haier ab36nacbea ac36nacbea ad36nambea ad36nahbea ab42nacbea ac42nacbea ad42nambea ad42nahbea...

143
MANUAL CODE: SYJS-006 -03 Rev.0 . Haier Group Auto-Restart function Group control(with a group controller) Auto-changeover The same outdoor unit can match with cassette \convertible\ duct type indoor unit With new environment friendly refrigerant R407C Weekly timing(with a weekly timer) Features Service Manual Commercial Air Conditioning 4HP 5HP Uni versal Outdoor Unit air conditioning AC36NACBEA+AU36NAIBEA AD36NAMBEA+AU36NAIBEA AB36NACBEA+AU36NAIBEA Remotoe control and Wired remote control(Optional) AC42NACBEA+AU42NAIBEA AD42NAMBEA+AU42NAIBEA AB42NACBEA+AU42NAIBEA AP42NACBEA+AU42NAIBEA AD36NAHBEA+AU36NAIBEA AD42NAHBEA+AU42NAIBEA

Upload: zsooti

Post on 28-Jul-2015

358 views

Category:

Documents


14 download

TRANSCRIPT

Page 1: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

MANUAL CODE: SYJS-006 -03 Rev.0 .

Haier Group

Auto-Restart function

Group control(with a group controller)

Auto-changeover

The same outdoor unit can match with cassette \convertible\

duct type indoor unit

With new environment friendly refrigerant R407C

Weekly timing(with a weekly timer)

Features

Service ManualCommercial Air Conditioning

4HP 5HP Universal Outdoor Unit air conditioning

AC36NACBEA+AU36NAIBEAAD36NAMBEA+AU36NAIBEA

AB36NACBEA+AU36NAIBEA

Remotoe control and Wired remote control(Optional)

AC42NACBEA+AU42NAIBEAAD42NAMBEA+AU42NAIBEA

AB42NACBEA+AU42NAIBEA

AP42NACBEA+AU42NAIBEA

AD36NAHBEA+AU36NAIBEA

AD42NAHBEA+AU42NAIBEA

Page 2: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

CONTENTS

1. Description of Products & Features…………………...…….2

2. Specifications…………………………. ………………...……6

3. Safety precaution…………………………..………………….14

4. Net dimensions of indoor and outdoor unit………………...17

5. Installation instructions ……………………. ………………..20

6. Parts and functions …………………………..…… ..……….48

7. Remote controller functions………………………….………50

8. Refrigerant diagram…………………………..……………....71

9. Electrical control functions……………………………………72

10. Diagnostic information(trouble shooting)…………….……78 11. Electrical data.........................................…………….……85

12. Exploded views and parts lists...............……………. ……8813. Perdormance curves……………............................... ……96

14. Noise level charts.....……………............................... ……10415. Air velocity distribution …………............................... ……106

CONTENTS

Contents……..............................................…...………...…….1

- 1 -

Page 3: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

1. Description of product code and brief introduction of the series

a) Description of the coding rule of the models

A U 36 N A I B D A

Climate type:T1

Design serial number

Air conditioner

Product series:one-tag-one

Outdoor unit

Product specification:valid digit above kilobi

Adaptive voltage:380-400V/50Hz

Appearance features

Product type: heat pump R407C

A B 36 N A C B D A

Climate type:T1

Design serial number

Air conditioner

Product series:one-tag-one

Product specification:valid digit above kilobi

Adaptive voltage:380-400V/50Hz

Appearance features

Product type: heat pump R407C

Product type:indoor unit P:Cabinet typeC:Convertible type B:Cassette type D:Duct type

b). Standard working condition

Operating Mode Indoor Operating Mode Outdoor Operating Mode

Nominal Cooling

Temp. Temp.Humidity

DB:27 WB:19 DB:35

DB:7 WB:6

WB:24

Humidity

DB:20 WB:15Nominal Heating

No.

1

2

Temp.Humidity

DB:27 WB:19 DB:35

DB:7 WB:6

WB:24

Humidity

DB:20 WB:15Nominal Heating

No.

1

2

2

Page 4: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

c)Brif introduction of the series: Convertible type:

AC36NACBEA+AU36NAIBEA AC42 NACBDA+AU42NAIBEA(1).Ceiling convertible,flexible installation,convenient

maintenance,saving the users' expenditures (2).Adopting three-phase power supply,applicable for household

and commercial usage (3).Dual air outlet design,floor air blowing,accelerating the indoor air

circulation, quick temperature adjustment (4).Long-distance air blowing,large power,large cooling/heating

ratio (5).Intelligent remote control,convenient and flexible control (6).Super-slim indoor unit design,luxury and nice-looking,saving

space,harmonious and unitive with the indoor environment (7).Adopting screw-fastening for the air inlet grill,firmly

fixed;adopting slipway insert-lock fastening method for the filter screen,convenient cleaning or replacing the filter screen without opening the air inlet grill.

(8).Group control,units up to 128 sets can be controlled . Duct type : AD36NAMBEA+AU36NAIBEA AD42NAMBEA+AU42 NAIBEATotally concealed machine body All the machine body is to be installed inside the ceiling, having no effect on the beauty of the room and without taking any room space. Air intake via the rear air intake duct This new design has changed the former unique pattern of air intake, and a larger distance between air intake and air return cycles as well as better air quality can be achieved. Flexible and easier installation The machine body is to be installed in a totally concealed way,its fan system has a longer distance coverage so as to supply its airflow to several rooms, and the indoor unit may be installed inside the ceiling of a room or corridor. The installation is simple and flexible, and there is no need to have specified personnel for management, thus cutting down the expenses; the machine is lighter and smaller, and convenient for installation, it takes an extremely small building space, thus lower the construction cost; the indoor unit is to be concealed inside the ceiling, and hence the usable space can be saved and the room decoration will not be affected.

3

Page 5: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

AB36NACBEA+AU36NAIBEA AB42NACBEA+AU42NAIBE AProducts characteristic: Completely invisible machine body: The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of air conditioner allows it to blend right into ceiling. Superbly efficient healthy filter: Superbly efficient antibiotic materials are utilized and can prevent germs from breeding efficiently . Flexible and easy installation Slim design with machine body, completely ceiling concealing and portable shape, all make it greatly easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional cost prices. It also features a specific drainage system with up to 600mm lift , which allows reducing installation spaces and ensures to drain smoothly. Thanks to its "smudge-free" mobile outlet grill, the ceiling can be protected from pollution effectively and allow the airflow to fit people's comfortable need much more. Compensation function of power failure: When meeting a power failure during running, no matter how long it will be, once the power is restored, air conditioner will automatic restart with the previous status. Safety and reliable control due to various signal controls 1 Inputting with press buttons on the panel 2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe temperature sensors, 3 Piping pressure signals 4 Compressor current signals 5 Testing signals 6 System time-shorten signal 7 Water overflowing signal 8 Communication signals between indoor unit and front plate or between indoor unit and outdoor unit . Silent design The use of radial outward flow turbine fan produces larger cyde airflow volume and acts to significantly decrease operating noise. When using remote-controlling mode, it is comfortable and convenient to operate.

Cassette type:

4

Advanced wire-controller and convenient remote-controllerThe new wired controller can connect with 16 indoor units without any device such as detectors.The new remote controller can be used for single unit or muti-free unit, or H-MRV,very convenient.

In addition, it can be compatible with the old remote controllers.

Low ambient temperature cooling function (optional) Equipped with high/low pressure protection switch

NEW

NEW

Page 6: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Climate type Type of Air Conditioner

T1 T2 T3

Cool only 18 43 0 35 21 52

Heat pump -7 43 -7 35 -7 52

Electricity heating 43 35 52

d). Brief Introduction for T1\ T2\ T3 working condition

Climate type Type of Air Conditioner

T1 T2 T3

Cool only 18 43 10 35 21 52

Heat pump -7 43 -7 35 -7 52

Electricity heating 43 35 52

5

Page 7: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function Cooling HeatingCapacity BTU/h 36000 41000

W 4000 3800W 5500 5500

EER or COP BTU/W 9 10.8Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Fan Type × Number

Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mm

kWdB(A)kg / kg

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mmkg / kg

Unit model (color)Compressor Model / Manufacture

TypeFan Type × Number

Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃External (L×W×H) mm×mm×mmPackage (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgRefrigerant Type / Charge g

Recharge quantity g/mLiquid mmGas mm

Connecting Methodmm

/43/41/39

/

/

//

//

/

/

Remote/

2-7

1325×920×370PVC 26/32

MAX.Piping length 50

Weight (Net / Shipping) /

Type of Four way valve //

Defrosting

PIPI

NG

R407C 380065

Pipe φ9.52φ19.05

Falre

Between I.D &O.MAX.Drop 30

Dimension //

//

/

/

//

Out

door

uni

t

/

Weight (Net / Shipping) 46/53

Pane

l Dimension 1340×950×801400×995×115

Weight (Net / Shipping)

/

45

Dimension 1230×840×280

/

0.061980/-/-

Centrifugal*1590+30/490+40/420+50

TP2M/φ7

item Model AB36NACBEA(SANYO)

5/

Total power inputMax. power input

Running /Max.Running

8.4/12

3N~ 380V-400V 50HZ

Indo

or u

nit

AB36NACBEA(WHITE)

Noise level (H-M-L)Electricity Heater

cooling:7.5/9.5;heating:6.5/9.5;

2.Specifications

6

Page 8: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function Cooling HeatingCapacity BTU/h 36000 41000

W 4000 3800W 5500 5500

EER or COP BTU/W 9 10.8Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Fan Type × Number

Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mm

kWdB(A)kg / kg

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mmkg / kg

Unit model (color)Compressor Model / Manufacture

TypeFan Type × Number

Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃External (L×W×H) mm×mm×mmPackage (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgRefrigerant Type / Charge g

Recharge quantity g/mLiquid mmGas mm

Connecting Methodmm

cooling:7.5/9.5;heating:6.5/9.5;45

Dimension

3pH,380V-400V 50HZ

item Model AC36NACBEA(SANYO)

5/

0.061600/1400/1200

Noise level (H-M-L)Electricity Heater

TP2M/9.52

Weight (Net / Shipping) 62/77

2-7

1980×761×295PVC 26/32

/48/-/44

1920×715×235

/

Between I.D &O.MAX.Drop 30

Out

door

uni

t

/

/

Dimension //

/

Defrosting

Indo

or u

nit

AC36NACBEA(WHITE)

PIPI

NG

R407C 380065

Pipe 9.5219.05Flare

Weight (Net / Shipping) /

Type of Four way valve //

/

//

Pane

l Dimension //

Weight (Net / Shipping)

MAX.Piping length 50

Remote/

/

/

//

/

/

Total power inputMax. power input

Running /Max.Running

/

/

/

/

/

CentrifugalX41350+30/1280+30/1050+30

7

Page 9: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function Cooling HeatingCapacity BTU/h 36000 41000

W 4000 3800W 5500 5500

EER or COP BTU/W 9 10.8Dehumidifying capacity 10‐³×m³/hPower cable

Power source N,V,HzA / A

Start Current AUnit model (color)

Fan Type × NumberSpeed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)

Fresh air hole dimension mmkW

dB(A)kg / kg

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mmkg / kg

Unit model (color)Compressor Model / Manufacture

Type

Fan Type × Number

Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgRefrigerant Type / Charge g

Recharge quantity g/mLiquid mmGas mm

Connecting Methodmm

/

MAX.Piping length 50

Wired/

/

/

//

/

/

/

//

//

Pane

l Dimension

Weight (Net / Shipping) /

Type of Four way valve //

Defrosting

Indo

or u

nit

AD36NAMBEA(WHITE)

PIPI

NG

R407C 380065

Pipe 9.5219.05Flare

Between I.D &O.DMAX.Drop 30

Out

door

uni

t

/

/

Dimension //

/

//

Weight (Net / Shipping) /

CentrifugalX31050/ 960/ 870/810

TP2M/9.52

Weight (Net / Shipping) 55/75

2-7

1557×800×370PVC 26/32

/43/-/39

1410×645×350

/

0.062040/1800/1600

item Model AD36NAMBEA(SANYO)

5/

Total power inputMax. power input

Running /Max.Running

/

Noise level (H-M-L)Electricity Heater

3N 380V-400V 50HZcooling:7.5/9.5;heating:6.5/9.5;

45

Dimension

8

Page 10: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function cooling heatingCapacity BTU/h 36000 41000Capacity kW 10.55 12.01Sensible heat ratio 79% /

W 4000 3800W 5500 5500

EER or COP W/W 2.64 3.16Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Type × NumberSpeed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mmOutlet distribution hole dimension mm

kWdB(A)kg / kg

Unit model (color)Model / ManufactureTypeType × NumberSpeed r/minFan motor output power kWAir-flow(H-M-L) m³/hType / Diameter mmTotal area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgType / Charge gRecharge quantity g/mLiquid mmGas mm

Connecting Methodmm

//

Refrigerant

/

Compressor

Fan

48/46/44

/

/

/

/

wired/

/

/

/

Type of Four way valve //

Defrosting //

MAX.Piping length 50

Weight (Net / Shipping) /

PIP

ING

R407C 380065

Pipe 9.5219.05flared

Between I.D &O.MAX.Drop 30

//

Heat exchanger/

//

TP2M/9.52

Out

door

uni

t

/Weight (Net / Shipping) 62/77

Dimension//

PVC 26/32

1197×828×355

item Model AD36NAHBEA

5/

Total power inputMax. power input

Running /Max.Running

centrifugal X2

Dimension

/

2580/2070/1560

2-7

1450×980×530

Fan

Heat exchanger

0.06

Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DBOutdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB

1090/1000/930

3PH 380V-400V 50HZ

Indo

or u

nit

AD36NAHBEA (grey)

Noise level (H-M-L)Electricity Heater

Cooling:7.5/9.5, Heating:6.5/9.545

Page 11: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function Cooling HeatingCapacity BTU/h 36000 41000

W 4000 3800W 5500 5500

EER or COP BTU/W 9 10.8Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Fan Type × Number

Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃External (L×W×H) mm×mm×mmPackage (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mm

kWdB(A)kg / kg

External (L×W×H) mm×mm×mmPackage (L×W×H) mm×mm×mm

kg / kgUnit model (color)Compressor Model / Manufacture

TypeFan Type × Number

Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgRefrigerant Type / Charge g

Recharge quantity g/mLiquid mmGas mm

Connecting Methodmm

Running /Max.Running

/

6000

MAX.Piping length 50

//

/

64/-/-

AUTO/

Capiliary

TP2M/9.52

43-60

0.15 840+30

ScrollC-SBN303H8A(SANYO)

Pane

l Dimension //

Weight (Net / Shipping) 91/111

Type of Four way valve DHF-12XPE

Defrosting

Indo

or u

nit

/

PIPI

NG

R407C 380065

Pipe 9.5219.05Flare

Between I.D &O.MAX.Drop 30

Out

door

uni

t

AU36NAIBEA(WHITE)

Axial-flow×2

Dimension 980×340×12501050×440×1375

0.92

Weight (Net / Shipping) /

Weight (Net / Shipping) /

/

//

/

/

//

/

item Model AU36NAIBEA(SANYO)

5/

Total power inputMax. power input

Noise level (H-M-L)Electricity Heater

3N380V-400V 50HZcooling:7.5/9.5;heating:6.5/9.5;

45

Dimension /

/

/

/

9

Page 12: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function Cooling HeatingCapacity BTU/h 42000 48000

W 4800 5000W 5700 7200

EER or COP BTU/W 8.75 9.6Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / A

Start Current AUnit model (color)Fan Type × Number

Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mm

kWdB(A)kg / kg

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mmkg / kg

Unit model (color)Compressor Model / Manufacture

TypeFan Type × Number

Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃External (L×W×H) mm×mm×mmPackage (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgRefrigerant Type / Charge g

Recharge quantity g/mLiquid mmGas mm

Connecting Methodmm

//

/

/

/

//

PVC 26/32

1400×995×115

Running /Max.Runningcurrent

/43/41/39

MAX.Piping length 50

Weight (Net / Shipping) /

Type of Four way valve //

Defrosting

PIPI

NG

R407C 400065

Pipe φ9.52φ19.05Flare

Between I.D &O.MAX.Drop 30

Dimension //

//

/

0.06

/

//

/

Remote control/

2-7

1325×920×370

8.4/12Weight (Net / Shipping)

/

/

3N~ 380V-400V 50HZ

Indo

or u

nit

AB42NACBEA(WHITE)

Out

door

uni

t

/

Weight (Net / Shipping) 46/53

Pane

l Dimension 1340×950×80

item model AB42NACBEA

5/

Total power inputMax. power input

Noise level (H-M-L)Electricity Heater

Cooling:8.3/10.2;Heating:9.5/12.6;

59.5

1980/-/-

Centrifugal590+30/490+40/420+50

TP2M/φ7

Dimension 1230×840×280

10

Page 13: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function Cooling HeatingCapacity BTU/h 42000 48000

W 4800 5000W 5700 7200

EER or COP BTU/W 8.75 9.6Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Fan Type × Number

Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mm

kWdB(A)kg / kg

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mmkg / kg

Unit model (color)Compressor Model / Manufacture

TypeFan Type × Number

Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgRefrigerant Type / Charge g

Recharge quantity g/mLiquid mmGas mm

Connecting Methodmm

Cooling:8.3/10.2;Heating:9.5/12.6;49.5

Dimension

3N380V-400V 50HZ

Item model AC42NACBEA(SANYO)

5/

0.061600/1400/1200

Noise level (H-M-L)Electricity Heater

TP2M/9.52

Weight (Net / Shipping) 62/77

2-7

1980×761×295PVC 26/32

/48/-/44

1920×715×235

/

Between I.D &O.MAX.Drop 30

Out

door

uni

t

/

/

Dimension //

/

Defrosting

Indo

or u

nit

AC42NACBEA(WHITE)

PIPI

NG

R407C 400065

Pipe 9.5219.05Flare

Weight (Net / Shipping) /

Type of Four way valve //

/

//

Pane

l Dimension //

Weight (Net / Shipping)

MAX.Piping length 50

Remote/

/

/

//

/

/

/

Total power inputMax. power input

Running /Max.Running

/

/

/

/

CentrifugalX21350+30/1280+30/1050+30

11

Page 14: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function Cooling HeatingCapacity BTU/h 42000 48000

W 4800 5000W 5700 7200

EER or COP BTU/W 8.75 9.6Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Fan Type × Number

Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mm

kWdB(A)kg / kg

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mmkg / kg

Unit model (color)Compressor Model / Manufacture

TypeFan Type × Number

Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgRefrigerant Type / Charge g

Recharge quantity g/mLiquid mmGas mm

Connecting Methodmm

/

MAX.Piping length 50

Wired/

/

/

//

/

/

/

//

//

Pane

l Dimension

Weight (Net / Shipping) /

Type of Four way valve //

Defrosting

Indo

or u

nit

AD42NAMBEA(WHITE)

PIPI

NG

R407C 400065

Pipe 9.5219.05Flare

Between I.D &O.MAX.Drop 30

Out

door

uni

t

/

/

Dimension //

/

//

Weight (Net / Shipping) /

Weight (Net / Shipping) 55/75

2-7

1450×9800×530PVC 26/32

/42/36/30

cooling:8.3/10.2;heating:9.5/12.6;49.5

Dimension 1410×645×350

/

0.062040/1800/1600

CentrifugalX31050/960/ 870/810

TP2M/9.52

3N380V-400V 50HZ

Item model AD42NAMBEA(SANYO)

55X2.5mm2

Total power inputMax. power input

Running /Max.Running

Noise level (H-M-L)Electricity Heater

12

Page 15: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function cooling heatingCapacity BTU/h 42000 48000Capacity kW 12.31 14.06Sensible heat ratio 79% /

W 4800 5000W 5700 7200

EER or COP W/W 2.56 2.81Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Type × NumberSpeed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mmOutlet distribution hole dimension mm

kWdB(A)kg / kg

Unit model (color)Model / ManufactureTypeType × NumberSpeed r/minFan motor output power kWAir-flow(H-M-L) m³/hType / Diameter mmTotal area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgType / Charge gRecharge quantity g/mLiquid mmGas mm

Connecting Methodmm

//

Refrigerant

/

Compressor

Fan

48/-/44

/

/

/

/

wired/

/

/

/

Type of Four way valve //

Defrosting //

MAX.Piping length 50

Weight (Net / Shipping) /

PIP

ING

R407C 400065

Pipe 9.5219.05flared

Between I.D &O.MAX.Drop 30

//

Heat exchanger/

//

TP2M/9.52

Out

door

uni

t

/Weight (Net / Shipping) 62/77

Dimension//

PVC 26/32

1197×828×355

item Model AD42NAHBEA

5/

Total power inputMax. power input

Running /Max.Running

centrifugal X2

Dimension

/

2580/-/1560

2-7

1450×980×530

Fan

Heat exchanger

0.06

Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DBOutdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB

1090+30/-/930+50

3PH 380V-400V 50HZ

Indo

or u

nit

AD42NAHBEA (grey)

Noise level (H-M-L)Electricity Heater

Cooling: 8.3/10.2, Heating: 9.5/12.649.5

Page 16: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function cooling heatingCapacity BTU/h 42000 50000Capacity kW 12.31 14.65

W 5000 6000W 6000 7200

EER or COP W/W 2.46 2.44Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Type × NumberSpeed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h Type / Diameter mmTotal Area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)

dB(A)kg / kg

Type / Charge gRecharge quantity g/mLiquid mmGas mm

Connecting Methodmm

0.06

Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DBOutdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB

590/400/350

1PH 380V-400V 50HZ

Indo

or u

nit

AP42NACBEA (white)

Noise level (H-M-L)

Cooling:8.5/10.2 Heating:10.0/12.0;49.5

Dimension

0.338

1560/-/-

2-7

1952×660×455PVC 26/32

1820×530×310

item Model AP42NACBEA

5/

Total power inputMax. power input

Running /Max.Running

centrifugalX1

TP2M/9.52

Weight (Net / Shipping) 62/77

PIP

ING

R407C 4000/

Pipe 9.5219.05flared

Between I.D &O.MAX.Drop 30MAX.Piping length 50

wired control

Refrigerant

Fan

Heat exchanger

48/-/44

Page 17: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Function Cooling HeatingCapacity BTU/h 42000 48000

W 4800 5000W 5700 7200

EER or COP BTU/W 8.75 9.6Dehumidifying capacity 10‐³×m³/hPower cablePower source N,V,Hz

A / AStart Current A

Unit model (color)Fan Type × Number

Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃External (L×W×H) mm×mm×mmPackage (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)Fresh air hole dimension mm

kWdB(A)kg / kg

External (L×W×H) mm×mm×mmPackage (L×W×H) mm×mm×mm

kg / kgUnit model (color)Compressor Model / Manufacture

TypeFan Type × Number

Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h

Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃

External (L×W×H) mm×mm×mm

Package (L×W×H) mm×mm×mm

Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm

Volume of Accumulator LNoise level dB(A)

material of reduce noise crankcase heater power W

kg / kgRefrigerant Type / Charge g

Recharge quantity g/mLiquid mmGas mm

Connecting Methodmm

Cooling:8.3/10.2;Heating:9.5/12.6;49.5

Dimension

PVC 26/32

3N380V-400V 50HZ

Item model AU42NAIBEA(SANYO)

5/

/

//

Noise level (H-M-L)Electricity Heater

Weight (Net / Shipping) /

/

//

//

/

Between I.D &O.MAX.Drop 30

Out

door

uni

t

AU42NAIBEA(WHITE)

Axial-flow×2

Dimension 980×340×12251050×440×1375

0.92

Defrosting

Indo

or u

nit

/

PIPI

NG

R407C 400065

Pipe 9.5219.05Flare

Weight (Net / Shipping) 91/116

Type of Four way valve DHF-12XPE

43-60

0.151180+30 840+30

ScrollC-SBN373H8A(SANYO)

Pane

l Dimension /

MAX.Piping length 50

//

42

64/-/-

Auto/

Capiliary

TP2M/9.52

Total power inputMax. power input

Running /Max.Running

6000

/Weight (Net / Shipping) /

//

/

13

Page 18: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

WARNING

CAUTIONWARNING

CAUTION

This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior

environment such as engineering shop could cause equipment malfunction.

Please entrust installation to either the company which sold you the equipment or to a professional contractor.

Defects from improper installations can be the cause of water leakage, electric shocks and fires.

Execute the installation accurately, based on following the installation manual. Again, improper installations can

result in water leakage, electric shocks and fires.

When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned

countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.

In regards to preparing this countermeasure, consult with the company from which you purchased the equipment,

and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold

concentration does occur,there is the danger of a resultant oxygen deficiency accident.

For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,

injury can result from a falling of the unit.

Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and

hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.

For electrical work, please see that a licensed electrician executes the work while following the safety standards

related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive

use circuits are used.

Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and

fires.

Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to

the terminal connection part, through properly securing it. Improper connection or securing can result in heat

generation or fire.

Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can

also result in heat generation or fire.

WARNING

In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.After completing the installation, along with confirming that no abnormalities were seen from the operation tests, pleaseexplain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's manual.Moreover, ask the customer to keep this sheet together with the owner's manual.

Please read these "Safety Precautions" first then accurately execute the installation work.Though the precautionary points indicated herein are divided under two headings, and those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the section. However, there is also a possibility of serious consequences in relationship to the points listed in the section as well.

- 14-

SAFETY PRECAUTIONS

3 SAFETY PRECAUTIONS

Page 19: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated

refrigerant (please see nameplate) within the refrigeration cycle.

Rupture and injury caused by abnormal high pressure can result from such mixing.

Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this

company can result in water leakage, electric shock, fire and refigerant leakage.

The position of indoor unit must be above the floor 2.5m.

WARNING

Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone

ground wire.

Improper placement of ground wires can result in electric shock.

The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not

installing an earth leakage breaker may result in electric shock.

Do not install the unit where there is a concern about leakage of combustible gas.

The rare event of leaked gas collecting around the unit could result in an outbreak of fire.

For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to

prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.

CAUTION

-15

SAFETY PRECAUTIONS

Page 20: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

185 185

30

52

88Screw Hole

(M10)

580

950

Power wiring Terminal

7018

18

38

34

0

38

38

01

25

0

25

16

3 Net dimensionsof indoor unit and outdoor unit 1)Outdoor unit

Page 21: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

1340

950

840

3022

020

5028

0

260

315270

135

160 30

0

295

1070

780

860-

890

615

615

1250-1280 (ceiling hole)

over10

00m

m

155

123055 55

220

over1500

over1500

over

1500

over

1500

(hanging position)

Model: AB36NACBEA Cassette type Indoor unit

- 17 -

NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

2)Indoor unit

Page 22: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Model: AC36NACBEA Convertible Indoor unit

R15

85

100

195

19201800

600

690

630

100

85

310

590

545

40

235

150 18

0

85 150

60

195

600

105

600

300300

555

30

110

60

8530

0

1010

25

6545

drainage pipe

NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

18

Page 23: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT

A-A

gas

pipe

liqui

d pi

pedr

aina

ge p

ipe

Model: AD36NAMBEA AD42NAMBEA

19

Page 24: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Model: AD36NAHBEA AD42NAHBEA

Page 25: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

5.1.1 Installation tools 1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner,

shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter

7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor

11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump 15 .Flat screwdriver

5.1.2 Standard accessories

Part name

QTY

Shape

Clamp

2 Piece

Washer

8 Piece 6 Piece

Clamp Paper pattern

1 Set

6321

3 Piece

Screw(M5 size)

For installationofpaper pattern

Drain hose

1 Piece

Please check if your unit is delivered with following

Part name

QTY

Shape

Dry batteryInsulator Sealing pad Sealing pad Sealing pad7 8 9 12

1 Piece 1 Piece

Insulator

2 Piece 1 Piece 1 Piece 2 Piece

Small sizeMedium sizeLarge sizeFor liquid pipeFor gas pipe R03, 7#

[Other]

OperationManualOrnamentpanelRemotecontroller

54

1110

5.1.3 Installation of indoor unit5.1.3.1 Before installation

Determine the way kto carry unit to installation place.Don't remove packing until unit reaches installation place.If unpacking is unkavoidable, protect unit properly.

5.1.3.2 Selection of installation place(1) Installation place shall meet the following and agreed by customers:

Place where proper air flow can be ensured.No block to air flow.Water drainage is smpoth.Place strong enough to support unit weight.Place where inclination is not evident on ceiling.Enough space for mainenance.Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. Thisis helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radiowave is strong)

- 20 -

INSTALLATION INSTRUCTIONS

5 INSTALLATION INSTRUCTIONS 5.1 Cassette type

Page 26: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

8

260

260

(2) Ceiling heightIndoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and InstallationManual of ornament panel.)

(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced)

Installation space

Air inletAir outlet

2500

Ove

r

Air outlet1500 Over1500 Over 1500 Over 1500 Over

Air outletAir inlet

Air inlet

5.1.3.3 Preparation

(1) Position of ceiling opening between unit and suspending bolt.Unit: mm

- 21 -

INSTALLATION INSTRUCTIONS

50~1

00

RoofAnchor boltLong nutSuspending bolt

Ceiling

(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole. Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer(3) Install a suspending bolt. (Use a M10 bolt)

To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For newceiling, use built-in type bolt or parts prepared in the field.Before going on installing adjust space between ceiling.

<Installation example>

Note: All the above mentioned parts shall be prepared in field.

890(Ceiling opening)(Distance between suspending bolts)1070

515

515

(Dist

ance

betw

een s

uspe

nding

bolts

)

860(

Cei

ling

open

ing)

780 20 Over

wn04
Page 27: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

5.1.3.4 Installation

4 5

7

(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.

(1) Install unit temporally

In the case of new ceiling

Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.

< After installation on the ceiling >(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))(4) Check unit's horizontal level.

Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level usinghorizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problemmay occur on floating switch, causing water leakage.)

(5) Remove the washer mounlting , and tighten the nut above.(6) Remove the paper pattern.

(1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. Fix the bracket firmly.(2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ).(3) Proceed with and of "In the case of new ceiling".

LevelPolythene pipe

3 4

In the case of ceiling already exists

Scrtews at the piping outlet is fixed at the cornerof drain pan.

Center of ceiling hole Paper pattern 4Paper pattern

5Screw (accessory)5Screw(accessory)

[Fix the paper pattern]

5.1.3.5 Refrigerant piping

As for outdoor piping, please refer to installation Manual of outdoor unit.

6 9

Apple refrigerant oil

Torque spanner

spanner

Piping joing

Flare nut

Medium size seal pad 9 (accessory)

Clip 3

Gas pipeLiquid pipe

Insulator (accessory)

(For liquid pipe)Insulator (accessory)

(For gas pipe)

7

6

(Cover the piping joint with seal pad.) R0.4 ~ 0.8

A

Pipesize

Tightentorque A(mm) Flare shape

9.52 3270~3990N.cm

(333~407kgf.cm)

19.059720~11860N.cm

(990~1210kgf.cm)

12.0~12.4

22.9~23.3

900.

545

2

Outdoor is precharged with refrigerant.Be sure to see the Fig.1, when connecting and removing piping from unit.For the size of the flare nut, please refer to Table 1.Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it.Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).Check piping joints for gas leakage. Insulate piping as shown in Fig. below.Cover joint of gas piping and insulator with seal .

Table 1

Diameter of Pipe

Liquid Pipe 9.52mm

Gas Pipe 19.5mm

Tighten Torque

42N. m

60N. m

- 22 -

INSTALLATION INSTRUCTIONS

Page 28: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

5.1.3.6 Installation of drainage pipe

1-1.5m

Use the self-provided stiff pipe and clip with unit. Insert water pipe into water plug until it reaches the white tape.Tighten the clip until head of the screw is less than 4mm from hose.Wind the drain hose to the clip using seal pad 8 .Insulate drain hose in the room.

2

<Cautions for the drain water lifting pipe>

Clip 2

Tape (White) Self-provided stiff pipe

Clip 2

4mm below

(accessory)

(accessory)Large size seal pad

Clip 2

10

Installation height shall be less than 280mm.There should be a right angle with unit, 300mm from unit.

Waterring can of plastic

(1) Install water drainage pipePipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.If downward slope can't be made, take other measures to lift it up.Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.

Slope over 1/100

75 b

elow

Self-provided stiff pipe(accessory)

500

belo

w

300mm below 1~1.5m

280

belo

w

500

belo

w

220

Drain hose 1(accessory) drain water lifting pipe

Suspending bracket

Clip(accessory)

2

Ove

r 100

(Note)

If several water hoses join together, do as per following proceedures.Connect water hoses with a T joint.

Specifieations of the water hoses shall meet the requirements for the unit running.

The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.

Method of water charging

11

When wiring is not complete

Charge water fromair outlet

Charge water frominspecting hole

Watering can of plasticpipe should be about100 mm long

100mm

Water drainage port formaintenance

(Drain water fromthis hole)

Self-provided stiff pipe Maintenance

Inspecting hole

Cover of controll box

PCB on indoorTerminal

Terminal blockConnect withoutdoor unit

1 2 3

L N

Power

1 2 3

Indoor

Outdoor

H07RN-F3G 4mm2

H05RN-F4G 0.75mm2

1 2 3R S T

1 2 3

N

Indoor

Power Outdoor

H05RN-F4G 0.75mm2

H07RN-F5G 2.5mm2

(2) Check if water drainage is smooth after installation.Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.

After wiring

Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uperpart of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block.Note, in this operation, fan will be running.Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove shortconnection of "CHECK" terminal.

Check water drainage in cooling operation. See also test run.

- 23 -

INSTALLATION INSTRUCTIONS

Page 29: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

5.1.3.7 Wiring

Terminal blockClip A

Cover of control box 1

Rubber tube A

Grounding lead

Cover of control box 2

Terminal blockConnect withoutdoor unit

OutIn

Field wiringAttach seal pad

Don't fail to seal it, or, water may come in.

Rubber tube Note: Have it sealed, leaving no space.

Seal pad (small size)( ) (Wind around wire)

12

All supplied parts. materials and wiring operation must in appliance with local code and regulations.Use copper wire only.When make wiring, please refer to wiring diagram also.All wiring work must be done by qualified electricians.A circuit breaker must be installed, which can cut power supply to all system.See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.Connecting of unitRemove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,tighten clamp A. Connect wires of correct pole to the terminal block inside.Wind seal (12) around wires. (Be sure to do that, or, dew may occur).Upon connecting, replace control box cover (1) and (2).

Obscrve the following when connecting power supply terminal block: Don't connect wires of different specifications to the same terminal block. (Loose wire may cause overheating of circuit) Connect wires of same specifications as shown in right Fig.

Connect wires of the samespecifications at two sides.

Don't connect wires of thesame specifications at one side.

Don't connect wires of thedifferent specifications.

<<WARNING>>

5.1.3.8 Wiring example

As for outdoor unit circuit, please see Installation Manual of outdoor unit.Note: All electric wires have their own poles, poles must match that on terminal block.

5.1.3.9 Installation of ornament panel

1. Prepare ornament panel Handling of ornament panel

Ornament panel shall not be placed face down or against wall, neither on an uneven object.Don' t bend carelessly the swing flap, or, problem may occur.

(1) Remove air inlet grill from ornament panel:Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)Lift it up for about 45 degree and remove it from ornament.Tear off adhesive tape fixing air filter on the back of the airinlet grill. (Refer to Fig. 2)

Cautions for the installationBe sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation, read alsothe Installation Manual of indoor unit.With this ornament , 2 or 3 air flow direction is not available. Suitable height is 3 m.

2

Accessory Pad Pad

1

Bar

- 24 -

INSTALLATION INSTRUCTIONS

Page 30: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

5 _ 8mm

3

2

2

1

4

Holding ring

Piping hole position

Swing flap motor

Fig. 7

SealIndoor unitCeiling material

Ornament panel

(2) Remove cover plate at corner Tear off the adhesive tape, and slide it off. (Refer to Fig. 3)

(1)

(2)

2. Install ornament panel on indoor unit.

As shown in Fig . 7, match the position ofswing flap motor with that of the indoor unitpiping hole , so that ormament panel can beplaced on to indoor unit.Installation of ornament panelPlace the holding ring on swing flao motorside teporarily on hooks of the indoor unit.(2 pcs)Put the other two holding rings on the hooks atboth side of the indoor unit. (Care should betaken not to push wiring of swing flap motorinto seals).Screw in all 4 screws under holding ring forabout 15mm. (Pancl will rise).Adjust the ornament panel as per Fig. 7 tocover opening on the ceiling.Tighten screws to redrce the thickness of sealsbetween ornament and indoor unit to 5-8mm.

1

2

3

4

5

If indoor unit is at horizontal leveland water drainage is smooth,then, indoor unit height can be ad-justed throrgh holes at corners ofornament panel.

If screws are not tighten tight, problems in Fig, 8might occur. Tighten screws properly.

If there are still space after tighteningof screws, please readjust the heightof indoor unit. (Refer to Fig. 9)

Leave no space. Fig. 9

Gas leakage.

Gas leakage from roof.

Contamination Mist exists and drop down.

Fig. 8

45

Fig. 2

Adhesive tape

Slide

Fig. 3

For indoor unit installation, please refer to Installation Manual.Hook

Caution

12

Leave no space.

Fig. 6

3. Mounting on high ceiling(1) Ornament panel can be mounted on ceiling as high as 3 m.(2) Please install pad as accessary.

Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4)Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.

Fig. 4

(3)Wiring on ornament panel Connecting of wiring of the swing flap motor on ornament panel. (2 places) (Refer to Fit . 10)

50

Cutting line

100a b

Place it on the frame.

Part a of the padPart a of the pad

Swing flap motor Fig. 5

Side of ornament panel

Fig. 10

Wiring diagramSide of indoor unit

If connecting is not made, error code(A7) appears on remote controller. So,make proper connecting.

- 25 -

INSTALLATION INSTRUCTIONS

Page 31: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

1

2

4. Installation of inlet grill and cover plateInstallation of inlet grillInstall in reversed order of “Prepare ornament pandl”.Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted asper customers request.

(1)

When installing inlet grill, take care not to twist wiring of swing flap motor.

Install cover plate on the corner As shown in Fig. 11 tie the cover plate onto the bolt on ornament plate. Install cover plate onto ornament plate. (Refer to Fig. 12)

(2)

Slide all five hold ringsto let them drop in holes

on ornament plate,

Fig. 12Fig. 11

bolt

5.1.3.10 Test running

Refer toTake special care during installation, check after working

(1)(2)(3)(4)(5)(6)

Proce-dure OperationOpen check valve on gas pipe.Open check valve on liquid pipe.Press ON/OFF button, select Cooling mode.Let it run for 3 min.Press air flow adjust button to make unit run properlyConfirm unit functions according to Operation Manual.

Upon installation of piping, water drainage and wiringwork, make test run to ensure proper unit operation.

(1)(2)(3)(4)(5)

Procedure Operation

Open check valve on gas pipe.Open check valve on liquid pipe.Press ON/OFF button, select Cooling mode.Let it run for 3 min.Cut main power supply after operation.

Conduct test run before installing ornament panel

Note:If unit doesn’t run due to certain problem, please see‘‘Note to unit maintenance’’.

Conduct test run after installation of ornament panel

- 26 -

INSTALLATION INSTRUCTIONS

Page 32: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

5.1.4 Installation of outdoor unit

580

380

5.1.4.1 Selection of installation placePlace strong enough to support the unit and will not cause vibration and noise.Place where discharged wind and noise do not cause a nuisance to the neighbors.Place where is less affected by rain or direct sunlight and is sufficiently ventilated, or to install a shield.Place with enough space for smooth air flow.The unit shall not be installed on an unspecifised metal frame (e.g. theft guard net).If the outdoor unit is installed close to a street, it shall be no less than 2.5m from the ground.

5.1.4.2 Fixing of the unitFix outdoor unit using M10 bolt to concrete floor horizontally.If installed on the wall or on top of a roof, bracket should be fixed securely to resist earthquake or storms.Use rubber pad during installation against unit vibration.Install the unit so that the angle of inclination must be less than 3 degrees.

2

Liquid(Thin)

Gas(Thick)

3way V.

2way V.

Vacuum pump

Gaugemanifold

2 Open

3

5.1.4.3 Air purging method: To use vacuum pumpFor those models which adopt R407C refriengerant shall only use vacuum pump topurg air.

Detach the service port's cap of 3-way valve, the valve rod'scap for 2-way valve and 3-way's, connect the service portinto the projection of charge hose (low) for gaugemanifold.Then connect the projection of charge hose (center) forgaugemanifold into vacuum pump.

1

Open the handle at low in gaugemanifold, operatevacuum pump. If the scale-moves of gause (low)reach vacuum condition in a moment, check 1 again.

Vacuumize for over 15min. And check the levelgauge which should read -0.1 MPa (-76 cm Hg)at low pressure side. After the completion ofvacuumizing, close the handle 'Lo' in gaugemanifoldand stop the operation of the vacuum pump.Check the condition of the scale and hold it for1-2min. If the scale-moves back in spite oftightening, make flaring work again, the returnto the beginning of 3 .

185 185

Installation dimension of outdoor unit (mm)

INSTALLATION INSTRUCTIONS

Page 33: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

4

5

6

8

7

90°

3

3way V.

2way V.

6

6

for 6 sec.Service port

3way V.

2way V.

90°

4

If it does not stop gas leakage, discharge wholerefrigerants from the serice port. After flaring workagain and vacuumize, fill up prescribed refrigerantfrom the gas cylinder.

Open the valve rod for the 2-way valve to andangle of anticlockwise 90 degree.After 6 seconds later, close the 2-way valve andmale the inspection of gas leakage.

In case of gas leakage, tightenparts of pipe connection. If leakagestops, then proceed steps.No gas leakage? 6

Detach the charge hose from the service port, open2-way valve and 3-way. Turn the valve rodanticlockwise until hitting lightly.

After attaching the each caps, check the gas leakagearound the caps.

To prevent the gas leakage, turn the service port'scap, the valve rod'd cap for 2-way valve and 3-way'sa lottle more than the point where the torque increasessuddenly.

7 Valve rod cap

7 Valve rod cap

3way V.

2way V.

5 Service port cap

If needing to remove the refrigerant gas when installation or repair , please refer to thefollowing procedures:1. Cut off the power2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out.3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure.

4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure pressure-switch properly.

- 28 -

INSTALLATION INSTRUCTIONS

Page 34: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

INSTALLATION INSTRUCTIONS

GAS LEAKAGE INSPECTION

After connecting the piping, check the joints for gas leakage with gas leakage detector.

CAUTION

HOW TO CONNECT WIRING TO THE TERMINALSA. For solid core wiring (or F-cable)(Fig.28A)(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire.(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screw driver.

B. For strand wiring(Fig.28B)(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand wiring.(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.

Fig. 28

Screw withspecial washer

Roundterminal

Wire

Terminalboard

Screw withspecial washer

Roundterminal

Wire

A. Solid wire

Insulation

Strip

25m

m

Loop

B. Strand wire

Strip

10m

m

Roundterminal

After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as shown in Fig.29

HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP

Fig. 29

Cord clamp

Insulation tube

Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

Item to the checked

5.5 Pay special care to the following and check after installation

Unproper installation may cause CheckIs indor indoor unit firmly installed?Is gas leakage dheck performed?

Is unit properly insulated?

Is water drainage smooth?

Is power voltage meet that stipulated on the nameplate?

Is wiring and piping correctly arranged?

Is unit safely grounded?Is wire size correct?

Are there any obstacles on air inlet and outlet grill ofindoor and outdoor unit?

Is record made for piping length and refrigerantcharging amount?

Unit might fall down, make vibration or noise.

This may lead to gas shortage.

Dew or water drop may occur.

Dew or water drop may occur.

Problem may occur or parts got burned.

Problem may occur or parts got burned.There might be a danger of electric shock.

Problem may occur or parts got burned.

This may cause poor cooling.

It is hard to control refrigerant chargingamount.

Page 35: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

(1) If possible, do not install the unit where it will be exposed to direct sunlight.(If necessary, install a blind that does not interfere with the air flow.)(2) Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible.(3) Install the unit where connection to the indoor unit is easy.(4) During heating operation, drain water flows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed.(Reverse cycle model only)(5) Do not place animals and plants in the path of the warm air.(6) Take the weight of the air conditioner into account and select a place where noise and vibration are small.(7) Select a place where the warm air and noise from the air conditioner do not disturb neighbors.(8) Provide the space shown in Fig.2 so that the air flow is not blocked. Also for efficient operation, leave open three of the four directions front, rear, and both sides.

For authorized service personnel only

5.2.1SELECTING THE MOUNTING POSITION 2. OUTDOOR UNIT

Decide the mounting position with the customeras follows:1. INDOOR UNIT

(1) Install the indoor unit level on a strong wall, floor, ceiling which is not subject to vibration.(2) The inlet and outlet ports should not be obstructed: the air should be able to blow all over the room.(3) Install the unit near an electric outlet or special branch circuit.(4) Do not install the unit where it will be exposed to direct sunlight.(5) Install the unit where connection to the outdoor unit is easy.(6) Install the unit where the drain pipe can be easily installed.(7) Take servicing, etc. into consideration and leave the spaces shown in Fig.1. Also install the unit where the filter can be removed.NOTE: The appearance may be different from models.

(1) Install the unit where it will not be tilted by more than 5•(2) When installing the outdoor unit where it may be exposed to the strong wind, fasten it securely.

Install at a place that can withstand the weight of theindoor and outdoor units and install positively so thatthe units will not topple or fall.

CAUTION(1)Do not install where there is the danger of com- bustible gas leakage.

(2) Do not install near heat sources.

(3) If children under 10 years old may approach the unit, take preventive measures so that they can- not reach the unit.

L2

L3

L1

500(Servicingspace)

Air outlet

Air inlet

Airinlet

Series 36 42Case

DistanceL1

L2

L3

open open open open500 500

300 300open open0 0

100 300 150 150 150300

I II III I II III

Be careful not to scratch the room air conditioner when handing it.After installation, explain correct operation to the customer, according to the operating manual.Let the customer keep this installation manual because it will be used when the room air conditioner is servicedor moved.

WARNING(1) For the room air conditioner to operate satisfactorily, install it as outlined in this installation manual.(2) Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available from our standard parts. This installation manual describes for the correct connections so that the installation set available from our standard parts should be used.

(3) Installation work must be performed in accordance with national wiring standards by authorized personnel only.(4) Never cut the power cord, lengthen or shorten the cord, or change the plug.

(5) Also, do not use an extension cord.

(6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.

(7) Do not turn on the power until all installation work is done.

WARNING WARNING

5.2 INSTALLATION INSTRUCTIONS--Convertible type

INSTALLATION INSTRUCTIONS

Page 36: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Floor consoleFig. 1

2 cmor more

Ceiling

Indoor unit

30 cmor more

30 cmor more

Left

Right

30 cmor more

30 cmor more

1.5m

1.5m

1.5m

Left Right

may be different

For series 36,42

Note: For series 36, 42 no floor console type, the function below about floor console is invalid to the series.

Fig. 2

Under ceiling

INSTALLATION INSTRUCTIONS

Page 37: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Mark Parts nameAdhesive tape

Saddle (L.S) with screwsConnecting electric cablefor indoor and outdoor

Drain hose

Heat insulation material

Piping hole cover

Putty

Plastic clamp

Optional parts

A

B

C

D

E

FG

H

5.2.2 STANDARD PARTSThe following installation parts are furnished.Use them as required.

ACCESSORIES

Name and shape Q'ty Application

6For fixing the wallbracket.For series 24,28,36,42no this part.

Tapping screw( 4x20)

Coupler heat insulator(large)1

For indoor side pipejoint (Large pipe)

Coupler heat insulator(small) 1 For indoor side pipejoint (Small pipe)

Nylon fastener1 For fixing the drain

hose

Drain hose

Non-adhesive tape

1

1

VT wire 1For fixing the drainhose L 280mmFor series 24,28,36,42VT wire is not available

Remotecontroller

Battery

1

2

Use for air conditioneroperation

For remote controllerunit

Name and shape Q'ty Application

1For series 24,28, 36,42the two cover plate arenot available

Cover plate (left)

Cover plate (right)

Installationtemplate

Anchor bolt

Spring washer

Special nut

Pipe hole cover

Wall hole cover

Main pipes

Connecting cables

1

2

1

4

4

4

1

1

1

1

For positioning theindoor unitFor under ceiling type.

For suspending theindoor unit from ceiling

4

Tapping screw( 4x10)

Cushion

Drain-elbow1

Only for the heat pumptype

Wall bracket 2For suspending the indoorunit on the wall.For series24,28,36,42 no this part.

INSTALLATION INSTRUCTIONS

wn04
Page 38: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

INSTALLATION PROCEDURE

PREPARING INDOOR UNIT INSTALLATION

1. REMOVE THE INTAKE GRILL

Install the room air conditioner as follows:

Open the intake grill and remove the three or four or six screws.(Fig. 3)

5.2.3CONNECTION PIPE REQUIREMENTTable 1

SeriesDiameter

Liquid side Gas sideMaximum length

Maximum height(between indoor and outdoor)

9.52 mm 19.05mm 50 m 15 m36

Remark: The main unit can be wired before the indoor unit is installed. Select the most appropriate installation order.For series36,42 not the power plug, but 3-core connecting cable.

Fig. 3Machine screw

Tapping screw

Tapping screw

Intake grill

INSTALLATION INSTRUCTIONS

42 9.52 mm 19.05mm 50 m 15 m

Select piping and drain directions. only have rear side(Fig.13)

A. UNDER CEILING TYPE-THE ONLY WAYUsing the installation template, drill holes for piping and anchor bolts(forholes).(Fig.12)

1. DRILLING FOR PIPING

Fig. 13

CAUTIONInstall the drain hose at the rear; it should not be installedon the top or right side.

When the directions are selected, drill 80mm and 50mm or 150mmdia. hole on the wall so that the hole is tilted downward toward theoutdoor for smooth water flow.

AB40 40

100mm

720m

m

87.5mm

147m

m32

6mm

247m

m

8553

series A B3642 1920 1840

18401920

Rear (Install the drain hosein the direction.)

Right

Wall6mm

60 to

70m

m

12.7mm

Fig. 16

Insert the anchor bolts into the drilled holes, and drive the pinscompletely into the anchor bolts with a hammer. (Fig. 16)

2. DRILLING HOLES FOR ANCHOR BOLTS AND INSTALLING THE ANCHOR BOLTS

Fig. 15

With a concrete drill, drill four 12.7 mm dia. Holes.(Fig.15)

3. INSTALLING BRACKETS

Fig. 17

Install the brackets with nuts, washers and springwashers.(Fig. 17)

Spring washer

Special nut Bracket

Page 39: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

4. INSTALLING INDOOR UNIT

68 16 21 28381

232

26.5

26.5

2-R2.5

10

187.5

4-R5

68162128381

23226.5

26.5

2-R2.5 10

187.54-R5

Reset the hex bolts as shown in Fig.18.

Hex bolt

8 to 13mmIndoor unit

Fig. 18

Apply the indoor unit to the brackets.(Fig.19)

Now, securely tighten the hex bolts in both sides.

Fig. 19

Bolt Bracket

Indoor unit

INSTALLATION INSTRUCTIONS

5. INSTALL THE DRAIN HOSESelect whether the drain hose will be connected to the left or rightside.(Fig.5)Insert the drain hose into the drain pan, then secure the drain hosewith a nylon fastener.(Fig.8)Wrap the insulation (drain hose)around the drain hose connection.(Fig.9)Be sure to arrange the drain hose correctly so that it is leveled lowerthan the drain hose connecting port of the indoor unit.(Fig.20)

Fig. 20 Remove the hole cover.

Fig. 21

When drain hose is arranged backward.Secure the drain hose with the VT wire. (Fig. 21)

OK

Arrange the drain hoselower than this portion

Drain hose

NO

VT wire hole

Drain hose

Piping hole

5.2.4 GAS LEAKAGE INSPECTION

After connecting the piping, check the joints for gas leakage with gas leakage detector.

CAUTION

HOW TO CONNECT WIRING TO THE TERMINALSA. For solid core wiring (or F-cable)(Fig.28A)(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire.(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screw driver.

B. For strand wiring(Fig.28B)(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed strand wiring.(2) Using a screwdriver, remove the terminal screw(s)on the terminal board.(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.

Fig. 28

Page 40: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

INSTALLATION INSTRUCTIONS

Fig. 28

Screw withspecial washer

Roundterminal

Wire

Terminalboard

Screw withspecial washer

Roundterminal

Wire

A. Solid wire

Insulation

Strip

25m

m

Loop

B. Strand wire

Strip

10m

m

Roundterminal

After passing the connection cord and power cable through the insulation tube, fasten it with the cord clamp, as shown in Fig.29

HOW TO FIXED CONNECTION CORD AND POWER CABLE AT THE CORD CLAMP

Fig. 29

Cord clamp

Insulation tube

Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

1. INDOOR UNIT SIDE(1) Remove the electric component box.

ELECTRICAL REQUIREMENTElectric wire size and fuse capacity:

Table 5

ELECTRICAL WIRING

Series

Connection cord (mm2)

Fuse capacity(A)

MAX

MIN

36 42

3.5

2.5

30

CAUTION(1) Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the electric parts.(2) Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.(3) Always fasten the outside covering of the connection cord with the cord clamp.(If the insulator is chafed, electric leakage may occur.)(4) Always connect the ground wire.

3.5

2.5

30

INDOOR UNIT SIDE

Fig. 30

Electric component box

Fig. 31Electric component box

Remove the four tappingscrews.

CAUTIONDo not remove the screws. If the screwsare removed, the electric componentbox will fall.

Page 41: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

(2) Pull out the electric component box.

Fig. 32

(3) Remove the electric component box cover.Fig. 33

(1) Remove the cord clamp.(2) Process the end of the connection cords to the dimensions shown in Fig.34.(3) Connect the end of the connection cord fully into the terminal block.

(4) Wiring

CAUTIONBe careful not to pinch the lead wiresbetween the electric component boxand base.

(4) Fasten the connection cord with a cord clamp.(5) Fasten the end of the connection cord with the screw.(6) The power cable and connecting are self-provided

Outdoorunit

Indoorunit

Outdoorunit

1 2 3

1 2 3NTSR

Base

Electric component box cover

Remove the three tapping screws.

Electric component box

INSTALLATION INSTRUCTIONS

5.2.5TEST RUNNING

(1) The power source capacity must be the sum of the room air conditioner current and the current of other electrical appliances. When the current contracted capacity is insufficient, change the contracted capacity.

(2) When the voltage is low and the air conditioner is dif- ficult to start, contact the power company the voltage raised.

CAUTION

1. CHECK ITEMS(1) INDOOR UNIT

(1) Is operation of each button on the remote control unit normal?(2) Does each lamp light normally?(3) Do not air flow direction louvers operate normally?(4) Is the drain normal?

(2) OUTDOOR UNIT

(1) Is there any abnormal noise and vibration during operation?(2) Will noise, wind, or drain water from the unit disturb the neighbors?(3) Is there any gas leakage?

ELECTRICAL WIRING

(1) Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner.

(2) Use a circuit breaker and receptacle matched to the capacity of the room air conditioner.

(3) The circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3mm between the contacts of each pole.

WARNING

(4) Perform wiring work in accordance with standards so that the room air conditioner can be operated safely and positively.

(5) Install a leakage circuit breaker in accordance with the related laws and regulations and electric company standards.

5.2.6 CUSTOMER GUIDANCEExplain the following to the customer in accordance with theoperating manual:

(1) Starting and stopping method, operation switching, temperature adjustment, timer, air flow switching, and other remote control unit operations.(2) Air filter removal and cleaning, and how to use air louvers.(3) Give the operating and installation manuals to the customer.

Page 42: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

For inspection and maintenance

When you change your address or the installation place

Electric work

Confirm the following items for safe and comfortable use of air conditioner.The installation work is to be burden on the sales dealer, and do not conduct it by yourself.

Installation placeAvoid installing the air conditionernear the place where possibility ofinflammable gas leakage exists.

Install the unit at well ventilatedplace.

Install the air conditioner firmlyon the foundation that can fullysupport the weight of the unit.

If not, it may cause vibration or noise.If some obstacle exist, it may causecapacity reduction or noise increase.

Explosion (Ignition) may occur.

Select the place so as not toannoy neighbor with the hot airor noise.

Snow protection work isnecessary where outdoor unit isblocked up by snow.

It is advisable not to install the air con-ditioner at the following special place.It may cause malfunction, consult thesales dealer when you have to installthe unit on such a place.

The place where corrosive gas generates(Hot spring area etc.)The place where salt breeze blows(Seaside etc.)The place where dense soot smoke existsThe place where humidity is extraordina-rily highThe place where near the machine whichradiates the electromagnetic waveThe place where voltage variation is con-siderably large

For details consult your sales dealer.

The electric work must be burden on the authorized engineer with qualification for electric work andgrounding work, and the work must be conducted in accordance with electric equipment technical standard.

The power source for the unit is to be of exclusive use.An earth leakage breaker should be installed.(This is necessary to prevent electric shock.)The unit must be grounded.

Special technology is required for removal or reinstallation of air conditioner, consult the salesdealer. Besides, construction expense is charged for removal or reinstallation.

The capacity of air conditioner will decrease by contamination of inside of unit when it is used forabout three years although depending upon the circumstances under which it is used, and so inaddition to the usual maintenance service, special inspection/maintenance service is necessary.It is recommended to make a maintenance contract (charged) by consulting your sales dealer.

5.3 INSTALLATION INSTRUCTIONS-Duct type

INSTALLATION INSTRUCTIONS

Page 43: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

a. Remove upper part of wireRemove upper part of wire controller

b. Install wire(1) For exposed installation, use 2 wood screws(accessory).

Note: Try as far as possible a flat surface for installation. Don't use excessive

PCB is mounted on lower part of wirecontroller, be careful not to damage

Lower part of wirecontroller

Upper part of wirecontroller

(2) For recessed installation, use 2 wood screws(accessory).

c. Indoor unit wiringConnect terminals (A,B,C,D) on lowerpart of wire controller to terminals (A,B,C,D) on PCB of indoor unit.

Hint:When make wiring, pleasekeepa distance between wiresand power supply cord.

Cord kind

Size

Shield wire (4 core) (refer to Hint 3,4)

0.33mm2

Wire size

Use shielede wires for telecommunicationbetween wire controller and indoor unit;indoor unit and outdoor unit. Ground theshield on one side.Otherwise misoperation because of noisemay occur.Signal wire is self-provided.

Shielded wire

ground

Lower part ofwire controller

A B C D

Upper part ofwire controller

wiring from here

d. Replace the upper part of wire controller

Hint: 1. Switch box and cord for wiring are not supplied.Be careful not to press the wiring.

2. Don't touch PCB with hand.

Hint: Tread surface of the terminal well so that shielding may not contact other part.

INSTALLATION INSTRUCTIONS

5.3.1 Installation of the wired remote controlller

Page 44: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Edging

(2) Installation where the area with strong winds.Install the unit so that the air outlet section of the unit must NOT be facedtoward wind direction.

(1) Open space requirement around the unit

b. Selection of the place of installation

a. Accessories"Edging" for protection of electric wires from anopening edge.

Select the place of installation satisfying the following conditions and, at the same time, obtaina consent from the client or user.

Place where air circulates.Place free from heat radiation from other heat sources.Place where drain water may be discharged.Place where noise and hot air may not disturb the neighborhood.Place where there is not heavy snowfall in the winter time.Place where obstacles do not exist near the air inlet and air outlet .Place where the air outlet may not be exposed to a strong wind.Place surrounded at four sides are not suitable for installation. A 1m or more of overheadspace is needed for the unit.Mount guide-louvers to place where short-circuit is a possibility.When installing several units, secure sufficient suction space to avoid short circuiting.

<Heat Pump model/Cooling Only model >WARNING

BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNINGINSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUSINJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.

Unit

Concrete foundationAnchor bolt

Concrete foundation Foundation anchor

Note (1) Give enough room for theconcrete foundation to fix by anchor bolts.

(a)

Note (1) Place the concrete foundation deepenough.

Install the unit so that the angle of inclination must be less than 3 degrees.

c. Installation of outdoor unit

Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .(1) Installation

L2

•L3

•L1

•500

(Servicingspace)

Air outlet

Air inlet

Airinlet

Unit: mm

•Case

Distance I II IIIopen open

open

500

150150 300300 0

L1

L2

L3

Anchor boltConcrete foundationUnitTo fix by bolts

To fix by bolts

Anchor bolt Concrete foundation

Unit

INSTALLATION INSTRUCTIONS

5.3.2 Installation of outdoor unit

Page 45: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

(1) Outline piping

d. Refrigerant piping

(2) Piping size

(3) Limitations for one way piping length and vertical height difference.One way piping length:less than 50m (for 36,42 series) Vertical height difference:less than 30m (for 36,42 series).

(4) Purging method ( the refrigerant is R407C)90

0.5

Outdoorunit

Service valve

Flare connection

Check joint

Gas pipe

Liquidpipe

Flare connection

Indoorunit

Install the removed flared nuts to the pipes to be connected,then flare the pipes.

Precautions for refrigerant piping

Do not twist or crush piping.Be sure that no dust is mixed in piping.Bend piping with as wide angle as possible.Keep insulating both gas and liquid piping.Check flare-connected area for gas leakage.

1Detach the service port's cap of 3-way valve, thevalve rod's cap for 2-way valve and 3-way's, connectthe service port into the projection of charge hose(low) for gaugemanifold. Then connect the projectionof charge hose (center) for gaugemanifold intovacuum pump.

To use vacuum pump

3

Vacuumize for over 15min. And check the level gaugewhich should read -0.1 MPa (-76 cm Hg) at lowpressure side. After the completion of vacuumizing,close the handle 'Lo' in gaugemanifold and stop theoperation of the vacuum pump.Check the condition of the scale and hold it for 1-2min.If the scale-moves back in spite of tightening, makeflaring work again, the return to the beginning of 3 .

2Open the handle at low in gaugemanifold, operatevacuum pump. If the scale-moves of gause (low)reach vacuum condition in a moment, check 1 again.

2-way valve

3-way valve

90•Service port4 90• for 6 sec.

Open

For series 36,42

3 Close

2 Open

4

Open the valve rod for the 2-way valve to and angleofanticlockwise 90 degree.After 6 seconds later, close the 2-way valve andmalethe inspection of gas leakage.

Gaugemanifold

Vacuum pump

2-way valve

3-way valve

For series 36,42

90•

Model

Gas pipingLiquid piping

19.05(3/4")x1.0mm9.52(3/8")x0.8mm

42 series

+_

INSTALLATION INSTRUCTIONS

19.05(3/4")x1.0mm 19.05(3/4")x1.0mm

36 series

9.52(3/8")x0.8mm 9.52(3/8")x0.8mm

Page 46: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

e. Electric wiringWARNING

DANGER OF BODILY INJURY OR DEATHTURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFOREMAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BECOMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

(1) Selection of size of power supply and interconnecting wires.

Precautions for Electric wiring

Electric wiring work should be conducted only by authorized personnel.Do not connect more than three wires to the terminal block. Always use round type crimpedterminal lugs with insulated grip on the ends of the wires.Use copper conductor only.

Select wire sizes and circuit protection from table below. (This table shows 20 m lengthwires with less than 2% voltage drop.)

Item

ModelPhase

3

Switch breaker(A)

Circuit breaker

Overcurrent protectorrated capacity (A)

Power sourcewire size

(minimum)

30 20 2.5mm2 36,42 series(380-400V,3N~,50Hz)

Switchbreaker

Earth leakage breakerLeak

current

30 30mA

Liquid pipe 9.52mm

Gas pipe 19.05mm

2-way valve

3-way valve

66 For series 36,42

If needing to remove the refrigerant gas when installation or repair , please refer to the following procedures:1. Cut off the power2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out.3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure.4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure pressure-switch properly.

3-way valve

2-way valve

7 Valve rod capService port cap7

For series 36,42

If it does not stop gas leakage, dischargewhole refrigerants from the serice port.After flaring work again and vacuumize,fill up prescribed refrigerant from the gascylinder.

Detach the charge hose from the service port, open2-way valve and 3-way. Turn the valve rodanticlockwise until hitting lightly.

6

In case of gas leakage, tightenparts of pipe connection. Ifleakage stops, then proceedsteps.

6No gas leakage?

5

CAUTION:If the refrigerant of the air conditioner leaks, it is necessary tomake all the refrigerant out, then charge the liquid refrigerantinto air conditioner according to the amount marked on thename plate.

7

8After attaching the each caps, check the gasleakage around the caps.

To prevent the gas leakage, turn the service port'scap, the valve rod'd cap for 2-way valve and 3-way'sa lottle more than the point where the torqueincreases suddenly.

INSTALLATION INSTRUCTIONS

Page 47: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

(2) Wiring connection

e. Test run

WARNING

Make wiring to supply power to the outdoor unit, so that the power for the indoor unit issupplied by and terminals.

DO NOT CONNECT THE NEUTRAL WIRE TO , OR PHASE. INTERCONNECT-ING WIRES MUST BE WIRED WITH SAME SYMBOLS ON THE TERMINALS OF BOTHINDOOR AND OUTDOOR UNIT.INCORRECT WIRING CAUSE EQUIPMENT DAMAGEOR FIRE.

N R S T

(3) Wiring procedure1) Remove set screws on the side before taking off the front panel toward the direction shownin figure.2) Connect wires to the terminal block correctly and fix the wires with a wire clamp equippednear by the terminal block.3) Route the wires in a proper way and penetrate the wires through the opening for electricwiring on the side panel.

(1) Before starting test run (for all Heat pump models)Confirm whether the power source breaker (main switch) of the unit has been turned on forover 12 hrs to energize the crankcase heater in advance of operation.

(2) Test runRun the unit continuously for about 30 minutes, and check the following.

Suction pressure at check joint of service valve for gas pipe.Discharge pressure at check joint on the compressor discharge pipe.Temperature difference between return air and supply air for indoor unit.

CAUTIONTHIS UNIT WILL BE STARTED INSTANTLY WITHOUT "ON" OPERATION WHEN ELECTRICPOWER IS SUPPLIED.BE SURE TO EXECUTE "OFF" OPERATION BEFORE ELECTRIC POWER ISDISCONNECTED FOR SERVICING.

This unit has a function of automatic restart system after recovering power stoppage.

Interconnectingwires

2

TB1

123

TB2123

TB

RSTN

Outdoorunit

Circuit breakerEarth leakagebreaker

Indoorunit

HIGH VOLTAGE

(For 36,42 series(380-400V,3N~,50Hz))

21

INSTALLATION INSTRUCTIONS

Page 48: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

INSTALLATION INSTRUCTIONS

5.3.3 Installation of indoor unit

(1) Preparation of indoor unitBefore or during the installation of the unit, assemble necessary optional panel etc. dependingon the specific type.

(2) Select places for installation satisfying following conditions and at the same time obtainthe consent on the part of your client user.

(a) Places where chilled or heated air circulates freely.When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases,suggest your client users to install air circulators.(b) Places where perfect drainage can be prepared and sufficient drainage.(c) Places free from air disturbances to the suction port and blowout hole of the indoor unit,places where the fire alarm may not malfunction or short-circuit.(d) Places with the environmental dew-point temperature is lower than 28 and the relativehumidity is less than 80%. (When installing at a place under a high humidity environment, paysufficient attention to the prevention of dewing such as thermal insulation of the unit.)(e) Ceiling height shall have the following height.

Combinationwith silentpanel

416mm416mm

50 or more

Obstacle

100 ormore

100 ormore

1000

or m

ore

Unit: mm

Installation space

42 series

(4) Preparation for suspending the unit

(a) Size of hole at ceiling and position of hanging bolts<Combination with silent panel>

57 A

B

C

(Hanging bolt position)

(Ceiling hole size)

(Panel dimensions)

137

30

30

(Ceiling ~ panelwrap dimensions)

(Cei

ling

~ pa

nel

wra

p di

men

sion

s)

(Han

ging

bolt p

ositio

n)

(Cei

ling

hole

siz

e)

(Pan

el d

imen

sion

s)

7554

5

690

750

70

(Pip

e co

-nn

ectio

n sid

e)

(b) Hanger bolts installationUse care of the piping direction when the unit is

DimensionsA

Unit: mm

B C

1406 1600 1660

1406 1600 1660

Model

42 series

36 series

Hanging bolt M10

Hole-in anchorHole-in plug

Insert

Concrete

installed.

36series

Page 49: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

(5) Installation of indoor unitFix the indoor unit to the hanger bolts.If required, it ispossible to suspend the unit to the beam, etc.Directly by use of the bolts without using the hanger bolts.

When the dimensions of main unit and ceiling holes does not match, it can be adjusted withthe slot holes of hanging bracket.

Note

Adjusting to the levelness(a) Adjust the out-of levelness using a level orby the following method.

Make adjustment so that the relation betweenthe lower surface of the unit proper and waterlevel in the hose becomes as given below.

(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of thefloat switch may occur.

Tap selection on blower unit (When the high performance filter is used.)Taps of blower unit are set at the standard selection at the shipping from factory. Wherethe static pressure is raised by employing such option as the high performance filter,etc., change the connection of connectors provided at the flank of control box as shownbelow.

(6) Drain Piping(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding acrossan elevation or making traps.

When connecting the drain pipe to unit, paysuffcient attention not to apply excess force tothe piping on the unit side. Also, fix the pipingat a point as close as possible to the unit.For drain pipe, use hard PVC general purposepipe VP-25(I.D.1") which can be purchasedlocally. When connecting, insert a PVC pipeend securely into the drain socket beforetightening securely using the attached drainhose and clamp. Adhesive must not be usedconnection of the drain socket and drain hose(accessory).

Drain hoseStagedifferencepartDrain socket

Drain socket

Main unit

VP 25 joint(field purchased)Pipe cover(large)

[for insulation](accessory)

VP 25(field purchased)

Pipe cover[for insulation](field purchased)

Drain hose(accessory)

Pipe cover(small)[for insulation](accessory)

Clamp(accessory) Adhesion

PVC hose

Piping sideSupply water

Water level

0~5 mm(0~0.2")

Bring the piping side slightly lower.

Hanging boltM10 nut

Main unit

M10 washer

M10 spring washer

Do not pipe under water

Keep free from traps

Avoid riding across an elevation

Air vent

Inproper pipingGood piping1.5m ~ 2m

Suspensionbolts

Heatinsulation

A downhill gradeof 1/100 or more

(b)

(c)

RedYellow

WhiteStandard tap (at shipping) High speed tap

Black

Whi

te

Conn

ector

whit

e

Conn

ector

whit

e

Con

trol b

ox s

ide

Mot

er s

ide

Mot

er s

ide

Red

Blue

RedYellow

WhiteBlue

RedYellow

WhiteBlue White

BlueRed

INSTALLATION INSTRUCTIONS

Page 50: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

VP 30

Secure the elevation as high as possible(approx. 100 mm)

A downhill grade of1/100 or more

Drain hose

Joint for VP 25(Local procurement)

600

(Max

imum

loca

l dra

in u

p di

men

sion

)

Right overhead

290~325mm

Attached drain hose clamp

Drain pipingMain unit

Drain situation can be checked with transparent socket

Remove grommet.Make sure to installit back after test.

Insert water supply hosefor 20 mm ~ 30 mm tosupply water.(Insert hose facingtoward bottom.)

Pour water into a convex joint.

When constructing drain piping for several units, positionthe common pipe about 100 mm below the drain outletof each unit as shown in the sketch. Use VP-30(11/4")or thicker pipe for this purpose.Be sure to provide heat insulation to hard PVC pipes ofindoor placement.Do not ever provide an air vent.The height of the drain head can be elevated up to apoint 500 mm above the ceiling, and when an obstacleexists in the ceiling space, elevate the piping to avoidthe obstacle using an elbow or corresponding gadget.When doing this, if the stretch for the needed height ishigher than 500 mm, the back-flow quantity of drain atthe event of interruption of the operation gets too muchand it may cause overflow at the drain pan. Therefore,make the height of the drain pipe within the distancegiven in the sketch below.Avoid positioning the drain piping outlet at a place wheregeneration of odor may be stimulated. Do not lead thedrain piping direct into a sewer from where sulfur gas

Drainage Test

Conduct a drainage test after completion of the electrical work.During the trial, make sure that drain flows properly through the piping and that no waterleaks from connections.In case of a new building, conduct the test before it is furnished with the ceiling.Be sure to conduct this test even when the unit is installed in the heating season.

Procedures

Supply about 1000 cc of water to the unit through the air outlet using a feed waterpump.

(d)

(e)

(f)

(h)

(g)

12

34

12

(In the electrical work has not beencompleted, connect a convex joint in thedrain pipe connection to provide a waterinlet. Then, check if water leaks from thepiping system and that drain flows through

INSTALLATION INSTRUCTIONS

- 45 -

Page 51: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Exhaust holeState seeing from top of unit

Side fresh air inlet

Rear fresh air inlet

Fig.1 Fig.2

(7) Installation work for air outlet ducts

Calculate the draft and external static pressure and select the length, shape and blowout.A Blowout duct

2-spot, 3-spot and 4-spot with 200 type duct are the standard specifications. Determinethe number of spots based on following table.Note (1) Shield the central blowout hole for 2-spot. (2) Shield the blowout hole around the center for 3-spot.

Limit the difference in length between spots at less than 2:1.Reduce the length of duct as much as possible.Reduce the number of bends as much as possible. (Corner R should be as larger aspossible.)

Use a band. etc. to connect the main unit and the blowout duct flange.Conduct the duct installation work before finishing the ceiling.

(8) Connection of suction, exhaust ducts

(a) Duct connection positioni) Fresh air inlet

Inlet can be selected from the side or rear faces depending on the working conditions.Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted.(Side inlet cannot be used.)

ii) Exhaust (Make sure to use also the suction.)Use the side exhaust port.

Good exampleBad exampleBad example

Ceiling surface

Heatinsulation Suction panel

(Silent panel)

Air conditioner main unit

B Special blowout (Option)

A Blowout duct (Optional or marketed item)

C

Hole for check

special inlet (option)(with air filter)

inlet duct (optional or

marketat item)

INSTALLATION INSTRUCTIONS

- 46 -

Page 52: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Item to the checked

5.4 Pay special care to the following and check after installation

Unproper installation may cause CheckIs indor indoor unit firmly installed?Is gas leakage dheck performed?

Is unit properly insulated?

Is water drainage smooth?

Is power voltage meet that stipulated on the nameplate?

Is wiring and piping correctly arranged?

Is unit safely grounded?Is wire size correct?

Are there any obstacles on air inlet and outlet grill ofindoor and outdoor unit?

Is record made for piping length and refrigerantcharging amount?

Unit might fall down, make vibration or noise.

This may lead to gas shortage.

Dew or water drop may occur.

Dew or water drop may occur.

Problem may occur or parts got burned.

Problem may occur or parts got burned.There might be a danger of electric shock.

Problem may occur or parts got burned.

This may cause poor cooling.

It is hard to control refrigerant chargingamount.

- 47 -

INSTALLATION INSTRUCTIONS

Page 53: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

(1) The position relation among hoisting screw (unit: mm)

(3) Hanger bolts installationUse care of the piping direction when the unit is installed.

Hanging bolt M10

Hole-in anchorHole-in plug

Insert

Concrete

360 1270250

794

853853

1103

Down side

Up side

(2) If necessary, cut the opening installation and checking needed on the ceiling. (If has ceiling)Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire(wire controller connection wire, indoor and outdoor unit connection wire) of indoor unit, so thatafter installation, they can be immediately connected with outdoor unit.

Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling evenand flat and prevent the ceiling from vibration. For details, please consult to the builder.

(Use M10 screw bolt)

In order to bear the weight of the unit, for existedceiling, using foundation screw bolt, for new ceiling,using burying embedded screw bolt, burying screwbolt or spot supplied other parts.

Before going on installation, adjust the gaps with ceiling.

3. Preparation before installation

High static pressure duct unit:

Page 54: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

4. Installation of indoor unitFix the indoor unit to the hanger bolts.

If required, it is possible to suspend the unit to the beam, etc.

Directly by use of the bolts without using the hanger bolts.

When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot

holes of hanging bracket.

Note

Adjusting to the levelness

(a) Adjust the out-of levelness using a level or by

the following method.

Make adjustment so that the relation between

the lower surface of the unit proper and water

level in the hose becomes as given below.

(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.

PVC hose

Piping side

Supply water

Water level

0~5 mm

(0~0.2")

Bring the piping side slightly lower.

Hanging boltM10 nut

Main unit

M10 washer

M10 spring washer

Drain hose

StagedifferencepartDrain socket

Drain socket

Main unit

VP 25 joint(field purchased)Pipe cover(large)

[for insulation](accessory)

VP 25(field purchased)

Pipe cover[for insulation](field purchased)

Drain hose(accessory)

Pipe cover(small)[for insulation](accessory)

Clamp(accessory) Adhesion

For drain pipe, use hard PVC general purpose pipeVP-25(I.D.1") which can be purchased locally. Whenconnecting, insert a PVC pipe end securely into thedrain socket before tightening securely using theattached drain hose and clamp. Adhesive must notbe used connection of the drain socket and drainhose (accessory).

(c)

5. Drain Piping

(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an

elevation or making traps.

When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the pipingon the unit side. Also, fix the piping at a point as close as possible to the unit.

Do not pipe under water

Keep free from traps

Avoid riding across an elevation

Air vent

Inproper pipingGood piping

1.5m ~ 2mSuspensionbolts

Heatinsulation

A downhill gradeof 1/100 or more

(b)

Page 55: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Drainage Test

Conduct a drainage test after completion of the electrical work.

During the trial, make sure that drain flows properly through the piping and that no water leaks

from connections.

In case of a new building, conduct the test before it is furnished with the ceiling.

Be sure to conduct this test even when the unit is installed in the heating season.

Procedures

Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.

Check the drain while cooling operation.

(g)

1

2

3

4

1

2

VP 30

Secure the elevation as high as possible(approx. 100 mm)

A downhill grade of1/100 or more

When constructing drain piping for several units,

position the common pipe about 100 mm below

the drain outlet of each unit as shown in the sketch.

Use VP-30(11/4") or thicker pipe for this purpose.

(d)

(e) The stiff PVC pipe put indoor side should be heat insulated.

(f) Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drainhose directly into drainage, where the gas with sulfur may be generated.

Backwater bendBecause the drain spout is at the position, which negative pressure may occur. So with the rise of waterlevel in the drain pan, water leakage may occur. In order to prevent water leakage, we designed abackwater bend.The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint.The backwater bend is set near the air conditioner.

As figure shown, set a backwater bend in the middle of drain hose.

H1

H2

H1=100mm or the static pressure of air sending motor

H2=1/2H1 (or between 50~100mm)

6. Installation of air suction and discharging duct

AInsulation

muffler cavity (air sending)

Sacking joint

Air volume adjuster

Air outlet

Enlarging chart ofprofile chart A

Vibration resistance hook

Checking meatus

Air conditionermain unit

Ceiling

Air suction grille with air filter

Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installationof suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawingand outer static pressure, and choose the discharging duct with proper length and shape.

Page 56: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

The calculation of duct resistance (the simple calculation is as follow table)

Straight part

Bend part

Air out part

Static pressure box

Air inlet grille (with air filter)

Calculate as per 1m length 1Pa, 1Pa/m

Each bend takes as a3~4m long straight duct

Calculate as 25Pa

Calculate as 50Pa/each

Calculate as 40Pa/each

Good exampleBad exampleBad example

The length difference among every duct is limited below 2:1.

Reduce the length of duct as possible as can.

Reduce the amount of bend as possible as can.

Use heat insulation material to bind and seal the part connecting main unit and the flare part of airdischarging duct. Perform duct installation work, before the fitment of ceiling.

7. Calculation method of the dimension of the simple quadrate air ductPresuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side ofthe air duct is fixed as 250mm, as shown below:

Note:1Pa/m=0.1mmAg/mThe chosen chart of simple duct

m3/h(m3/n)100200300400500600(10)800

1,0001,200(20)

250 x 60(mmxmm)

250 x 90250 x 120250 x 140250 x 170250 x 190250 x 230250 x 270250 x 310

Shape

ItemAir volume

Square duct

Dimension

m3/h(m3/n)

1,4001,600

1,800(30)200024003,000(50)3,5004,0004,5005,0005,5006,000(100)

(mmxmm)

250 x 350250 x 390

250 x 430250 x 470250 x 560250 x 650250 x 740250 x 830250 x 920250 x 1000250 x 1090250 x 1180

Shape

ItemAir volume

Square duct

Dimension

Static pressure box

Air conditioner

Equipped withair filter (bought)

BA

A

A

600m3/h(10m3/min)

Duct(mmxmm)

2400m3/h(40m3/min)

250x560

250x190

Air volume

B

A

300m3/h(5m3/min)

Duct(mmxmm)

1200m3/h(20m3/min) 250x310

250x120

Air volume

HDU-24H03/H

HDU-28H03/H

HDU-42H03/H

Page 57: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

8. The attentive matters in installation of air suction and discharging duct

Recommend to use anti-frost and sound-absorbingduct. (locally bought)The duct installation work should be finishedbefore the fitment of ceiling.

The duct must be heat insulated.

The specific air-discharging outlet should be installed atthe place where the airflow can be reasonably distributed.

The surface should leave a checking meatus for checkingand maintenance.

9. The examples of improper installation

Do not use air in duct and take the ceiling inner side instead. The result is because of the irregularouter air mass, strong wind and sunshine, the humidity is increased.

There may be water drop on the outside of duct. For cement and other new constructions, even ifnot taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiberto perform heat preservation to the whole. (use iron net to bind the glass fiber)

Maybe exceeding the unit operation limit (for example: when indoor dry bulb temperature is 35 C,wet bulb temperature 24 C), it may lead to overload of compressor.

Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction,when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow,leading to water leakage.

AirAir

Duct

Special air discharging outlet

Use screw bolt to fix

Air discharging fan

Improper example

Page 58: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

10. The operation method of fan controllerThrough the fan controller switch in the electric box, the air volume of this unit can be continuouslyadjusted.

It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment).

The air volume set should be in the operation air volume range.

Figure I shows the position of fan controller in the electric box and operation method.

After finishing the electric work, perform test run. According to the main points in Figure II making thechosen switch No. accordant. And confirm if it reaches the needed air volume.

Note:1) When operating the fan controller, it is possible to touch the electric charging part, so do cut off thepower supply.

2) Do not set the dial at the position less than 1.

3) The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacitynumber may exceed the permitted operation capacity range, so it is impossible to operate.

4) When delivering from factory, the capacity number of fan controller is set at “No.5”.

Rotate this switch

(capacity numbersetting:No. 1 ~ No. 8)

Once the fan controllerhas trouble, this linkercan perform emergencyassistant control. Whenthis linker is connectedto the linker from thePCB, it can operate withtotal load.

When this linker isconnected to the linkerfrom the PCB, throughthe fan speed adjustmentpanel to adjust speed.

High Condition of standard air volume

Low (air volume 100Pa)

Ou

ter

stat

ic p

ress

ure

Pa

Example ofduct

Lower limit Upper limit

Standard air volume(m3/min)

The example of the method of choosing capacity number:

1) If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m3/min

as working condition point, according to Figure II “The characteristic chart of air volume”, the capacity numberof fan controller is No. 2.

2) If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m3/min as

working condition point, according to Figure II “The characteristic chart of air volume”, the capacity numberof fan controller is No. 4.

200

150

100

50

026 30 34 35 40 43

•••

••

•• •

Figure 1 Figure 2

Page 59: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

11. Refrigerant pipe[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may causewater leakage.]

The outdoor unit has been charged with refrigerant.

When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown,use spanner and torque spanner together.When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Usehand to twist 3-4 rings, then fasten with spanner.

Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown.Only use seal cushion to bind the joint part of air pipe and heat insulation parts.

Paste the refrigerant oil here

Torque spanner

Spanner

Pipe joint

Cone nut

Middle size seal cushion (accessory)

(Use seal cushion tobind the pipe joint)

Clamp

Heat insulation (accessory)

(for liquid pipe)

(for gas pipe)

Heat insulation (accessory)

Gas pipe

Liquid pipe

Liquid pipe Gas pipe Electric box

Upper

Air inlet Air outlet

Down sideDrain hose connection mouth

VP25 PVC pipe

9.52 12.0~12.4

22.9~23.3

3270~3990 N.cm(333~407 kgf.cm)

9720~11860 N.cm(990~1210 kgf.cm)

(mm)

Specification of pipe

15.88

Tighten torque ConeCone dimensionA (mm)

R0.4~0.8

A

90 0.5

45 2

310

30

53080510

Page 60: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

2. Cut and flaring method

Use pipe cutter to cut the pipe, the burrs must be removed.

After inserting the flarer, perform flared nut.

Test run

The following items must be noticed carefully during installation. After finishing installation,performing checking.

After installing the refrigerant pipe, drain hose and electric wire properly, perform test run to ensurethe system not have trouble.

Test run

(1) Open the stop valve of gas pipe.

(2) Open the stop valve of liquid pipe.

(3) Press ON/OFF button to start operation, use wire controller to set to Cooling operation.

(4) Confirm the function of the unit according this manual.

Other instruction1. Power supply

The air conditioner must use a special power circuit. The user should provide by himself withspecial switch (25A~30A), grounding wire. The wiring should be done by a qualified electricianaccording to the wiring rules specified by national standard

An creepage breaker should be installed.

The grounding wire and null wire of the power cord should be strictly separated. It is incorrect toconnect the null wire with grounding wire.

AFlarer

Liquid pipe

Gas pipe

Gas pipe

Dimension A (mm)

1.0-1.2

1.4-2.2

1.4-2.2

Pipe diameter

9.52mm (3/8”)

19.05mm (3/4”)

15.88mm (5/8”)

Correct Incorrect

Slant Broken Burrs Uncompleted Too long

Page 61: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Drain Hose

Swing fender

Refrigerant pipeCable lineEarthing line

Air filter

Outlet

Suction grill

(located in the suction grill)

In cooling operation,todischarge the waterfrom inside the room.

Discharge unit (built in)

(located in the outlet)

Remote Controller

PARTS AND FUNCTIONS

Electric box assy Inlet grill assy

Outlet grill assy

1320X715X235(AXBXC)

Remote control PCB

Convertible type Indoor unit :

6.Parts and functions

Cassette type Indoor unit :

- 48 -

Page 62: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Air inlet

Air outlet

(Inside of unit)Compressor

For series 36, 42

PARTS AND FUNCTIONS

Compressor (inside)

6.1 Drawing

Air outlet

Air inlet

Duct

For series 36, 42

Outdoor unit

Duct type(mid static pressure)

- 49 -

Page 63: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

High static pressure

Air outlet

Air inlet

Duct

Duct

Drainpipe

Page 64: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

14.HIGH/SO ButtonUsed to select HIGH or SOFT operation.

21

22

31

29

32

FRESH

HIGH/SOTIMER

SET

FILTER

B A

M D

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

OFF

AUTO

1

2

3

4

67

9

10

11

15

13

5

8

16

17

30

34

35

33 2324

25

26

2728

20

12

14

Remote controller

1.TEMP Setting Button(Used to set temperature. Setting ranges:16 C to 30 C)In Up/Down function, for controlling up anddown filter.

2.SWING ButtonIf you press this button once, auto swing willbe activated.If you press this button again, the louver willfix in the present position.

3.Power ON/OFF Button Used for unit start and stopAfter power on, the LCD of remote controllerwill display the previous operation state (exceptfor TIMER,SLEEP and SWING state).

4.Operation MODEUsed to select operation mode.Every time you press MODE button, operation modechanges according to following sequence:

5.HEALTH ButtonUsed to set health mode, if the unit has the negative ion functionand oxygen bar function.

AUTO FANHEATCOOL DRY

6.CLOCK ButtonUsed to set correct time.

(Note: if time of TIMER ON is the same as TIMEROFF,TIMER ON/OFF cannot be set)

10.RESET ButtonPress this button by using a sharp article to resumethe correct operation of the remote controller in caseof need, i.e. for example in case of malfunctions dueto electromagnetic noise.

17.SLEEP Button(The clock must be corrected before setting sleepfunction)Used to set sleep mode.

13.Up and down ButtonUsed to set TIMER and CLOCK up or down.

8. FILTER ButtonUsed to set up/down function of filter.

NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating. 2.HIGH/SO button This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high functon" will be cancelled automatically after 15 minutes running.

11.LOCK ButtonUsed to lock operation button and LCD displaycontents: by pressing this button, other buttons comesout of function and lock state display appears; if you pressit again, lock state will be no more active and lock statedisplay will disappear.

7.Remote controller functions

7.CLOCK ButtonUsed to select TIMER ON, TIMER OFF.

9. CODE ButtonUsed to select code A or B, for this unit, the code is A.

18

12.LIGHT ButtonUsed to light the control panel (only for cabinet unit)

15.SET ButtonUsed to confirm TIMER and CLOCK settings.16.FRESH ButtonUsed to set fresh mode, the unit will draw in fresh air.

19

36

Page 65: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Clock Set

Displays when healthy run function is set.

22.TEMPERATURE Display

34.LOCK State Display

33.BATTERY Energy DisplayNotify the user when it is time to changethe batteries.

24.HIGH/SO Display25.SIGNAL SENDING Display26.FRESH AIR Display27.ELECTRICAL HEATING Display

29.HEALTH Display

32.SLEEP State Display

31.Operation MODE DisplayAUTO RUN COOL RUN DRY RUN HEAT RUN FAN RUN

35.FAN SPEED Display

23.AUTO SWING Display

19.TIMER OFF Display

21.FILTER Display

36.TIMER ON Display

When unit is started for the first time and after replacing batteries in remotecontroller, clock should be adjusted as follows:1.Press CLOCK button, clock indication of " AM " or " PM " flashes.2.Press or to set correct time. Each press will increase or decrease 1 min. If the button is kept pressed, time will increase or decrease quickly.3.After time setting is confirmed, press "SET" : AM or PM stop flashing, while clock starts working.Note:AM means morning and PM means afternoon.

When operating the remote controller in an area whereelectronically controlled lights are installed or wireless handsetsare used, please move closer to the indoor unit as the functionof the remote controller might be affected by signals emittedby the above mentioned equipments.

Battery loading

Confirmation indicatorIf no indication is displayed after press ON/OFF button,reload the batteries.

AUTO

LO

MID

HI

AUTO

Remote Controller' OperationWhen in use, direct signal transmissionhead to the receiver placed on the indoorunit

The distance between the remote controller and the receivershould be max 7m and there should be no obstacle between them.Do not throw the remote controller; prevent it from beingdamaged.

18.FAN ButtonUsed to select fan speed:LOW,MID,HIGH,AUTO.

Note:It is recommended that the batteries be removed from thecompartment if the remote controller is not used for an extendedperiod.The remote controller is programmed for automatic test ofoperation mode after the batteries are replaced. When the testis conducted, all icons will appear on the screen and thendisappear if the batteries are properly fitted.

Caution:

If the remote controller does not operate as designed afterfitting new batteries of the sametype, press the Reset button (marked ) with a pointed article.

20.CLOCK Display

30.DEHUMIDIFICATION Display

28.Some other buttonsAll these functions are not available now.

FRESH

HIGH/SOTIMER

SET

FILTER

HEALTH

RESET LOCK

SLEEPMODE

CLOCK

CODE LIGHT

321

Battery loadingBatteries are fitted as follows:

Loading the batteryEnsure that batteries are correctly placed in the compartmentas required for positive and negative terminals.

Replacing the battery compartment lidThe battery compartment lid is reinstalled in the reversesequence.

Display reviewPress the button to see if batteries are properly fitted. Ifno display appears, refit the batteries.

Remove the battery compartment lidSlightly press and disengage the battery compartment lid markedwith ì î and then hold the remote controller by the uppersection and then remove the battery compartment lid by pressingin the direction of the arrow as shown in the figure above.

* ** *

Page 66: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Fan Operation 1.Unit startPress ON/OFF button to start your air conditioner.Previous operation status appears on LCD (except forTIMER, SLEEP, and SWING setting).

2.Select operating modePress MODE button. At each press, operation modechanges as follows:

3. Adjust fan speedPress FAN button. At each press, fan speed changes asfollows:

Air conditioner will run at the selected fan speed.When in AUTO mode, unit will adjust fan speedaccording to room temperature automatically.

4. Unit stopPress ON/OFF button to stop unit.

Then select FAN

About FAN modeWhen the air conditioner runs in FAN mode,it is not possible to select AUTO FAN or toset temperature.

AUTO FANHEATCOOL DRY

A

FRESH

HIGH/SOTIMER

SET

FILTER

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

AUTO

41 3

2LOW MID HIGH

Page 67: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

AUTO, COOL , HEAT and DRY Operation

1. Unit startPress ON/OFF button,unit starts.Previous operation status appears on LCD (except for TIMER,SLEEP and SWING setting)

3.Temperature setting

Then select AUTO run or select COOL operation or

select DRY operation or select HEAT operation

2.Select operation modePress MODE button. At each press, operation mode changesas follows:

Press TEMP button.Every time the button is pressed, temp. setting increases1 C; if the button is kept pressed, temp. setting will increasequickly.

Every time the button is pressed, temp. setting decreases1 C, if the button is kept pressed, temp. setting will decreasequickly.Set proper temperature

4.Adjust FAN buttonPress FAN button. At each press, fan speed changes as follows:

Air conditioner will run at the selected fan speed.

5. Unit stopPress ON/OFF button,unit stops.

In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditionerwill select COOL, HEAT or FAN mode automatically according to the room temperature.In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittentlyat LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit willonly run FAN operation.In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.

AUTO FANHEATCOOL DRY

AUTO LOW MID HIGH

FRESH

HIGH/SOTIMER

SET

FILTER

A

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

AUTO

Temp. setting +2 CTemp.setting

On reaching temp.setting+2 C, unit will run in mildDRY mode.

Ultra-low air flow

COOL operation startswhen room temp.ishigher than temp.setting.

3

5 1

3

4

2

AUTO

Page 68: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Press SWING button.Up and down airflow varies upwardsand downwards. Left and right airflowvaries left and right sides.

Always use SWING button on the remotecontroller to adjust flaps. Adjusting them by handmay result in air conditioner's abnormally running.

Displays on the LCD disappear.All indicators on the indoor unit go out.Swing louver automatically close the air outlet.

After unit stops:

AUTO SWING

Adjusting air flow direction

AUTO SWING

When the automatic swing louver moves to the properangle, press SWING button can fix the airflow direction.

Please carefully set temperature when children,old or infirm people ues the air conditioner.

In case of great humidity, If the vertical flapsare completely turned towards left or right, thelouver will drop water.

Never adjust the louver directly by hand, as thiscould make it work abnormally.If the louver workabnormally, stop unit, restart and adjust the louverby remote controller.

Hints:As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpfulfor a better air circulationAs in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful fora better air circulation.Be careful not to catch a cold when cold air blows downward directly.

In COOL or DRY mode, do not leave the louver indownward position for a long time, as the watervapor close to the grille may condense and watermay drop from the air conditioner.

FRESH

HIGH/SOTIMER

SET

FILTER

A

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

AUTO

Page 69: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Sleep FunctionBefore going to bed you can press down the SLEEP button and the air conditioner will run so as to makeyou sleep more comfortably.Before using this function, the clock must be set.

Use of SLEEP functionAfter the unit's start, set running mode and then press SLEEP button once to make the air conditionerhave the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button / : you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1hour: "xh" and "OFF" indications appear on the display.

Operation Mode

1.In COOL, DRY modeOne hour after sleeping operation start, the temperatureis 1 C higher than the setting one. After another hour,temperature rises 1 C: sleep run continuously for another6 hours and then stops. The actual temperature is higherthan the setting one which is to prevent from being toocold to your sleep.

2.In HEAT modeOne hour after sleeping operation start, the temperatureis 2 C lower than the setting one. After another hour,temperature decreases by 2 C more. Temperature willautomatically rise by 1 C after another 3 hours'continuous operation. The actual temperature is lowerthan the setting one which is to prevent from being toohot to your sleep.

3.In AUTO mode.The air conditioner will run in corresponding sleepoperation according to the automatically selectedoperation mode.

SLEEP RUN BEGINS SLEEP RUN STOPS

SETTING T SHUT DOWN

about 6 hrs

1 hrs

In COOL,DRY mode

increase 1 C

increase 1 C

SLEEP RUN BEGINS SLEEP RUN STOPS

SETTING T SHUT DOWN

1 hrs1 hrs

3 hrsabout 6 hrs

increase 1 C

decrease 2 C

decrease 2 C

Notes:After setting SLEEP function, it is not possible to set clock.If set-sleep time does not reach 8 hours, unit will automatically stop operationafter set time is reached.Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first,then set SLEEP. After set SLEEP function, the TIMER function cannot beset.

In HEAT mode

FRESH

HIGH/SOTIMER

SET

FILTER

A

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

OFF

AUTO

Page 70: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Every time the button is pressed, time increases 10 minuts.If the button is kept pressed, time changes quickly.

Timer ON/OFF FunctionSet clock correctly before starting TIMER operation

1.Unit startAfter unit start, select your desired operation mode (operationmode will be displayed on LCD)

2.TIMER mode selectionPress TIMER button on the remote controller to change TIMERmode. Every time the button is pressed, display of TIMER modechanges as follows:

ON OFF ON OFFAM12:00 AM12:00PM 12:00 PM 12:00

TIMER ON TIMER OFF TIMER ON-OFF

blank

Then select TIMER mode as needed (TIMER ON or TIMER OFF).Now or will flash.

3.TIMER setting (press time adjust buttons )

Every time the button is pressed, time decreases 10 minuts.If the button is kept pressed, time changes quickly.It can be adjusted within 24 hours at will.

4.Confirm settingAfter setting correct time, press SET button to confirm time. Now

Time displayed: unit starts or stops at X hour X min (TIMER ONor TIMER OFF)5.Cancel TIMER modeJust press TIMER button several times until TIMER mode disappears.

Hints:After replacing batteries or if a power failure occurs, TIMER settingmust be reset.Remote controller has memory function. When you use TIMERmode next time, just press SET button after mode selection if timersetting is the same as the previous one.

Note:After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time,just press CLOCK button once: clock time will be displayed (if you press the button again continuously,youcan adjust clock). 5 seconds later, the display will show TIMER time again.

ON OFF

ON OFFor stop flashing.

FRESH

HIGH/SOTIMER

SET

FILTER

A

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

1

2

3 4

Page 71: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Timer ON-OFF FunctionSet clock correctly before starting TIMER operation

1.Unit startAfter unit start, select your desired operation mode (operationmode will be displayed on LCD)

2.TIMER mode selectionPress TIMER button on the remote controller to change TIMERmode. Every time the button is pressed, display of TIMER modechanges as follows:

OFF

3.Time setting for TIMER ON

4.Timer confirming for TIMER ONAfter setting correct time, press TIMER button to confirm time. Now

5.Timer setting for TIMER OFFPress time buttons and follow the same procedures in " Time settingfor TIMER ON"

Press time button

ON stops to flash, while starts flashing.

Time displayed : unit starts at X hour X min.

6.Time confirming for TIMER OFFAfter time setting, press SET button to confirm time. stops to flash.

Time displayed: unit starts at X hour X min.

7.Canel TIMER modeJust press TIMER button several times until TIMER mode disappears.According to the time setting sequence of TIMER ON and TIMER OFF,either start-stops or stops-start can be realized.

If the time setting of TIMER ON is the same as TIMER OFF, TIMERON-OFF function cannot be set.

ONThen select TIMER ON-OFF mode. will flash.

Every time the button is pressed, time increases 10 minuts.If the button is kept pressed, time will changes quickly.

Every time the button is pressed, time decreases 10 minuts.If the button is kept pressed ,time will changes quickly.It can be adjusted within 24 hours at will.AM refers to morning and PM refers to afternoon.

OFF

FRESH

HIGH/SOTIMER

SET

FILTER

A

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

OFF

1

3 654

2

ON OFF ON OFFAM12:00 AM12:00PM 12:00 PM 12:00

TIMER ON TIMER OFF TIMER ON-OFF

blank

Page 72: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

After the air conditioner has operated for a certain period, dust hasaccumulated on the filter, and the filter up/down function can be usedto clean it.

1.Whether unit starts or stops, continuously press FILTER button for 3 seconds, and enter the filter up/down waiting status (when unit stops, the yellow TIMER indicator flashes, and filter and clock indication are displayed on the remote controller. Only the FILTER button, the temperature buttons " " " " and time buttons are active).

2.Press temperature button or time button in filter up/down waiting status: the up/down mechanism makes the filter moving downward and does not stop until it has reached the maximum limit.

3.Press temperature button or time button in filter up/down waiting status: the up/down mechanism makes the filter to moving upward till near the surface board and then automatically adjusts it to reset (when adjusting to reset, it will not be controlled by the remote controller till the adju- stment is finished).

4.During moving downward, press temperature button or time button: moving stops.

5.During moving downward, press temperature button or time button: moving stops.

6.Continuously press FILTER button 3 seconds again to cancel the filter up/down waiting mode (unit stops, the yellow timer indicator stops flashing, the filter goes back to the original position, the remote controller goes back to off status and only clock is displayed).

Note:If the filter does not thoroughly go back to the original position, only needs tooperate several times repeatedly.

Filter Up/Down

" "

" "

" "

" "

" "

" "" "

" "

(Only for AB182ACBEA)

FRESH

HIGH/SOTIMER

SET

FILTER

A

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT1

Page 73: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Press the HIGH/SO button twice

NOTICE:When the air conditioner is operating in " High Mode " , unevenness of room air temperaturemay occur due to the intensive operation in a short time.Anyway, operation in "High Mode", does not last for more than 15 minutes, then regularoperation is automatically restored.

" High mode " Operation

If the button is pressed once, the indication is displayedon the remote controller. If you press the button once again,the indication disappears, regular operation is restored and fanspeed goes back to the mode set before "High Mode" operation.

Press the HIGH/SO button noceThe indication appears on the display of the remotecontroller and operation in "High Mode" starts.The AUTO fan speed is automatically set and the correspondingindication is also displayed.

Outline of operation in "High Mode"This function is suitable when the set temperature must bereached in the shortest delay.The button "HIGH/SO", referred to this function, is effectivein Cooling/Heating mode (not in Auto/Dry/Fan modes).

ON

OFF

FRESH

HIGH/SOTIMER

SET

FILTER

A

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

AUTO

1

Page 74: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Press the HIGH/SO button twice

NOTICE:When the air conditioner is operating in " High Mode " , unevenness of room air temperaturemay occur due to the intensive operation in a short time.Anyway, operation in "High Mode", does not last for more than 15 minutes, then regularoperation is automatically restored.

" Soft mode " Operation

If the button is pressed once, the indication is disappearsfrom the remote controller's display. If you press the buttononce again, regular operation is restored and fan speed goesback to the mode set before "Soft Mode" operation.

Press the HIGH/SO button twiceThe indication appears on the display of the remotecontroller and operation in "Soft Mode" starts.The AUTO fan speed is automatically set and the correspondingindication is also displayed.

Outline of operation in "Soft Mode"Operation in "Soft Mode", more silent, is suitable when noisesshould be reduced, e.g.. for reading or sleeping.The button "HIGH/SO", referred to this operation, is effectivein Cooling/Heating mode (not in Auto/Dry/Fan modes).

ON

OFF

FRESH

HIGH/SOTIMER

SET

FILTER

A

HEALTH

RESET LOCK

SLEEP

FAN

TEMP

ONOFFSWING

MODE

CLOCK

CODE LIGHT

OFF

AUTO

1

Page 75: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

C

HEALTH

SET RECOVERY

CHECK

F

Cautions:On cooling only unit, heatingmode is not available.

Note:The above information is the explanation ofthe displayed information therefore varieswith those displayed in actual operation.

CLOCKUsed to adjust time.

TIMERUsed to set timermode.

stands for time plus/minus,used to adjust time.

Used for unit start andstop.

POWER ON/OFF

MODE

Used for selectindoor operationmode.

FAN SPEED

Used for select indoorair flow.

HEALTHUsed for settingindoor healthfunction.

TEMP + -

Used for changingset temperature.

RECOVERYused to switchover air-exchanging mode.

SWING

Used for sett ingindoor swing mode.

Auto-diagnost icbutton.

Filter-cleaned button.

FILTER

RESETReset correctmode button.

Wired controller YR-E12 functions:

CHECK

+ -

Buttons and functions of the wired controller

Page 76: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Buttons function: MODE:used for select indoor operation mode. FAN:used for select indoor air flow. SWING:used for setting indoor swing mode. HEALTH:used for setting indoor health function. TEMP + -:used for changing set temperature. CLOCK:used to adjust time. +、-:stands for time plus/minus, used to adjust time. TIMER:used to set timer mode. RECOVERY:used to switch over air-exchanging mode. CHECK:auto-diagnostic button. FILTER:filter-cleaned button.

RESET:reset correct mode button.

Display description: [MODE] [AUTO]:auto operation mode [MODE] [FAN ONLY]:air-throwing mode [MODE] [COOL]:Cooling operation mode [MODE] [DRY]:Dehumidification mode [MODE] [HEAT]:Heating operation mode [MODE] [HEAT] [TES]:In heating mode, auxiliary electric heater is running. Only when the unit

with auxiliary electric heater is in auxiliary electric heating mode, it will display. [FAN] [AUTO]:auto fan running

Page 77: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

[FAN] [HIGH]:high fan speed [FAN] [MED]: medium fan speed [FAN] [LOW]: low fan speed [FAN] [FIX]: fixed fan speed, it will display only when fixed fan speed is requested to main indoor

unit. [CENTRAL]: central control mode [OPERATION] :running mode [STAND BY] : waiting mode [PRE-HEAT] : pre-heating mode [DEFROST]: defrosting mode [FILTER] : request of filter to be cleaned [HEALTH]:health function [UNIT NO.] [CEN.ADD]:central control address, the address number will display on “88” [SYS.ADD.]:system address, the address number will display on “88” [CHECK]:auto-diagnostic, trouble shooting [DEMAND]:compulsory operation function, when it works, [CENTRAL] will flash [SWING]:swing mode [ROOM TEMP.]:indoor ambient temperature [SET TEMP.]:set admired temperature [TIMER][ON] :timer function is on, it will switch over in the sequence below:

[ON][OFF] → [ON][OFF][DAILY] →[ ] [TIMER][OFF] :timer function is off [TIMER][ON][OFF] :timer function ON-OFF [TIMER][ON][OFF][DAILY]:timer ON-OFF will switch over in turn daily [CLOCK]:clock display, the displaying time is the current time of the clock. [UP]、[DOWN]:indicator of filter elevating [VENTILATION][AUTO]:auto ventilation mode [VENTILATION][RECOVERY]:fully heat exchanging ventilation mode [VENTILATION][NORMAL]:normal ventilation mode FAN ONLY OPERATION: 1)Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”. 2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch

over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN ONLY]. Select [FAN ONLY].

3)Select fan speed: press FAN button, then you see in the display section [FAN] switch over in below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed. 4)Power off: press ON/OFF button, indoor unit will be powered off, there are only time and the ambient temperature in the screen.

Page 78: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

AUTO operation, COOLING, HEATING and DEHUMIDIFICATION operation 1) Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”. 2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN ONLY]. Select [FAN ONLY]. 3) Change set temperature: press TEMP + or – every time, [SET] will display, and set temperature will increase/reduce 1℃(F). 4) Select fan speed: press FAN button, then you see in the display section [FAN] switch over in below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed. 5) Select [SWING]: press [SWING] button,swing function is valid. Press again, swing function is invalid. 6) Set [HEALTH]: used to set the indoor health function. Press it once, [HEALTH] will display in the display section, then indoor health function is valid. Press it again, [HEALTH] will disappear, then the health function is invalid. This function is valid only for the unit with health function. 7) Power off: press ON/OFF button, indoor unit is powered off. There are only time and the ambient temperature in the screen. Set TIMER operation: Adjust clock: when powered on, for the first time to set timer function, the clock will be adjusted. Press “CLOCK” button, and set the current clock. Now, “CLOCK” will flash at the frequency of 2Hz every minute. Press the clock +/- button; the current clock can be adjusted. Until the proper time comes, press [SET]. TIMER ON operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [ON], then [TIMER] [ON] flashes, press the clock +/- button to adjust the time of TIMER ON, press [SET] button. TIMER OFF operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [OFF], then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET] button. TIMER ON-OFF operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [ON] [OFF]. Firstly, [TIMER][ON] flashes, press the clock +/- button to adjust the time of TIMER ON, press [SET]. [TIMER][ON] will be constant on. Then [TIMER] [OFF] flashes, press the clock +/- button

Page 79: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

to adjust the time of TIMER OFF, press [SET]. The time sequence of timer on and timer off will determine the mode is [TIMER] [ON] →[OFF] or [TIMER] [OFF] →[ON]. Note: 1. If the two times are the same, the unit will adjust the state after set time arrives according to the current state. If current state is in running mode, after set time arrives the unit will switch to “power off“ state. If current state is in “power off” mode, after set time arrives, the unit will switch to running mode. 2. When in TIMER setting state, if you do not input any button in continuous 10 seconds, the unit will think [SET] pressed. Cancel TIMER operation: In the timer operation state, press [TIMER] button, the unit will quit from the current timer operation state, and the set data will be memorized, then enter the next timer mode. After timer be set, press ON/OFF to cancel timer mode. When in running again, timer mode will be continuous (without timer).

[FILTER] function When the wired controller receives the filter-cleaned signal from indoor unit, [FILTER] will display. After finishing clean, press [FILTER], the sign [FILTER] disappears, and the controller will send the filter reset signal to indoor unit. When the sign [FILTER] not display, it is invalid to press [FILTER] in short time. FILTER ELEVATING function: (only for the unit with elevating function) In power off state, press [FILTER] for 5 seconds to enter filter elevating set state. In this state, the sign [FILTER] will flash at the frequency of 2Hz. By pressing [+] TEMP [-], filter can go up or down. Press TEMP [+], in timer section [UP] will display, while press TEMP [-], in timer section [DOWN] will display. Press [FILTER] button to quit the mode. DEMAND operation function: In the stop state of cooling mode, press [ON/OFF] button for 5 seconds to enter [DEMAND] cooling operation state, the sign [DEMAND] will display. In the 7-segmet liquid crystal screen of set temp. section, “0” will display in first position, which shows that No. 0 indoor unit has enter demand operation. In the second position, “L” will display, in the meantime, [COOL] will flash, [FAN][AUTO] is constant on. Press TEMP [+] [-] to set different indoor unit. Press [ON/OFF] to cancel [DEMAND] operation. In the stop state of heating mode, press [ON/OFF] button for 5 seconds to enter [DEMAND] heating operation state, the sign [DEMAND] will display. In the 7-segmet liquid crystal screen of set temp. section, “0” will display in first position, which shows that No. 0 indoor unit has enter demand operation. In the second position, “H” will display, in the meantime, [HEAT] will flash, [FAN][AUTO] is constant on. Press TEMP [+] [-] to set different indoor unit. Press [ON/OFF] to cancel [DEMAND] operation. VENTILATION mode (only for the unit with fresh air function or heat recovery function) Press [RECOVERY] button, then the unit will switch over the ventilation mode: [ ]→ [VENTILATION][AUTO]→ [VENTILATION][RECOVERY] → [VENTALATION][NORMAL]

Page 80: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

→[ ], please select appropriate ventilation mode. Query indoor malfunction history: In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence (unit number is in decimals). At the same time, in the time region, there will be the current malfunction and the latest time malfunction, the displaying format is [XX:YY], in which XX stands for the current malfunction, if normal, it will display “――”; YY stands for the latest time malfunction. The failure code of every unit will display for 3 seconds. After the failure codes of all indoor units in the whole group are displayed, the mode will quit automatically. Clear abnormal state and malfunction history: In normal state, press [CHECK] button for 5 seconds to clear abnormal states, at the same time, wired controller will send the data of “clear abnormal state”, but the malfunction history still retains. In normal state, press [CHECK] button for 15 seconds, except for malfunction states, the malfunction history in wired controller will be cleared. Query indoor performance state: In normal state, press both buttons of [CHECK] and [FILTER] for 5 seconds, in the set temperature region in the screen, [XX] will display, XX is indoor number, which can be selected by pressing [TEMP] [+] [-]. In the timer region in the screen, [YZZZ] will display, in which Y stands for data type, ZZZ stands for the corresponding data. which can be selected by pressing [CLOCK] [+] [-].

Y ZZZ Type A Indoor capacity (W) Nominal cooling

capacity/10, decimal B Request of indoor capacity(Hz) Actual value, decimal C Temperature of indoor ambient

temp. sensor TA Actual value, decimal

d Temperature of indoor gas pipe sensor TC1

Actual value, decimal

E Temperature of indoor liquid pipe sensor TC2

Actual value, decimal

F Open degree of indoor PMV Actual value, decimal g Preset ――― H Outdoor total capacity Actual value, decimal

In check mode, press [CHECK] to quit the check mode, and go into normal running mode.

Page 81: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

How to change the function switches? No. Type State of

switch Function description

Connected Central controller J01 Changeover of Wired controller and central controller

Cut off Wired controller

Connected Set as simple controller J02 Changeover of type of wired controller Cut off Set as standard controller

Connected Use the sensor in the wired controller

J06 Selection of room temp. sensor

Cut off Use the sensor in the indoor unitConnected Common control J07 Auto reset after power

failure Cut off Auto reset after power failure Connected Yes J03 Display of room

temperature Cut off No ON Set as slave controller SW01

① Changeover of master or slave controller OFF Set as master controller

ON ℉ SW01②

℃ or ℉ OFF ℃ Connected Indoor unit in shorted time

function D1 Shorten time function

Cut off Common control Connected Send compulsorily defrost signal

to indoor unit D2 Compulsorily defrost

Cut off Common control Note: The switches in grey can be operated after opening the cover of wired controller.

Page 82: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Electrical functions of wired controller: 1.Switch over method: wired control master unit/wired control slave unit/remote control unit

Control method Socket /jumper

Wired control master unit

Wired control slave unit

Remote control unit

CN23 Short circuit Not short circuit Not short circuit CN30 Short circuit Short circuit Not short circuit CN21 Blank Blank To remote receiver

board J19 Short circuit Short circuit Cut circuit Signal terminal block A,B,C connected

to wired controller B,C connected to wired controller

A,B,C not connected to wired controller

Function difference between master wired controller and slave one: Contrastive items Master wired controller Slave wired controller Function All of functions Only with below functions:

ON/OFF, MODE, FAN SPEED, SET TEMP., SWING

2. Wiring connections of wired controller:

indoor N

BA C

wired controller

indoor 1 indoor 2

indoor 1

21 3

A B C A B C

indoor 16

control wiring of wired controller, polar.

indoor 15

1 2 3

A B C

wired controller wired controller wired controller

wired controller wired controller

wired controller

wired controller

indoor 1

wired controller wired controller wired controller

A

B C

(master unit)

polar wirepolar wire

polar wire

There are three methods to connection wired controller and the indoor units: A. One wired controller can control max. up to 16 sets of indoor units, and

1

Page 83: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

3 pieces of polar wire must connect the wired controller and the master unit (the indoor unit connected with wired controller directly), the others connect with the master unit through 2 pieces of polar wire. B. One wired controller controls one indoor unit, and the indoor unit connects with the wired controller through 3 pieces of polar wire. C. Two wired controllers control one indoor unit. The wired controller connected with indoor unit is called master one, the other is called slave one. Master wired controller and indoor unit; master and slave wired controllers are all connected through 3 pieces of polar wire. 3. Communication wiring: The wired controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white 2-yellow 3-red) is connected with the terminal A、B、C of wired controller respectively. The communication wiring is 4 meter long; if the actual length is more than it, please distribute wiring according to below table:

Communication wiring length(m) Dimensions of wiring <100 0.3mm2X3-core shielded wire ≥100 and <200 0.5mm2X3-core shielded wire ≥200 and <300 0.75mm2X3-core shielded wire ≥300 and <400 1.25mm2X3-core shielded wire ≥400 and <600 2mm2X3-core shielded wire

※ One side of the shielded sheet of communication wire must be earthed.

2

Page 84: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

8 REFRIGERANT DIAGRAM

Piping Systematic Diagram for Cooling/Heating Type Air Conditioner

Outdoor UnitIndoor Unit

One-way Valve

Filter

Reversing Valve

Stop Valve

StopValve

Capillary Tube

He

at E

xch

an

ge

r

He

at E

xch

an

ge

r

Cooling Operation

Heating Operation

Quieter

Co

mp

resso

r

REFRIGERANT DIAGRAM

- 71-

Page 85: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

9.1 Control Features

The brief introduction includes those for each item of various types of air conditioners and their electric control functions. The brief introduction includes those for each item of various types of air conditioners and their electric control functions. 7.1 Brief introduction of electric control 7.1 Brief introduction of electric control (1) Automatic run (1) Automatic run a. Cooling-heating type

After the machine being started and running mode changes to AUTO, the system will decide running mode according to difference between the present room temperature and setting temperature, then runs as the decided mode. In the following selections, Tr means room temperature and Ts means setting temperature.

Select running mode according to the following conditions at the first time to enter Auto mode: Tr Ts-3 to select cooling mode (with setting temperature being Ts +3)

Tr<Ts-3 to select heating mode (with setting temperature being Ts) After the system entering auto run mode, the running mode can convert automatically

according to variation of room temperature between cooling, blowing and heating in the way shown as the chart below:

Room

temperature

fa

ng

lli

Cooling Ts+3

Cooling

Room

tem

perature rising

Blowing

Ts-3 Ts-3

Heating b. Single Cooling Type

Select running mode according to the following conditions at the first time to enter Auto mode: Tr Ts + 3 to select cooling mode

Tr < Ts + 3 to select blowing mode

After the system entering auto run, the running mode can convert automatically according to variation of room temperature between cooling and blowing functions in the way shown as the chart below:

Room

temperature

all

f

ing

Cooling

Ts+3 Room

tem

perature rising

Blowing

Cooling Blowing

Ts-3

9 ELECTRICAL CONTROL FUNCTIONS

-72 -

ELECTRICAL CONTROL FUNCTIONS

Page 86: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

(2) Auto Selection of Wind Speed In the following, Tr means room temperature while Ts means setting temperature. a. During cooling program conversion of wind speed from the low to high won’t work until the present speed has continued for 3 minutes while conversion from the high to low needs no time delay. The chart below is the sketch map of conversion:

Ts 2

Ts 1 Medium speed

Medium speed

Temperature

falling

Temperature

rising

Low speed

High speed

Low peed

High speed Ts 3

Ts

b. During heating program applicable for cooling-heating type , conversion of wind speed from the low to high won’t work until the present speed has continued for 3 minutes while conversion from the high to low needs no time delay. The hart below is the sketch map of conversion:

Low speed

Ts 1

Ts 2 Medium speed

Medium speed

Temperature

rising

High speed

High speed

Temperature

falling

Ts Low speed

Ts 3

(3) Dehumidifying program In the following, Tr means room temperature while Ts means setting temperature.

a. After the system entering dehumidifying program, the compressor, outdoor and indoor blowing fans run according to the following rules: (1) Tr > Ts + 2 , the compressor and outdoor blowing fan run continuously while indoor

- 73 -

ELECTRICAL CONTROL FUNCTIONS

Page 87: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

blowing fan runs at setting wind speed. This working area is defined as area A. (2) Ts Tr Ts + 2 , the compressor and outdoor blowing fan run for 10 minutes then

pause for 6 minutes, while indoor blowing fan runs at low wind speed. This working area is defined as area B.

(3) Tr < Ts, the compressor and outdoor blowing fan stop working while outdoor blowing fan runs at low wind speed. This working area is defined as area C.

a. After dehumidifying program starting, the system converts between A, B and C areas

according to variations of room temperature with running mode being shown as the chart below:

Room

tem

perature falling

Area BArea B

Area C

Ts

Area A Area A Ts 3

Ts 1

Room

tem

perature rising Ts 1

Area C

(4) Cutoff protection against overload and overheat During heating program, if the indoor blowing fan has been started and the compressor has been running more than 2 minutes, and the temperature of indoor coil pipe (Ticp) > 64 , the outdoor blowing fan will stops running; If Ticp ≤ 50 and the outdoor blowing fan has kept stop state for 45 seconds, then it will restore rotation; If Ticp > 67 and such temperature has last for 10 seconds, the compressor will stop running and indoor blowing fan run according to conditions as it reaches setting temperature. When Ticp < 58 , and the compressor has kept stop state over 3 minutes, then the compressor and outdoor blowing fan will restore normal running.

Cutoff protection for heating current After 60 seconds from the compressor being started, if CT current exceeds I1 (9.2A) and

such case has kept 5 seconds, the outdoor blowing fan will stop. If 45 seconds has passed after the outdoor blowing stops and the current of the compressor is less than I2 (7.5A), the blowing fan will restore running. If CT current exceeds I3 (14.3A) and such case lasts for 3 seconds, the compressor and outdoor blowing fan will stop. The compressor will not restore running until 3 minutes passes with CT current less than 12A. (5) Cool wind prevention during heating program

At the first time entering heating program or after ending the latest frost removal, if the temperature of indoor coil pipe (Ticp) < 28 , the indoor blowing fan will stop running; If 28 Ticp < 38 , the indoor blowing fan will run at low speed; If Ticp > 38 or the compressor has been running for more than 4 minutes, the indoor blowing fan will run at

- 74-

ELECTRICAL CONTROL FUNCTIONS

Page 88: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

setting wind speed. (6) Afterheat blowing during heating program

During heating program, the compressor will stop running (except overheat protection or frost removal) while the indoor blowing fan will firstly run for 50 seconds at low speed then stop. (7) Frost removal control (applicable for cooling-heating type)

Starting conditions for frost removal: A The indoor unit is in overload protection and outdoor blowing fan stops. The outdoor

blowing fan does not enter overheat mode in 10 minutes after it is restarted, the compressor has run over 45 minutes totally while 20 minutes continuously, and the temperature of indoor coil pipe is lower than 43 ;

B After the compressor continuously running for 20 minutes, the temperature of indoor coil pipe falls 1 every 6 minutes and such case continuously appears three times, and the temperature of indoor coil pipe is less than 40 , and 5 minutes have passed after the compressor is restarted;

C The compressor has run totally over 3 hours while 20 minutes continuously, and the temperature of indoor coil pipe is less than 40 ;

D The difference between room temperature and the one of indoor coil pipe is less than 16 and the compressor has totally run over 45 minutes while 20 minutes continuously;

Frost removal will start if any one of the above conditions is satisfied. Ending conditions for frost removal:

1 Time of frost removal has exceeded 9 minutes; 2 CT current exceeds I4(8.2A)

Actions of each load after the frost removal starts: The compressor and outdoor blowing fan stop, and indoor blowing fan also stops.

55 seconds later the reversal valve is closed and next 5 seconds later the compressor is started.

Actions of each load after the frost removal ends: The compressor stops running while outdoor blowing fan immediately runs at high

speed, 55 seconds later the reversal valve is opened and next 5 seconds later the compressor restores running and indoor blowing fan runs as conditions for cool wind prevention.

(8) Freeze protection After the compressor has run for 9 minutes, the system will check temperature of indoor coil pipe (Ticp). If Ticp is less than -1 , the compressor and outdoor blowing fan will stop. They will run again after the compressor stops if both the following conditions are satisfied:

1) 3 minutes have passed since compressor stops. 2) Ticp exceeds 7 . (9) 3 minutes protection for compressor

After compressor stops, it cannot be started until 3 minutes later. During the machine’s running, if time after loosing power not exceeds 3 minutes, the compressor cannot be

- 75-

ELECTRICAL CONTROL FUNCTIONS

Page 89: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

restarted until 3 minutes later after it is reenergized. 10 Power breakdown memory

If the machine suddenly loses power while running, or stops for maintenance or trouble shooting, it will restart running as the status when it stops after the power is restored. Note: 1. Function setting: Continuously press sleep button on the remote controller 10

times in 5 seconds and buzzer on control panel shall beep 4 times. 2. Memory content: Running mode, wind speed setting, temperature setting,

swing status. 3. Cancel: Press sleep button on the remote controller 10 times and buzzer on

control panel beeps 2 times. (11) Control of water pump

a. In cooling (including automatic cooling mode) and dehumidifying modes, the water pump works if the compressor runs while stops 5 minutes later after the compressor stops.

b. When water tank is fully filled, the float switch will be off. The water pump will start to work after a controller has detected this signal and it will continue working for 5 minutes after the float restores to normal state.

c. If the full water signal is detected continuously over 5 minutes, the water pump indicator lamp will flash to alarm and compressor stops running. The water pump will run 5 minutes, then pause for 5 seconds before next 5 minutes’ running, ... until the float restores to normal state, after which the pump will run for 5 minutes then stop.

(12) Monitoring of remote network

Through preset interface, the air conditioner is connected to remote control detector (made by Haier) with 2-core cables for wire communication, to execute instructions sent from computer or centralized controller via remote control detector and meanwhile send present running status and trouble information of the machine to remote control detector. Connection between air conditioner and remote control detector:

CN11 PC board

1

2

A- A+

Interface for remotecontrol detector

(13) Trial run Under shut-down state, hold pressing mandatory button. The buzzer will beep once, then twice after 5 seconds. Release the button to enter mandatory cooling mode, under which the indoor blowing fan runs at high speed with both the compressor and outdoor blowing fan working. Press the mandatory button again can end the mandatory mode.

- 76 -

ELECTRICAL CONTROL FUNCTIONS

Page 90: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Return

Return

9.3 Defrost operation flow chart

Return

Condition for

compressor OFF

OFF compressor

Open outdoor fun

Compressor off or 55s?

4-way value ON

Compressor

ON ?

Clear the sign of defrosts

Return

Operation indoorfun motor

Return

Come to defrost

Compressor ON

E-Heat off for 30s?

Turn off compressoroutdoor fun

Turn off 4-way value

Compressor ON

Return

Return

Turn off for 55s?

B

ELECTRICAL CONTROL FUNCTIONS

Page 91: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

10. Diagnostic information10.1 Failure coderemote control type unit:

failure description indoor runninglamp flash times

indoor ambient temp. sensor failure 1indoor coil temp.sensor failure 2outdoor ambient temp. sensor failureor 4-way valve broken down in heating mode

3

outdoor coil temp. sensor failure 4over-current protection failure or phase sequence fault 5refrigerant system pressure too high or low 6communication between indoor PCB and receiver panel failure 8communication between indoor PCB and outdoor PCB 9drainage failure 10Note: For convertible type unit, drainage failure is not available.

Wired control type unit failure code:for old wired controller

Failure description Failure code on wired controller

Indoor ambient temp. sensor abnormal E1 Indoor coil temp. sensor abnormal E2 Outdoor ambient temp. sensor abnormal E3 Outdoor coil temp. sensor abnormal E4 Over current protection E5 Over high or low pressure protection E6 Communication between panel and indoor abnormal

E8

Communication between indoor and outdoor abnormal

E9

Water pump failure E0

Page 92: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Failure code with wired controller YR-E12: For

remote

type, flash

times

Failure

code on

wired

controller

For central

control,

failure code

Failure description Reason

10 08 21 Drainage system failure Float switch broken down for more than

25m continuously

1 01 01 Indoor ambient temp. sensor

failure

sensor broken down or short circuit for

more than 2m continuously

2 02 02 Indoor coil temp. sensor failure sensor broken down or short circuit for

more than 2m continuously

3 4A 11 Outdoor ambient temp. sensor

failure

sensor broken down or short circuit for

more than 2m continuously

4 49 12 Outdoor coil temp. sensor

failure (compressor

discharging temp. sensor)

Sensor broken down or short circuit for

more than 2m continuously

5 48 10 Over-current protection CT check abnormal 3 times in 30m

6 53 14 High pressure abnormal High pressure switch acts 3 times in 30m

8 07 06 Communication between wired

controller and indoor abnormal

Communication abnormal for more than

4m continuously

9 06 05 Communication between

indoor and outdoor abnormal

Communication abnormal for more than

4m continuously

11 0B 30 Outside alarm signal input Outside signal broken down for more than

10s

12 03 20 Gas pipe temp. sensor

abnormal

Sensor broken down or short circuit for

more than 2m continuously

13 0D 31 Solenoid valve abnormal Solenoid valve act incorrectly 3 times

continuously

15 05 17 EEPROM abnormal EEPROM data missing

Page 93: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

R(25℃)=10K (Indoor unit Pipe sensor)

Therameter Sensor temperature(℃) resistance(KΩ) temperature(℃) resistance(KΩ)

-15 66.53 45 4.549 -20 87.42 50 3.788 -25 116.0 55 3.170 -10 51.8 60 2.660 -5 39.55 65 2.223 0 30.88 70 1.912 5 24.30 75 1.630 10 19.20 80 1.395 15 15.38 85 1.200 20 12.36 90 1.035 25 10.00 95 0.8967 30 8.141 100 0.7796 35 6.668 105 0.6802 40 5.492 110 0.5955

R(25℃)=23K (Indoor unit ambinent sensor)

Therameter Sensor temperature(℃) resistance(KΩ) temperature(℃) resistance(KΩ)

-10 139.5 60 5.243 -5 105.3 65 4.336 0 80.14 70 3.603 5 61.51 75 3.008 10 47.58 80 2.522 15 35.36 -20 251.8 20 27.93 -19 235.9 25 23.00 -18 223.1 30 18.30 -17 210.1 35 14.65 -16 197.9 40 11.79 -15 186.5 45 9.556 -14 176.9 50 7.780 -13 165.9

sensor resistance value

79

Page 94: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

10.2 Trouble Shooting - Detailed for engineer Malfunction flow chart: analyze and diagnose If the air-condition fails to cooling or heating function and other functions, please check

the system as follows:

1.Cooling

Y

change the designed TEMP.

replacing compressor

superaddition condensate

clear the filter

enact fan speed of high or middle speed

airiness circle improperly

heat insulation of condensate pipeline between indoor unit and outdoor unit is normal

N

N

compressor fault

quantity of condensate charge is not enough

fan speed at low-speed

air entrance filter obstruct

Y

Y

Y

Y

condensate flowage failure

fails in cooling

begining

N

N

fault in 4-way vavle

the cooling load beyond the allowable arange

the enactment TEMP. right or not

Y

Y

Y

insulate the two pipeline respective

redesign the TEMP.

change the 4-way vavle

use arange is right or not

Y

Figure 9-1

80

Page 95: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

2. Heating

Y

change the designed TEMP.

replacing compressor

superaddition condensate

clear the filter

enact fan speed of high or middle speed

airiness circle improperly

heat insulation of condensate pipeline between indoor unit and outdoor unit is normal

N

N

compressor fault

quantity of condensate charge is not enough

fan speed at low-speed

air entrance filter obstruct

Y

Y

Y

Y

condensate flowage failure

fails in heating

begining

N

N

fault in 4-way vavle

the heating load beyond the allowable arange

the enactment TEMP. right or not

Y

Y

Y

insulate the two pipeline respective

redesign the TEMP.

change the 4-way vavle

use arange is right or not

Y

blowing cold air fault in 4-way vavlereplacing the 4-way vavle

Y

prevent cold air failure

pipe sensor of indoor unit is fault

replacing the 4-way vavle

Y

Figure 9-2

81

Page 96: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

10.3 Malfunction and Solution of Wired controller 1) There is nothing on display of wire control organ, and the air-conditioner failure to

operate

if the diode on indoor unit is lumines

if there's voltage on the primary side of tranaformer

if the fuse of indoor unit PCB.is normal

if the primary side of power supply transformer is short

replacing the transformer

check the port row of power supply

if the transform of PCB.socket is normal

replacing the transformer

redo the connection work

if power supply and communication line are connected correctly

replacing the PCB. of indoor unit

if there'e DC 12V between the four ports:A,B,C and D which on wire control organ

begining

Y

Y

if there's AC 220V of power suplay on PCB. of indoor unit

Y

repacing the wire control organ

Y

N

Y

Y

Y

N

NY

NN

if there's AC 15V on transformer subside of indoor unit PCB.

N

Y

Figure 9-3

82

Page 97: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

2) The wire control organ displays the alarm signal with “E0” “E0” means the floater switch of indoor unit is abnormal

replacing the switch

if the function of the floater is normal

if the floater swith is orientated correctly

the alarm signal of wire control organ is E0

begining

amend the oritation of the floater switch

N

Y

N

Figure 9-4

3) The wire control organ displays the alarm signal with “E1”

“E1” means indoor ambient temperature sensor is abnormal

amend the position of the sensor

if the indoor ambient sensor is orientated correctly

replacing the sensor

N

if the resistance of sensor is right

Y

N

wire control organ displays the alarm signal with E1

begining

Figure 9-5

Notation: The resistance of indoor ambient sensor is 23K

83

Page 98: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

4) The wire control organ displays the alarm signal with “E2” “E2” means indoor piping temperature sensor is abnormal

the alarm signal of wire control organ is E2

replacing the sensor

if the resistance of the sensor is right

N

Y

amend the position of sensor

N

begining

if the position of piping Temp.sensor is right

Figure 7-6 Notation: The resistance of piping temperature sensor is 10K

8) The wire control organ displays the alarm signal with “E8” “E8” means malfunction of communication between control panel and indoor units

if the potrs A and B,or C and D are short

replacing the wire control organ

connect the wire correctly

if the four ports on wire control connected correspondingwith the port on PCB of indoor unit

if the ports:A,B,C and D are connected well

if the wire control organ can matches the PCB of indoor units

begining

connect the wire correctly

connect the wire correctly

N

Y

Y

Y

N

N

N

Figure 9-7

Page 99: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

11. Electrical Data 11.1 Wiring Diagram 11.1.1 Outdoor unit

2. Dashed parts is optional for Low Ambient Temp. Cooling,and there is no relay in only Cooling type

NOTE:1. Dashed parts is not available for only Cooling type

single phase outdoor wiring diagram

3. Dashed parts is optional for Low Ambient Temp. Cooling,and there is no relay in only Cooling type

2. Dashed parts are not available for only Cooling type

NOTE:1. Dashed parts is not available for Cooling capacity below 42000Btu/h

3-phase outdoor wiring diagram

Page 100: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

11.1.2 Indoor unit

NOTE:1. Dashed parts are not availble in convertible type2. Dashes part is not avaliable below Cooling capacity 42000Btu type3. Remote central controller is optional4. P16 and P17 are used for room card function

over 24000BTU/h convertible type wiring diagram

NOTE:1. Parts in dashed frame are not available for cassette type unit2. Central controller is optional3. P16 and P17 are used for room card function

over 24000BTU/h cassette type wiring diagram

Page 101: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

2. Dashed part is ont avaliable below Cooling capacity 28000Btu type

over 24000BTU/h mid ESP duct type wiring diagram

Note:1.Dashed parts are not available in duct type.

3.Remote central controller is optional.4.P16 and P17 are used for room card function

WYR

Wiring Diagram For 24000/42000BTU/h cabinet Unit

TERMINAL BLOCK

TO O

UTD

OO

R U

NIT

Y/G

RB

W

Y/G

R

B

W

T3.15A/250VAC

FUSE

TRANS.PIPING TEMP

CONTROLLERCN3

CN12

CN11

CN8DOOR SWITCH

CN5

CN6

CN7

SWING MOTOR

FAN MOTOR

FAN MOTOR CAP.

CN1N S(N-W)

CN9

ROOM TEMP.

Page 102: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

High ESP duct type wiring diagram

Note:1.Dashed parts are not available in duct type2.Dashed part is fan speed controller kit.3.Remote central controller is optional4.P16 and P17 are used for room card function

WYR

Page 103: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Circuit for 3-phase outdoor unit: 1 2 3 4 5 6

A

B

C

D

654321

D

C

B

A

Title

Number RevisionSize

B

Date: 5-Nov-2003 Sheet of File: C:\Documents and Settings\zhanjie\×ÀÃæ\0010451429.DDBDrawn By:

+12 1

2

CN4RTB-1.5-2P

1

2

CN1XHB2P3

C23

0.1UF/250V

C8104

C12200UF/35V

Vin 1

GN

D2

Vout3RG1 7805

C7104 C24

0.1UF/250V

+5

D8 D11

D10D9 L1

VR

N

RW102

R13470

C21470UF/16V

R11

1K

R10

1K

D54148

+5

C6104

CT1

C224.7UF/50V

+5

R245.1K

R255.1K

C174.7UF/50V

R1

200K

C1622uF/250V

R362K/3W

R462K/3W

R262K/3W

D24007

D14007

D34007

D44007

R16

10K/0.5W

R15

10K/0.5W

S

R62.2K

C2103

R533K

IC2 TLP521-1

IC1 TLP371

R8

1K

R710K

R12

560

C3103

C4 103

+5

+5

+12

+12

C5104

JK5

OJE-SS-112DM

JK7

OJE-SS-112DM

A11

A22

A33

A44

A55

A66

A77 Q7 10Q6 11Q5 12Q4 13Q3 14Q2 15Q1 16

GND8 VCC 9

IC4ULN2003A

12

CN5B2B-VH-W

R1910K

R1810K

R1710K

C10 103

C11 103

C12 103

12CN2

VHB2B

R305.6K

R281K

R35 33K/2W

R33 33K/2W

D74148

IC7 TLP521-1

C19103

L1

R315.6K

R29560

R34 33K/2W

R32 33K/2W

D64148

IC6 TLP521-1

C18

103

N

TEST

OSC14MHz

+5

+5

LED1

+5

+5

+5

N

L3

L2

FUSE

T3.15A/250V

4-way valve wind

C20104

EX T

HTE

MP

TH

12

CN7B2B-VH-B

IRQ1

PTA02

PTA16

PTA28

PTA39

PTA4 23

PTA5 27

VSS3

OSC14

OSC2/PTA65

VDD7

PTB0 21

PTB1 20

PTB2 18

PTB3 17

PTB4 15

PTB512

PTB611

PTB710

PTD0 16

PTD1 19

PTD2 24

PTD3 22

PTD4 26

PTD5 25

PTD614

PTD713

RST 28

IC3MC68HC908JL3ECP

12CN11

XHB2B

C25104

R2647K

R2710K

C27 103

12CN10

VHB2B

R2010K

compressor

JK1JQ1P

JK2OJE-SS-112DM

123

CN9B3B-VH-W

R23

560

R9 1M

+5

12

CN3XHB2B

12

CN12XHB2B

LX102LX1

D14D15

D13D120057W

250

250

250

250

250

250

250

250

LH

S14K350 AU42NABCEA

0010451295

R21 10K

fan motor

Page 104: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Circuit for single-phase outdoor unit (capacity is over 24000BTU/h):

1 2 3 4 5 6

A

B

C

D

654321

D

C

B

A

Title

Number RevisionSize

B

Date: 5-Nov-2003 Sheet of File: C:\Documents and Settings\zhanjie\×ÀÃæ\0010451293.DDBDrawn By:

+12 1

2

CN4RTB-1.5-2P

1

2

CN1XHB2P3

C23

0.1UF/250V

C8104

C12200UF/35V

Vin 1

GN

D2

Vout3RG1 7805

C7104 C24

0.1UF/250V

+5

D8 D11

D10D9 L1

VR

N

RW102

R13470

C21470UF/16V

R11

1K

R10

1K

D54148

+5

C6104

CT1

C224.7UF/50V

+5

R245.1K

R255.1K

C174.7UF/50V

R1

200K

C1622uF/250V

R362K/3W

R462K/3W

R262K/3W

D24007

D14007

D34007

D44007

R16

10K/0.5W

R15

10K/0.5W

S

R62.2K

C2103

R533K

IC2 TLP521-1

IC1 TLP371

R8

1K

R710K

R12

560

C3103

C4 103

+5

+5

+12

+12

C5104

JK5

OJE-SS-112DM

JK7

OJE-SS-112DM

A11

A22

A33

A44

A55

A66

A77 Q7 10Q6 11Q5 12Q4 13Q3 14Q2 15Q1 16

GND8 VCC 9

IC4ULN2003A

12

CN5B2B-VH-W

R1910K

R1810K

R1710K

C10 103

C11 103

C12 103

12CN2

VHB2B

R30 5.6K

L1

R31 5.6K

N

TEST

OSC14MHz

+5

+5

LED1

+5

+5

FUSE

T3.15A/250V

4-way valve wind

C20104

EX T

HTE

MP

TH

12

CN7B2B-VH-B

IRQ1

PTA02

PTA16

PTA28

PTA39

PTA4 23

PTA5 27

VSS3

OSC14

OSC2/PTA65

VDD7

PTB0 21

PTB1 20

PTB2 18

PTB3 17

PTB4 15

PTB512

PTB611

PTB710

PTD0 16

PTD1 19

PTD2 24

PTD3 22

PTD4 26

PTD5 25

PTD614

PTD713

RST 28

IC3MC68HC908JL3ECP

12CN11

XHB2B

C25104

R2647K

R2710K

C27 103

12CN10

VHB2B

R2010K

compressor

JK1JQ1P

JK2OJE-SS-112DM

123

CN9B3B-VH-W

R23

560

R9 1M

+5

12

CN3XHB2B

12

CN12XHB2B

LX102LX1

D14D15

D13D120057W

250

250

250

250

250

LH

S14K350 AU242ACBEA

0010451293

R21

10K

fan motor

Page 105: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

0010451167 PCB information – circuit diagram

12345678

10111213141516

9

IC1

2003

C32 104

1 P2-P6187

E64.7uF

INOUT

W1

7812

RL1JQ1AP-1

RL3JQ1AP-A

RL6JQ1AP-A

RC30.033uF+120

N8

9013

765

1234

8IC5

24C

01A

XT1

8.00M

1

7

CN13

1

4

CN14

12

CN16

12345678

10111213141516

9

IC2

2003

RL8JQ1P-A

RL7JQ1P-A

RL5JQ1AP-A

RL2JQ1AP-A

RL4JQ1AP-A

N7 9013

N6 9013

1

IRQ/50Hz2

RESET3

56

NOP4

BEEP7

IR89

101112

NET-O13

NET-I141516

NOP171819

NOP20

Vss21

Vdd22

25

SCL23

SDA24

A26

B27

C28

D29303132 NOP 33

3435363738394041

4748

VDDAREF 44AVss 45

4950

4243

NOP 46

515253VREFH 54VDDA 55VSSA 56CGMXFC 57OSC2 58OSC1 596061626364

487

P/GP/G

IC3

AB32

RB4

SW2

RO 1/RE 2DE 3DI 4GND5

VCC8 B7 A6

IC4 MAX487

R23 1K

R52

10K

R661M

R294.7K

R284.7K

R53 10K

R54 10K

R19

1K

C23103

C26 104

C28 104

1 P11187

1 P8187

1 P7187

1 P12187

1 P13187

1 P14187

C34 104

RC20.033uF+120

RC10.033uF+120

BUZ1

R67 100 R35 4.7K

R46 10KR16 1K

R17 1K

R18 1K

R57 4.7K

R55

10K

C25 104

C6102

C19103

C17103

C18103

C5 102

C27

104

GND+5V

14 CN6

12

CN11

1

CN15

R45 10K

R44 10K

RB3RB2 RB5

SW1

E74.7uF

1 P1187

C2

0.1UF/275V

FUSE1

T3.15A/250VC1

0.1UF/275V

CN1RV1

D1-D4

1

4

CN4

T1

TRAN1-2

E12200uF

INOUT

W2

7805C33

104

N49013

N59013

R26 4.7K

R27 4.7K

DL2DL1

LED1

R12560

R13

1K

R61 20K

LB1

E3

470uF/16V

E9

1uF

D18

1N41

48

1 2 3 4 5CN19

R47 10KR48 10K

R40 10K

R304.7K

N9

R10

330

IC6TLP371

R5 33K

C4 103LED3

D9IC7TLP521

R21

1K

R3610K

C3

103

R4

2.2K

R210K/0.5W

R3 10K/0.5W

D101N4007

1

24

5 6

1

2 3

4

C22103

C29104

E4100uF

R62 20KR60 20K

1

P15

187

R51 10KR59 10KR56 10K

R50 10K

1

CN12

RB1

C12103

C13103

R49 10K

C8102

C11103

C10103

C9103

12CN8

E5

4.7uF

R14

1K

R15

1K

D17

1N4148

C14 103

C15 103

C16 103

1 P9187

1 P10187

1 2 3 4 5CN20

C31 104

R8 10

1

CN7

1

CN5

D124148D134148

ABC

R344.7K

R41 10K

R6456K

R4310K C21

103N1 9013

R24

1K

IC10

TLP741/541

IC9

TLP521

R6327K

C24103

D164148

D154148D144148

LED4

R324.7K

R7 10

R25 2.4K

LED5

N29013

N39013

R33

1K

R11 330

R22 1K

R314.7K

C7102

R39 10K

D111N4007

IC8

TLP521-1 1

P17187

P16187R9 220

R6680

R1100K/1W

R65200K

R201K E8

2.2uFC20103

J1 J2 J3 J4 J5 J6 J7 J8 J9 J10

J1

J2

J3

J4

J5

J6

J7

J8

J9

J10

1/60

CHECK

C35104

C36

104

N109013

12

CN17D194148

12

CN22

12

CN23

12

CN10

LED2

R58

1K

+5

+5

+12

+5

+5

+5

+12

+12

+5

+12

+12

+5v

+5

+5

+5

+5

EEPROM

+5

+5

+12

VDD

+5

+5

+5

+5

+5

+5

+5v

+12

VDD

1

Page 106: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

0010451167 PCB information – characters on board(horizontal)

Page 107: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

0010451167 characters on board(vertical)

Page 108: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

0010451167 PCB information – port and definition

P1——connect to external power supply, live line: L (220VAC)

P2——connect to external power supply, neutral line: N (0VAC)

P3、4、5、6——control external load, neutral line: N1、N2、N3、N4(0VAC)

P7——control external load, electrical heat: HEAT (control output 220VAC)

P8——control external load, health function: OXYGEN (control output 220VAC)

P9——control external load, humidification: HUMI (control output 220VAC)

P10——control external load, SWING(control output 220VAC)

P11——control external load, WATER PUMP(control output 220VAC)

P12——control external load, indoor fan motor low speed: L(control output

220VAC)

P13——control external load, indoor fan motor mid speed: M(control output

220VAC)

P14——control external load, indoor fan motor high speed: H(control output

220VAC)

P15 — — communication with fixed frequency single outdoor unit:

COMM(0~220VAC)

P16——input control, signal live line: L’(220VAC)

P17——input control, signal neutral line: N’(0VAC)

CN1——input port of transformer (220VAC)

CN2——input port 1 of transformer (no use)

CN3——input port 2 of transformer (no use)

Page 109: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

CN4——input port 3 of transformer (1-2、14VAC,3-4、12VAC)

CN5——input control, connecting port to wired controller: CONTROLLER(1.

power supply: 12VAC, 2. power supply: 0VAC, 3. communication: COMM.)

CN6 —— input control, ambient temp.-coil temp. sensor connecting port:

ROOM/PIPE(1-2、ROOM,3-4、PIPE。)

CN7——control external load, fresh air control: FRESH(1. blank, 2. power

supply 0VDC, 3. control output: 12VDC.)

CN8——input signal: FREEZE(no use)

CN9——input control(no use)

CN10——communication with fixed frequency single outdoor unit: (0~12VDC)

CN11——input signal, door switch: DOOR(1-2 short circuit is normal, cut off

P8 output)

CN12——input signal, external alarm input: ALARM(1-3 short circuit is normal,

if cut off, air conditioner stops work.)

CN13——input signal, wiring port of remote receiver board: RECEIVE BOARD

(1. power supply 5VDC, 2. power supply 0VDC, 3. remote signal, 4. signal output of

running lamp 0VDC, 5. signal output of timer lamp 0VDC,6. signal output of power

lamp 0VDC, 7. signal output of water pump running lamp 0VDC)

CN14——control external load, elevating function (1. signal of door switch

close, 2. output of elevating direction control 0VDC, 3. output of elevating power

control 0VDC, 4. power supply 12VDC)

CN15——input signal, water level of float switch (1-3 short circuit is normal, cut

Page 110: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

off shows that level exceeds the limitation)

CN16——input control, wiring port of central controller: REMOTE(1、RS485-B,

2、RS485-A。)

CN17——output signal, output signal of failure alarm, control external load,

12V/ALM(1. control output 0VDC, 2. power supply 12VDC)

CN18——output signal (no use)

CN19——control external load, swing 1(1、16VDC,2、0VDC,3、0VDC,4、

0VDC,5、0VDC.)

CN20——control external load, swing 2(1、16VDC,2、0VDC,3、0VDC,4、

0VDC,5、0VDC.)

CN21——input signal, spring switch, CHECK(1、input signal of earthing, 2.

power supply 0VDC)

CN22——short circuit means selecting single split communication type.

CN23——short circuit means selecting multi split communication type.

Page 111: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

0010451167 PCB information – function selection(ON is 1, OFF is 0)

The standard condition for PCB in factory

SW1:4 bits are OFF

SW2:4 bits are OFF

SW3:4 bits are ON

SW4:2 bits are ON

SW5:4 bits are ON

SW1-1——address selection of central controller 0, address selection of wired

controller 0

SW1-2——address selection of central controller 1,address selection of wired

controller 1

SW1-3——address selection of central controller 2,address selection of wired

controller 2

SW1-4——address selection of central controller 3,address selection of wired

controller 3

SW2-1——address selection of central controller 4

SW2-2——address selection of central controller 5

SW2-3——address selection of central controller 6

SW2-4——logistic relationship of control function(door card control and remote/

wired control)0 means logistic relationship is “and”, 1 means the later coming is

preferential.

J1,SW3-1——function selection-control type: 1 means remote control, 0 means

Page 112: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

wired control.

J2,SW3-2——function selection-temperature compensation in heating mode:

1means “yes”, 0means “no”.

J3,SW3-3——function selection-outdoor communication: 1means “yes”, 0means

“no”. This PCB must be 1.

J4,SW3-4——function selection-heat pump unit: 1means “heat pump”, 0means

“cooling only”.

1/60——test in short circuit, but in operation short circuit mustn’t be permitted.

CHECK——short spring switch control, it also can be used as switch of

convertible type except for testing.

J5,SW4-1——function selection-elevating function: 1means “yes”, 0means “no”.

J6,SW4-2——function selection –health function: 1means common (indoor fan

motor running); 0 means special (indoor, outdoor running).

J7,SW5-1——function selection –swing mode: 1 means common(simultaneous

motor), 0 means special (swing motor).

J8,SW5-2——function selection – system combination: 1means fixed frequency

single unit, 0 means fixed frequency multi split.

J9,SW5-3——function selection –group control: 1 stands for the master unit (its

address in wired controller is 0), 0 stands for the slave units (the address should be

set by the dip switch, their addresses only can be in the range: 1~15)

J10,SW5-4——function selection –preset: 1 no meaning, 0 no meaning

Page 113: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

0010451167 PCB information- control type

Control type selection between remote and wired: select by dip switch J1, SW3-1

(1 means remote control;0means wired control).

For remote control type, please use remote controller YR-H71, and a remote

receiver is equipped with indoor unit. For wired control type, wired controller

YR-E12 will be used, 3-core shied wire is equipped with indoor unit.

Door card control: controls ON/OFF, the start up setting will comply with last time

request memorized according to condition memorize function. Its difference with

emergency switch of convertible type unit lies: the emergency switch control will

perform in the condition: 24degrees, auto fan speed in auto mode.

The function combination between door card and remote/wired control type: select

by dip switch: SW2-4(0 means “and”, 1 means later coming is preferential.)

Dip switch position in wired control type: Only one indoor unit of all indoor units

connected with wired controller is the master unit, whose address is 0, function

selection switch(J9,SW5-3)is 1. The others are slave units, and the quantity can be

0~15, whose addresses are(SW1:1~4)from 1 ~15, and cannot repeat.

Wiring request in wired control type: the wired controller ports A-B-C are

connected with indoor port CN5(1-2-3) through 3-core shield wire. Requirements:

1. Port A only connects with either of indoor port CN5(1)

2. Port B connects with port CN5 (2) of all indoor units.

3. Port C connects with port CN5 (3) of all indoor units.

Page 114: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Dip switch position in central control type: the addresses (SW1:1~4;SW2:1~4)

of indoor units connected with central controller can not repeat. In principle, they

should be in the order from small to big.

Wiring request in central control type: port A-B is connected with indoor port

CN16(A-B)through 2-core shield wire. Requirements:

1. Port A connects with port CN16(A)of all indoor units.

2. Port B connects with port CN16(B)of all indoor units.

When only use remote control type, please select remote control unit, and install

according to installation manual, there is no other special request.

When only use wired control type, please select wired control unit, and install

according to installation manual. When control multi indoor units, take care the

requirements of dip switch and wiring, there is no other special request.

When only use central control type, please firstly install according to air conditioner

requests and set the dipswitch, there is no other special request.

When central control type(128×)and remote control type are used simultaneously,

set the dip switch according to central control type, there is no other special request.

When central control type(128×)and wired control type (16×)are used

simultaneously, max. indoor units sets: 128×16 can be controller. Address setting of

central controller can be met firstly, and then modulate the address setting of slave unit

wired controlled.

Page 115: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

10. Exploded view cassette type: AB36NACBEA and AB42NACBEA are the same.

Page 116: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No. Spare parts numberSpare parts description inenglish Qty. Model

Failurerate

the proportion ofthe spare-partstock Remark

1 001A1232307 Electrical box cover2 1 AB42NACBEA 0.00% 0.000% ×2 001A1232306 Electrical box cover1 1 AB42NACBEA 0.00% 0.000% ×3 0010451265 Terminal block 1 AB42NACBEA 0.00% 0.000% ×4 001A3600232 fan mortor capacitor 1 AB42NACBEA 0.04% 0.048% *5 0010451262 Transformer 1 AB42NACBEA 0.01% 0.012%6 0010451167 Indoor PCB 1 AB42NACBEA 0.02% 0.024% *7 001A1232305 Electrical box 1 AB42NACBEA 0.00% 0.000% ×8 001A1301815 fan motor filter 1 AB42NACBEA 0.00% 0.000% ×9 001A1231308 Wind ring 1 AB42NACBEA 0.00% 0.000% ×

10 001A1434927 Drin pan accessory 1 AB42NACBEA 0.00% 0.000% ×11 001A0900066 Drin pan assy. 1 AB42NACBEA 0.00% 0.000% ×12 001A5102015 Flange screw nut 1 AB42NACBEA 0.00% 0.000% ×13 001A1301710 Fan in-built part 1 AB42NACBEA 0.00% 0.000% ×14 0010250212 Centrifugal fan 1 AB42NACBEA 0.02% 0.024% *15 001A3000195 Indoor fan motor 1 AB42NACBEA 0.02% 0.024% *16 001A1301668 Motor bracket 1 AB42NACBEA 0.00% 0.000% ×17 001A1301669 Motor holder 1 AB42NACBEA 0.00% 0.000% ×18 001A1301679 Evaporator holder 2 AB42NACBEA 0.00% 0.000% ×19 0010752260 Heat exchanger assy. 1 AB42NACBEA 0.01% 0.012%20 001A0100507 Bottom plate assy. 1 AB42NACBEA 0.00% 0.000% ×21 001A1101187 Swing 4 AB42NACBEA 0.00% 0.000% ×22 001A3900006 Pipe temp. sensor 1 AB42NACBEA 0.00% 0.000% ×23 001A1301677 pump Bracket 1 AB42NACBEA 0.00% 0.000% ×24 001A3400160 Float Switch 1 AB42NACBEA 0.00% 0.000% ×25 001A01001096 Evaporator holded plate 1 AB42NACBEA 0.00% 0.000% ×26 001A1434920 Drainage hose 1 AB42NACBEA 0.00% 0.000% ×27 001A3000197 Water pump 1 AB42NACBEA 0.00% 0.000% ×28 001A1301659 pipe holder plate 1 AB42NACBEA 0.00% 0.000% ×29 001A3900159 nvironment temperature sens 1 AB42NACBEA 0.00% 0.000% ×30 001A1439315 collar clamp 1 AB42NACBEA 0.00% 0.000% ×31 0010451255 Remote Controller 1 AB42NACBEA 0.01% 0.012%32 001A1734260 Heat insulation pipe1 1 AB42NACBEA 0.00% 0.000% ×33 001A1734261 Heat insulation pipe2 1 AB42NACBEA 0.00% 0.000% ×

Parts list

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with theactual quantity 3 months later.

6.The spare parts price on net is FOB Qingdao term.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-partswarehouse,and should be marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer maystock in the spare-part warehouse accord with the actual case,should be marked with " ".

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.Thespare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-partwarehouse,should be marked with " x ".

5,Above should be improved accord with the reply of the market half a year per time.

Page 117: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Convertible type

AC36NACBEA and AC42NACBEA are the same

Page 118: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No. Spare parts number Spare parts description in english Qty. ModelFailurerate

the proportionof the spare-part stock Remark

1 001A1231278 inlet grill assy 3 AC42NACBEA 0.00% 0.000% ×2 001A2400108 air filter 3 AC42NACBEA 0.00% 0.000% ×3 001A1101167 front panel assy 1 AC42NACBEA 0.00% 0.000% ×4 001A17341009 pad 1 AC42NACBEA 0.00% 0.000% ×5 001A13011280 Eletrical box 1 AC42NACBEA 0.00% 0.000% ×6 001A1301379 Eletrical box cover 1 AC42NACBEA 0.00% 0.000% ×7 0010451167 PCB 1 AC42NACBEA 0.02% 0.024% *8 0010451262 transformer 1 AC42NACBEA 0.01% 0.012%9 001A3600098 capacitor 2 AC42NACBEA 0.04% 0.048% *10 0010451265 termonal block 1 AC42NACBEA 0.00% 0.000% ×11 001A5701062 Power line clip 1 AC42NACBEA 0.00% 0.000% ×12 001A3900159 environment temp. Sensor indoor 1 AC42NACBEA 0.00% 0.000% ×13 001A1301580 motor bracket 4 AC42NACBEA 0.00% 0.000% ×14 001A1301582 scroll case right 2 AC42NACBEA 0.00% 0.000% ×15 001A1200325 drain pan assy 1 AC42NACBEA 0.00% 0.000% ×16 001A1101172 mounting plate 1 AC42NACBEA 0.00% 0.000% ×17 0010751099 air pipe 1 AC42NACBEA 0.00% 0.000% ×18 0010752148 liquid pipe 1 AC42NACBEA 0.00% 0.000% ×19 001A1301588 partition plate 1 AC42NACBEA 0.00% 0.000% ×20 001A1301577 plate assy right 1 AC42NACBEA 0.00% 0.000% ×21 001A1301579 right wallboard 1 AC42NACBEA 0.00% 0.000% ×22 001A1231277 Ornamental plate right 1 AC42NACBEA 0.00% 0.000% ×23 001A1301574 left scroll case 2 AC42NACBEA 0.00% 0.000% ×24 001A2331071 centrifugal fan 4 AC42NACBEA 0.02% 0.024% *25 001A1301581 motor bracket 2 AC42NACBEA 0.00% 0.000% ×26 0010450626 Indoor fan motor 2 AC42NACBEA 0.02% 0.024% *27 001A1301578 left wallboard 1 AC42NACBEA 0.00% 0.000% ×28 001A1231276 ornamental plate (left) 1 AC42NACBEA 0.00% 0.000% ×29 001A3900006 Pipe temp. sensor indoor 1 AC42NACBEA 0.00% 0.000% ×30 001A1431878 Indicator light cover 1 AC42NACBEA 0.00% 0.000% ×31 0010400410 receive panel 1 AC42NACBEA 0.02% 0.024% *32 001A1231279 ornamental plate of panel(left) 1 AC42NACBEA 0.00% 0.000% ×33 001A1231280 middle ornamental plate 4 AC42NACBEA 0.00% 0.000% ×34 001A1101169 Long blade assy 1 AC42NACBEA 0.00% 0.000% ×35 001A1431800 fixing bracket left 1 AC42NACBEA 0.00% 0.000% ×36 001A0100431 left fixing bracket 1 AC42NACBEA 0.00% 0.000% ×37 001A1231272 left top cover assy 1 AC42NACBEA 0.00% 0.000% ×38 001A1231274 front top cover assy 3 AC42NACBEA 0.00% 0.000% ×39 001A1231281 Ornamental plate of panel right 1 AC42NACBEA 0.00% 0.000% ×40 001A0100435 outlet grill hold middle 3 AC42NACBEA 0.00% 0.000% ×41 001A1231275 top cover assy 3 AC42NACBEA 0.00% 0.000% ×42 001A1101170 long blade 2 1 AC42NACBEA 0.00% 0.000% ×43 001A0100432 outlet grill hold right 1 AC42NACBEA 0.00% 0.000% ×44 001A1231273 right top cover assy 1 AC42NACBEA 0.00% 0.000% ×45 001A1431746 fixing bracket right 1 AC42NACBEA 0.00% 0.000% ×46 001A1443745 prompting pole 1 AC42NACBEA 0.00% 0.000% ×47 001A3000198 Synchromotor 1 AC42NACBEA 0.02% 0.024% *48 0010451255 Remote Controller 1 AC42NACBEA 0.01% 0.012%49 001A1734260 Heat insulation pipe1 1 AC42NACBEA 0.00% 0.000% ×50 001A1301575 plate assy left 1 AC42NACBEA 0.00% 0.000% ×51 0010752258 evaporator 1 AC42NACBEA 0.01% 0.012%52 001A1101171 Rear guard plate 1 AC42NACBEA 0.00% 0.000% ×

Parts list

Page 119: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Duct type

AD36NAMBEA\AD42NAMBEA

Page 120: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No.Spare partsnumber Spare parts description in English Qty. Model

Failurerate

the proportion ofthe spare-partstock Remark

1 001A1101223 Guard plate 1 1 AD42NAMBEA 0.000% 0.000% X2 001A1101226 Guard plate 2 1 AD42NAMBEA 0.000% 0.000% X3 0010752912 Evaporator assembly 1 AD42NAMBEA 0.010% 0.012%4 001A0100744 Right fixing plate assembly 1 AD42NAMBEA 0.000% 0.000% X5 001A1101203 Supporting plate assembly(right) 1 AD42NAMBEA 0.000% 0.000% X6 001A1301988 Seal ring for scroll case 3 AD42NAMBEA 0.000% 0.000% X7 001A2331089 Centrifugal fan 3 AD42NAMBEA 0.020% 0.024% *8 001A17621153 Cushion 1 AD42NAMBEA 0.000% 0.000% X9 001A17621151 Cushion 1 AD42NAMBEA 0.000% 0.000% X

10 001A17341291 Cushion 4 AD42NAMBEA 0.000% 0.000% X11 001A14311066 Air outlet 4 AD42NAMBEA 0.000% 0.000% X12 001A17341292 Cushion 4 AD42NAMBEA 0.000% 0.000% X13 001A1101227 inlet wind connect frame 1 AD42NAMBEA 0.000% 0.000% X14 001A17341156 Cushion 1 AD42NAMBEA 0.000% 0.000% X15 001A17341269 Cushion 1 AD42NAMBEA 0.000% 0.000% X16 001A1101228 Long fixing tendon 1 AD42NAMBEA 0.000% 0.000% X17 001A1101224 Enclosure 1 AD42NAMBEA 0.000% 0.000% X18 001A1101225 Inlet wind connect frame 1 AD42NAMBEA 0.000% 0.000% X19 0010451262 Transformer 1 AD42NAMBEA 0.010% 0.012% *20 001A1101206 Electrical box 1 AD42NAMBEA 0.010% 0.012%21 001A1452909 Rubber ring 1 AD42NAMBEA 0.000% 0.000% X22 001A1452861 Rubber ring 1 AD42NAMBEA 0.000% 0.000% X23 0010451167 indoor PCB 1 AD42NAMBEA 0.020% 0.024% *24 0010451265 Terminal block 1 AD42NAMBEA 0.020% 0.024% *25 001A3600134 Fan capacitor 1 AD42NAMBEA 0.040% 0.048% *26 001A3600237 Fan capacitor 1 AD42NAMBEA 0.040% 0.048% *27 001A1301796 Electrical box cover assembly 1 AD42NAMBEA 0.000% 0.000% X28 001A5002256 Fixing bolt 3 AD42NAMBEA 0.000% 0.000% X29 001A1309785 W ater pump fixing stand 1 AD42NAMBEA 0.000% 0.000% X30 001A17511246 Damping pad 3 AD42NAMBEA 0.000% 0.000% X31 001A3000250 Dual shaft electric motor 1 AD42NAMBEA 0.020% 0.024% *32 0010450169 Water pump motor 1 AD42NAMBEA 0.020% 0.024% *33 001A1301786 Floater fixing stand 1 AD42NAMBEA 0.000% 0.000% X34 001A14341141 Water drain pipe assembly 1 AD42NAMBEA 0.000% 0.000% X35 001A1301783 Connecting plate 2 1 AD42NAMBEA 0.000% 0.000% X36 001A1301784 Water pump support 1 AD42NAMBEA 0.000% 0.000% X37 001A1301782 Connecting plate 1 1 AD42NAMBEA 0.000% 0.000% X38 001A3400076 Float switch 1 AD42NAMBEA 0.000% 0.000% X39 001A1301789 Fixed handle 1 2 AD42NAMBEA 0.000% 0.000% X40 001A1301790 Fixed handle 2 2 AD42NAMBEA 0.000% 0.000% X41 001A3000251 Single shaft electric motor 1 AD42NAMBEA 0.000% 0.000% X42 001A1101205 Scroll case 3 AD42NAMBEA 0.000% 0.000% X43 001A0100743 Left fixing plate assembly 1 AD42NAMBEA 0.000% 0.000% X44 001A0900094 Water collecting pan assembly 1 AD42NAMBEA 0.000% 0.000% X45 001A17621350 Cushion 1 AD42NAMBEA 0.000% 0.000% X

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spareparts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-partwarehouse,should be marked with " x ".5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.

Parts list

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The firsttime should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,andshould be marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock inthe spare-part warehouse accord with the actual case,should be marked with " ".

Page 121: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No.Spare partsnumber Spare parts description in English Qty. Model

Failurerate

the proportion of thespare-part stock Remark

1 0010850776 Guard plate 1 1 AD36NAMBEA 0.000% 0.000% X2 001A1101226 Guard plate 2 1 AD36NAMBEA 0.000% 0.000% X3 0010752257 Evaporator assembly 1 AD36NAMBEA 0.010% 0.012%4 001A0100744 Right fixing plate assembly 1 AD36NAMBEA 0.000% 0.000% X5 001A1101203 Supporting plate assembly(right) 1 AD36NAMBEA 0.000% 0.000% X6 001A1301988 Seal ring for scroll case 3 AD36NAMBEA 0.000% 0.000% X7 001A2331089 Centrifugal fan 3 AD36NAMBEA 0.020% 0.024% *8 001A17621153 Cushion 1 AD36NAMBEA 0.000% 0.000% X9 001A17621151 Cushion 1 AD36NAMBEA 0.000% 0.000% X

10 001A17341291 Cushion 4 AD36NAMBEA 0.000% 0.000% X11 001A14311066 Air outlet 4 AD36NAMBEA 0.000% 0.000% X12 001A17341292 Cushion 4 AD36NAMBEA 0.000% 0.000% X13 001A1101227 inlet wind connect frame 1 AD36NAMBEA 0.000% 0.000% X14 001A17341156 Cushion 1 AD36NAMBEA 0.000% 0.000% X15 001A17341269 Cushion 1 AD36NAMBEA 0.000% 0.000% X16 001A1101228 Long fixing tendon 1 AD36NAMBEA 0.000% 0.000% X17 001A1101224 Enclosure 1 AD36NAMBEA 0.000% 0.000% X18 001A1101225 Inlet wind connect frame 1 AD36NAMBEA 0.000% 0.000% X19 0010451262 Transformer 1 AD36NAMBEA 0.010% 0.012% *20 001A1101206 Electrical box 1 AD36NAMBEA 0.010% 0.012%21 001A1452909 Rubber ring 1 AD36NAMBEA 0.000% 0.000% X22 001A1452861 Rubber ring 1 AD36NAMBEA 0.000% 0.000% X23 0010451167 indoor PCB 1 AD36NAMBEA 0.020% 0.024% *24 0010451265 Terminal block 1 AD36NAMBEA 0.020% 0.024% *25 001A3600134 Fan capacitor 1 AD36NAMBEA 0.040% 0.048% *26 001A3600237 Fan capacitor 1 AD36NAMBEA 0.040% 0.048% *27 001A1301796 Electrical box cover assembly 1 AD36NAMBEA 0.000% 0.000% X28 001A5002256 Fixing bolt 3 AD36NAMBEA 0.000% 0.000% X29 001A1309785 W ater pump fixing stand 1 AD36NAMBEA 0.000% 0.000% X30 001A17511246 Damping pad 3 AD36NAMBEA 0.000% 0.000% X31 001A3000250 Dual shaft electric motor 1 AD36NAMBEA 0.020% 0.024% *32 0010450169 Water pump motor 1 AD36NAMBEA 0.020% 0.024% *33 001A1301786 Floater fixing stand 1 AD36NAMBEA 0.000% 0.000% X34 001A14341141 Water drain pipe assembly 1 AD36NAMBEA 0.000% 0.000% X35 001A1301783 Connecting plate 2 1 AD36NAMBEA 0.000% 0.000% X36 001A1301784 Water pump support 1 AD36NAMBEA 0.000% 0.000% X37 001A1301782 Connecting plate 1 1 AD36NAMBEA 0.000% 0.000% X38 001A3400076 Float switch 1 AD36NAMBEA 0.000% 0.000% X39 001A1301789 Fixed handle 1 2 AD36NAMBEA 0.000% 0.000% X40 001A1301790 Fixed handle 2 2 AD36NAMBEA 0.000% 0.000% X41 001A3000251 Single shaft electric motor 1 AD36NAMBEA 0.000% 0.000% X42 001A1101205 Scroll case 3 AD36NAMBEA 0.000% 0.000% X43 001A0100743 Left fixing plate assembly 1 AD36NAMBEA 0.000% 0.000% X44 001A0900094 Water collecting pan assembly 1 AD36NAMBEA 0.000% 0.000% X45 001A17621350 Cushion 1 AD36NAMBEA 0.000% 0.000% X

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare partsmay be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should bemarked with " x ".

5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.

Parts list

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The firsttime should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3months later.2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and shouldbe marked with"*"3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in thespare-part warehouse accord with the actual case,should be marked with " ".

Page 122: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

High static pressure duct unit

Page 123: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No. Spare parts numberSpare parts description inenglish Qty. Model Failure rate

the proportion ofthe spare-partstock Remark

1 001A01001000 connection frame of inlet air 1 AD42NAHBEA 0.000% 0.000% x2 0010151123 hanging 4 AD42NAHBEA 0.000% 0.000% x3 0010851049 boarding assy. of liquid pipe 1 AD42NAHBEA 0.000% 0.000% x4 001A0100999 fix blot assy. 1 AD42NAHBEA 0.000% 0.000% x5 001A01001002 bottom plate assy. 1 AD42NAHBEA 0.000% 0.000% x6 001A1301205 air discharge framework 1 AD42NAHBEA 0.000% 0.000% x8 0010800284 cover board assy. 1 1 AD42NAHBEA 0.000% 0.000% x9 0010800282 fix tendon assy. 1 1 AD42NAHBEA 0.000% 0.000% x10 0010800285 cover board assy. 2 1 AD42NAHBEA 0.000% 0.000% x11 001A13011050 bracket of floater 1 AD42NAHBEA 0.000% 0.000% x12 0010800290 evaporator fixing plate 3 1 AD42NAHBEA 0.000% 0.000% x13 0010752259 evaporator assy. 1 AD42NAHBEA 0.000% 0.000% x14 0010800286 cover board assy. 3 1 AD42NAHBEA 0.000% 0.000% x15 0010800283 fix tendon assy. 2 1 AD42NAHBEA 0.000% 0.000% x16 0010800289 evaporator fixing plate 2 1 AD42NAHBEA 0.000% 0.000% x17 0010451262 transformer 1 AD42NAHBEA 0.020% 0.024% *18 0010400298 relay 3 AD42NAHBEA 0.030% 0.036% *19 001A3600254 fan motor capacitor 1 AD42NAHBEA 0.040% 0.048% *20 001A13011035 electrical box cover 1 AD42NAHBEA 0.010% 0.012%21 001A3300352 Fan Speed Controller 1 AD42NAHBEA 0.020% 0.024% *22 001A5745116 Power line clip 1 AD42NAHBEA 0.000% 0.000% x23 0010451470 wiring harness 1 AD42NAHBEA 0.000% 0.000% x24 0010451167 indoor PCB 1 AD42NAHBEA 0.020% 0.024% *25 0010451265 termianl block 1 AD42NAHBEA 0.020% 0.024% *26 0010800287 electrical box assy. 1 AD42NAHBEA 0.000% 0.000% x27 0010752120 liquid pipe assy. 1 AD42NAHBEA 0.000% 0.000% x28 0010700869 air pipe assy. 1 AD42NAHBEA 0.000% 0.000% x30 0010800290 evaporator fixing plate 3 1 AD42NAHBEA 0.000% 0.000% x31 001A3400160 float switch 1 AD42NAHBEA 0.000% 0.000% x32 001A13011045 motor fixing bolt 1 AD42NAHBEA 0.000% 0.000% x33 001A13011045 motor fixing bolt 1 AD42NAHBEA 0.000% 0.000% x34 001A13011039 motor bracket 1 AD42NAHBEA 0.000% 0.000% x35 001A13011040 snail shell 1 1 AD42NAHBEA 0.000% 0.000% x36 001A2301102 fan 1 1 AD42NAHBEA 0.020% 0.024% *37 001A13011044 hermitic circle of snail shell 1 AD42NAHBEA 0.000% 0.000% x38 001A13011044 hermitic circle of snail shell 1 AD42NAHBEA 0.000% 0.000% x39 001A2301103 fan 2 1 AD42NAHBEA 0.020% 0.024% *40 001A13011041 snail shell 2 1 AD42NAHBEA 0.000% 0.000% x41 001A5401035 washer 1 AD42NAHBEA 0.000% 0.000% x42 001A3000291 indoor motor 1 AD42NAHBEA 0.020% 0.024% *43 0010800329 drain pan assy. 1 AD42NAHBEA 0.000% 0.000% x44 0010800280 guarding plate assy.2 1 AD42NAHBEA 0.000% 0.000% x45 0010800281 guarding plate assy.1 1 AD42NAHBEA 0.000% 0.000% x

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spareparts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-partwarehouse,should be marked with " x ".

5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.

Parts list

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The firsttime should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,andshould be marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock inthe spare-part warehouse accord with the actual case,should be marked with " ".

Page 124: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No. Spare parts numberSpare parts description inenglish Qty. Model Failure rate

the proportion of thespare-part stock Remark

1 001A01001000 connection frame of inlet air 1 AD36NAHBEA 0.000% 0.000% x2 0010151123 hanging 4 AD36NAHBEA 0.000% 0.000% x3 0010851049 boarding assy. of liquid pipe 1 AD36NAHBEA 0.000% 0.000% x4 001A0100999 fix blot assy. 1 AD36NAHBEA 0.000% 0.000% x5 001A01001002 bottom plate assy. 1 AD36NAHBEA 0.000% 0.000% x6 001A1301205 air discharge framework 1 AD36NAHBEA 0.000% 0.000% x8 0010800284 cover board assy. 1 1 AD36NAHBEA 0.000% 0.000% x9 0010800282 fix tendon assy. 1 1 AD36NAHBEA 0.000% 0.000% x10 0010800285 cover board assy. 2 1 AD36NAHBEA 0.000% 0.000% x11 001A13011050 bracket of float 1 AD36NAHBEA 0.000% 0.000% x12 0010800290 evaporator fixing plate 3 1 AD36NAHBEA 0.000% 0.000% x13 0010752259 evaporator assy. 1 AD36NAHBEA 0.000% 0.000% x14 0010800286 cover board assy. 3 1 AD36NAHBEA 0.000% 0.000% x15 0010800283 fix tendon assy. 2 1 AD36NAHBEA 0.000% 0.000% x16 0010800289 evaporator fixing plate 2 1 AD36NAHBEA 0.000% 0.000% x17 0010451262 transformer 1 AD36NAHBEA 0.020% 0.024% *18 0010400298 relay 3 AD36NAHBEA 0.030% 0.036% *19 001A3600254 fan motor capacitor 1 AD36NAHBEA 0.040% 0.048% *20 001A13011035 electrical box cover 1 AD36NAHBEA 0.010% 0.012%21 001A3300352 Fan Speed Controller 1 AD36NAHBEA 0.020% 0.024% *22 001A5745116 Power line clip 1 AD36NAHBEA 0.000% 0.000% x23 0010451470 wiring harness 1 AD36NAHBEA 0.000% 0.000% x24 0010451167 indoor PCB 1 AD36NAHBEA 0.020% 0.024% *25 0010451265 termianl block 1 AD36NAHBEA 0.020% 0.024% *26 0010800287 electrical box assy. 1 AD36NAHBEA 0.000% 0.000% x27 0010752120 liquid pipe assy. 1 AD36NAHBEA 0.000% 0.000% x28 0010700869 air pipe assy. 1 AD36NAHBEA 0.000% 0.000% x30 0010800290 evaporator fixing plate 3 1 AD36NAHBEA 0.000% 0.000% x31 001A3400160 float switch 1 AD36NAHBEA 0.000% 0.000% x32 001A13011045 motor fixing bolt 1 AD36NAHBEA 0.000% 0.000% x33 001A13011045 motor fixing bolt 1 AD36NAHBEA 0.000% 0.000% x34 001A13011039 motor bracket 1 AD36NAHBEA 0.000% 0.000% x35 001A13011040 snail shell 1 1 AD36NAHBEA 0.000% 0.000% x36 001A2301102 fan 1 1 AD36NAHBEA 0.020% 0.024% *37 001A13011044 hermitic circle of snail shell 1 AD36NAHBEA 0.000% 0.000% x38 001A13011044 hermitic circle of snail shell 1 AD36NAHBEA 0.000% 0.000% x39 001A2301103 fan 2 1 AD36NAHBEA 0.020% 0.024% *40 001A13011041 snail shell 2 1 AD36NAHBEA 0.000% 0.000% x41 001A5401035 washer 1 AD36NAHBEA 0.000% 0.000% x42 001A3000291 indoor motor 1 AD36NAHBEA 0.020% 0.024% *43 0010800329 drain pan assy. 1 AD36NAHBEA 0.000% 0.000% x44 0010800280 guarding plate assy.2 1 AD36NAHBEA 0.000% 0.000% x45 0010800281 guarding plate assy.1 1 AD36NAHBEA 0.000% 0.000% x

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare partsmay be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should bemarked with " x ".

5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.

Parts list

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The firsttime should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and shouldbe marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in thespare-part warehouse accord with the actual case,should be marked with " ".

Page 125: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea
Page 126: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No.Spare partsnumber

Spare parts description inenglish Qty. Model

Failurerate

the proportion ofthe spare-partstock Remark

1 001A1231233 Inlet grill 1 AP42NACBEA 0.00% 0.000% ×2 001A1301502 Inlet grill insert 2 AP42NACBEA 0.00% 0.000% ×3 0010850578 Front panel 1 AP42NACBEA 0.00% 0.000% ×4 001A0600657 Operation panel 1 AP42NACBEA 0.00% 0.000% ×5 001A1432687 Horizontal blade 6 AP42NACBEA 0.00% 0.000% ×6 001A1734970 Vertical air outlet pad 2 AP42NACBEA 0.00% 0.000% ×7 001A1431689 Vertical blade 1 AP42NACBEA 0.00% 0.000% ×8 001A1734832 Air damper pad 1 AP42NACBEA 0.00% 0.000% ×9 001A1301508 Air damper 1 AP42NACBEA 0.00% 0.000% ×

10 0010751945 Heat exchanger assembly 1 AP42NACBEA 0.01% 0.012%11 001A1301847 Evaporator left mounting plate 1 AP42NACBEA 0.00% 0.000% ×12 001A1301848 Evaporator right mounting plate 1 AP42NACBEA 0.00% 0.000% ×13 0010150194 Left board 1 AP42NACBEA 0.00% 0.000% ×14 001A17341222 Left board pad 1 AP42NACBEA 0.00% 0.000% ×15 001A1301846 Top cover plate 1 AP42NACBEA 0.00% 0.000% ×16 001A1431994 Cover 1 AP42NACBEA 0.00% 0.000% ×17 001A17561372 Side board horizontal pad 1 AP42NACBEA 0.00% 0.000% ×18 0010150195 Right board 1 AP42NACBEA 0.00% 0.000% ×19 001A0100787 Back guard 1 AP42NACBEA 0.00% 0.000% ×20 001A1101145 Wiring plate 1 AP42NACBEA 0.00% 0.000% ×21 001A1734842 Thermal insulation pipe 1 AP42NACBEA 0.00% 0.000% ×22 001A5002078 Special nut 1 AP42NACBEA 0.00% 0.000% ×23 001A0100575 Bottom plate 1 AP42NACBEA 0.00% 0.000% ×24 001A1745106 Plastic cushion 1 AP42NACBEA 0.00% 0.000% ×25 001A3000249 Motor 1 AP42NACBEA 0.02% 0.024% *26 001A5739020 Mounting wiring clamp 1 AP42NACBEA 0.00% 0.000% ×27 001A1101146 Pipe press plate 1 AP42NACBEA 0.00% 0.000% ×28 001A1752911 Cushion rubber 1 AP42NACBEA 0.00% 0.000% ×29 001A1452695 Cushion rubber 1 AP42NACBEA 0.00% 0.000% ×30 0010250163 Drain pan 1 AP42NACBEA 0.00% 0.000% ×31 001A1452695 Fan pad 1 AP42NACBEA 0.00% 0.000% ×32 001A5102050 Nut 1 AP42NACBEA 0.00% 0.000% ×33 001A2300095 Centrifugal fan 1 AP42NACBEA 0.02% 0.024% *34 001A1742931 Down shell press plate cushion 1 AP42NACBEA 0.00% 0.000% ×35 001A1301445 Down shell press plate 1 AP42NACBEA 0.00% 0.000% ×36 001A1431647 Wiring clamp (plasticizing) 1 AP42NACBEA 0.00% 0.000% ×37 001A1301437 Filter guide AP42NACBEA 0.00% 0.000% ×38 0010200026 Air ring 1 AP42NACBEA 0.00% 0.000% ×39 001A0100385 Down shell 1 AP42NACBEA 0.00% 0.000% ×40 001A2400102 Filter 1 AP42NACBEA 0.00% 0.000% ×41 001A0100075 Door lock 1 AP42NACBEA 0.00% 0.000% ×42 001A1734967 Sealing plate 1 AP42NACBEA 0.00% 0.000% ×43 001A17621241 Sealing plate 1 AP42NACBEA 0.00% 0.000% ×44 001A1757833 Cushion rubber 1 AP42NACBEA 0.00% 0.000% ×45 001A3000016A Synchro-motor 1 AP42NACBEA 0.02% 0.024% *46 001A1301448 Wring cover 1 AP42NACBEA 0.00% 0.000% ×47 001A1431647 Wire clamp 1 AP42NACBEA 0.00% 0.000% ×48 001A4000107 Terminal block(6 colume) 1 AP42NACBEA 0.00% 0.000% ×49 0010450450 Transformer 1 AP42NACBEA 0.01% 0.012%50 001A3600134 Fan capacitor 1 AP42NACBEA 0.04% 0.048% *

Parts list

Page 127: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

51 001A1452695 Cushion rubber 1 AP42NACBEA 0.00% 0.000% ×52 0010401369 Indoor PCB 1 AP42NACBEA 0.02% 0.024% *53 / / AP42NACBEA54 001A1301447 Electric box 1 AP42NACBEA 0.00% 0.000% ×55 001A1301444 Mounting beam 1 AP42NACBEA 0.00% 0.000% ×56 001A1734967 Sealing plate 1 AP42NACBEA 0.00% 0.000% ×57 001A1752840 Supporting plate 1 AP42NACBEA 0.00% 0.000% ×58 001A3900006 Pipe temp. sensor 1 AP42NACBEA 0.00% 0.000% ×59 001A0100407 Splint 1 AP42NACBEA 0.00% 0.000% ×

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.Thespare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-partwarehouse,should be marked with " x ".

5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted withthe actual quantity 3 months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-partswarehouse,and should be marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer maystock in the spare-part warehouse accord with the actual case,should be marked with " ".

Page 128: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

14

Model: AU36NAIBEA\AU42NAIBEAOutdoor

Page 129: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No.Spare partsnumber

Spare parts description inEnglish Qty. Model

Failurerate

the proportion ofthe spare-partstock Remark

1 001A0100122 Front grille 2 AU42NAIBEA 0.0000% 0.0000% X

2 001A1301707 service panel assy 1 AU42NAIBEA 0.0000% 0.0000% X

3 001A1301640 Front panel 2 AU42NAIBEA 0.0000% 0.0000% X

4 001A5402022 Axial fan 2 AU42NAIBEA 0.0200% 0.0240% *

5 0010450279 Fan motor 2 AU42NAIBEA 0.0200% 0.0240% *

6 001A0100740 Bracket for fan motor 1 AU42NAIBEA 0.0000% 0.0000% X

7 0010751389 Condenser assy. 1 AU42NAIBEA 0.0100% 0.0120%8 0010451291 AC contactor 1 AU42NAIBEA 0.0100% 0.0120%9 001A3600018 Capacitor for fan motor 2 AU42NAIBEA 0.0400% 0.0480% *

10 001A4000158 connection block 1 AU42NAIBEA 0.0100% 0.0120%11 0010451346 Resumable transformer 1 AU42NAIBEA 0.0500% 0.0600% *

12 0010451295 outdoor PCB 1 AU42NAIBEA 0.0200% 0.0240% *

13 001A3900110 ambient temp. sensor 1 AU42NAIBEA 0.0100% 0.0120% *

13 0010451314 coil temp. sensor 1 AU42NAIBEA 0.0100% 0.0120% *

13 0010450398 discharging temp. sensor 1 AU42NAIBEA 0.0100% 0.0120% *

14 001A5736055 clip for sensor 1 AU42NAIBEA 0.0000% 0.0000% X

15 0010451265 Terminal block 1 AU42NAIBEA 0.0100% 0.0120%17 001A0100827 Top cover assy. 1 AU42NAIBEA 0.0000% 0.0000% X

18 001A0100733 Slide plate(right) 1 AU42NAIBEA 0.0000% 0.0000% X

19 001A1303642 Back grille 1 AU42NAIBEA 0.0000% 0.0000% X

20 0010400127 High pressure switch 1 AU42NAIBEA 0.0000% 0.0000% X

21 001A21111254 segregator 1 AU42NAIBEA 0.0000% 0.0000% X

22 0010850850 4-way valve 1 AU42NAIBEA 0.0000% 0.0000% X

23 001A2500121 coil of4-way valve 1 AU42NAIBEA 0.0200% 0.0240% *

24 001A2400128 muffle 1 AU42NAIBEA 0.0000% 0.0000% X

25 0010750471 Compressor 1 AU42NAIBEA 0.0600% 0.0720% *

26 0010451431 wiring harness 1 AU42NAIBEA 0.0100% 0.0120%27 001A2500149 2-way stop valve 1 AU42NAIBEA 0.0000% 0.0000% X

28 001A2500150 3-way stop valve 1 AU42NAIBEA 0.0000% 0.0000% X

29 001A1301762 Valve pedestal 1 AU42NAIBEA 0.0000% 0.0000% X

30 001A0100735 Bottom cover assy. 1 AU42NAIBEA 0.0000% 0.0000% X

31 001A5701062 Power line clip 1 AU42NAIBEA 0.0000% 0.0000% X

32 001A0100734 Partition plate 1 AU42NAIBEA 0.0000% 0.0000% X

33 001A17561212 Partition plate tray 1 AU42NAIBEA 0.0000% 0.0000% X

34 001A1436160 handle 1 AU42NAIBEA 0.0000% 0.0000% X

35 001A1301763 cover 1 AU42NAIBEA 0.0000% 0.0000% X

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.Thespare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be marked with " x ".5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.

Parts list

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted withthe actual quantity 3 months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-partswarehouse,and should be marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer maystock in the spare-part warehouse accord with the actual case,should be marked with " ".

Page 130: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

No.Spare partsnumber

Spare parts description inEnglish Qty. Model

Failurerate

the proportion of thespare-part stock Remark

1 001A0100122 Front grille 2 AU36NAIBEA 0.0000% 0.0000% X2 001A1301707 service panel assy 1 AU36NAIBEA 0.0000% 0.0000% X3 001A1301640 Front panel 2 AU36NAIBEA 0.0000% 0.0000% X4 001A5402022 Axial fan 2 AU36NAIBEA 0.0200% 0.0240% *5 0010450279 Fan motor 2 AU36NAIBEA 0.0200% 0.0240% *6 001A0100740 Bracket for fan motor 1 AU36NAIBEA 0.0000% 0.0000% X7 0010850975 Condenser assy. 1 AU36NAIBEA 0.0100% 0.0120%8 0010451291 AC contactor 1 AU36NAIBEA 0.0100% 0.0120%9 001A3600018 Capacitor for fan motor 2 AU36NAIBEA 0.0400% 0.0480% *

10 001A4000158 connection block 1 AU36NAIBEA 0.0100% 0.0120%11 0010451346 Resumable transformer 1 AU36NAIBEA 0.0500% 0.0600% *12 0010451295 outdoor PCB 1 AU36NAIBEA 0.0200% 0.0240% *13 001A3900110 ambient temp. sensor 1 AU36NAIBEA 0.0100% 0.0120% *13 0010451314 coil temp. sensor 1 AU36NAIBEA 0.0100% 0.0120% *13 0010450398 discharging temp. sensor 1 AU36NAIBEA 0.0100% 0.0120% *14 001A5736055 clip for sensor 1 AU36NAIBEA 0.0000% 0.0000% X15 0010451265 Terminal block 1 AU36NAIBEA 0.0100% 0.0120%17 001A0100827 Top cover assy. 1 AU36NAIBEA 0.0000% 0.0000% X18 001A0100733 Slide plate(right) 1 AU36NAIBEA 0.0000% 0.0000% X19 001A0100767 Back grille 1 AU36NAIBEA 0.0000% 0.0000% X20 0010400127 High pressure switch 1 AU36NAIBEA 0.0000% 0.0000% X21 001A21111254 segregator 1 AU36NAIBEA 0.0000% 0.0000% X22 0010850850 4-way valve 1 AU36NAIBEA 0.0000% 0.0000% X23 001A2500121 coil of4-way valve 1 AU36NAIBEA 0.0200% 0.0240% *24 001A2400128 muffle 1 AU36NAIBEA 0.0000% 0.0000% X25 0010750196 Compressor 1 AU36NAIBEA 0.0600% 0.0720% *26 0010451431 wiring harness 1 AU36NAIBEA 0.0100% 0.0120%27 001A2500149 2-way stop valve 1 AU36NAIBEA 0.0000% 0.0000% X28 001A2500150 3-way stop valve 1 AU36NAIBEA 0.0000% 0.0000% X29 001A1301762 Valve pedestal 1 AU36NAIBEA 0.0000% 0.0000% X30 001A0100735 Bottom cover assy. 1 AU36NAIBEA 0.0000% 0.0000% X31 001A5701062 Power line clip 1 AU36NAIBEA 0.0000% 0.0000% X32 001A0100734 Partition plate 1 AU36NAIBEA 0.0000% 0.0000% X33 001A17561212 Partition plate tray 1 AU36NAIBEA 0.0000% 0.0000% X34 001A1436160 handle 1 AU36NAIBEA 0.0000% 0.0000% X35 001A1301763 cover 1 AU36NAIBEA 0.0000% 0.0000% X

4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.Thespare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-partwarehouse,should be marked with " x ".5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.

Parts list

1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted withthe actual quantity 3 months later.

2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-partswarehouse,and should be marked with"*"

3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer maystock in the spare-part warehouse accord with the actual case,should be marked with " ".

Page 131: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

PERFORMANCE CURVES

Cool capacity graph

6789

1011121314

-7 5 15 25 35 43

Outdoor DB( )

Cap

acity

(KW

) 20

22

25

27

30

32

Indoor

DB( )

EER graph

1

1.5

2

2.5

3

3.5

4

-7 5 15 25 35 43

Outdoor DB( )

EER

202225273032

Indoor

DB( )

1)AD36NAMBEA+AU36NAIBEA

13 Performance curves a)performance curves

- 96 -

Page 132: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Heat capacity graph (only heat type available)

6

7

8

9

10

11

12

13

-7 -5 0 6 10 15

Outdoor DB( )

Cap

acity

(KW

)

16

18

20

22

24

26

28

Indoor

DB( )

COP graph (only heat type available)

1

1.5

2

2.5

3

3.5

4

-7 -5 0 6 10 15

Outdoor DB( )

CO

P

16

18

20

22

24

26

28

Indoor

DB( )

- 97 -

Page 133: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

2)AB36NACBEA+AU36NAIBEA

Cooling capacity graph

EER graph

a

b

- 98 -

PERFORMANCE CURVES

6789

1011121314

-7 5 15 25 35 43

Outdoor DB( )

Cap

acity

(KW

) 20

22

25

27

30

32

Indoor

DB( )

1

1.5

2

2.5

3

3.5

4

-7 5 15 25 35 43

Outdoor DB( )

EER

202225273032

Indoor

DB( )

Page 134: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

Cooling capacity graph

EER graph

a

b

3)AB42NACBEA+AU42NAIBE A

- 99-

PERFORMANCE CURVES

0

2

4

6

8

10

12

14

16

18

-7 5 15 25 35 43

Outdoor DB( )

Cap

acity

(KW

) 20

22

25

27

30

32

Indoor

DB( )

1

1.5

2

2.5

3

3.5

4

4.5

5

-7 5 15 25 35 43

Outdoor DB( )

EER

20

22

25

27

30

32

Indoor

DB( )

Page 135: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

4)AC36NACBEA+AU36NAIBEA

PERFORMANCE CURVES

Cool capacity graph

6789

1011121314

-7 5 15 25 35 43

Outdoor DB( )

Cap

acity

(KW

) 20

22

25

27

30

32

Indoor

DB( )

EER graph

1

1.5

2

2.5

3

3.5

4

-7 5 15 25 35 43

Outdoor DB( )

EER

202225273032

Indoor

DB( )

- 100 -

Page 136: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

5)AC42NACBEA+AU42NAIBEA

PERFORMANCE CURVES

Cool capacity graph

0

2

4

6

8

10

12

14

16

18

-7 5 15 25 35 43

Outdoor DB( )

Cap

acity

(KW

) 20

22

25

27

30

32

EER graph

Indoor

DB( )

1

1.5

2

2.5

3

3.5

4

4.5

5

-7 5 15 25 35 43

Outdoor DB( )

EER

20

22

25

27

30

32

Indoor

DB( )

- 101 -

Page 137: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

5 7 10 15 20

( C)

( C)

( C)

b)Ambient temperature range for cooling operation:

ou

tdo

or a

mb

ien

t tem

pe

ratu

re

Ambient temperature range for heating operation:

indoor ambient temperature

indoor ambient temperature

un

loa

d p

erio

d

con

secu

tive o

pe

ratio

n

15

20

10

5

0

-5

-10

25 27 30

20

25

( C)

30

35

40

50

15

15

ou

tdo

or a

mb

ien

t tem

pe

ratu

re

un

loa

d p

erio

d

con

secu

tive o

pe

ratio

n

20 23 25 28 300

102

Page 138: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

c). Capability modification curver

Alteration curve of outdoor air dry-bulb temperature

Alteration curve of outdoor air wet-bulb temperature

Outdoor air dry-bulb temperature( )

15

12

11

87

9

20

-10 -5 0 5 10 15

30 35 40 43

capability m

odifica

tion(kw

)

capability m

odifica

tion(kw

)

13

15

AU42NAIBEA (Cold producing/Heat producing)

103

lp
low electrostatic level
lp
electrostatic level
lp
low electrostatic
lp
level
lp
electrostatic
lp
level
Page 139: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

22

14. NOISE LEVEL CHARTS 1)Convertible Type

Cooling

Heating

- 104 -

Page 140: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

2)Cassette type

Cooling

Heating

-105 -

Page 141: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

1)AB36NACBEA AB42NACBEA

Air Velocity Distribution

CoolingBlowy angle:40

Temperature Distribution

CoolingBlowy angle:40

a. Cooling / Air Velocity Distribution

b. Cooling / Temperature Distribution

04 2 1

m/s

1 20

4

m/s

2

27

4 2 1

25

22

0 1 2

27

04

25

22

2

- 106-

AIR VELOCITY DISTRIBUTION

15.Air Velocity Distribution

Page 142: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

2) AC36NACBEA

Air Velocity Distribution

CoolingBlowy angle:25

Temperature Distribution

CoolingBlowy angle:25

a. Cooling / Air Velocity Distribution

b. Cooling / Temperature Distribution

AIR VELOCITY DISTRIBUTION

0

2.4

5.5

27

0

2.4

22

25

5.5

27

0

2.4

22

25

5.5

- 107-

Page 143: Haier Ab36nacbea Ac36nacbea Ad36nambea Ad36nahbea Ab42nacbea Ac42nacbea Ad42nambea Ad42nahbea Ap42nacbea Au36naibea Au42naibea

3)AD36NAMBEA\ AD42NAMBEA

cooling

coolingair discharge angle 5

Air Velocity distribution

Temperature distribution

air discharge angle 5

0

1.8

2.4

0.5

5.5

25

0

1.8

2227

5.5

2.4

AIR VELOCITY DISTRIBUTION

- 108 -