./..-5 PSV 5(6).1.-5 PSV 5 (6)./..-5 PSL..F/..-5 PSL..D/..-5PSL UNF 6.1./.. PSV UNF 6../..-5 (PSV..F/..-5) (PSV..D/..-5)

PSL ...F../..-5 (PSV...F../..-5)

PSL...D../..-5 (PSV...D../..-5)

PSL...PA(PB,PC,PD)/..-5 (PSV...PA(PB,PC,PD)/..-5)

3.1.4 Additional elements for the connection blocks

Order example:

PSL 5. 1F100 /320 -5 -...- E1- G24

PSV 6S.1F /350 -5 -...- E1- G24

Table 8: Coding for control oil supply (for symbol, see sect. 3.1.1 and 3.1.2)

Table 9: Arbitrary idle pump circulation for all consumers by means of 2/2-way solenoid valve acc. to D 7470 A/1.

Coding Description

If not required

With WN 1F, idle pump circulation if valve is de-energized (emergency stop)

With WN 1D, idle pump circulation if valve is energized

With pressure limiting valve, which can be activated as a second pressure stage (specify pressure inbar) (pre-set, pressure tool adjustable from 50 to 400 bar). Example: Type 51F100/350-5..De-energized pmax 100 barEnergized pmax 350 bar

Prop. pressure limiting valve enables variable adjustment of the system pressurePressure ranges: PA = 100 ... 320 bar; PB = 15 ... 250 bar; PC = 18 ... 315 bar; PD = 18 ... 400 bar

no coding

F

D

F...

orD...

PA, PB,

PC, PD

Coding Description

no coding

1

2

Without pressure reducing valve for actuations A, C, or P acc. to table 17 in sect. 3.2., in case of an external controloil supply (min. 20 bar up to max. 40 bar) or via end plate type E7(8) A.. acc. to table 11 in sect. 3.1.5

With integrated pressure reducing valve for internal control oil supply for actuations H(HA).. and E(EA).. or as pick-up for other control valves (max. permissible control oil flow approx. 2 lpm) Control pressure: Coding 1: approx. 20 bar (+ return pressure at R)

Coding 2: approx. 40 bar (+ return pressure at R)

Coding Description

no coding

/...

Version without pressure limiting valve (only type PSV)

With pressure limiting valve at type PSL and PSV, when a pressure specification is added.Non-piloted: PSV 5NPiloted: PSL(V) 5(6), PSL(V) UNF 6

PSM 6 and PSM UNF 6

Symbols

Table 10: Tool adjustable pressure limiting valve for the main pressure. Adjustable from 50 up to 400 bar, after slackening the lock-nut (For symbol, see sect. 3.1.1 and 3.1.2).

Page 7: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 7

E7 E8 E9 E10

E13E13 UNF

E14E14 UNF

E15E15 UNF

E16E16 UNF

ZPL 53ZPL 52

3.1.5 End plates

Order example: PSL 51F100/380 - 5 - 52.. - E1 - G24

Table 11: End plates

External port T (separate re-turn pipe tothe tank)

Internalcontrol oil returngallery 1)

End plate

Standard end plate

With additional inlet port Y e.g. for connecting the LS-control pipe of a subsequent PSV spool valve bank.

Possibility for arbitrary shut-off of the idle pump circulation by means of a directly mounted 3/2-way directional seated valve WN1H acc. to D 7470 A/1

Like E1/E4, but with additional port R

Like E2/E5, but with additional port R

Like E1/E4, but with additional port P

Like E2/E5, but with additional port P

Like E1, however with additionally integrated pressure reducing valve (control pressure: 1 = approx. 20 bar, 2 = approx. 40 bar) 2)

Like E2, however with additionally integrated pressure reducing valve (control pressure: 1 = approx. 20 bar, 2 = approx. 40 bar) 2)

Adapter plate to continue a prop. direct. valve bank size 5 with sections of size 3

Adapter plate to continue a prop. direct. valve bank size 5 with sections of size 2

1) The internal control oil return gallery is to be used only in systemswhere the return pressure is below 10 bar.

2) Similar to control fluid supply via the connection block, see table 8in sect. 3.1.4.Intended for applications, where the control pressure must be main-tained constant (e.g. to achieve a defined switching pressure). Thecontrol pressure is influenced by the back pressure in the returngallery with the standard version, where the control fluid supplytakes place in the connection block.

Order coding of an end plate as individual part (example): SL5 - E1

SL5 - E6 - G 24

SL5 - ZPL 52

Description

Symbols

E4 E5 E6E4 UNF

E7 A1 E8 A1E7 A2 E8 A2

E1 E2 E3E1 UNF

Tapped ports

DIN ISO 228/1 (BSPP)(Standard):T, Y = G 1/4P = G 1R = G 1 1/4

SAE J 514 (E.. UNF):T, Y = 7/16-20 UNF-2B

(SAE-4)P, R = 1 5/16-12 UN-2B

(SAE-16)

E1 E4

E1 UNF E4 UNF

E2 E5

E3 E6

E7 E9

E8 E10

E13 E15

E13 UNF E15 UNF

E14 E16

E14 UNF E16 UNF

E7 A1 ---E7 A2

E8 A1 ---E8 A2

ZPL 53

ZPL 52

Page 8: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 8

3.2 Add-on spool valves3.2.1 Directional spool valve

Order example: PSV 61/380 - 5 - 52 L 160/80 A300 F1 /EA - E1- G24 Order code for single section (examples): Directional spool valve:

SL5-52 J 80/40 F2/EA-G24

Valve spool (individual): SL5 - J 120/40

Attention: Size specification absolutely necessary, here SL5 !The valve spools are subsequently inter-changeable, e.g. if a different flow rating thaninitially planned becomes necessary (seesect. 7.3)

Table 13: Spool valve; basic unit

Coding Basis for max. consumer oil flow

Standard, with inflow controller, for simultaneous load compensated movementof several consumers.

Without inflow controller intended for singularly / successively actuated functions. Ifmore valve sections are actuated, only the one acting against the highest load pres-sure will move proportional to the spool elevation. Additional functions on the con-sumer side are not possible. The max. consumer flow depends on the 3-way flow con-troller in the connection block. For the max. flow of the indiv. section, see table 13.

With inflow controller (for symbol see coding 2) but with reinforced spring at the 2-way flow controller (control pressure approx. 9 bar). Can be used only together withconnection block type PSL.U(Y)H../...-5- or type PSV fed by a variable displacementpump / constant pressure system. See also note in sect. 7.1a.

4/3-way directional spool valve, as pre-selector valve (see also flow pattern symbols page 10)

2

1

5

8 4)

Table 14: Symbols

L M F H J B R OJ, B, R, O, I, Y Z

Valve spool withreturn throttling toassist oscillationdampening, seenote sect. 7.1g)

Table 15: Max. flows P→A(B) acc. to the coding

1) The consumer flow for ports A and B canbe selected freely and independentlye.g. 63/40, 40/80. This allows tailoringthe flow exactly to the respective requirements, while still maintaining thefull functional stroke. Additional there isthe possibility of a stroke limitation.

2) Qnom - flow for coding 2

|pcontroller stand-by-pressure of the flowcontroller of the pumpExample:Qnom = 120 lpm, |pcontroller = 14 bar

QA,B , 200 lpm (guideline)

3) Attention:

A spacer plate type SL5-ZPL55/9 (seesect. 3.2.2) has to be installed right af-ter the connection block whenever typePSL 5(6), PSV 5(6) u. PSM 6 is com-bined with a valve section with ancillaryblock (coding SL5-A.. acc. to table 12and 19) as otherwise it is not possible tomount a fitting in port R

4) Only available with tapped ports G 1(BSPP) i.e. coding is -58 (acc. to table12). Only recommended together withflow pattern coding L and when operat-ed at the top end of the flow range.

Flow coding QA, B (lpm)

at consumer port A and B 1)

16 25 40 63 80 120 160

16 25 40 63 80 120 160

20 32 51 80 110 150 210

Valid for PSL (integrated 3-way flow controller|p + 9 bar) otherwise as guide line

20 32 51 80 110 150 210

See coding 1 (only for port A)

Table 16: Secondary pressure limiting valves, no shock valves (only avail. for spool valves featuring a inflow controller,code numbers 2 and 5 acc. to table 15 !)

Description

Without pressure limitation

Pressure limitation at A with pressure specification

Pressure limitation at B with pressure specification

Pressure limit. at A and B with pressure specification

Common pressure limitation for A and B with pressurespecification

Coding

no coding

A...

B...

A...B...

C...

Pressure limitation pmin = 50 bar; pmax = 400 bar

Example: SL5-52 H120/63 A250 B200/A

see page 9,table 17and 18

controllerratingB,A px2,0xQQ ∆≈

Table 12: Tapped ports A and B

Coding Tapped ports

5 G 1 (DIN ISO 228/1 (BSPP))

A 3) With ancillary blocks acc. to table 19

Valve spoolcoding acc.to table 13

2

1 2)

5

8

Page 9: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 9

Table 17: Functional cut-off (only avail. for spool valves with inflow controller coding 2 and 5 acc. to table 15!)

Description

Without functional cut-off

Electric functional cut-off at A or B

Electric functional cut-off at A and B

Prop. pressure limitation at A or B as well as A and B

Load signal ports U and W (G 1/8 (BSPP)) for externalcircuitry

Common load signal port X for external circuitry (G 1/8 (BSPP))

Coding

no coding

F1, F2

F3

FP1, FP2, FP3

FPH1, FPH2, FPH3 1)

S, S1

X

A residual pressure of approx. 18 bar will remain in the consumer system when thefunctional cut-off or prop .-pressure limitation are deenergized, this pressure willbe approx. 14...17 bar, with version S and approx. 7 bar with version X (always with depressurized return).

Table 18: Possible combinations of the additionalfunctions

Pressurelimitation

no coding

A or B

A and B

C

Additional: F1 ... F3 or FP(H)1 ... FP(H)3

may be combined with X(see page 10 bottom)

Functional cut-off

no S X F1, F2, F3, S1

cod- FP1, FP2, FP3

ing FPH1, FPH2, FPH3

' ' ' '

' ' ' '

' -- ' --

Symbols (example)

Order example:

PSL 51 F/300 - 5 - A 2 H 40/40 C200/EA /5 AS220 BS220 - E4 - G 24

Valve section suited formounting of an ancillary block

Ancillary block

Table 19: Ancillary blocks 3)

Coding

/5

/UNF5

/5 AS... BS...

/UNF5 AS... BS...

/5 AN.. BN..

/UNF5 AN... BN...

/5 AL..

/5 BL..

Brief description

Without additionalfunctions

With shock valves at Aand B (routed to the op-posing side), with pres-sure specification (bar)

With shock and suc-tion valves at A and B,with pressure specifi-cation (bar)

With over-centervalves at A or B (foradditional data, see D 7918 type LHT 5)

Symbols Coding

/5 VV

/5 VX

/5 XV

/5 DRH

/UNF 5 DRH2)

Brief description

With shut-offvalves EM 42Vacc. to D 7490/1(one or both sided)blocking the con-sumer with zeroleakage (Qmax

approx. 160 lpm)

Releasable checkvalves (release ratio1: 2.5)

Symbols

Tapped ports A and B:conf. DIN ISO 228/1 (BSPP) = G 1conf. SAE J 514 = 1 5/16-12 UN-2B (SAE-16)

1) With additional pushbutton for the emergencyactuation (no additional tool needed)

- 6 - A6 - 250 -

Pressure setting

Flow (lpm) / Release ratio

Bypass-throttle D2

Coding A 6 B 6 C 6 D 6 E 6 F 6

(lpm) 250 200 150 100 50 25

0 4 5 6 7 8

Plugged 0.4 0.5 0.6 0.7 0.8Standard

1:6 1:4.26 1:3 1:1.95 1:1.56 1:0.79

Coding

(# mm)

Releaseratio

2) Version with pre-release is available; Coding: /5 DRH VV; For details, see D 6110 type DRH 5

3) Attention: See foot note 3) page 4 or foot note 4) page 5!

Page 10: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 10

4/3-way directionalspool valve withoutinflow controller

.1...

4/3-way directional spoolvalve with inflow controller

.2... (.5...)

4/3-way directionalspool valve utilizedas pre-selector valve

.8...

Standard version

acc. to table 13

With respect to flow con-figuration and actuation,these symbols are neutraland must be supplement-ed by the correspondingflow pattern symbols illus-trated in table 12, 19 or 20see also example in table19 and sect. 6.

Additional function:Secondary pressure limi-tation acc. to table 16 forspool valves with inflowcontroller (no shock valve!).

Example: SL5-52L160/80A300B200F3/EA-G24

..A... ..B... ..A...B... ..C...

Functional cut-off, acc. totable 17, for spool valveswith inflow controller.

Possible combinations:

..S (S1)

A..SB..SA..B..S

..X

A..XB..XA..B..X

..F1, FP1, FPH1 (X)

A..F1, FP1, FPH1 (X)B..F1, FP1, FPH1 (X)A..B..F1, FP1, FPH1 (X)

..F2, FP2, FPH2 (X)

A..F2, FP2, FPH2 (X)B..F2, FP2, FPH2 (X)A..B..F2, FP2, FPH2 (X)

..F3, FP3, FPH3 (X)

A..F3, FP3, FPH3 (X)B..F3, FP3, FPH3 (X)A..B..F3, FP3, FPH3 (X)

here type F1 here type FP2 here type F3

Page 11: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 11

1) Application examples for actuation H.. or F...

Remote control by control pressure reducing valve FB2/18 or KFB2/18 acc. to D 6600 or see sect. 7.1 c.Attention: The hydraulic actuation type FA (FEA) instead of HA (HEA) has to be used, when ancillary blocks with additional functions acc. to table 19 are selected.The difference between actuation HA and FA is the orientation of the control ports.

2) Prepared for retrofitting of a solenoid actuation

3) Version TH with additional pushbutton for the emergency actuation (no add. tool is needed)

4) Plug is not scope of delivery

5) Attention: Observe notes and example circuit drawings in sect. 7.6; Also available version HE (FE) - (solenoid and hydraulic actuation)

Table 21: Additional features for the actuations

Type of actuation/ coding

A, EA, E0A, HA,PA, C

E, EA, E0A, HEA

A, EA, C

E, EA, HEA

Suffix

1

T

TH 3)

G

B 4)

Description

Manual actuation without hand lever

The additional manual emergency actuation of the solenoidfor the integrated prop. pressure reducing valves is not avail-able in combination with suffix B (quarter-turn plug).

ET, EA1T, HEATH

EA1GS, CG, A1GS

EB, EABS, EA1B

EA1, C1

Example

Table 20: Types of actuation (for further explanations, see sect. 4.3)

Nomenclature

Manipulated variables

Manual actuation Electro-hydraulic actuation

Hydraulic actuation 1) Pneumatic actuation

Spring return

Detent Purelyelectro-hydraulic

In comb.with manualactuation

Purelyhydraulic

In comb.with manualactuation

In comb. withsolenoid andmanual actuation

Actuation angle min. approx. 5°max. approx. 30°

A C E EA

E0A 2)H HA

FA

HEA 5)FEA

P

PA

Coding andsymbols

Control current ratio I/INmin. approx. 0.2max. approx. 1

Control pressure (bar)min. approx. 5max. approx. 18

Control pres-sure (bar)min. appr. 2.5max appr. 6

Note: Approximate figures for start of flow (= min) at A or B up to the max. consumer flow according to the flow codingtable 15, see curves sect. 4.2.

Reinforced version of the spring cover, intended when high pressuresurges are expected in the T-line.

Solenoid with quarter-turn connection (quarter-turn plug PA 6, Co. Schlemmer D-85586 Poing, suited for taperwith quarter-turn design 10 SL). It is not available in combination with suffix T and TH (manual emergency actuation)

Page 12: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 12

Coding

ZPL 5 S/H

ZPL 5 V/E

Brief description

Shut-off valve for arbitrary blockage of the pump galleryfor all subsequent consumers. This shut-off valve is eitheropen (S) or closed (V) while deenergized. Actuation is hydraulically (/H) or via solenoid (/E).Main application is where one or more consumers haveto be blocked e.g. due to safety or functional reasons.

pswitch % 12 bar (pmax S = 400 bar)

ZPL 5 P6 R6 Additional pump and return port G 1 1/4 (BSPP)

ZPL 55/9 Spacer plate (9 mm) between connection block and firstvalve section, necessary when equipped with an ancil-lary block with additional functions (acc. to table 19),see also footnote 3) page 4 and footnote 4) page 5.

3.2.2 Intermediate plate

Order example: PSL 51/250-5 -32 H 63/40 /EA

-ZPL 5 S/H

-32 L 25/16 /EA-E4-G24

ZPL 5 S/H ZPL 5 V/E

ZPL 5 P6 R6 ZPL 55/9

Symbols

Table 22: Intermediate plate

Directional seatedvalve type WN1H acc. to D 7470A/1

Page 13: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 13

4. Further characteristic data

Nomenclature

Design

Mounting

Installation position

Ports

Port size

Surface treatment

Mass (weight) approx.

PSL, PSV, or PSM see sect 3.1

Spool valve, bankable, up to 10 spool valve sections, all-steel design

Valve bank: M10; see dimensional drawings in sect. 5 ++

Arbitrary

4.1 General and hydraulic

4/3-way directionalspool valve:

Standardversion

With additional functions

Actuations A, E, H, P, E0A EA, HA, PAHEA

3.7 kg4.1 kg4.6 kg

A .. C, S

3.7 kg4.1 kg4.6 kg

A .. B .. F(P, PH)1(2,3)

4.1 kg4.5 kg5.0 kg

Pressure fluid

Temperature

Rec. contamination class

Pressure

Hydraulic fluid acc. to DIN 51524 table 1 to 3; ISO VG 10 to 68 acc. to DIN 51519Viscosity range: min. approx. 4; max. approx. 1500 mm2/secOptimal operation range: approx. 10...500 mm2/secAlso suitable are biologically degradable pressure fluids of the type HEPG (Polyethyleneglycol) andHEES (synthetic ester) at operation temperatures up to approx. +70°C.HETG (rape seed oil) is not suited!

Ambient: approx. -40...+80°C (Attention: Explosion-proof versions approx. -40 ... +40°C)Fluid: -25 ... +80°C, pay attention to the viscosity range! (Attention: Explosion-proof versions approx. -25 ... +70°C)

Restriction for version with ex-proof solenoid:

Ambient: max 40°C; Fluid: max 70°CStart temperature down to -40°C are allowable (Pay attention to the viscosity range during start!),as long as the operation temperature during subsequent running is at least 20K (Kelvin) higher.Biological degradable pressure fluids: Pay attention to manufacturer's information. With regard tothe compatibility with sealing materials do not exceed +70°C.

ISO 4406 18/14

pmax = 400 bar (6000 psi); Ports P, P1, A, B, LS, M, Y

The max. pressure achievable a t the consumer side of the spool valves is lowered by the amount,equivalent to the internal control pressure drop at the 3-way flow regulator of the PSL (see curves)or at the pump controller (PSV). Return ports R(R1) are rated ≤ 20 bar (50 bar with enforced springhousing, table 21. It is recommended to employ end plate E1, E2, E3, etc. with an additional leak-age port, in case return pressure > 20 bar is anticipated. Port T pressureless via a separate pipe(e.g. 6x1) to the tank, port Z approx. 20 (similar to coding table 8) (outlet); ≤ 40 bar (inlet)

For control pressure, see Q-I-characteristics. The internal control oil circuit is sufficiently protected against malfunctions caused by contamina-tion by means of a gap filter.

Max. consumer flow 16 ... 160 (210) lpm or acc. to table 15 in sect. 3.2.1.

Ancillary /(UNF) 5 = 1.5 kgblocks: /(UNF) 5 AS.. BS.. = 2.4 kg

/(UNF) 5 AN.. BN.. = 2.3 kg/5 AL.., /5 BL.. = 3.4 kg/5 VV(VX, XV) = 2.4 kg/(UNF) 5 DRH = 2.3 kg

Intermediate ZPL 3 S/H = 5.0 kgplates: ZPL 3 V/E = 5.0 kg

ZPL 3 P6 R6 = 5.9 kgZPL 53 = 2.6 kgZPL 52 = 2.6 kgZPL 55/9 = 0.7 kg

P = Pressure inlet (pump) / lead-onR = ReturnA, B = Consumer portsF = Pressure resistant returnU, W, X = Load-signal outlet at the indiv. spool

valve sectionLS, DW = Load-signal outlet e.g. connection to

the pump controller with PSV. Attention: No pressure input!

M = Pressure gauge port (pump side)

Z = Pilot pressure port (20...40 bar inlet, 20 bar outlet)

T = Control oil return portY = Load-signal inlet port

End plate E2, E5, E8, E10,E14(UNF) and E16(UNF)

P, R, A, B, F = Acc. to type coding (see sect. 3.1)M, LS, Z, T, Y, DW = G 1/4 (DIN ISO 228/1 (BSPP)) or

7/16-20 UNF-2B (SAE-4, SAE J 514)U, W, X = G 1/8 (DIN ISO 228/1 (BSPP))

All surfaces corrosion-inhibiting, gas nitridedSolenoid at actuation E.. and additional functions F1...F3, FP1...FP3, FPH1...FPH3: are zinc galvanized and olive passivatedHousing with actuation P and PA: Anodized.

Connection PSV 5(6) = 4.5 kg 1) End plates: E1, E2, E4, E5 = 2.5 kgblock: PSV 5(6)./.. = 7.7 kg 1) E1(4) UNF = 2.5 kg

PSM 6 = 4.5 kg 1) E3, E6 = 3.1 kgE7 to E16 UNF = 3.0 kg

1) + 0.6 kg for versions with WN1F(D), PA ... PD E7 A1(2), E8 A1(2) = 2.5 kg

Control circuit

Flow

Page 14: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 14

4.2 Curves

Oil viscosity during measurement approx. 60 mm2/sec

Connection block

Pressure limiting valve Type PSL: Circulation pressure P → R(F)

Input / consumer flow curve(Guideline, example directional spool valve with inflow controller type SL5-52../..)

Control current I (A) 24V DC

Control current I (A) 12V DCControl pressure (bar)hydraulic actuation H, F

Hand lever angel (o)manual actuation A, C

Flow coding (acc. to table 15)

Flow coding (acc. to table 15)

Co

nsu

mer

flo

w Q

A(B

)(lp

m)

Co

nsu

mer

flo

w Q

A(B

)(lp

m)

Directional spool valve section

2-way inflow controller Back pressure (full elevation)

Secondary pressure limiting valvesCoding A.. B..; C.. acc. to table 16 in sect. 3.2.1

Pre

ssure

set

ting

(bar

)

Bac

k p

ress

ure

|

p (b

ar)

Pre

ssure

set

ting

(bar

)

Bac

k p

ress

ure

|p

(bar

)

Co

nsu

mer

pre

ssure

(bar

)

Pump delivery flow Q (lpm)

Pump delivery flow Q (lpm)

Flow Q (lpm)

Flow Q (lpm) Flow Q (lpm)

Prop. pressure limiting valveCoding PA ... PD acc. to table 9, sect. 3.1.4Coding FP(H)1, FP(H)2, FP(H)3 acc. to table 17 in sect. 3.2.1

Pre

ssure

set

ting

(bar

)

Control current I (A)

A(B) →R

(valve spool L,M,F,H)

Page 15: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 15

Actuating moment [Nm]Idle position End position

Version A approx. 3.0 approx. 7.5Version HA, HEA, PA approx. 5.0 approx. 16.5Version EA, E0A approx. 3.0 approx. 12.0

Version with detent, fixation of the valve spools at any desired position (idle position with special notch)

Proportional solenoid, manufactured and tested acc. to VDE 0580Twin solenoid with armature chambers sealed to the outside and internally connected to the return duct. Thereby the armature is maintenance-free lubricated and protected against corrosionby the hydraulic fluid.

4.3 Actuations

For other data, such as codings, symbols etc., see sect. 3.2

Actuation A

Actuation C

Actuation E, EA, (HEA)

I - Stroke curve

Oil viscosity during measurementapprox. 60 mm2/s

Explosion-proof version ofactuation E, EA, (HEA)(Voltage specification G 24ex)

Attention:

Observe operating manual B 01/2002!

Not in combination with func-tional cut-off F(FP).. (table 17)or all other solenoids mount-ed on connection blocks (table 9),ancillary blocks (table 19),intermediate plates (table 22)and end plates (table 11)

Certificate of conformity TÜV - A02 ATEX 0007 XEx-proof level EEX m II 120°C (T4), (conforming EN 50 014 + EN 50 028)Duty cycle (ED) 100% ED, one coil energized per solenoid housingProtection class IP 65 (conforming DIN VDE 0470/EN 60529/IEC529)Nom. voltage UN 24V DC

Current, cold I20 0.88 A

Lim. current IG (Ilim) 0.63 A

Power, cold P20 21.5 W

Lim. power PG 10.8 W

Residual ripple of the 15%supply voltageConditions of use:Max. ambient temperature 40°CMax. fluid temperature 70°CEach solenoid must be safe guarded by a fuse, conf. IEC 127 or DIN 41571, IF < 1.8 A (medium)

Surface coating Housing zinc galvanized Coil and connection cavity are moulded

Attention: Do not expose to direct sun light (shielding is required)!Electrical lay-out and test procedures conforming EN 50014, VDE 0170/0171 T1 and T9Electrical connection 4 x 0.5 mm2

Cable length 3m (cable ÖLFLEX-440P)For connection scheme, see above “Actuation E, EA”(standard version).

Additional notes:

See also Sk 7814, as well asfor additional componentssect. 7.5.1!

Actuation H.., H

Actuation P, PA

Control pressure approx. 5 bar (start of stroke)approx. 18 bar (full stroke) Max. permissible pressure 25 bar (50 bar for enforced version)

The remote control lines to control port 1 and 2 have to be piped externally. Supply is via proportional piloting valve e.g. type FB 2/18 etc. or KFB 2/18 (both acc. to D 6600).

Control pressure approx. 2.5 bar (start of stroke)approx. 6 bar (full stroke)

Rated voltage UN 24V DC 12V DCCoil resistance R20 27.2 Ω 6.7 ΩCurrent, cold I20 0.88 A 1.8 ALim. current IG (Ilim) 0.63 A 1.26 APower, cold P20 = UN x I20 21 W 22 WLim. power PG = UN x IG 10.8 W 10.6 WCut-off energy WA ≤ 0.3 Ws ≤ 0.3 WsRel. duty cycle (ED) 100% 100%(reference temp. 11 = 50°C)Protection class (assembled) IP 65 (DIN EN 60529 /

IEC 60529)IP 67 (coding EB, EAB)

Required dither frequency 40...70 Hz(best 55 Hz)

Dither amplitude 1) 20% ≤ AD ≤ 35%Electr. connection DIN 43650A

Circuitry Coil a Coil b

1) 100⋅= −

G

peakpeakD

I

I(%)A

Actuation EB, EAB

1 2

3

Quater-turn plug PA 6

Control current I/IN

Sp

oo

l str

oke

Page 16: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 16

4.4 Functional cut-off

On/Off solenoid with manual emergency actuation

Rated voltage UN 24V DC 12V DC

Coil resistance, cold R20 34.8 Ω 8.7 Ω

Current, cold I20 0.68 A 1.38 A

Current, hot I70 0.48 A 0.97 A

Rated performance PN = UN x I20 16.6 W 16.6 W

Rel. duty cycle 100% 100%

(reference temp. 11 = 50°C)

Protection class (assembled) IP 65 (DIN EN 60529 / IEC 60529)

Electrical connection DIN 43650A

Cut-off energy WA ≤ 0.3 Ws

Circuitry Coil b Coil a

Functional cut-off

Prop. solenoid with manual emergency actuation. For circuitry, see functional cut-off and forelectrical data, see actuation E, EA

Prop. pressure limitation

Page 17: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 17

5. Unit dimensionsAll dimensions are in mm and are subject to change without notice!

5.1 Connection blocks and end plates(For dimensions of the adapter plate, see page 21)

Type PSV 5.(F,D) - 5

PSV 6.(F,D) - 5

Type PSV 5N see sect. 7.7

Directional spool valvesections, see sect. 5.3 ++

For missing dimensionsof the end plates, seesect. 5.2

Directional seated valve WN1F(D) 1)e.g. PSV 51F-5

Without WN1.. e.g. PSV 6-5

1) Version with pressure limiting valve, which can be arbitrarilyactivated e.g. PSV...F(D) 300-5 see bottom of page 18.

Tapped ports conf. DIN ISO 228/1 (BSPP):

P and R = G 1 (type PSV 5...)= G 1 1/4 (type PSV 6...)

M, LS and Z = G 1/4

Tapped ports conf. SAE J 514:

P and R = 1 5/8-12 UN-2B (SAE-20)

LS, Z, M = 7/16-20 UNF-2B (SAE-4)

Intermediateplate ZPL 55/9

PSV 5 38.5

PSV 6 36.5

b

Page 18: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 18

Type PSV 5(6) ../.. -5

PSL 5(6).(F, D)/...-5

PSM 6.(F, D)/...-5

Directional seated valveWN1F(D) e.g. PSL 51F/350-5

Version with pressure limitingvalve, which can be arbitrarily activated (see below).

Without WN1..e.g.PSV61/300-5

For missing dimensionsof the end plates, seesect. 5.2

PSV 5./., PSL 5./.

PSV 6./., PSL 6./.PSM 6./.

PSV UNF 6./.PSL UNF 6./.PSM UNF 6./.

Directional spoolvalve sestions,see sect. 5.3 ++

Pressure limiting valve(a/f 12, a/f 13)

a b

22 75

26 74

26 72Version with pressure limiting valve, which can be arbitrarily activated(see table 9) e.g. PSL 51F80/320-5

Tapped ports conf. DIN ISO 228/1 (BSPP):

P and R = G 1 (type PSV(L) 5..)= G 1 1/4 (type PSV(L) 6..)= G 1 1/4 (type PSM 6..)

M, LS, and Z = G 1/4DW = G 1/4 (type PSM 6..)

Tapped ports conf. SAE J 514:P and R = 1 5/8-12 UN-2B (SAE-20)LS, Z, M = 7/16-20 UNF-2B (SAE-4)

Intermediate plateZPL 55/9

Version with pressure limiting valve (see table 9) e.g. PSL 51PA (PB, PC, PD)/350-5

Page 19: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 19

Type PSL 5(6) U..(F, D)/.. - 5

PSL 5(6) UH..(F, D)/.. - 5

Type PSL 6 Y ..(F, D)/.. - 5

PSL 6 YH ..(F, D)/.. - 5

Directional seatedvalve WN1F(D) 1)e.g. PSL 6 UH1F

For missing dimensionsof the end plates, seesect. 5.2

For missing dimensions of theend plates, seesect. 5.2

Directional spool valves,see sect. 5.3 ++

Directional spool valves,see sect. 5.3 ++

Directional seated valveWN1F(D) e.g. PSL 6 Y1F/380-5

Without WN1..e.g. PSL 6 YH1/320-5

Without WN1..e.g. PSL 5U1/320-5

View from bottom islike illustrated above!

1) Version with pressure limiting valve,which can be arbitrarily activated (seebottom of page 18).

Pressure limiting valve(a/f 12, a/f 13)

Tapped ports conf. DIN ISO 228/1 (BSPP):P and R = G 1 (type PSV 5..)

= G 1 1/4 (type PSV 6..)M, LS, and Z = G 1/4

Tapped ports conf. DIN ISO 228/1 (BSPP):P, R, and F = G 1 1/4 M, LS, and Z = G 1/4

PSL 5 U 22 75.5

PSL 6 U 26 74

a b

Page 20: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 20

End plate

E13 to E16

E13 UNF to E16 UNF

End plate E7 to E10

E7 A1, E7 A2

E8 A1, E8 A2

Tapped ports

conf. DIN ISO 228/1 (BSPP):R = G 1 1/4 (E 7 to E 10)P = G 1 (E 13 to E 16)T = G 1/4 (E 1 to E 16)Y = G 1/4 (E 2, E 4 to E 16)

conf. SAE J 514:P, R = 1 5/16-12 UN-2B (SAE-16) (E13 UNF to

E16 UNF)T, Y = 7/16-20 UNF-2B (SAE-4) (E1 UNF, E4 UNF)

Port T is plugged with version E9 and E10

For missing specifications see above!

For missing specificationssee above!

Port Y is pluggedwith version E13,E13 UNF, E15,and E15 UNF

Port T is plugged with versionE15 (UNF) and E16 (UNF)

Port Y isplugged withversion E7,E9, and E7 A1(2)

Type E3 and E6 Directional seatedvalve type WN 1 H

Type E1, E2, E4 and E5

E1 UNF and E4 UNF

Port Y isonly appar-ent with E2and E5 !

a/f 19 max. torque 60 Nm

M10, 10 deep

Port T isplugged withversion E4,E4 UNF, andE5!

Port T ispluggedwith version E6

For missing specificationssee above!

5.2 End plate

M10, 10 deep

M10, 10 deep

M10, 10 deep

Page 21: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 21

5.3 Directional spool valves with manual actuation A, C

Switching position

Switching position

Hand lever can alsobe mounted here.Thread. M8,15 deep

Elevationstop inter-mediateplate

Travel stopfor flowlimitation at A

Travelstop forflow limitation at B

Endplateside

Connectionblock side

Later angling of the lever housing and/or exchanging the valve spools is possible, see sect. 7.3.

Port B is omitted with coding 58 (table 12, 13)

Contour ofthe add-onspool valvesize 5

Contour of the add-onspool valve size 3(acc. to D 7700-3)

Contour of the add-onspool valve size 2(acc. to D 7700-2)

Adapter plate type ZPL 53 Adapter plate type ZPL 52

M 10, 10 deep

M 10, 10 deep

app

rox.

228

Page 22: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 22

5.5 Directional spool valves with actuation H, HA, and HEA

Actuation Type HTravel stop for flow limitation at A

At typeHA

Travel stopfor flow limi-tation at B

Tapped ports 1 and 2:= G 1/4 (DIN ISO 228/1 (BSPP))= 7/16-20 UNF-2B

(SAE-4, SAE J 514)

1) Lever housing at EA and HA(FA) can be angled at 180° in the samemanner as described at sect. 7.3

2) This dimension depends on the manufacturer of the plug and can be upto 50 mm depending on the max. permissible size acc. to DIN 43560.

For elevationstop, see sect.5.3 manualactuation A etc.

ActuationType EA, E0A 1)

Travel stopfor flowlimitation at A

Actuation Type E

Plug canbe angledby 180°

Travel stop for flowlimitation at B

For elevation stop,see sect. 5.3 manual actuation Aetc.

5.4 Directional spool valves

with actuation EA, E0A, E

Actuation Type EB and EAB Type ET, EAT, ETH, and EATH

Quarter-turnplug PA 6

With type E0A.-.: Tapped plug (Z 7709 047, complete withO-ring 12.42x1.78 HNBR 90 ShO-ring 9x1.5 NBR 90 Sh and O-ring 7625 109/1)

Solenoid withactuation typeHEA..

Manual emer-gency actuation

Pushbuttoncoding TH

approx.38.5 2)

ActuationType HA, HEA, FA, FEA 1)

At typeFA

app

rox.

58

app

rox.

63

app

rox.

63

app

rox.

77

Page 23: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 23

5.6 Directional spool valves with actuation P, PA

Actuation Type P Actuation Type PA

Tapped ports 1 and 2:G 1/8 (BSPP)

For elevationstop, seesect. 5.3 manual actu-ation A etc.

Travel stop forflow limitationat A

Travel stop for flowlimitation at B

5.7 Ancillary blocks

Type /5

/UNF 5

Add-on spool valvesections acc. to 5.3

Socket head screwsISO 4762-M10x40-A2-70;max. torque 40 Nm Tapped ports A and B :

/5.. = G 1 (DIN ISO 228/1 (BSPP))/UNF 5.. = 1 5/16-12 UN-2B (SAE-16, SAE J 514)

app

rox.

120

app

rox.

77

Page 24: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 24

Type /5 AS.. BS..

/UNF 5 AS.. BS..

/5 AN.. BN..

/UNF 5 AN.. BN..

Socket head screws ISO 4762-M10x60-A2-70max. torque 40 Nm

Socket head screws ISO 4762-M10x60-A2-70max. torque 40 Nm

Socket head screws ISO 4762-M10x70-A2-70max. torque 40 Nm

Socket head screws ISO 4762-M10x70-A2-70max. torque 40 Nm

Type /5 AL..

Type /5 BL..

Type /5 VV(VX, XV)

Shut-offvalve typeEM 42V isomittedwith /5 XV

Max.torque 60 Nm

Shut-off valvetype EM 42Vis omittedwith /5 VX

Tapped ports A and B:

/5.. = G 1 (DIN ISO 228/1 (BSPP))

/UNF 5.. = 1 5/16-12 UN-2B (SAE-16, SAE J 514)

Pressure adjustmentA-side with type /..AS.. BSB-side with type /..AN.. BN

Pressure adjustmentB-side with type /..AS.. BSA-side with type /..AN.. BN

Continuation section 5.7 ancillary blocks

app

rox.

32 ap

pro

x. 8

2ap

pro

x. 8

2

app

rox.

76

app

rox.

76

Page 25: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 25

5.8 Intermediate plates type ZPL 5...

Port S is pluggedwith type ZPL 5 S(V)/E

Tapped ports

/5 DRH = G1 (DIN ISO 228/1 (BSPP))

/UNF 5 DRH = 1 5/16-12 UN-2B (SAE-16, SAE J 514)

Tapped portsDIN ISO 228/1 (BSPP):

S = G 1/4

P and R = G 1 1/4

Type ZPL 5 S(V)/H

Type /5 DRH

/UNF 5 DRH

Type ZPL 5 S(V)/E Type ZPL 5 P6 R6

Continuation section 5.7 ancillary blocks

Socket head screwsISO 4762-M10x70-A2-70max. torque 40 Nm

Page 26: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 26

5.9 Spool valves with secondary pressure limitation, functional cut-off and prop. pressure limitation

Type A... Type B... Type A...B... Type C...

Type S Type X

Type S1

Tapped ports U, W, and X = G 1/8 (BSPP)

For missing data (directional spool valvesand actuations) see section 5.3 to 5.6!

Type F1 to A...B...F3...

FP1 to A...B...FP3

FPH1 to A...B...FPH3

Pushbutton (manual emergencyactuation) with type FPH..

Connec-tionblockside

Endplateside

Manual emer-gency actuation

P→B P→A

approx. 58

app

rox.

68

Page 27: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 27

6. Circuit examples

Example 2:

The diagrams show a typical valve bank for cranes with hydraulic control.

Control by PSL; supply of pressurizedoil by constant delivery pump

PSL 51/300 - 5 - 52 L 120/120 C200 /A

- 52 L 40/63 A100 F1/EA

- 52 H 120/63 F3/A

- 51 M 40/80 /A-E1-G 24

to the consumer 2e.g. lifting

to the consumer 1e.g. swiveling

to the consumer 3e.g folding

to the consumer 4e.g. supporting

Connection blockPSL 51/300-5-

Add-on spool valves 5 2L 120/120 C200/A

Add-on spool valves5 2L 40/63 A100 F1/EA

Add-on spool valves5 2H 120/63 F3/A

Add-on spool valves51M 40/80/A

End-plateE 1

Control by PSV; Pressurized oil supply by variable displacement pump without pressure limiting valve,but with solenoid valve for arbitrary idle pump circu-lation.Only difference to example 1 is the connection blockwith similar versions and arrangement of the add-onvalves.

PSV 51F- 5 - 52 L 120/120 C200/A

- 52 L 40/63 A100/EA

- 52 H 120/63 F3/A

- 51 M 40/80 /A-E1-G 24

Example 1:

Page 28: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 28

a) The connection block

There are additional damping variations available for the LS-signal duct (type PSV, coding S or B) listed in table 2 and 5 (apartfrom the standard versions acc. to sect. 3.1.1 and 3.1.2). These are required, if strong (load-) oscillations are externally inducedon the control circuit. However, a general rule concerning the use of the one or the other variation can not be given.

To coding G

This version lacks the sequence valve at the damping element which is apparent at the standard version to enable quick depressurization down to the pre-load pressure during idle position of the valve spool. This results in a stronger damping effect than with the standard version, as all fluid from the spring cavity of the 3-way flow controller must pass the thread typethrottle. Main application is with consumers prone to low-frequent oscillations - drawback is the delayed depressurization downto the pre-load pressure during idle position of the valve spool (pro-longed run-down).

To coding H

When on account of the required consumer velocity at least one spool valve with reference number 5 (raised circulation pressure) isutilized, then, in order to maintain the necessary pressure difference between 2- and 3-way flow controller, the circulation pressure ofthe 3-way flow controller must be raised to approx. 14 bar. This means, of course, greater power dissipation.

To coding U (or UH)

The pump idle circulation pressure is reduced by means of an additional by-pass valve, if all directional spool valves are in idleposition (see also curves in sect. 4.2). The valve opens automatically if the occurring load pressure (LS pressure) drops below25% of the (still remaining) pump pressure.Attention: A minimum pump delivery flow of approx. 150 lpm must be maintained for electro-hydraulic actuation with internal control oil supply. The control pressure (& pump circulation pressure) is not sufficient for elevating the spool at lower deliv-ery flows. Load pressure must be min. 20 bar.

To coding UH

The control pressure of the 3-way flow controller must be raised by approx. 15 bar to ensure a pressure difference between 2- and 3-way flow controller if at least one directional spool valve coding 5 (increased circulation pressure) is used due to the required consumer velocity. An increased dissipation power of the control system is obliged with this. The by-pass valve (seecoding U) is therefore integrated as standard to minimize pressure losses during idle pump circulation.

To coding Y, YH

Additional, pressure resistant port F for the excess oil from the 3-way flow controller. This enables to control separately located consumers by making use of the excess delivery flow not consumed by the prop. directional spool valve bank. When connecting two valve banks type PSL in series, it is necessary to employ version YH for the first one to maintain a sufficient pressure drop required for a flawless control function.

b) To the spool valve sections

To coding 1 (example SL5-51 L 120/63...)On the one hand, there is a higher consumer flow with directional spool valves without an inflow controller (coding 1) in compar-ison with one having a 2-way flow controller (coding 2, 5), as the flow is then directly dependent on the control pressure of eitherthe connection block's 3-way flow controller (type PSL approx. 10 bar), or the metering valve of a variable displacement pump(approx. 14 to 20 bar) for type PSV. On the other hand, the load-independence is lost, if several consumers are actuated simul-taneously, because the consumer with the highest load pressure rules the pressure level of the LS-signal given to the 3-way flowcontroller and therefore defines the available flow in the system. As soon as another valve with higher load pressure is actuatednow, the flow for the first consumer can only be regulated by throttling, i.e. if the highest load pressure varies, the spool elevation(= throttling) of the first valve section has to be reset to maintain a constant delivery flow to the consumer. This consumer flow canbe calculated approximately by:

To coding 2 (example SL5-52 0 63/63...)The standard version of the spool valve section is load compensated and is equipped with an inflow controller (coding 2). Due tothe control pressure of the inflow controller (approx. 6 bar), it regulates a constant flow related only to the spool elevation (groove edges at the spool act like a metering orifice), making its delivery independent of other consumers or system pressure:

To coding 5 (example SL5-55 H 160/80...)This version features an increased control pressure enabling higher consumer flows (see also above coding 1 and 2). The pressure of this flow controller (coding 5) is approx. 9 bar resulting in a 1.25 higher flow when compared to the standard version (coding 2).It makes only sense to use this version for flow codings higher than 160, as a higher control pressure causes higher losses aswell!

c) Variations for special operation conditions or requirements

Operation at potentially explosive areas

Variation: - Hydraulic actuation (type H, HA or HEA) - Pneumatic actuation (type P or PA)- Electro-hydraulic actuation (type E and EA) in a explosion-proof version, conforming EEX m II T4.

Order coding: G 24ex (see also section 4.3)

Maritime ambient climate

The aggressive sea atmosphere requires sufficient corrosion protection of all moving part of the actuations with hand lever. Theactuation shaft in the hand lever housing is therefore made of stainless steel as standard. All other parts are either corrosion inhibiting gas nitrided or made of stainless steel (exception: Housing of pneumatic actuation P or PA which is made ofanodized light alloy).

7. Appendix7.1 Notes for selection and lay-out of:

controllernomB,A p,QQ ∆⋅⋅≈ 20

springpQ ∆≈

Page 29: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 29

Pressure surges in the return duct

A return pressure of approx. 50 bar is approved (see sect. 4.1). At higher return pressure no guarantee for the reliability of the actuation solenoids can be given!.

d) Use of variable displacement pumps

With Load-sensing controls in alliance with variable displacement pumps, the LS-signal duct for the pump pressure/flowcontroller (Load-Sensing metering valve) is relieved, to minimize circulation losses during idle position (no consumer flow ). Thisrelieve takes place via the proportional spool valve sections. The pump would have to work during no-lift position with all the remaining flow against the pressure set at the safety valve of the pressure regulator without this decompression.As there exist spool valves without this limiting possibility at the market, some brands of pressure/flow controllers feature aninternal bypass orifice or throttle between LS-signal entrance and decompressed leakage outlet.In case of the prop. spool valves type PSV this is not necessary and can even cause malfunctions due to loss of control oil. The control oil flow is consciously limited (approx. 2 lpm) for functional reasons (slow-motion of the consumer).Attention: Care must therefore be taken, to ensure that a possible bypass orifice in the pressure/flow regulator is plugged!Example: Pressure/flow regulator of manufacturer Mannesmann Rexroth, Brueninghaus Hydraulik; Type DFR1 (orifice plugged)should be used instead of type DFR (with orifice).

e) Combination with load-holding valves

It can happen due to exterior variations of load and resonance that the control system starts to oscillate, if three regulation devices, the 3-way flow controller of the pump or the connection block, the 2-way flow controller at the spool valve section andthe load holding insert are connected in series. This can be effectively suppressed by systematic use of a bypass orifice and acombination of throttle, check valve and pre-load valve within the control oil circuit at the load-holding valve type LHDV acc. toD 7770. A similar behavior can be achieved with over center valves type LHT acc. to D 7918.

f) Combination of more than 10 spool valves

A total of max. 10 spool valves can be linked, via a consecutive connection of the LS-signal duct. It is irrelevant, whether the spoolvalves are arranged in one or more valve banks. This restriction is caused by the limited oil flow being available (ensuring slow-motion movements). A chaining via external shuttle valves is to be used, if more than 10 spool valves in separated directionalspool valve banks are to be coupled via the LS-signal.

g) Flow pattern symbol variants

Flow pattern symbol J, B, R, O, and I, Y, ZOscillations may occur depending on application during start (e.g. winches) or during normal operation (e.g. crane booms). Theycan be caused by the natural frequency of the hydraulic motors or external load variations e.g. swinging load. The flow coding(table 15) of the respective spool should correspond to the cylinder ratio as far as possible.

7.2 Seal kits

Connection block DS 7700-51

Valve section DS 7700-52

In addition for pneumatic actuation DS 7700-53

Intermediate plate ZPL 53 DS 7700-32

Intermediate plate ZPL 52 DS 7700-22

Note: This listing of components coversonly the most essential ones, someother seals e.g. soft iron rings etc.(acc. to spare parts lists E 7700 ++)have to be added.

Symbols Description Application

J, B, R, O Creation of a back pressure of approx. 20bar at 1/3 spool lift and more.

When combined with over-centervalves e.g. for boom controls

I, Y, Z Creation of a back pressure of approx.100 bar for up to 1/3 spool lift.

Hydraulic motors (because of pressurerise due to area ratio 1:1),e.g. with cabin slewing

SymbolsI, Y, Z

Symbols

I Y Z

SymbolsJ, B, R, O

Qmax A, B

|pA(B)-R

Page 30: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 30

7.3 Notes on changing the spool

The valve spools arenot matched to onespool housing. There-fore valve spools canbe changed at anytime to adapt to alteredconsumer consump-tion. See notes on changingthe spool: Connec-

tion blockside

Endplateside

Lever housingangled at 180°

Controlgrooves

Notes on changing the valve spool

1. Slacken screws ; (ISO 4762-M6x8-8.8-A2K), remove spring cover

2. Remove screw < (M 6x40, flat head screw DIN 7991)

3. Remove spring assembly including spring cap =4. Slacken screws > (ISO 4762-M6x60-8.8-A2K)

5. Lift lever housing including spool out of spool housing, drawing ?@6. Remove lock washer DIN 6799-3.2 and bolt AB7. Assemble with (new) spool in reverse sequence

Note: The control grooves of the valve spool always have to direct towards the end plate (installed state)Exeption: Valve spools with flow coding 160 do not have control grooves.

Indications for angling the lever housing by 180° (inversion of the shifting mode)

As set out in points 1 to 7 above, however instead of a new valve spool the existing one has to be disconnected, angled at 180° and

remounted (see above mentioned note). The intermediate plate C, together with the lever housing, have to be angled at 180°.

7.4 Notes for converting the connection block

The connection blocks type PSL 5(6)...-5 and PSL UNF 6..-5 can be converted any time into a connection block for variable displacement pump systems (correct type then PSV 5(6) S../..-5 or PSV UNF6 S). This requires replacing the parts listed below.

Attention: The screw (part No. 6380 013) D or SOLEX carburetor jet M4x0.6 E are secured with Loctite. Loctite (or similar) must

be applied again when replacing these parts.

This conversion cannot be carried out at the type PSL 5(6) U(H) and PSL 6Y since the integrated valve combination forbids a combination with variable displacement pump systems.

It is necessary to replace the tapped plug by the damping screw (7778 301) F, while converting a type PSV to type PSL (does not

apply to type PSV 5(6)S..-5 and PSV UNF 6S..-5; as these are already equipped with it).

Type PSL 5(6)./...-5 Type PSV 5(6)S./...-5

D

E

Tappedplug

F

Page 31: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 31

1. Plug MSD 3-309 (standard, is scope of delivery)SVS 296107 Plug with LED's for functional cut-off acc. to sect. 3.2 table 17

(For more details, see D 7163)

2. Electric amplifier EV 22 K2-12(24) acc. to D 7817/1One card can control two valve sections

3. Electric amplifier EV 1 M2 - 12/24 orEV 1 M2 - 24/48 acc. to D 7831/1 A remote control joy-stick with direction switches is required additionally (see detailed information in D 7831/1 sect. 5.2).

4. Programmable logic valve control type PLVC acc. to D 7845 ++

5. Electrical joystick type EJ1, EJ2 and EJ3 acc. to D 7844

6. Radio controls are accepted, if they fulfill the standards of Sk 7814.(Approved brands: HBC-Elektronik in D-74564 Crailsheim, HETRONIK Steuer-Systeme in D-84085 Langquaid, NBB-Nachrichtentechnik in D-75248 Ölbronn-Dürrn)

7.5 Recommended optional components 7.5.1 For electro-hydraulic actuations

7.5.2 Load-holding valves

Load-holding valves type LHDV acc. to D 7770 and note sect. 7.1e;Type LHK acc. to D 7100 suitable only for "very rigid" systems and directional spool valves without inflow controller(coding 1 acc. to table 15, sect. 3.2.)

7.5.3 Other valves

Prop. spool valve type PSL(V) size 3 acc. to D 7700-3(may be combined via intermediate plate ZPL53 with size 5)

Prop. spool valve type PSL(V) size 2 acc. to D 7700-2(may be combined via intermediate plate ZPL52 with size 5)

Prop. spool valve type PSL(V)F size 3 and 5 acc. to D 7700-F(manifold mounting spool valves)

Prop. pressure reducing valve type PMZ acc. to D 7625

7.6 Indications of actuation HEA

The following notes to the connection of the valve bank have to be observed to ensure a flawless function of the electric and hydraulic actuation.

b) Combination with common hydraulic joy-sticks

The pressure reducing valves integrated in the joy-sticks openthe consumer line to the tank during idle position. The control oilflow would escape via this bypass when a valve is simultaneouslyactuated via the solenoid. Therefore it is a must to provide checkvalves for the control lines at this kind of circuitry. The same ap-plies to hydraulic actuation. The used throttles however limit thebypass leakage. The control oil supply must be dimensioned sothat this leakage can be compensated (> 0.7 lpm per actuatedvalve section plus the internal leakage of the hydraulic joy-stick).

a) Combination with hydraulic control devices similar to type FB,

KFB acc. to D 6600

These control devices can be directly connected, due to theirfunction and low internal leakage.

Page 32: Hawe Prop Dir Spool Valve Psl, Psm, Psv

D 7700-5 page 32

7.7 Connection block type PSV 5N

Order example 1:

Order example 2:

Order example 3:

PSV 5N1 300/270 - 5

PSV 5N2 V 250/230 - 5

PSV 5N Z 350/310 - 5

Basic type, version with arbitrary shut-off of thepump gallery (the additional damping S isintegrated as standard, seetable 5 in sect. 3.1.2)

For control oil supply, see table 8 in sect. 3.1.4

no coding

V

Z

Without arbitrary relief, prepared for retrofitting of a directional seated valve type EM11 S(V) acc. to D 7490/1

With 2/2-Directional seated valve type EM11 V acc. to D 7490/1 (closed when deenergized)

With 2/2-Directional seated valve type EM11 S acc. to D 7490/1 (open when deenergized)

The high control pressure of variable displacement pump controllers may lead to unintentional movements of consumers with lowload pressure, even while the respective valve is in its idle position.The pump gallery is completely blocked with type PSV5N to ensure a definitive separation of pump and consumer circuit. This takesplace by means of a solenoid valve.The LS-gallery together with the LS-controller may be additionally relieved via a separate 2/2-way directional seated valve.

Symbols Type PSV 5N..- Type PSV 5N..V Type PSV 5N..Z

M 10, 10 deep

app

rox.

67

approx. 80

Setting LS-pressure limitation

Setting main pressure limiting valve

LS-relief, arbitrarily switched