DESCRIPTION BULLETIN NO. Cover Page - Electric Actuators & Accessories OME-100 Standard & Optional Features OME-101 OM Actuator Standard Features OME-102 OM Actuator Optional Features OME-103 Valve / Actuator Selection Chart OME-104 OM1 Actuator Specifications OME-105R1 OM2 & OM3 Actuator Specifications OME-106R1 OM4, OM5 & OM6 Actuator Specifications OME-107R1 OM7 & OM8 Actuator Specifications OME-108R1 OM9, OM10, OM11, & OM12 Actuator Specifications OME-109R1 OM2-OM6 Actuator with Integral Local Control OME-110 OM1 Wiring Diagram On-Off 110/1/60 OME-111 OM2-OM12 Wiring Diagram On-Off 110/1/60 OME-112 OM1 Wiring Diagram Modulating 110/1/60 OME-113 OM2-OM12 Wiring Diagram Modulating 110/1/60 OME-114 Travel Cam & Limit Switch Adjustment OM1 OME-115 Travel Cam & Limit Switch Adjustment OM2-OM12 OME-116 Mechanical Stop Adjustment OME-117 Modulating Control Board OM1 Diagram OME-118R2 Modulating Control Board OM2-OM13 Diagram OME-119R2 Modulating Control Board- Adjustment OME-120R1 Modulating Control Board- Adjustment Continued OME-121R1 Modulating Control Board- Adjustment Continued OME-122R1 Modulating Control Board- Adjustment Continued OME-123R1 Troubleshooting OME-124 Troubleshooting OME-125 Wiring Diagram-Quarter Turn Actuator OM1 - OM13 110V 220V AC 1-Phase OME-126 hallenger alve SECTION 5 INDEX

Upload: hoangcong

Post on 20-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

DESCRIPTION BULLETIN NO.

Cover Page - Electric Actuators & Accessories OME-100

Standard & Optional Features OME-101

OM Actuator Standard Features OME-102

OM Actuator Optional Features OME-103

Valve / Actuator Selection Chart OME-104

OM1 Actuator Specifications OME-105R1

OM2 & OM3 Actuator Specifications OME-106R1

OM4, OM5 & OM6 Actuator Specifications OME-107R1

OM7 & OM8 Actuator Specifications OME-108R1

OM9, OM10, OM11, & OM12 Actuator Specifications OME-109R1

OM2-OM6 Actuator with Integral Local Control OME-110

OM1 Wiring Diagram On-Off 110/1/60 OME-111

OM2-OM12 Wiring Diagram On-Off 110/1/60 OME-112

OM1 Wiring Diagram Modulating 110/1/60 OME-113

OM2-OM12 Wiring Diagram Modulating 110/1/60 OME-114

Travel Cam & Limit Switch Adjustment OM1 OME-115

Travel Cam & Limit Switch Adjustment OM2-OM12 OME-116

Mechanical Stop Adjustment OME-117

Modulating Control Board OM1 Diagram OME-118R2

Modulating Control Board OM2-OM13 Diagram OME-119R2

Modulating Control Board- Adjustment OME-120R1

Modulating Control Board- Adjustment Continued OME-121R1

Modulating Control Board- Adjustment Continued OME-122R1

Modulating Control Board- Adjustment Continued OME-123R1

Troubleshooting OME-124

Troubleshooting OME-125

Wiring Diagram-Quarter Turn Actuator OM1 - OM13 110V 220V AC 1-Phase OME-126

hallenger

alve

SECTION 5INDEX

3” SERIES 10 C/W OM1MODULATING ACTUATOR

BULLETIN NO.OME-100

ELECTRIC ACTUATORSELECTRIC ACTUATORSELECTRIC ACTUATORSELECTRIC ACTUATORS

& ACCESSORIES& ACCESSORIES& ACCESSORIES& ACCESSORIES

8” SERIES 20 C/W OM-4MODULATING ACTUATOR

8” 3-WAY VALVE ASSEMBLYC/W OM3 MODULATING

ACTUATOR

NON-CLUTCH DESIGN

ELECTRIC ACTUATORS STANDARD FEATURES

• CERTIFICATES Manufactured to ISO 9001 CSA and CE approved

• GEAR TRAIN Self-Locking, eliminates the need for a motor brake.

• OUTPUT TORQUE Twelve models available, output torques from 310”lbs to 31,150”lbs

• MANUAL OVERRIDE Non-clutch design, override can be operated without engaging or dis-engaging a clutch. Manual override remains stationary while motor is running

• ENCLOSURE: Nema 4X, Powder coated aluminum housing. IP67: Waterproof and Dust-proof

• POSITION INDICATOR All models have a high visibility indicator on top of the actuator cover.

• MOTOR: 110/1/60 Extended duty cycle induction motor. Built-In thermal protection (135°C) (275°F)

• HEATER All models have a Heater and Thermostat.

• WORKING CONDITIONS: Ambient Temperature: Heater Not Energized (-5°C)(23°F)(+60°C)(140°F) Heater Energized (-40°C)(-40°F)

• SWITCHES: All models have four colour coded switches. Two for travel adjustment, and two for auxiliary switches.

OPTIONAL FEATURES

• MODULATING CONTROL BOARD The input and output signals can be selected by adjusting the DIP switches on the control board. Input Selection - 4-20MA, 1-5V, 2-10V Output Selection - 2-10V, 4-20MA Valve fail position can be selected by adjusting the dip switches on the control board to fail on loss of signal to: (A) FAIL CLOSE (B) FAIL OPEN (C) FAIL IN LAST PLACE

• FEEDBACK POTENTIOMETER: 1K or 5K OHM feedback signal.

• CURRENT POSITION TRANSMITTER: 4-20MA output signal for position indication

• LOCAL CONTROL UNIT: Local/Remote selection switches, OPEN/OFF/CLOSE selection.

• VOLTAGE OPTIONS

• TORQUE SWITCHES: Adjustable cam activated torque switches to provide over-load protection.

Actuators are available in various voltages: 12 and 24VDC 12 and 24VAC 220 AC Single Phase 220, 380 and 440 VAC 3 Phase.

hallenger

alve

BULLETIN NO.OME-101

hallenger

alve

BULLETIN NO.OME-102

OM ELECTRIC STANDARD FEATURES

A space heater keeps the component parts of theactuator dry and prevents condensation for lowtemperature and humidity.

AUXILIARY

hallenger

alve

BULLETIN NO.OME-103

OM ELECTRIC OPTIONAL FEATURES

VALVE DISC TYPE WET SERVICE ACTUATOR MODEL NUMBER

SIZE FR=FULL RATED CLOSE OFF 2-WAY 3-WAY

U/C=UNDERCUT PRESSURE P.S.I. ASSEMBLY ASSEMBLY

2” F.R. 225 OM-1 OM-1

2.5” F.R. 225 OM-1 OM-1

3” F.R. 225 OM-2 OM-2

3” U/C 100 OM-1 OM-1

4” F.R. 225 OM-2 OM-2

4” U/C 100 OM-1 OM-2

4” U/C 50 OM-1 OM-1

5” F.R. 225 OM-3 OM-3

5” U/C 100 OM-2 OM-2

5” U/C 50 OM-1 OM-2

6” F.R. 225 OM-3 OM-3

6” U/C 100 OM-2 OM-3

6” U/C 50 OM-2 OM-2

8” F.R. 225 OM-4 OM-4

8” U/C 100 OM-3 OM-3

8” U/C 50 OM-2 OM-3

10” F.R. 225 OM-6 OM-6

10” U/C 100 OM-4 OM-4

10” U/C 50 OM-3 OM-4

12” F.R. 225 OM-7 OM-7

12” U/C 100 OM-4 OM-4

12” U/C 50 OM-4 OM-4

14” F.R. 150 OM-7 OM-7

14” F.R. 100 OM-6 OM-6

14” F.R. 50 OM-5 OM-6

16” F.R. 150 OM-7 OM-8

16” F.R. 100 OM-7 OM-7

16” F.R. 50 OM-6 OM-7

18” F.R. 150 OM-8 OM-8

18” F.R. 100 OM-7 OM-7

20” F.R. 150 OM-9 OM-10

20” F.R. 100 OM-9 OM-9

20” F.R. 50 OM-8 OM-8

24” F.R. 150 OM-11 OM-12

24” F.R. 100 OM-10 OM-11

24” F.R. 50 OM-9 OM-10

hallenger

alve

BULLETIN NO.OME-104

VALVE/ACTUATOR SELECTION CHARTOM ELECTRIC ACTUATOR/CHALLENGER BUTTERFLY VALVE

Note: Allow 5.00” for Cover Removal.

Dimensions: Mounting Flange ISO 5211 F03/F05

A B C D E F G H I J K L M N S

4.25” .315” 45° 6.10” .590” 1.41” M5 4 M6 4 1.97” 5.51” .748” 1 1/2”NPT

OUTPUT TORQUE: 310 LB-INCH.

CYCLE TIME: 12 SEC / 90° ROTATION

DUTY CYCLE: 30% ON-OFF

75% MODULATING

MOTOR: 110/1/60 (OPTIONAL VOLTAGES AVAILABLE)

THERMAL OVERLOAD: STANDARD

CURRENT 110V: RUN 0.6A

START 0.6A

LOCK 0.7A

ENCLOSURE: NEMA 4X (ALUMINUM POWDER COATED)

HEATER & THERMOSTAT: STANDARD

AUXILIARY SWITCHES: TWO STANDARD

MANUAL OVERRIDE: STANDARD - (NON-CLUTCH DESIGN)

WEIGHT 6 LB

hallenger

alve

BULLETIN NO.OME-105R1

OM1 ELECTRIC ACTUATOR

A

D

BN-S

øM

øF

øK

øI*JL

øG*H

E

C

* With modulating card D=7.28”

hallenger

alve

BULLETIN NO.OME-106R1

OM2-3 ELECTRIC ACTUATOR

A

B

D

F

EøHG

N-SøI-M

*With Modulating Card D=11.42

Note: Allow 8.00” for Cover Removal.

Dimensions: Mounting Flange ISO 5211 F07

A B C D E F G H I M N S

7.88” 12.99” 7.88” 10.04” 1.18” 4.92” .866” 2.76” M8 4 2 1/2”NPT

OUTPUT TORQUE: OM2 - 800 LB-INCH

OM3 - 1330 LB-INCH

CYCLE TIME: OM2 - 15 SEC / 90° ROTATION

OM3 - 22 SEC / 90° ROTATION

DUTY CYCLE: 30% ON-OFF

75% MODULATING

MOTOR: 110/1/60 (OPTIONAL VOLTAGES AVAILABLE)

THERMAL OVERLOAD: STANDARD

CURRENT 110V: OM 2 OM 3

RUN 1.0A 1.2A

START 1.8A 1.8A

LOCK 1.6A 1.6A

ENCLOSURE: NEMA 4X (ALUMINUM POWDER COATED)

HEATER & THERMOSTAT: STANDARD

AUXILIARY SWITCHES: TWO STANDARD

MANUAL OVERRIDE: STANDARD - (NON-CLUTCH DESIGN)

WEIGHT 25 LB

A

BøC

F

D

E

øH

øI-M

G

N-S

Note: Allow 9.00” for Cover Removal.

Dimensions: Mounting Flange ISO 5211 F10

A B C D E F G H I M N S

11.81” 14.96” 9.21” 12.40” 1.57” 7.68” 1.37” 4.01” M10 4 2 1/2”NPT

OUTPUT TORQUE: OM4 - 3540 LB-INCH

OM5 - 4425 LB-INCH

OM6 - 5753 LB-INCH

CYCLE TIME: OM4 - 16 SEC / 90° ROTATION

OM5 - 22 SEC / 90° ROTATION

OM6 - 28 SEC / 90° ROTATION

DUTY CYCLE: 30% ON-OFF

75% MODULATING

MOTOR: 110/1/60 (OPTIONAL VOLTAGES AVAILABLE)

THERMAL OVERLOAD: STANDARD

CURRENT 110V: OM4 OM5 OM6

RUN 1.9A 2.0A 2.1A

START 3.8A 3.8A 3.8A

LOCK 3.6A 3.6A 3.6A

ENCLOSURE: NEMA 4X (ALUMINUM POWDER COATED)

HEATER & THERMOSTAT: STANDARD

AUXILIARY SWITCHES: TWO STANDARD

MANUAL OVERRIDE: STANDARD - (NON-CLUTCH DESIGN)

WEIGHT 49 LB

hallenger

alve

BULLETIN NO.OME-107R1

OM4-5-6 ELECTRIC ACTUATOR

Note: Allow 11.00” for Cover RemovalDimensions: Mounting Flange ISO 5211 F14

A B C D E F G H I J K L Mø N S

17.72” 13.39” 9.21” 16.54” 2.36” 11.61” 5.51” 45° M16 4 7.09” .394” 1.37” 2 1/2”NPT

OUTPUT TORQUE: OM7 - 8850 LB-INCH

OM8 - 13275 LB-INCH

CYCLE TIME: 46 SEC / 90° ROTATION

DUTY CYCLE: 30% ON-OFF

75% MODULATING

MOTOR: 110/1/60 (OPTIONAL VOLTAGES AVAILABLE)

THERMAL OVERLOAD: STANDARD

CURRENT 110V: OM7 OM8

RUN 3.1A 3.3A

START 8.5A 9.0A

LOCK 9.0A 9.0A

ENCLOSURE: NEMA 4X (ALUMINUM POWDER COATED)

HEATER & THERMOSTAT: STANDARD

AUXILIARY SWITCHES: TWO STANDARD

MANUAL OVERRIDE: STANDARD - (NON-CLUTCH DESIGN)

WEIGHT 80 LB

hallenger

alve

BULLETIN NO.OME-108R1

OM7-8 ELECTRIC ACTUATOR

øA

B

N-S

øC

D

øF

E

øM

øI*JøK

H

øG

L

Note: Allow 11.00” for Cover Removal.

Dimensions: Mounting Flange ISO 5211 F16

A B C D E F G H I J K L M P N S

18.50” 13.78” 10.24” 23.23” 3.93” 15.50” 45° .472” M20 4 2.95 ” 6.50” 8.70” 14.17 2 1/2”NPT

OUTPUT TORQUE: OM9 - 17,700 LB-INCH

OM10 - 22,125 LB-INCH

OM11 - 26,550 LB-INCH

OM12 - 30,100 LB-INCH

CYCLE TIME: 58 SEC / 90° ROTATION

DUTY CYCLE: 30% ON-OFF

75% MODULATING

MOTOR: 110/1/60 (OPTIONAL VOLTAGES AVAILABLE)

THERMAL OVERLOAD: STANDARD

CURRENT 110V: OM9 OM10 OM11 OM12

RUN 3.3A 4.0A 4.5A 4.0A

START 5.8A 6.5A 6.5A 8.0A

LOCK 5.9A 5.9A 5.9A 7.5A

ENCLOSURE: NEMA 4X (ALUMINUM POWDER COATED)

HEATER & THERMOSTAT: STANDARD

AUXILIARY SWITCHES: TWO STANDARD

MANUAL OVERRIDE: STANDARD - (NON-CLUTCH DESIGN)

WEIGHT 125 LB

hallenger

alve

BULLETIN NO.OME-109R1

OM9-10-11-12 ELECTRIC ACTUATORA

B P

N-S

øC

øFD

E

øI*J

øM

øL

øK

H

G

OM2-OM3 ( ALLOW 8.00” FOR COVER REMOVAL)

A B C D E F G H I M N S

15.94” 8.07” 10.83” 13.78” 1.18” 4.92” .866” 2.76” 4 M8 2 1/2” NPT

OM4-OM6 ( ALLOW 9.00” FOR COVER REMOVAL)

A B C D E F G H I M N S

17.91” 12.00” 12.20” 16.14” 1.57” 7.68” 1.37” 4.01” 4 M10 2 1/2” NPT

NOTE: SEE BULLETIN OME-106 & OME-107 FOR ACTUATOR SPECIFICATIONS

B

A

C

D

F

E

øH

N-S

øI-M

G

hallenger

alve

BULLETIN NO.OME-110

OM2-6 ELECTRIC ACTUATOR WITH INTEGRAL LOCAL CONTROL

WIRING DIAGRAMOM-1 & OM-A 110V/220V AC1-PH 30% DUTY CYCLE

hallenger

alve

BULLETIN NO.OME-111

NOTE:(1). “N” CONNECTS TO 1.(2). “L” CONNECTS TO 3 FOR “OPEN”.(3). “L” CONNECTS TO 4 FOR “CLOSE”.(4). LS - - LIMIT SWITCH.(5). USING LESS THAN 3A CURRENT FORSWITCHES “A,B,C,E,F”.(6) “L” CONNECTS TO 7 FOR HEATER.(7) ABBREVIATIONS N.F.B.: NO FUSE BREAKER C.S.: CONTROL SWITCH O.L.: OVER LOAD

WIRING DIAGRAMOM2-OM12 ON-OFF 110/1/60 30% DUTY CYCLE

hallenger

alve

BULLETIN NO.OME-112

NOTE:(1). “N” CONNECTS TO 1.(2). “L” CONNECTS TO 3 FOR “OPEN”.(3). “L” CONNECTS TO 4 FOR “CLOSE”.(4). LS - - LIMIT SWITCH.(5). USING LESS THAN 3A CURRENT FORSWITCHES “A,B,C,E,F”.(6) “L” CONNECTS TO 7 FOR HEATER.(7) ABBREVIATIONS N.F.B.: NO FUSE BREAKER C.S.: CONTROL SWITCH O.L.: OVER LOAD

(SEE BULLETIN NO. OME-118 FOR CONTROL BOARD ADJUSTM ENT)

WIRING DIAGRAMOM-1 & OM-A MODULATING 110/1/60

hallenger

alve

BULLETIN NO.OME-113

(SEE BULLETIN NO OME-119 FOR CONTROL BOARD ADJUSTME NT)

WIRING DIAGRAMOM-2-OM-12 MODULATING 110/1/60

hallenger

alve

BULLETIN NO.OME-114

THE TRAVEL CAMS ARE SET TO CONTROL THE OPEN AND CLOSED POSITION OF THE VALVE. THEPOSITION IS SET TO STOP THE TRAVEL OF THE ACTUATOR WHEN THE TRAVEL CAMS ACTIVATETHE LIMIT SWITCH.

STANDARD IS TWO LIMIT SWITCHES, ONE FOR OPEN, ONE FOR CLOSED. THE BOTTOM LIMITSWITCH IS NORMALLY THE OPEN POSITION (FULL CCW). THE TOP LIMIT SWITCH IS NORMALLYTHE CLOSED POSITION (FULL CW).

2-AUXILIARY SWITCHES ARE STANDARD AND ARE SET INDEPENDENT OF THE TWO PRIMARYCONTROL LIMIT SWITCHES.

THE TRAVEL CAMS CAN BE ADJUSTED BY 2.5mm HEX SPANNER.

TRAVEL CAM AND LIMIT SWITCH ADJUSTMENT OM1

hallenger

alve

BULLETIN NO.OME-115

Counter-clockwise decrease openingdegree.

THE TRAVEL CAMS ARE SET TO CONTROL THE OPEN AND CLOSED POSITION OF THE VALVE. THEPOSITION IS SET TO STOP THE TRAVEL OF THE ACTUATOR WHEN THE TRAVEL CAMS ACTIVATETHE LIMIT SWITCH.

STANDARD IS TWO LIMIT SWITCHES, ONE FOR OPEN, ONE FOR CLOSED. THE BOTTOM LIMITSWITCH IS NORMALLY THE OPEN POSITION (FULL CCW). THE TOP LIMIT SWITCH IS NORMALLYTHE CLOSED POSITION (FULL CW).

2-AUXILIARY SWITCHES ARE STANDARD AND ARE SET INDEPENDENT OF THE TWO PRIMARYCONTROL LIMIT SWITCHES.

THE TRAVEL CAMS CAN BE ADJUSTED BY 2.5mm HEX SPANNER.

TRAVEL CAM AND LIMIT SWITCH ADJUSTMENT OM2-OM12

hallenger

alve

BULLETIN NO.OME-116

NOTE: MECHANICAL STOPS HAVE BEEN FACTORY SET AND DO NOT REQUIRE FURTHERADJUSTMENT.

IF ADJUSTMENT IS REQUIRED, IT MUST BE DONE IN THE FOLLOWING ORDER:

1 TURN THE OPEN AND CLOSE STOPS COUNTERCLOCKWISE APPROXIMATELY ONE FULL TURN.

2 MANUALLY CLOSE THE ACTUATOR TO THE DESIRED POSITION AND SET THE CLOSE TRAVELCAM (REFER TO BULLETIN OME-115 FOR MODEL OM-1 AND BULLETIN OME-116 FOR MODELOM-2 THROUGH 12)

3 TURN THE CLOSE MECHANICAL TRAVEL STOP CLOCKWISE UNTIL IT CONTACTS THE GEARSEGMENT. REVERSE THE TRAVEL STOP ONE FULL TURN AND SET THE JAM NUT.

4 FOLLOW STEPS 2 & 3 FOR SETTING THE OPEN STOP.

CAUTION: THE ELECTRIC TRAVEL STOPS MUST BE SET AHEAD OF THE MECHANICAL STOPS ORDAMAGE TO THE GEARS WILL OCCUR.

MECHANICAL STOP ADJUSTMENT

hallenger

alve

BULLETIN NO.OME-117

hallenger

alve

BULLETIN NO.OME-118R2

OM 1

The Diagram is based on the actuator in 110 / 220v voltage.

ADJUSTMENT - MODULATING CONTROL BOARD

hallenger

alve

BULLETIN NO.OME-119R2

ADJUSTMENT - MODULATING CONTROL BOARDOM 2 13

The are nine LED lights. And their functions

are listed on Bulletin NO. OME-123R1

DIP-SWITCH SETTING (S 1 - S 8)CAUTION: DO NOT ALTER SWITCH POSITIONS WHILE ACTUAT OR IS TURNED ON

8 7 6 5 4 3 2 1

ON OFF OFF OFF ON OFF OFF ON Factory Setting

OFF ON 4-20mA input

OFF OFF 1-5V input

ON OFF 2-10V input

OFF ON OFF 4-20mA output

ON OFF ON 2-10V output

OFF 20 mA / 5V / 10V increase signal to open

ON 20 mA / 5V / 10V decrease signal to open

ON OFF Fail close on loss of signal when S6 is off

OFF ON Fail open on loss of signal when S6 is off

ONON

ONON

Fail in last position on loss of signal when S6 is offFail in last position on loss of signal when S6 is oN

Comparison Control Part Control Object

Feedback Sig-

Input Signal:

4-20mA

2-10V DC

1-5V DC

Output Signal:

4-20mA

2-10V DC

Control Volume

Valve 90°

270°

SUPPLIED VOLTAGE: 24 DC / AC, 110V / 220V AC 1 - PHASE

WORKING TEMPERATURE: -5 - + 60°C

WITH HEATER -40°C

ADJUSTMENT - MODULATING CONTROL BOARD

PROCEDURE

hallenger

alve

BULLETIN NO.OME-120R1

hallenger

alve

BULLETIN NO.OME-121R1

FUNCTION SETTING

S1, 2INPUT SIGNAL SELECT

“4-20mA” SET 1- ON / 2- OFF

“1-5V “ SET 1-OFF / 2-OFF

“2-10V SET 1-OFF / 2-ON

S3, 4, 5 OUTPUT SIGNAL SELECT “4-20mA SET 3-OFF / 4-ON / 5-OFF

“2-10V SET 3-ON / 4-OFF / 5-ON

ADJUSTMENT - MODULATING CONTROL BOARD

WHEN S6 SETS “ ON “

S 6 INPUT SINGNAL SELECT4 mA, 2V, 1V valve fully closed

20mA, 10V, 5V valve fully-closed

SET 6 - ON

S 7, 8 POSITION SELECT

( When feedback signal fails )

“Fail-Closed” set 7-ON / 8-OFF

“Fail-Open set 7-OFF / 8-ON

“Fail in last position” SET 7-ON / 8-ON

WHEN S6 SETS “OFF”

S 6 INPUT SIGNAL SELECT

4 mA, 2V, 1V valve fully closed

20mA, 10V, 5V valve fully-closed

set 6-OFF

S 7, 8 POSITION SELECT( When the feedback signal fails )

“Fail-Closed” set 7-OFF / 8-ON“Fail-Open” set 7-ON / 8-OFF“Fail in last position” set 7-OFF / 8-OFF

NOTE: THE STANDARD FACTORY PRESETTING IS 1,4,8 FOR ON AND 2,3,5,6,7 FOR OFF.

hallenger

alve

BULLETIN NO.OME-122R1

ADJUSTMENT - MODULATING CONTROL BOARD

Sensitivity Switch Setting

SW 2

SW 2: 1, 2, 3 - 0 Sensitivity switch:

When to switch to “1” : The highest sensitivity and the 0-90° can be divided up to around 50 times movement.

When switch to “0” : The lowest sensitivity and the 0-90° can be divided up to around 10 times movement.

The sensitivity decreases 7 times movement by sectors from SW 1 to SW 2, SW2 to SW 3,SW 3 to

SW 4 and so on.

SETTINGS FOR OPEN AND CLOSE ( FOR 0M 2 - OM 13 )

The settings are set in factory, though in some cases re-set may be requred when a particular rate of

signal is requested

OPEN SETTING

a) Keep pressing “SET” for 2 seconds, until LED 9 comes on, it will enter the manual mode.

b) Keep pressing “UP” and let the actuator run to fully-open position, LED 2 comes on, then apply

input signal ( 5V or 10V or 20mA)

c) Press “MODE” once. The “OPEN” setting is complete.

CLOSE SETTING

a) Keep pressing “DOWN” let the actuator run to fully-closed position, LED 1 comes on, then apply

input signal ( 1V or 2V or 4mA).

b) Press “MODE” once. The CLOSE” setting is complete.

After completing the above settings, press “SET” once.

0

9

8

76

5

3

4

2

1

hallenger

alve

BULLETIN NO.OME-123R1

ADJUSTMENT - MODULATING CONTROL BOARD

LAMP SIGNAL ( FOR OM 2 - OM 13 )

LED1: When actuator is fully-closed, LED1 comes ON.LED2: When actuator is fully-open, LED2 comes ON.

LED3: When you open the power of the actuator, LED3 comes ON.LED4: When the wrong power supply is applied to the actuator, LED4 comes ON.LED5: When the wrong signal type is applied to the actuator, LED5 comes ON.LED6: When the motor thermostat opens (over-heating), LED6 comes ON.LED7: When the output signal is short-circuited, LED7 comes ON.LED8: When the motor current is excessive, LED8 comes ON.LED9: When the actuator is operated manually, LED9 comes ON

If the LED is flashing after the operating check is complete, refer to the following.

Lamp Possibilities Solution

NO LAMP a) No power supply

b) The voltage is over 260V and caused the

board to burn out.

c) Wrong connection for the # 8, #9 of the

VR.

a) Check the power supply.

b) Check the voltage.

c) Check the wiring.

LED 5 a) Setting in 2-10V input signal but supply 4-

20mA. ( LED 5 —- ON )

b) Setting in 2-10V input signal and the sig-

nal is over 13.5V ( LED 5 —-ON )** Setting in 4-20mA but supply 2-10V signal. Theactuator will operate by 2-7V. But if the signal over7.2V the LED 5 will turn on.

Confirm the input signal.

LED 6 Motor thermostat turned off. Too high frequency for rated duty cycle.

LED 7 Output signal short circuit a) Confirm the wiring of output signal # 11(-)-#12 (+).

b) Whether # 11 & # 12 output signal short circuit

LED 2, LED 7 Incorrect wiring for 2-10V output signal. Confirm the wiring of output signal # 6 (-) - # 7 (+).

LED 8 Motor current is excessive. Too high frequency for rated duty cycle.

LED 9 Manual mode- Setting position for open &

close.

After completing the settings, press “SET” once.

MODULATING BOARD TROUBLESHOOTING

hallenger

alve

BULLETIN NO.OME-124

TROUBLESHOOTING

ON-OFF CONTROLLER

MOTOR DOES NOT OPERATE ANDOVERHEATS

POSSIBLILITIES SOLUTION

Supply power for # 3 - # 4 simultaneously

( Parallel Connection)

Check the wiring

The capacitor failed. (Check to see if the surface of the

capacitor is deformed)

Replace with new part

Valve’s seat is depressed ( valve has been set at

fully closed position for a long period)

Use hand - wheel for test or replace valve seat

Check if any foreign objects in flow stream Check for obstructions

Broken motor stem or bearing Replace with new parts

THE ACTUATOR IS OPERATINGBUT MOTOR IS HOT

POSSIBLILITIES SOLUTION

Starting the actuator too frequently. ( too high frequency

for rated duty cycle)

Change system bandwidth or replace to a higher duty

cycle actuator.

Overload This situation often happens after operating for a long

time. It is suggested to replace the valve.

Under or over requested voltage. Check the supply circuit.

The gear jams the mechanical stops in fully-open or

closed position.

Reset the mechanical stops and limit switches

OPERATING TWO OR MORE ACTUATORSSIMULTANEOUSLY. THE ACTUATOR WORKS

ABNORMALLY SOMETIMES AND THE MOTOR ISHOT

POSSIBLILITIES SOLUTION

Parallel connection Check circuits, install relay for separation.

Refer to wiring diagram onBulletin No. OME-126

THE VALVE CAN’T FULLY OPEN OR CLOSEDURING TEST BY EITHER POWER SUPPLY OR

HAND-WHEEL

POSSIBLILITIES SOLUTION

Check for flange misalignment. Check with the installer to resolve the problem.

hallenger

alve

BULLETIN NO.OME-125

TROUBLESHOOTING

ON-OFF CONTROLLER

THE CAPACITOR HAS FAILED

POSSIBLILITIES SOLUTION

a) Overload (exceeds the rated torque of the actuator Replace with new part.

b) Cycling over the rated duty cycle. Check motor duty rating

THE LED IS FLASHING AFTER OPERATINGCHECK IS COMPLETE

POSSIBLILITIES SOLUTION

Refer to Bulletin No. OME-123R1

THE LAMP ON THE MODULATING BOARDIS ON BUT THE ACTUATOR DOESN’T WORK

( OR IT CAN ONLY TURN TO FULLY OPEN/CLOSEPOSITION

POSSIBLILITIES SOLUTION

The signal is connected opposed: ( equal to signal

failure)

Confirm if the input signal and the wiring are correct.

CAN’T OPERATE BY MODULATINGCONTROLLER

POSSIBLILITIES SOLUTION

a) Fault VR

b) The sector gear of the VR is loose.

a) Replace a new VR.

b) Switching the dip switches #7 to OFF, # 8 to ON and

remove the input signal. The actuator will operate to

fully close then set the sector gear again. Put all the

parts back after all adjustment and setting

MODULATING CONTROLLER

hallenger

alve

BULLETIN NO.OME-126

WIRING DIAGRAM- QUARTER TURN ACTUATOR

OM 1 - OM 13 110 V 220 V AC 1- PHASE

Same Switch Coupling Wiring

NOTE:

1) The wiring is based on the 3 sets of motor for one switch - 2 sets is open

and 1 set is closed. ( if more sets, the rest can be done by the same logic)

2) When a set of control wire or switch needs to control two or more actuators

at the same time, please refer to the wiring diagram.

3) Add 1 pc. contactor for separation to prevent interference from condenser

coupling.

4) C1=3a3b contactor.