1010 GENERAL CONDITIONS AND STATEMENTS:A. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOBSPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING,AND SITE DRAWINGS. CONSULT THESE DRAWINGS FOR DEPRESSIONS, ANDOTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS. THE CONTRACTORSHALL COMPARE AND COORDINATE WITH ALL DISCIPLINES AND REPORT ANYDISCREPANCIES TO ARCHITECT PRIOR TO FABRICATION.
B. DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. ANYDISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEERBEFORE PROCEEDING WITH THE AFFECTED PART OF THE WORK.
C. DO NOT SCALE OFF DRAWINGS OR DETAILS. DIMENSIONS PROVIDED ONPLAN OVERIDE ANY SCALED DIMENSIONS. SEE ARCHITECTURAL DRAWINGSFOR DIMENSIONS AND ELEVATIONS NOT SHOWN.
D. THE STRUCTURE DEPICTED ON THE DRAWINGS IS DESIGNED TO BE SELF-SUPPORTING, STABLE AND STRUCTURALLY SOUND AFTER THE BUILDING ISCOMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINEERECTION PROCEDURES AND SEQUENCE TO INSURE SAFETY OF THE BUILDINGAND ITS COMPONENTS DURING ERECTION. THIS INCLUDES PROVIDINGTEMPORARY SHORING, SHEETING, BRACING, GUYS OR TIEDOWNS TO RESISTLOADS IMPOSED BY GRAVITY, SOIL, CONSTRUCTION LOADS, WIND AND SEISMIC(WHERE APPLICABLE).
E. DETAILS, NOTES, KEYNOTES OR ANY INFORMATION SHOWN ON ANY PARTOF THE DRAWINGS SHALL BE APPLIED TO ALL APPLICABLE OR SIMILARCONDITIONS AND IF NOTED AS TYPICAL OR SHOWN FOR ONE CONDITION,SHALL BE APPLIED FOR ALL LIKE OR SIMILAR CONDITIONS UNLESS NOTEDOTHERWISE. THE CONTRACTOR MUST USE, IN CONJUNCTION WITHSTRUCTURAL DRAWINGS, ARCHITECTURAL, MECHANICAL, ELECTRICAL,PLUMBING AND SITE DRAWINGS TO DETERMINE WHERE CONDITIONS THAT ARELIKE OR SIMILAR APPLY.
F. WHERE A CONFLICT EXISTS BETWEEN STRUCTURAL DRAWINGS ANDSTRUCTURAL SPECIFICATIONS THE DRAWINGS SHALL GOVERN.
STRUCTURAL NOTES
1061 DESIGN LOADS:THE STRUCTURAL SYSTEM FOR THIS BUILDING HAS BEEN DESIGNED INACCORDANCE WITH THE 2007 EDITION OF THE FLORIDA BUILDING CODE (2007FBC) WITH FLORIDA BUILDING CODE 2009 SUPPLEMENT, BY THE SOUTHERNBUILDING CODE CONGRESS INTERNATIONAL, INC. THE FOLLOWINGSUPERIMPOSED LOADINGS HAVE BEEN UTILIZED:
DEAD LOADS: LIVE LOADS:ROOF =15 PSF ROOF =20 PSF
WIND DESIGN LOADS: ASCE 7-05WIND BORNE DEBRIS REGION
H = 19 FT 140 MPH (3 SECOND GUST)IMPORTANCE FACTOR I = 1.15 EXPOSURE CKz = 1.0 Kzt = 1.0 Kd = 0.85GCpi = 0.18BUILDING CATEGORY: III
BUILDING IS CONSIDERED TO BE ENCLOSED.EXTERIOR GLAZINGS ARE TO BE IMPACT RESISTANT OR PROTECTED INACCORDANCE WITH 2007 FBC, WITH 2009 SUPPLEMENTS.
1120 SUBMITTAL (SHOP DRAWING) REVIEW:A. SUBMITTALS (SHOP DRAWINGS) WILL BE REVIEWED FOR GENERALCOMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTSONLY. IF ANY DEVIATIONS FROM CONTRACT DOCUMENTS BECOMEAPPARENT DURING REVIEW, AS A COURTESY, ENGINEER/ARCHITECT MAYMARK UP DEVIATIONS ON SHOP DRAWINGS DURING THE SUBMITTALPROCESS. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTORTO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS INCLUDING BUTNOT LIMITED TO QUANTITY, LENGTH, ELEVATIONS AND DIMENSIONS.FABRICATION REQUIREMENTS, CONSTRUCTION MEANS AND METHODS,COORDINATION OF WORK WITH OTHER TRADES OR CONSTRUCTION SAFETYREQUIREMENTS.
B. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TOSUBMITTAL TO THE ARCHITECT/ENGINEER. DRAWINGS SUBMITTED WITHOUTREVIEW, OR IF SUBMITTAL IS INCOMPLETE, WILL BE REJECTED AND WILLNOT BE REVIEWED. JENKINS & CHARLAND/TRC WORLDWIDE ENGINEERING,INC WILL NOT BE RESPONSIBLE FOR DELAYS CAUSED BY REJECTEDDRAWINGS.
C. SHOP DRAWING SUBMITTALS SHALL FOLLOW THE REQUIREMENTS INCONTRACT SPECIFICATIONS SECTION 01330
D. THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGSUNLESS OTHERWISE SPECIFIED IN WRITING BY THE ENGINEER.
E. CHANGES AND ADDITIONS MADE ON RE-SUBMITTALS SHALL BE CLEARLYFLAGGED AND NOTED. THE PURPOSE OF THE RE-SUBMITTALS SHALL BECLEARLY NOTED ON THE LETTER OF TRANSMITTAL. ARCHITECT/ENGINEERREVIEW WILL BE LIMITED TO THOSE ITEMS CAUSING THE RE-SUBMITTAL.
1121 DELEGATE ENGINEERING COMPONENTS AND REQUIREMENTS:A. THE FOLLOWING SYSTEMS AND COMPONENTS AS A MINIMUMREQUIRE FABRICATION AND ERECTION DRAWINGS PREPARED BY ADELEGATED ENGINEER:
LIGHT GAUGE STEEL EXTERIOR WALL SYSTEMS, LIGHT GAUGESTEEL TRUSSES, WOOD FLOOR OR ROOF TRUSSES, ALUMINUM WALLSYSTEMS, GLAZED CURTAIN WALLS, PREFABRICATED STEEL STAIRS &RAILINGS, ARCHITECTURAL PRECAST CONCRETE ELEMENTS,STRUCTURAL PRECAST SYSTEMS, GLASS FIBER REINFORCEDCONCRETE PANEL SYSTEMS, OPEN WEB STEEL JOISTS, STRUCTURALSTEEL CONNECTIONS REQUIRING ENGINEERING, CONCRETE TILT-WALL ERECTION DRAWINGS, REINFORCING FOR CONCRETE TILT WALLERECTION, PRESTRESSED CONCRETE PILES, WOOD I-JOISTS.
B. SUBMITTALS SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECTAND APPLICABLE CODES, LIST THE DESIGN CRITERIA, AND SHOW ALLDETAILS AND PLANS NECESSARY FOR PROPER FABRICATION ANDINSTALLATION. CALCULATIONS AND SHOP DRAWINGS SHALL IDENTIFYSPECIFIC PRODUCT UTILIZED. GENERIC PRODUCTS WILL NOT BEACCEPTED.
C. SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED UNDERTHE DIRECT SUPERVISION AND CONTROL OF THE DELEGATEDENGINEER.
D. SHOP DRAWINGS AND CALCULATIONS REQUIRE THE IMPRESSEDSEAL, DATE AND SIGNATURE OF THE DELEGATED ENGINEER.COMPUTER PRINTOUTS ARE AN ACCEPTABLE SUBSTITUTE FORMANUAL COMPUTATIONS PROVIDED THEY ARE ACCOMPANIED BYSUFFICIENT DESCRIPTIVE INFORMATION TO PERMIT THEIR PROPEREVALUATION. SUCH DESCRIPTIVE INFORMATION SHALL BEAR THEIMPRESSED SEAL AND SIGNATURE OF THE DELEGATED ENGINEER ASAN INDICATION THAT HE/SHE HAS ACCEPTED RESPONSIBILITY FORTHE RESULTS. SEPIAS DO NOT REQUIRE SIGNATURE AND SEAL. THESTRUCTURAL ENGINEER WILL RETAIN ONE SIGNED AND SEALEDBLUELINE PRINT FOR RECORD.
E. DRAWINGS PREPARED SOLELY TO SERVE AS A GUIDE FORFABRICATION AND INSTALLATION (SUCH AS REINFORCING STEEL SHOPDRAWINGS OR STRUCTURAL STEEL ERECTION DRAWINGS) ANDREQUIRING NO ENGINEERING DO NOT REQUIRE THE SEAL OF ADELEGATED ENGINEER. HOWEVER, ALL STRUCTURAL STEELCONNECTIONS NOT DETAILED ON THESE DRAWINGS SHALL BEDESIGNED AND DETAILED BY DELEGATE ENGINEER, BASED ON LOADSAND PROJECT REQUIREMENTS PROVIDED HEREIN.
F. CATALOG INFORMATION ON STANDARD PRODUCTS DOES NOTREQUIRE THE SEAL OF A DELEGATED ENGINEER.
G. REVIEW BY THE STRUCTURAL ENGINEER OF RECORD OFSUBMITTALS IS LIMITED TO VERIFYING THE FOLLOWING:
a) THAT THE SPECIFIED STRUCTURAL SUBMITTALS HAVE BEENFURNISHED.
b) THAT THE STRUCTURAL SUBMITTALS HAVE BEEN SIGNED ANDSEALED BY THE DELEGATED ENGINEER.
c) THAT THE DELEGATED ENGINEER HAS UNDERSTOOD THE DESIGNINTENT AND HAS USED THE SPECIFIED STRUCTURAL CRITERIA. (NODETAILED CHECK OF CALCULATIONS WILL BE MADE).
d) THAT THE CONFIGURATION SET FORTH IN THE STRUCTURALSUBMITTALS IS CONSISTENT WITH THE CONTRACT DOCUMENTS. (NODETAILED CHECK OF DIMENSIONS OR QUANTITIES WILL BE MADE).
H. SUBMITTALS NOT MEETING THE ABOVE CRITERIA WILL NOT BEREVIEWED.
2011 FOUNDATIONS:A. GEOTECHNICAL INVESTIGATION, TESTING, STUDIES, FOUNDATIONRECOMMENDATIONS, AND SITE PREPARATION REQUIREMENTS HASNOT BEEN PERFORMED BY TRC WORLDWIDE ENGINEERS, INC.
B. SEE THE FOLLOWING REPORT FOR COMPLETE GEOTECHNICALRECOMMENDATIONS AND INSTALLATION PROCEDURES. SITEPREPARATION AND FOUNDATION INSTALLATION SHALL COMPLY WITH:
REPORT No.: 0530.1000029.000PREPARED BY: UNIVERSAL ENGINEERING SERVICESTITLED: PROPOSED WATER TREATMENT PLANT BUILDING
PORT OF THE ISLANDS RO TREATMENT PLANTDATED: APRIL 19, 2010
C. FOUNDATION DESIGN IS BASED ON AN SOIL BEARING PRESSURE OF2,000 PSF.
D. GEOTECHNICAL REPORT'S RECOMMENDATIONS FOR SITEPREPARATION AND TESTING SHALL BE CONSIDERED AS PROJECTREQUIREMENTS AND IS PART OF CONTRACT DOCUMENT.
3201 REINFORCING STEEL:A. SHALL BE ASTM A615 GRADE 60 DEFORMED BARS (WELDABLEREINFORCING "DBA" SHALL CONFORM TO ASTM A-706 GRADE 60), FREEFROM OIL, SCALE AND RUST AND PLACED IN ACCORDANCE WITH THETYPICAL BENDING DIAGRAM AND PLACING DETAILS OF ACI STANDARDSAND SPECIFICATIONS. SECURE APPROVAL OF SHOP DRAWINGS PRIOR TOCOMMENCING FABRICATION. REINFORCING BAR DETAILING SHALLCOMPLY WITH ACI 315 "MANUAL OF STANDARD PRACTICE FOR DETAILINGREINFORCED CONCRETE STRUCTURES".
B. UNLESS NOTED OTHERWISE ON SECTIONS AND DETAILS, PROVIDE THEFOLLOWING CONCRETE COVER FOR REINFORCING STEEL:
REINFORCING STEEL COVER (PRESTRESSED AND NON-PRESTRESSEDCONCRETE) CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACTWITH GROUND
SLABS, WALLS, JOISTS#14 & #18 BARS 1 1/2"#11 BAR & SMALLER 3/4"
BEAMSTIES, STIRRUPS 1 1/2"
COLUMNSTIES 1 3/4"
CONCRETE EXPOSED TO WEATHER OR EARTH*#6 BAR THRU #18 BARS 2"#5 BAR, W31 OR D31 WIRE, AND SMALLER 1 1/2"
GRADE BEAMSTIES, STIRRUPS - TOP & FORMED FACES 2"
BOTTOM & UNFORMED FACES 3"
FOOTINGS & PILECAPSTOP 2"BOTTOM & SIDES 3"
* ALL GARAGE AND BALCONY TOP SLABS ARE TO BE CONSIDEREDEXPOSED TO WEATHER.
COVERAGE TO REINFORCING REQUIREMENTS APPLIES ALSO TO ANYEDGE OF SLAB OR OPENING.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DRIPS,CHAMFERS, REGLETS, SLOTS, SLEEVES, ANCHORS, AND INSERTS. UNLESSSHOWN ON STRUCTURAL DRAWINGS NO OPENINGS LARGER THAN 12"x12"SHALL BE PLACED IN SLABS OR WALLS. FOR OPENINGS NOT SHOWN ONSTRUCTURAL DRAWINGS, APPROVALS MUST BE OBTAINED FROM THEENGINEER PRIOR TO FABRICATION OF STEEL AND PLACEMENT OFCONCRETE. LOCATION DRAWINGS FOR ALL SLEEVES AND BLOCKOUTS INTHE CONCRETE SHALL BE SUBMITTED FOR APPROVAL BY THESTRUCTURAL ENGINEER PRIOR TO PLACEMENT.
D. ALL CONDUIT, SLEEVES, AND PIPES EMBEDDED IN OR PASSING THRUCONCRETE SHALL CONFORM TO SECTION 6.3 OF ACI 318 AND THEFOLLOWING:
1. SLEEVES AND PIPES SHALL BE PLACED SO THAT REINFORCING STEEL CAN BE PLACED WITH THE SPECIFIED COVER AND CLEAR DISTANCE BETWEEN BARS.
2. THE CONCRETE COVERING OF PIPE AND SLEEVES SHALL NOT BE LESS THAN 11/2 INCHES. CLEAR DISTANCE BETWEEN SUCH PIPES AND SLEEVES SHALL NOT BE LESS THAN SIX INCHES.
3. CONDUIT AND PIPES PLACED IN SLABS AND TOPPING OVER SLABS SHALL NOT BE LARGER IN OUTSIDE DIAMETER THAN ONE-THIRD THE THICKNESS OF SLAB OR TOPPING, AND SHALL BE PLACED IN THE MIDDLE THIRD OF SLAB DEPTH.
4. CONDUITS AND PIPES PLACED IN COLUMNS SHALL NOT DISPLACE MORE THAN 4% OF THE CROSS SECTIONAL AREA OF COLUMN AND SHALL BE LOCATED ON THE CENTER LINE OF COLUMN. OUTLET BOXES TO BE NOT DEEPER THAN REQUIRED CLEARANCE FOR REINF.
5. INSERTS W/ 3/4" MAX. EMBEDMENT SHALL BE USED TO SUPPORT CONDUITS, PIPES, AND DUCT FROM THE SLAB. 1-3/8" DEEP (MAX.) UNISTRUT INSERTS (OR APPROVED EQUAL) ME BE USED TO SUPPORT MECHANICAL AND PLUMBING EQUIPMENT AT CORRIDORS ONLY (AVOID CONFLICT W/ POST-TENSION TENDONS).
E. CONCRETE WALLS SHALL BE CAST MONOLITHIC WITH ADJOININGCOLUMNS UNLESS SPECIFICALLY NOTED OTHERWISE. CONCRETE FORSUCH WALLS SHALL BE THE SAME TYPE AND STRENGTH AS SPECIFIEDCOLUMNS.
F. ALL CONTINUOUS BARS SHALL HAVE CLASS B FULL TENSION LAPSUNLESS INDICATED OTHERWISE. PROVIDE CORNER BARS AT ALL WALL,GRADE BEAM AND STRIP FOOTING CORNERS. BARS SHALL BE THE SAMESIZE AND SPACING AS THE HORIZONTAL REINFORCING. INTERSECTINGWALLS, GRADE BEAMS AND STRIP FOOTINGS SHALL BE DOWELEDTOGETHER IN THE SAME MANNER. PROVIDE 2 NO. 4 TOP DIAGONAL BARS4'-0" LONG AT ALL REENTRANT CORNERS IN ALL SLABS ON GRADE ANDELEVATED SLABS.
G. SHOP DRAWINGS SHALL DETAIL ALL CONCRETE WALLS IN ELEVATION.
3103 PLUMBING SLEEVES:MINIMUM SLEEVE SPACING SHALL BE THREE DIAMETERS CENTER TOCENTER OF THE LARGER SLEEVE OR 6" CLEAR BETWEEN SLEEVES,WHICHEVER IS GREATER. PRIOR TO CONSTRUCTION SLEEVELOCATIONS AND SIZES SHALL BE APPROVED BY THE ENGINEER.
3104 CONSTRUCTION AND CONTROL JOINTS:A. CONSTRUCTION OR CONTROL JOINTS SHALL BE PROVIDED IN SLABS ONGRADE SO THAT THE MAXIMUM DISTANCE BETWEEN JOINTS SHALL BE NOMORE THAN 3 TIMES THE SLAB THICKNESS FEET, OR AS SHOWN ON PLANS.SAWCUT CONTROL JOINTS SHALL BE MADE AS SOON AS SLAB WILLSAFELY SUPPORT MEN AND EQUIPMENT AND THE SLAB WILL NOT BEDAMAGED BY EQUIPMENT. ASPECT RATIO (LONGSIDE TO SHORTSIDE OFCONCRETE AREA) SHALL NOT EXCEED 1.5.
B. ANY DEVIATION, ADDITION OR DELETION OF CONSTRUCTION ORCONTROL JOINTS FROM THAT SHOWN ON THE PLANS MUST BE REVIEWEDBY THE ENGINEER. ALTERNATE OR ADDED CONSTRUCTION JOINT LOCATIONSARE ACCEPTABLE ONLY AS A CHANGE ORDER, WHICH WILL INCLUDEENGINEERING CHARGES BY THE ENGINEER OF RECORD FOR REDESIGN OFTHE STRUCTURE, SHORING, ETC.
2201 SOIL COMPACTION:A. AS A MINIMUM REQUIREMENT AND UNLESS A MORE STRINGENTSITE PREPARATION IS PROVIDED BY GEOTECHNICAL ENGINEER,THE FOLLOWING SHALL BE PROVIDED. REMOVE TOPSOIL OVERTHE ENTIRE BUILDING AREA AND 10 FEET BEYOND BUILDING LINESAS INDICATED IN GEOTECHNICAL REPORT. PREPARE SUBGRADEAND PLACE FILL UNDER BUILDING AND WITHIN 10 FEET OF BUILDINGIN ACCORDANCE WITH GEOTECHNICAL REPORT. ANY FILL INLOCATIONS NOTED ABOVE SHALL BE COMPACTED TO CONTRACTSPECIFICATIONS OF 98% MODIFIED PROCTOR OR GREATER ASREQUIRED BY GEOTECHNICAL ENGINEER AND SHALL BE PLACED INLIFTS AS REQUIRED BY GEOTECHNICAL ENGINEER. IN NOINSTANCE SHALL LIFTS EXCEED 8" IN HEIGHT.
B. LOCATIONS FAILING TO MEET THE REQUIREMENTS SHALL BERECOMPACTED AND RETESTED AT THE CONTRACTORS EXPENSEAND AS DIRECTED BY THE INDEPENDENT GEOTECHNICALCONSULTANT.
3101 FORMWORK AND SHORING (CONCRETE SLABS AND BEAMS):1. NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HASREACHED AT LEAST TWO-THIRDS OF THE 28 DAY DESIGN STRENGTH(& ALL TENDONS STRESSED FOR PT SLABS). A MINIMUM OF 3 STORIESOF SHORING AND (/OR) RESHORING SHALL BE USED WHICH SHALLCONSIST OF ONE COMPLETE SET OF VERTICAL SHORES AND TWOSETS OF VERTICAL SHORES THAT COMPRISE AT LEAST 50% OF ACOMPLETE SET.
a) DRAWINGS FOR SHORING AND RESHORING SHALL BE PREPARED BYA FLORIDA REGISTERED PROFESSIONAL ENGINEER.
b) DESIGN, ERECTION AND REMOVAL OF ALL FORMWORK, SHORESAND RESHORES SHALL MEET REQUIREMENTS SET FORTH IN ACISTANDARDS 347 AND 301.
c) SUBMIT SIGNED & SEALED SHORING DRAWINGS INCLUDING POURSEQUENCE AND CALCULATIONS, WHERE NECESSARY, TODEMONSTRATE THAT THE POUR SEQUENCE AND SHORING/RE-SHORING METHODS DO NOT OVERSTRESS THE STRUCTURE. THISANALYSIS SHALL INCLUDE STRESSES CAUSED BY SHRINKAGE OFSTRUCTURAL SLAB. PROVIDE LOCATION AND DETAILS OF POURSTRIPS IF REQUIRED TO REDUCE SHRINKAGE AND RESTRAINT CRACKS.
d) SHORING INSPECTIONS SHALL BE PERFORMED BY THE SHORINGENGINEER.
2. UNLESS ARCHITECT SPECIFIES OTHERWISE, CONSTRUCTFORMWORK SO CONCRETE SURFACES CONFORM TO THE TOLERANCELIMITS OF ACI 117 [STANDARD SPECIFICATIONS FOR TOLERANCES FORCONCRETE CONSTRUCTION MATERIALS]. THE CLASS OF SERVICE FOROFFSET BETWEEN ADJACENT PIECES OF FORMWORK FACINGMATERIAL SHALL BE CLASS B FOR SURFACES PERMANENTLY EXPOSEDTO PUBLIC VIEW AND CLASS D FOR SURFACES THAT WILL BEPERMANENTLY CONCEALED.
5150 ALUMINUM:ALUMINUM FABRICATION SHALL BE IN ACCORDANCE WITH APPLICABLEPROVISIONS OF THE ALUMINUM ASSOCIATION "STANDARD FOR ALUMINUMSTRUCTURES". ALL MEMBERS SHALL BE ALUMINUM ASSOCIATIONSTANDARD STRUCTURAL SHAPES. WELDING OF ALUMINUM SHALL BE INACCORDANCE WITH AWS D1.2, "STRUCTURAL WELDING CODE - ALUMINUM",LATEST EDITION. FABRICATION WORK SHALL BE IN ACCORDANCE WITHCURRENT INDUSTRY PRACTICE.
ROLLED SECTIONS SHALL CONFORM TO ASTM B308, ALLOY 6061-T6. PLATEMATERIAL SHALL CONFORM TO ASTM B209, ALLOY 6061-T6.
BOLTS SHALL BE HOT-DIP GALVANIZED, ELECTRO-GALVANIZED, CADMIUMPLATED OR ALUMINIZED STEEL, 300 SERIES STAINLESS STEEL, ORALUMINUM.
WHERE ALUMINUM ALLOY PARTS ARE IN CONTACT WITH, OR AREFASTENED TO STEEL MEMBERS OR OTHER DISSIMILAR MATERIALS, THEALUMINUM SHALL BE KEPT FROM DIRECT CONTACT BY PAINTING WITHZINC CHROMATE PRIMER IN ACCORDANCE WITH FEDERAL SPECIFICATIONTT-P-645, FOLLOWED BY (2) COATS OF PAINT CONSISTING OF 2 LBS. OFALUMINUM PASTE PIGMENT (ASTM SPECIFICATION D962-66, TYPE Z, CLASSB) PER GALLON OF VARNISH MEETING FEDERAL SPECIFICATION TT-V-81d,TYPE II, OR EQUIVALENT. STAINLESS STEEL OR HOT-DIP GALVANIZEDSTEEL PLATE IN CONTACT WITH ALUMINUM NEED NOT BE PAINTED.
ALUMINUM SHOULD NOT BE PLACED IN DIRECT CONTACT WITH CONCRETE,GROUT, MASONRY, WOOD, FIBERBOARD OR OTHER POROUS MATERIALTHAT MAY ABSORB WATER AND CAUSE CORROSION. WHEN SUCHCONTACTS CANNOT BE AVOIDED, AN INSULATING BARRIER BETWEEN THEALUMINUM AND THE POROUS MATERIAL SHALL BE INSTALLED. ALUMINUMSURFACES SHALL BE GIVEN A HEAVY COAT OF ALKALI RESISTANTBITUMINOUS PAINT OR OTHER COATING PROVIDING EQUIVALENTPROTECTION BEFORE INSTALLATION.
SEE ARCHITECTURAL DRAWINGS FOR FINISH REQUIREMENTS.
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:3
6 P
M
STRUCTURAL NOTES
S 01
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
SHEET INDEX
SHEETNUMBER DESCRIPTION
S 01 STRUCTURAL NOTES
S 02 STRUCTURAL NOTES & ABBREVIATIONS
S 03 FOUNDATION & PLATFORM FRAMING PLANS
S 04 ROOF FRAMING PLAN
S 05 TYPICAL FOUNDATION & PLATFORM FRMGSECTIONS & DETAILS
S 06 TYPICAL MASONRY SECTIONS & DETAILS
S 07 TYPICAL HOLLOW CORE & CONCRETESECTIONS & DETAILS
S 08 SCHEDULES
S 09 STAIR SECTIONS & DETAILS
S 10 TANK PLANS & SECTIONS
S 11 TYPICAL DETAILS
F1
-1'-4"
C1/P1
STRUCTURAL NOTES
3601 POST-INSTALLED ANCHORS:A. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIEDON THE DRAWINGS. ALL POST INSTALLED ANCHORS TO BE A316STAINLESS STEEL.
B. CONTRACTOR SHALL OBTAIN APPROVAL FROM ENGINEER OF RECORDPRIOR TO USING POST-INSTALLED ANCHORS FOR MISSING ORMISPLACED CAST-IN-PLACE ANCHORS.
C. CARE SHALL BE GIVEN TO AVOID CONFLICTS WITH EXISTING REBARWHEN DRILLING HOLES. HOLES SHALL BE DRILLED AND CLEANED PERTHE MANUFACTURER'S INSTRUCTIONS.
D. UNLESS SPECIFIED OTHERWISE, ANCHORS SHALL BE EMBEDDED INTHE APPROPRIATE SUBSTRATE WITH A MINIMUM EMBEDMENT OF 8 TIMESTHE NOMINAL ANCHOR DIAMETER OR THE EMBEDMENT REQUIRED TOSUPPORT THE INTENDED LOAD. ANCHORS SHALL BE INSTALLED PER THEMANUFACTURER'S INSTALLATION INSTRUCTIONS AT NOT LESS THANMINIMUM EDGE DISTANCE AND/OR SPACING INDICATED IN THEMANUFACTURER'S LITERATURE.
E. SUBSTITUTION REQUESTS SHALL BE SUBMITTED TO THE ENGINEERFOR APPROVAL.
4203 MASONRY WALLS:A. MASONRY UNITS SHALL MEET ASTM C90 FOR HOLLOW LOAD BEARINGTYPE MASONRY WITH UNIT STRENGTH OF 1900 PSI ON THE NET AREA(f'm = 1500 PSI). MORTAR SHALL BE TYPE "M" OR "S" AND MEET ASTMC270. GROUT SHALL BE 2000 PSI MINIMUM COMPRESSIVE STRENGTH ANDMEET ASTM C476.
B. BLOCK CELLS SHALL BE GROUT FILLED WITH VERTICAL REINFORCINGBARS, SAME SIZE BARS AS REINFORCING, AT CORNERS,INTERSECTIONS, EACH SIDE OF OPENINGS OVER 4 FEET WIDE, AND ASSHOWN ON THE PLANS. DOWELS SHALL BE USED TO PROVIDECONTINUITY INTO THE STRUCTURE ABOVE AND/OR BELOW, UNLESSNOTED OTHERWISE. AT VERTICAL BAR TERMINATION, HOOK INTOFOOTING AND BOND BEAM, TIE BEAM, OR SLAB AT TOP OF WALL. USEMETAL LATH, MORTAR, OR SPECIAL UNITS TO CONFINE CONCRETE ANDGROUT TO AREA REQUIRED. MASONRY SHALL BE LAID IN RUNNING BONDPATTERN UNLESS NOTED OTHERWISE. ALL CELLS BELOW GRADE ARE TOBE GROUTED SOLID.
C. PROVIDE 9 GAUGE GALVANIZED HORIZONTAL JOINT REINFORCING(DUR-O-WALL OR ENGINEER APPROVED SUBSTITUTION) AT ALTERNATEBLOCK COURSES 16" O.C. VERTICALLY.
D. CONTROL JOINTS SHALL BE PROVIDED IN CONCRETE MASONRYCONSTRUCTION AT LOCATIONS INDICATED ON DRAWINGS. HORIZONTALWALL REINFORCING SHALL BE STOPPED EACH SIDE OF CONTROLJOINTS. SEE ARCHITECTURAL DRAWINGS FOR SEALANT REQUIREMENTSAT CONTROL JOINTS.
E. SUBMIT PROPOSED GROUT MIX DESIGN FOR REVIEW PRIOR TO USE.MIX SHALL BE UNIQUELY IDENTIFIED BY MIX NUMBER OR OTHERPOSITIVE IDENTIFICATION. GROUT SLUMP SHALL BE BETWEEN 8 AND 11INCHES. USE OF SUPERPLASTICIZER IS PROHIBITED.
F. CELLS TO BE GROUT FILLED SHALL HAVE VERTICAL ALIGNMENTSUFFICIENT TO MAINTAIN A CLEAR, UNOBSTRUCTED, CONTINUOUSVERTICAL GROUT SPACE. CLEANOUT OPENINGS SHALL BE PROVIDED ATTHE BOTTOM OF CELLS TO BE GROUT FILLED IN EACH POUR IN EXCESSOF 5 FEET IN HEIGHT. ANY OVERHANGING MORTAR OR OTHEROBSTRUCTION OR DEBRIS SHALL BE REMOVED FROM THE INSIDES OFSUCH CELL WALLS. THE CLEANOUTS SHALL BE SEALED BEFOREGROUTING, AFTER INSPECTION.
G. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT TOP ANDBOTTOM AND AT INTERVALS NOT EXCEEDING 192 BAR DIAMETERS.CELLS CONTAINING REINFORCEMENT SHALL BE FILLED SOLIDLY WITHGROUT. GROUT SHALL BE CONSOLIDATED AT TIME OF PLACING BYVIBRATING AND RECONSOLIDATED LATER BY VIBRATING BEFOREPLASTICITY IS LOST.
H. PLACE GROUT IN LIFTS NOT EXCEEDING 5 FT.. MINIMUM CELLDIMENSION SHALL BE IN ACCORDANCE WITH TABLE 5 OF ACI 530.1 (3" x 3"FOR COARSE GROUT). MAXIMUM POUR HEIGHT SHALL BE LIMITED TO 12FT..
I. WHEN THE GROUTING IS STOPPED FOR ONE HOUR OR LONGER,HORIZONTAL CONSTRUCTION JOINTS SHALL BE MADE BY STOPPING THEPOUR OF GROUT NOT LESS THAN 1-1/2 INCH BELOW THE TOP OF THEUPPERMOST UNIT GROUTED.
J. PROVIDE BRACING FOR TOP OF ALL INTERIOR CMU WALLS. WHERECONNECTION DETAILS ARE NOT SHOWN, PROVIDE A 1" GAP BETWEENWALL AND BOTTOM OF STRUCTURE. BRACE TOP OF WALL WITH 14 GABENT PLATE 4x4x0'-6" LONG AT 4'-0" OC. PROVIDE (3) 1/4" HILTI KWIK CONII SCREWS TO WALL AND (4) #10 SCREWS TO BOTTOM OF STRUCTURE(OR EQUIVALENT CAPACITY CONNECTION). CONNECTION TO ALLOW FOR1" DEFLECTION OF STRUCTURE THROUGH USE OF SLOTTED HOLES.
K. CONCRETE MASONRY QUALITY CONTROL:
1. WORK IN PROGRESS SHALL BE INSPECTED FOR CONFORMANCEWITH SPECIFIED MATERIALS AND THAT WORKMANSHIP ANDCONSTRUCTION IS IN COMPLIANCE WITH PLANS, SPECIFICATIONS, AND INDUSTRY STANDARDS.
2. STRENGTH DETERMINATION SHALL BE MADE USING UNIT STRENGTHOR PRISM TESTS IN ACCORDANCE WITH ACI 530.
4205 TIE BEAMS:BEAMS WITH THE PREFIX "TB" SHALL BE OF CONCRETE, POURED AFTER THEBLOCK WALLS BELOW ARE IN PLACE. REINFORCING SHALL BE CONTINUOUSTHROUGH TIE BEAMS WITH MINIMUM LAP SPLICES OF 48 BAR DIAMETERS ANDBENT BARS AT CORNERS. USE METAL LATH, MORTAR, OR SPECIAL UNITS TOCONFINE CONCRETE TO AREA REQUIRED, IN ACCORDANCE WITH ACI 530.1(SOLID METAL OR FELT CAVITY CAPS ARE PROHIBITED).
4207 LINTELS:MASONRY OPENINGS UP TO 12'-2" WIDE SHALL BE SPANNED WITH PRECASTCONCRETE "U" LINTELS. PROVIDE ADDITIONAL REINFORCING PER "LINTELREINFORCING SCHEDULE". SUBMIT MANUFACTURER SPAN TABLES FORREVIEW.
AR - ANCHOR RODALT - ALTERNATEAPPROX - APPROXIMATELYARCH - ARCHITECTARCHL - ARCHITECTURALB/ - BOTTOM OFBC - BOTTOM CHORDBLDG - BUILDINGBM - BEAMBOTT - BOTTOMBRG - BEARINGC/C - CENTER TO CENTERCIP - CAST IN PLACECJ - CONTRACTION JOINTCL - CENTERLINECLR - CLEARCMU - CONCRETE MASONRY UNITCOL - COLUMNCONC - CONCRETECONFIG - CONFIGURATIONCONT - CONTINUOUSCONTR - CONTRACTORCTR - CENTERDBL - DOUBLEDET - DETAILDIA - DIAMETERDIM - DIMENSIONDN - DOWNDR - DRAINDWG - DRAWINGEA - EACHEE - EACH ENDEF - EACH FACEEJ - EXPANSION JOINTEL - ELEVATIONELEV - ELEVATORENGR - ENGINEEREOR - ENGINEER OF RECORDEOS - EDGE OF SLABEQ - EQUALEW - EACH WAYEXIST - EXISTINGEXP - EXPANSIONEXT - EXTERIORFD - FLOOR DRAINFIN - FINISHFLR - FLOORFND - FOUNDATIONFOM - FACE OF MASONRYFS - FAR SIDEFT - FOOTFTG - FOOTINGGA - GAGEGALV - GALVANIZEDGC - GENERAL CONTRACTORGT - GIRDER TRUSSHC - HOLLOW COREHCP - HOLLOW CORE PLANKHDG - HOT DIPPED GALVANIZEDHG - HIP GIRDERHK - HOOKHORIZ - HORIZONTALHP - HIGH POINTHS - HIGH STRENGTHIJ - ISOLATION JOINTINFO - INFORMATIONINS - INSULATIONINT - INTERIORIRR - IRREGULARJB - JOIST BEARINGJBE - JOIST BEARING ELEVATIONJR - JAMB REINFORCINGJT - JOINT
K - KIP(s), 1000 POUNDSKLF - KIPS PER LINEAR FOOTKJ - CONSTRUCTION JOINTL - ANGLELG - LONGLLH - LONG LEG HORIZONTALLLV - LONG LEG VERTICALLP - LOW POINTLW - LONG WAYLWT - LIGHTWEIGHTMFR - MANUFACTURERMAS - MASONRYMO - MASONRY OPENINGMATL - MATERIALMAX - MAXIMUMMECHL - MECHANICALMTL - METALMIN - MINIMUMMISC - MISCELLANEOUSNS - NEAR SIDENIC - NOT IN CONTRACTNTS - NOT TO SCALENW - NORMAL WEIGHTOC - ON CENTEROH - OPPOSITE HANDOPNG - OPENINGPAF - POWER ACTUATED FASTENERSPART - PARTITIONPARTL - PARTIALPCJ - PRECAST CONCRETE JOISTPL - PLATEPLF - POUNDS PER LINEAR FOOTPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPT - POST TENSIONEDPrT - PRESSURE TREATEDR - RADIUSREG - REGULARREINF - REINFORCINGREM - REMAINDERREQD - REQUIREDREV - REVISED/REVISIONRM - ROOMRO - ROUGH OPENINGRQMTS - REQUIREMENTSSCHED - SCHEDULESECT - SECTIONSIM - SIMILARSL - SLOPESOG - SLAB-ON-GRADESP - SPIRALSQ - SQUARESS - STAINLESS STEELSTD - STANDARDSTL - STEELSTRUCTL - STRUCTURALSW# - SHEARWALLSW - SHORT WAYT/ - TOP OFTB - TIE BEAMTC - TIE COLUMNTEMP - TEMPERATURETJ - TIE JOISTTR - TRUSSTYP - TYPICALUNO - UNLESS NOTED OTHERWISEVERT - VERTICALW/ - WITHW/O - WITHOUTWD - WOODWF -WALL FOOTINGWP - WORK POINTWWR - WELDED WIRE REINFORCING
ABBREVIATIONS
BOTTOM REBAR
TOP REBAR
REINF SYMBOLSCOLUMN SYMBOLS
#, NO.
#
-+
SS
+0'-0"
&
8"
SPOT ELEVATION TOP OF CONCRETE
TOP OF STEEL ELEVATION
POUNDS (FOLLOWING)
MINUS OR COMPRESSION
NUMBER (PRECEEDING)
TOP OF FOOTING ELEVATION
PLUS OR TENSION
CENTERLINE
BEAM SPLICE
L E G E N D
DETAIL INDICATOR
SECTION INDICATOR
BRICK
PLATE
ITEM
EARTH
CONCRETE (SECTION)
CONCRETE (PLAN)
SYMBOL
AND
STEP IN STRUCTURE OR DEPRESSED SLAB
BAR PLACEMENT
BAR SPACING
BAR SIZE
E=`E'
C=`C'
B=BOTTOM
T=TOP4/12T
INDICATES COLUMN THRU
INDICATES COLUMN BELOW
INDICATES COLUMN ABOVE
T/STL. EL. +20'-8" or (+20'-8")
COLUMN/PILASTER MARK
FOOTING MARK
TOP OF FOOTINGELEVATION
LOAD BEARING CONCRETE BLOCK (CMU)
STEP IN FTG., GRADE BM. OR OTHERSTRUCTURAL ELEMENT
1"
S0.3
1
S0.3
1
0'-0"
CL
PL
CL
WATERSTOP:SHALL BE EXTRUDED PVC WATERSTOPS, RIBBED PROFILE. CORNERS, TEES,AND CROSSES SHALL BE PREFABRICATED BY THE WATERSTOPMANUFACTURER. ALL MATERIALS TO MANUFACTURE WATERSTOPS SHALL BEVIRGIN PVC MATERIAL. THE USE OF REWORKED PVC OR OTHER SUBSTITUTE ISNOT PERMITTED. PVC WATERSTOPS SHALL BE NATURAL COLOR, OFF-WHITE,MILKY COLOR. PVC WATERSTOPS SHALL BE AS MANUFACTURED BYGREENSTREAK OR AN APPROVED EQUAL,BUT SPLICED AS PERMANUFACTURERS INSTRUCTIONS. ALL CONSTRUCTION JOINTS AT LIQUIDRETENTION WALLS AND SLABS SHALL INCLUDE A WATERSTOP. WATERSTOPSSHALL BE CENTERED IN JOINT.
WATERSTOPS FOR CONSTRUCTION JOINTS SHALL BE GREENSTREAK #679 FOR6 INCH WIDTH AND GREENSTREAK #646 FOR 9 INCH WIDTH OR EQUAL ASDETERMINED BY ENGINEER.
WATERSTOPS FOR EXPANSION JOINTS AND CONTRACTION JOINTS SHALL BEGREENSTREAK #731 - 9 INCH WIDTH OR EQUAL AS APPROVED BY ENGINEEREXCEPT AS OTHERWISE NOTED.
CONSTRUCTION JOINTS: CONTRACTOR SHALL SUBMIT DESIRED CONSTRUCTIONJOINT LAYOUT FOR THE PRE-TREATMENT STRUCTURE FOR ENGINEER REVIEWPRIOR TO STARTING CONSTRUCTION. ALL CONSTRUCTION JOINTS SHALL BEROUGHENED AS DEFINED BY ACI STANDARDS.
PLACE ALL CONCRETE “IN THE DRY”.
PIPE CONCRETE CRADLE TYPE PIPE SUPPORTS: SEE MECHANICAL DRAWINGS.
STEEL BAR GRATING:SEE PLANS FOR SPECIFICATIONSBAND ALL GRATING AT OUTSIDE EDGES AND AT ALL OPENINGS SUCH ASFOR PIPE.STAIR TREADS SHALL BE SERRATED TREADS W/ 2"x3/16" BEARING BARS.
3202 WELDED WIRE FABRIC:TO CONFORM TO ASTM A185, FREE FROM OIL, SCALE AND RUST ANDPLACED IN ACCORDANCE WITH THE TYPICAL PLACING DETAILS OFACI STANDARDS AND SPECIFICATIONS. MINIMUM LAP SHALL BE ONESPACE PLUS TWO INCHES. USE OF FLAT MANUFACTURED SHEETS ISREQUIRED
3301 CONCRETE:A. SHALL BE PER AN APPROVED MIX DESIGN PROPORTIONED TOACHIEVE A STRENGTH AT 28 DAYS AS LISTED BELOW WITH APLASTIC AND WORKABLE MIX:
4000 PSI FOR FOUNDATIONS4000 PSI FOR COLUMNS, TIE BEAMS,AND ALL OTHER STRUCTURAL
CONCRETE 5000 PSI FOR CHLORINE CONTACT TANK AND WASTE WATERHOLDING TANK
CONCRETE SHALL BE PLACED AND CURED ACCORDING TO ACI 301-05 STANDARDS AND SPECIFICATIONS.
B. SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDEROR LAB TESTS FOR REVIEW PRIOR TO USE. ONLY TYPE II CEMENTSHALL BE USED FOR SLAB-ON-GRADE CONCRETE. MIX SHALL BEUNIQUELY IDENTIFIED BY MIX NUMBER OR OTHER POSITIVEIDENTIFICATION. MIX SHALL MEET THE REQUIREMENTS OF ASTM C33FOR COARSE AGGREGATE. CONCRETE SHALL COMPLY WITH THEREQUIREMENTS OF ASTM STANDARD C94 FOR MEASURING, MIXING,TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME STAMPEDWHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROMTHE TIME THE MIXING WATER IS ADDED UNTIL IT IS DEPOSITED IN ITSFINAL POSITION SHALL NOT EXCEED ONE AND ONE HALF (1-1/2)HOURS. IF FOR ANY REASON THERE IS A LONGER DELAY THAN THATSTATED ABOVE, THE CONCRETE SHALL BE DISCARDED. IT SHALL BETHE RESPONSIBILITY OF THE TESTING LAB TO NOTIFY THE OWNER'SREPRESENTATIVE AND THE CONTRACTOR OF ANY NONCOMPLIANCEWITH THE ABOVE. SLABS SHALL BE CURED USING A DISSIPATINGCURING COMPOUND MEETING ASTM STANDARD C309 TYPE 1-D ANDSHALL HAVE A FUGITIVE DYE. THE COMPOUND SHALL BE PLACED ASSOON AS THE FINISHING IS COMPLETED OR AS SOON AS THE WATERHAS LEFT THE UNFINISHED CONCRETE. SCUFFED OR BROKEN AREASIN THE CURING MEMBRANE SHALL BE RECOATED DAILY. CALCIUMCHLORIDES SHALL NOT BE UTILIZED; OTHER ADMIXTURES MAY BEUSED ONLY WITH THE APPROVAL OF THE ENGINEER.
C. CONCRETE MIX DESIGNS SHALL INCLUDE A WRITTENDESCRIPTION INDICATING WHERE EACH PARTICULAR MIX IS TO BEPLACED WITHIN THE STRUCTURE. FAILURE TO COMPLY MAY RESULTIN REJECTION OF THE MIX. IF ACCEPTED, PEA ROCK PUMP MIX USEIS LIMITED TO VERTICAL ELEMENT POURS AND BEAM POURS LESSTHAN 60 LINEAL FEET PER POUR.
D. CONCRETE DESIGN MIX SUBMITTALS SHALL INCLUDE TESTED,STATISTICAL BACK-UP DATA AS PER CHAPTER 5 OF ACI 318.
E. WATER/CEMENTITIONS MATERIAL RATIO FOR CONCRETE SHALLNOT EXCEED 0.45 BY WEIGHT.
F. WHERE SPECIFIED COLUMN CONCRETE STRENGTH IS 1.4 TIMESTHE SPECIFIED SLAB CONCRETE STRENGTH, SEE COLUMNSCHEDULE FOR PUDDLING REQUIREMENTS. IF REQUIRED, THESTRENGTH OF THE PUDDLED CONCRETE SHALL BE AT LEAST EQUALTO THE STRENGTH OF THE COLUMN CONCRETE. PUDDLING SHALLEXTEND 2'-0" MINIMUM FROM FACE OF COLUMN IN ALL DIRECTIONS.
G. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR DRIPS,CHAMFERS, REGLETS, SLOTS, SLEEVES, ANCHORS, AND INSERTS.UNLESS SHOWN ON STRUCTURAL DRAWINGS NO OPENINGS LARGERTHAN 12"x12" SHALL BE PLACED IN SLABS OR WALLS. FOR OPENINGSNOT SHOWN ON STRUCTURAL DRAWINGS, APPROVALS MUST BEOBTAINED FROM THE ENGINEER PRIOR TO FABRICATION OF STEELAND PLACEMENT OF CONCRETE. LOCATION DRAWINGS FOR ALLSLEEVES AND BLOCKOUTS IN THE CONCRETE SHALL BE SUBMITTEDFOR APPROVAL BY THE STRUCTURAL ENGINEER PRIOR TOPLACEMENT.
H. CONCRETE WALLS SHALL BE CAST MONOLITHIC WITH ADJOININGCOLUMNS UNLESS SPECIFICALLY NOTED OTHERWISE. CONCRETEFOR SUCH WALLS SHALL BE THE SAME TYPE AND STRENGTH ASSPECIFIED COLUMNS.
I. CONFORM TO ACI 306R FOR COLD WEATHER CONCRETING ANDACI 305R FOR HOT WEATHER CONCRETING WHEN ANY COMBINATIONOF HIGH TEMPERATURE, LOW RELATIVE HUMIDITY AND WINDVELOCITY TEND TO IMPAIR THE QUALITY OF THE CONCRETE.CONCRETE IS TO BE REJECTED IF ITS TEMPERATURE AT TIME OFPLACEMENT IS 90°F OR ABOVE. PROTECT SURFACES OF EXPOSEDCONCRETE FROM PRECIPITATION DAMAGE UNTIL ADEQUATESTRENGTH IS GAINED TO PREVENT DAMAGE.
3304 CONCRETE TESTING:A. AN INDEPENDENT TESTING LABORATORY SHALL PERFORM THEFOLLOWING TESTS ON CAST IN PLACE CONCRETE:
a)ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OFPORTLAND CEMENT CONCRETE." SLUMP SHALL RANGE FROM 3 TO 5INCHES.
b)ASTM C39 - "STANDARD TEST METHOD FOR COMPRESSIVESTRENGTH OF CYLINDRICAL CONCRETE SPECIMENS."
B. A SEPARATE TEST SHALL BE CONDUCTED FOR EACH CLASS, FOREVERY 50 CUBIC YARDS (OR FRACTION THEREOF), 5,000 S.F. OFSURFACE AREA OR EACH PLACEMENT OF EACH MIX DESIGN OFCONCRETE PLACED IN ANY ONE DAY. REQUIRED CYLINDER(S)QUANTITIES AND TEST AGE AS FOLLOWS:
1 AT 3 DAYS (FOR 5000 PSI PT SLABS) 1 AT 7 DAYS 2 AT 28 DAYS
ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDER THEDIRECTION OF THE ENGINEER, IF REQUIRED. IF 28 DAY STRENGTH ISACHIEVED, THE ADDITIONAL CYLINDER(s) MAY BE DISCARDED. ANYADDITIONAL CYLINDERS REQUESTED BY CONTRACTOR SHALL BE ATCONTRACTOR'S EXPENSE.
C. CYLINDERS AND TEST REPORTS SHALL BE CLEARLY LABELED WITHDATE SAMPLED AND WHERE CONCRETE WAS SPECIFICALLY PLACED.
D. TEST REPORTS SHALL BE KEPT AT JOB SITE, WITH COPIES SENTDIRECLY TO ENGINEER.
3307 PENETRATIONS:NO PENETRATIONS SHALL BE MADE IN ANY STRUCTURAL MEMBERSOTHER THAN THOSE SPECIFICALLY DESIGNATED ON THESTRUCTURAL DRAWINGS WITHOUT PREVIOUS APPROVAL OF THEENGINEER. CONTRACTOR SHALL SUBMIT A PENETRATION PLAN FORAPPROVAL INDICATING ANY PENETRATIONS NOT SHOWN ON THESTRUCTURAL DRAWINGS PRIOR TO CONCRETE PLACEMENT.
3406 HOLLOW-CORE SLABS:A. SHALL BE PRESTRESSED CONCRETE HOLLOW-CORE SLABSDESIGNED IN ACCORDANCE WITH ACI 318 FOR THE SUPERIMPOSEDLOADS LISTED IN GENERAL NOTE 1061.
B. PRECAST MANUFACTURER IS RESPONSIBLE FOR THE DESIGN OFPRECAST CONCRETE STRUCTURE, INCLUDING PRECAST CONCRETECOMPONENTS, EMBEDDED METAL IN CAST IN PLACE CONCRETE, ANDMETHODS OF CONNECTION FROM PRECAST COMPONENTS TOBUILDING STRUCTURE.
C. PRECAST MANUFACTURER SHALL SUBMIT SHOP DRAWINGS ANDCALCULATIONS FOR REVIEW BY THE STRUCTURAL ENGINEER OFRECORD PRIOR TO FABRICATING ANY MATERIAL. SHOP DRAWINGSSHALL BEAR THE SIGNATURE AND IMPRESSED SEAL OF A FLORIDAREGISTERED PROFESSIONAL ENGINEER.
D. PRECAST CONCRETE MANUFACTURER SHALL PROVIDE SUPPORTFROM ADJACENT COMPONENTS FOR ALL COMPONENTS CUT FOROPENINGS DUCTWORK, VENT PIPES, AND SKYLIGHTS. COORDINATESIZE AND LOCATION OF OPENINGS WITH ARCHITECTURAL,MECHANICAL AND PLUMBING DRAWINGS.
E. MIMIMUM COMPRESSIVE STRENGTH OF GROUT FOR GROUTINGBETWEENAND AT ENDS OF PLANKS SHALL BE 4,000 PSI.
F. INSTALL PRECAST PLANKS WITH RESTRAINED ENDS AND ENSURE AFIRE RESISTANCE RATING OF 4 HOURS.
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:3
7 P
M
STRUCTURAL NOTES & ABBREVIATIONS
S 02
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
UP
UP
A/C COND.
MM
MM
MM
MM
3"
11/2"
3"
3"
11/2"
3"
1-top2
3
AM top
bottom
bottom
SSSS
S
S S
SS
SS
DN
DN
UP
UP
2
A
TC1 TC1
7 5/8"
F15
3
F12SP
F7
1
F7
4
C2C1C1C2
MW
1M
W1
MW
2
MW2
MW
2
MW
2
MW2
MW
2
MW2
MW
2
MW2
MW
2
WF36
WF24
MW2
WF24
WF
36
WF
36
WF
36
WF36
WF24
WF24
WF24
WF
24
WF
24
WF
24 W
F24
WF
24
WF
24
WF
36
WF
36W
F36
36'-2" 61'-8" 16'-2"
CJ
TC2TC1
TC1 TC1TC1 TC1
CHLORINE CONTACT TANK, SEE SHEETS 10 FOR PLAN & SECTIONS, SEEPROCESS DWGS FOR LOCATION
PUMP SLAB, SEE SHT S10 FOR SIZE & REINF,SEE PROCESS DWGSFOR LOCATION
A/C SLAB
WASTE WATERHOLDING TANK, SEESHEET S 10 FORPLAN & SECTIONS,SEE PROCESSDWGS FORLOCATION
CJ CJ CJ CJ CJ
CJ
CJ
CJ
CJ CJ CJCJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
12'-5
1/2
"8'-4
"18'-1
0 1
/2"
4'-8
"
28'-8" 22'-8 3/4" 7'-7 1/4" 12'-0"
TC
1
TC
1
HSS3X3X3/16(14 TOTAL)SEE 2/S 03
CJ
CJ
-3' - 0"
T/FTG
TC1 TC1
-2' - 0"
T/FTG
1
17
1
1
1
2 2
2
2 2
22 2 2 2
15'-8 5/8"
JR2JR2
JR2
JR2
JR2
JR2
JR2
CJ
11S 05
10S 06
TYP
2S 05
2S 05
9S 06
TYP
-3' - 0"
T/FTG
-2' - 0"T/FTG
-3' - 0"
T/FTG -2' - 0"
T/FTG
T/FTG-2' - 0"
SEE 9/S 05,TYP-2' - 0"
T/FTG
10S 06
3
JR2
JR2
9S 06
3
3 3 3
3
3
10S 06
10S 06
CJ
9S 06
TYP
CJ
CJ
CJ CJ
CJ CJ
-3' - 0"
T/FTG
11S 06
4"SIDEWALK
4"SIDEWALK
CJ
CJ
CJ
CJ
TY
P
MCJ
MCJ
MC
J
MCJ
17
3S 05
3S 05
3S 05
TYP
11S 07
CJ
CJ
1919
CJ
CJ
CJ
CJ
1919
T/FTG
-2'-6"
T/FTG
-2'-6"
18
18
17
2
FOUNDATION PLAN NOTES:1. REINFORCED 6" CONCRETE SLAB-ON-GRADE WITH 6x6-W2.9xW2.9 WWR LOCATED AT CENTER OF SLAB. CUT ALTERNATE CROSS WIRES AT JOINT. SLAB-ON-GRADE SHALL BE CASTON A 15 MIL VAPOR RETARDER OVER WELL COMPACTED FILL MATERIAL. SEE GEOTECHNICAL REPORT FOR SUBGRADE PREPARATION. TOP OF SLAB ELEVATION =0'-0" (8.2' NGVD) UNLESSNOTED OTHERWISE.
2. CJ DESIGNATES SLAB-ON-GRADE TOOLED OR SAW-CUT CONTROL JOINT. FOR TYPICAL DETAILS SEE SHEET S 05.
3. CENTER ALL FOOTINGS ON WALL OR COLUMN UNLESS NOTED OTHERWISE.
4. "WF" DESIGNATES WALL FOOTING. TOP ELEVATION OF ALL FOOTINGS -2'-0" (6.2' NGVD), UNLESS NOTED OTHERWISE.
5. FOR FOOTING AND COLUMN SCHEDULE, SEE SHEET S 08. SEE S 05 FOR TYP DETAILS.
6. SEE MEP DRAWINGS FOR SLAB-ON-GRADE PENETRATIONS.
7. "MW" DESIGNATES CMU WALL. SEE SHEETS S 06 & S 08 FOR SCHEDULES & DETAILS.
8. "TE" DESIGNATES THICKENED SLAB EDGE. FOR DETAILS SEE 2/S 05 & 3/S 05.
9. "JR" DENOTES JAMB REINFORCING, SEE SCHEDULE S 08.
10. SLOPE CONCRETE SLAB 1" TO FLOOR DRAINS. TYP
C10X5.28
C10X
5.2
8C
10X
5.2
8C
10X
5.2
8C
10X
5.2
8
C10X5.
28
C10X5.28
C10X
5.2
8C
10X
5.2
8C
10X
5.2
8C
10X
5.2
8C
10X
5.2
8C
10X
5.2
8
T/GRATING 3' - 6"
4
C10x5.28
C10x5.28
C10x5.28
C10x5.28
6
5
16S 05
C10X
5.2
8
PLATFORM FRAMING NOTES
1. REFER TO SHEET S 09 FOR TYPICAL STAIR & RAILINGDETAILS.
2. CONNECTION OF GRATING SHALL BE PROVIDED BY THEGRATING MFR.
3. ALL PLATFORM FRAMING, STAIR & GUARDRAILS TO BE 6061-T6 ALUMINUM.
4. ALL PLATFORM GRATING TO BE STAINLESS STEEL.
A CJ
CJ
CJ
(14TOTAL)
1
17S 05
5T@11"
6R@7"
1'-6 1/8"2'-2 7/8"
2'-2
7/8
"
6 1
/8"
5'-8
"6'-2
1/4
"6'-2
1/4
"5'-8
"
6 1
/8"
S 0515
6"
S 078
6
PLATFORM FOUNDATION NOTES
1. REFER TO SHEET S 09 FOR TYPICAL PLATFORM, STAIR &RAILING DETAILS.
2. ALL PLATFORM FRAMING AND CONNECTORS TO BESTAINLESS STEEL.
3. CONTRACTOR SHOULD MEASURE AS BUILT CONDITIONSPRIOR TO FABRICATING PLATFORM AND STAIRS
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
1/2
010 1
1:4
6:3
1 A
M
FOUNDATION & PLATFORM FRAMING PLANS
S 03
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
1/8" = 1'-0"S 03
1 FOUNDATION PLAN
NORTH
NORTH
1/4" = 1'-0"S 03
3
CALCITE PLATFORMFRAMING PLAN
KEYNOTES-
KEY# DESCRIPTION
13 8" CONCRETE SLAB FOUNDATION 2'-6" x 12'-0"(4,000 PSI) W/ #5 @ 12" OC EW MID DEPTH.
14 12" (5,000 PSI) CONCRETE BASE SLAB W/ #6@6"OC T&B AND #4 TEMP REINFORCING @ 12" OCT&B.
15 8" (5,000 PSI) CONCRETE WALLS W/ #5 VERT @6" OC EA FACE, #4@12" OC EA FACE HORIZ.
16 8" (5,000 PSI) CONCRETE WALLS W/ #6@6" OCEA FACE VERT, #4@12" OC HORIZ EA FACE.
17 4" (4,000psi) CONCRETE SIDE WALKREINFORCED W/6x6-W2.0 WWR AT MID DEPTH.SAWCUT CONTROL JOINTS AT 4'-0" OC SEETYPICAL DETAIL ON S-05
18 6" CONCRETE SLAB ON GRADE REINFORCEDW/6x6-W2.9xW2.9 WWR SEE HVAC DRAWINGSFOR LOCATION & SIZE.
19 (2)#4x4'-0" LG @ 3" OC CENTERED IN SLAB.
KEYNOTES-
KEY# DESCRIPTION
7 8" CONCRETE (5,000 PSI) TOP SLABREINFORCED W/ #5 @ 6" OC T&B AND #4 @ 10"OC TEMP T&B.
8 10" CONCRETE (5,000 PSI) BASE SLABREINFORCED W/ #6 @ 6" OC T&B AND #4 @ 10"OC TEMP T&B.
9 10" CONCRETE (5,000 PSI) WALLS REINFORCEDW/ #6 @ 6" OC EF VERT AND #4 @ 10" OC HORIZTEMP EA FACE.
10 6" CONCRETE (5,000 PSI) WALL W/ #6 @ 6" OCVERT AND #4 @ 12" OC TEMP.
11 12" CONCRETE SLAB (4,000 PSI) W/ #5 @ 12" OCEW T&B.
12 10" CONCRETE SLAB (4,000 PSI) W/ #5 @ 12" OCEW MID DEPTH.
KEYNOTES-
KEY# DESCRIPTION
1 CONCRETE HOUSE KEEPING PAD. SEE DETAILSFOR THICKNESS & REINFORCING. SEESECTIONS 13/S 05 & 14/S 05.
2 STAINLESS STEEL MC8x8.5 CONNECTED TOEMBED PL's. SEE SECTION 2/S 08.
3 STAINLESS STEEL BAR GRATING HEAVYWELDED 2"x1/4" SPACED AT 1 3/16" McNICHOLSGHB SERIES 19W4 OR ENGINEER APPROVEDEQUAL.
4 ALUMINUM BAR GRATING 2"x3/16" SPACED AT 13/16" McNICHOLS GAL SERIES 19SG4 ORENGINEER APPROVED EQUAL.
5 L3x3x3/16 CROSS BRACING, TYP
6 ALUMINUM RT3.5x3.5x0.25, TYP
1/4" = 1'-0"S 03
2
CALCITE PLATFORMFOUNDATION PLAN
NORTH
2
A
31 4
CB1 CB1 CB2
19' - 0"
T/BM
TB1
TB1
1/4"
/FT
SLO
PE
1/4"
/FT
SLO
PE
10"
HO
LLO
W C
OR
E P
LAN
K10
" H
OLL
OW
CO
RE
PLA
NK
T/TIE BM
T/TIE BM2
S 07
2S 07
TB
1T
B1
TB
2T
B2
1S 07
CB3 CB3
CB3 CB3
18' - 0"
TB
2T
B2
1S 07
3S 07
W16X40
(+14'-0")
7S 07
6S 07
7S 07
6S 07
5S 07
5S 07
4S 07
2S 08
2S 08
(STEEL BEAM DESIGNED FOR 1TON HOIST)
5S 07
ROOF FRAMING PLAN NOTES:
1. ROOF FRAMING TO BE 10" HOLLOW CORE PLANK W/ EACH JOINT REINFORCED WITHA CONTINUOUS #4 BAR AND GROUTED SOLID. TOP AND BOTTOM SURFACE TO HAVESMOOTH FINISH. SEE SPECIFICATIONS.
2. HOLLOW CORE PLANK SHALL BEAR ON A CONTINUOUS BEARING PAD.
3. HOLLOW CORE BEARING ELEVATION = SEE PLANT/TIE BEAM = SEE PLAN
4. "TB#" DENOTES A CONCRETE TIE BEAM. FOR SCHEDULE SEE SHEET S 08.
5. "CB#" DENOTES A CONCRETE BEAM. FOR SCHEDULE SEE SHEET S 08.
6. SEE S 08 FOR GROSS WIND UPLIFT PRESSURES.
7. SEE 9/S07 FOR HANGER DETAILS.
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:3
9 P
M
ROOF FRAMING PLAN
S 04
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
1/8" = 1'-0"S 04
1 ROOF FRAMING PLAN
SLOPE SLOPE
LAP SCHEDULE
BAR LAP
LAP PER SCHED.
STD.HOOK
LAP PER SCHED.
CLR SEEGENERALNOTESTYP
2"
"S"
2"
2"
*
2"
2"
"S"
2"
2"
2"
"S"
"S"
"S"
#4 1'-10"
#5 2'-4"
#6 3'-4"
CORNER BAR TOMATCH BAR SIZE& QUANTITY OFNON-HOOKEDBARS
HORIZ BARS PERBEAM SCHED
ALL BARSTO HAVEHOOK
ST
DH
OO
K
CORNER DETAIL NOTES:"S" INDICATED STIRRUP OR TRANSVERSE FOOTING REINFORCING SPACING (WHERE INDICATED)* APPLIES TO DIMENSIONS LESS THAN 2 TIMES LAP SPLICE OF BARS (i.e. 3'-8" FOR #4 BAR).
STD HOOK
2x8 KEY ATCONSTRUCTION JOINTS
12
*#4 CONT
#4@12" OC
(2) #5 CONT T&B IF DIM"A" EXCEEDS 2'-0" USE #4@ 10" OC HORIZ. INSTEADOF (2) #5 CONT
NOTES:* AS REQUIRED NOT LESS THAN 6 UNLESS FORMED EDGE.** OR AS INDICATED ON ARCHL, COORDINATE W/ SITE CIVIL.
8"
1'-0
"
0"
MIN
**
2'-0
" M
AX
2' - 0"
CLR
3"
1" CLR, SEE GEN NOTES
3'-0
" M
AX
"A"
SEE CIVIL DWGSFOR SIDEWALKSLAB
TE, SEE PLAN
FOR FTGSEE PLAN
#4@12"OC
0'-8"
0'-8"
#4@12"OC
4'-0"
(3)#4 CONTT/FTG
EL=SEEPLAN
1'-0" 1 1/2"
PLA
N
SE
E
6 3
/4"
FTG
FTG1
1 MAX
NOTE:LOWER FOOTING AS REQUIRED TO PROVIDE MAX 1:1SLOPE FROM BOTTOM EDGE OF FOOTING TO BOTTOMOF TRENCH EXCAVATION, OR LOWER FOOTING ASSHOWN BELOW, SO THAT TOP OF FOOTING IS BELOWPIPE, CONDUIT, ETC.
PIPE, CONDUIT, ETC.
BTM OF EXCAVATION FOR TRENCHOR BTM OF ADJACENT FOOTING
PIPE, CONDUIT, ETC
WWR SEE PLAN.PROVIDE IN SHEETS NOT ROLLS
PROVIDE CHAIRS OR SUPPORTBARS TO AVOID DRAPE*
15 MIL VAPOR RETARDER
PREPARED SUBGRADE SEEGEOTECHNICAL REPORT
* SEE GENERAL NOTES FOR OPTIONAL FIBER REINF IN LIEU OF WWR
2"
CLR
PLA
N
SE
E
SAW CUT AS SOON AS POSSIBLEWITHOUT RAVELING CONCRETE (4 TO 6 HOURS AFTER POUR)
NOTE: SEE PLAN FOR CJ LOCATIONS
JOINTFILLER SAW CUT
CUT ALTERNATECROSS WIRES ATJOINT
15 MILVAPORRETARDER
1/4
t
2"
CLR
1st POUR 2nd POUR
15 MIL VAPORRETARDER
FORMED CONSTRUCTIONJT W/ KEYWAY
COMPACTED SUBBASE,SEE GEOTECHNICAL
REPORT FORREQUIREMENTS
DISCONTINUE WWR AT JT
1'-6" 1'-6"
2 3
/4"
2 1
/2"
2 3
/4"1 1/2"
CORNER EDGE INTERIOR
EDGE OF SLAB
ISOLATION JT
COLUMNSEE PLAN
EDGE OFSLAB
EDGE OF SLAB
ISOLATION JTCOLUMNSEE PLAN
ISOLATION JT
COLUMNSEE PLAN
CONSTRUCTION JTOR CONTROL JT *
* IF THERE IS NO CONSTRUCTION JT ORCONTROL JT ADD (2)#4x4'-0" LG IN SLAB.CENTER ON COLUMN.
CONSTRUCTION JTOR CONTROL JT *
MIN
4"
SE
E P
LA
N
SEE PLAN
MIN
4"
MIN
4"
SE
E P
LA
N
SEE PLAN
MIN
4"
* IF THERE IS NO CONSTRUCTION JT ORCONTROL JT ADD (2)#4x4'-0" LG IN SLAB.CENTER ON COLUMN.
"S" TO BE:8" FOR CONCRETE WALLS, 16" MAX.12" FOR CONCRETE WALLS, 24" MAX UNO ON FOUNDATION PLAN
FTG REINF
SAME SIZE AND NO. ASTYP FOOTING REINFSEE PLAN OR SECTIONS 1'-0"
1'-0"
"S"
2x"S" 3" CLRFOR MASONRY WALLSFOR CONCRETE WALLS
"S"
2x"S"
CLR
2"
FOR MASONRY WALLSFOR CONCRETE WALLS
WALL ORPIER
1/2" PREMOLDEDFILLER
t3'-0
"
S 0512
SEE PLAN
8"
TYP
1'-0"
#4@12" OCHORIZ
10"
3"
CLR
3" CLR
2"
CLR
#5@12" OCT&B
#5@12"OC T&B
CONT#5 SOG, SEE
PLAN
#5@12" OCVERT
NOTE: REFER TO ARCH DWGS FORSLOPES. SLOPE TO DRAINS.
MIN
1 1/2" BRG
STEEL GRATINGSEE PLAN
CONSTRUCTION JOINT
CONC TRENCHWALL SEE PLAN
STAINLESS STEELL2x2x3/16 W/ 5/8"øx27/8" LG HS @ 32" OC
SOG SEEPLAN
EQ EQ1 1/2" 1 1/2"
EQ
EQ
1 1
/2"
1 1
/2"
1/4
BASE PL 3/4"x10"x10" W/ (4)SS 3/4"ø WEDGE BOLTS W/MIN 5" EMBED
COLSEE
PLAN
1/2"ø SSTHROUGH BOLT
3/8" PL SPACER
BEAM,SEE PLAN
COLUMN,SEEPLAN
3/8" GUSSETPLATE
ALUMINUM L3x3x3/16 SEE PLANFOR FORCE X-BRACE ANGLESBACK TO BACK
1/4 6N.S. & F.S.
3/16
EM
BE
D
5"
ALUM RT COLSEE PLAN
3/4" ALUMINUM BASE PL
1" SHRINKCOMPENSATINGGROUT
CROSS BRACE SEEPLAN
3/8" ALUMINUMGUSSET PL 4"x8"
1/4
3/4" SS WEDGE BOLT
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:4
1 P
M
TYPICAL FOUNDATION & PLATFORM FRMGSECTIONS & DETAILS
S 05
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
1" = 1'-0"S 05
1
TYP TIE BEAM/FOOTING CORNER ENLARGED PLANDETAILS
3/4" = 1'-0"S 05
2 TYP TURNED DOWN SLAB 3/4" = 1'-0"S 05
3 FOOTING AT TURNED DOWN EDGE
3/4" = 1'-0"S 05
10 TYP FOUNDATION INFLUENCE DETAIL
3/4" = 1'-0"S 05
4 TYP SLAB ON GRADE SECTION
1 1/2" = 1'-0"S 05
5 TYP CONTROL JOINT SLABS-ON-GRADE (CJ) 3/4" = 1'-0"S 05
6
TYPICAL CONSTRUCTION JOINT FORSLAB-ON-GRADE
3/4" = 1'-0"S 05
8 TYPICAL COLUMN ISOLATION JOINT DETAILS 3/4" = 1'-0"S 05
9 TYP STEPPED FOOTING DETAIL
1" = 1'-0"S 05
7 ISOLATION JOINT (IJ)
3/4" = 1'-0"S 05
11 TRENCH SECTION
1 1/2" = 1'-0"S 05
12 GRATING BEARING SECTION 3/4" = 1'-0"S 05
15
TYP SQUARE COLUMNBASE PLATE
3/4" = 1'-0"S 05
16 SECTION 1 1/2" = 1'-0"S 05
17 PLATFORM COLUMN BASE SECTION
16"
MIN
UN
O
CLEAN OUT OPENINGS ATGROUT FILLED CELL LOCATIONS.FOR WALLS OVER 4 FT. HIGH
FOUNDATION
GROUT FILLED CELL. PLACEAND CONSOLIDATE GROUT IN 5FT LIFTS. GROUT SOLID ALLCELLS BELOW GRADE
MORTAR CROSS WEBSADJACENT TO FILLEDCELLS
ASTM C-90CMU's
SET FIRST COURSE INFULL MORTAR BEDDING
PLACE METAL LATH OR WIRE SCREENOVER CORES NOT TO BE FILLED (SHEET METALAND FELT PROHIBITED)
VERTICAL REINFORCING W/MATCHING DOWELS IN FOUNDATION.LAP PER SCHEDULE
HORIZ. LADDER-TYPE JOINT REINF @16" O.C. STARTING AT FIRST COURSEABOVE FOUNDATION. LAP SPLICES 6".USE PREFAB L's AND T's AT WALLINTERSECTIONS
CAST IN PLACE REINF CONC TIE BEAM,WHERE DESIGNATED "TB" ON PLAN.PROVIDE AS A MINIMUM AT ALL BEARINGWALLS
#3 STIRRUPS @ 24" OCMIN & @ 6" OC OVERMASONRY OPENINGS W/CLOSED STIRRUPS
(2)#5 MIN T&B
TYPICAL HEAD
TYPICAL JAMB
SEE LINTELSCHEDULE
PRECASTPRE-ENGINEERED
CONCRETELINTEL "U" OR
BLOCK*
OPENING
WIDTH
WALL DIMENSION
AND REINFORCING
CONCRETE BLOCK OR CONCRETE
DEPTH 8" WALL 12" WALL
2'-0" 1#4BOT. 1#4BOT.
2'-1" 3'-6" 1#4BOT. 1#5BOT.
3'-7" 5'-0" 1#5BOT. 2#5BOT.
5'-1" 6'-6" 1#5BOT. 2#5BOT.
6'-7" 8'-0" 1#5BOT. 2#5BOT.
8'-1" 10'-0" 1#5BOT.
MIN. MAX.
CMU LINTEL SCHEDULESOLIDGROUTEDLINTEL
* SUBMIT MANUFACTURER LOAD TABLESFOR REVIEW PRIOR TO CONSTRUCTION
TYPICAL SILL
SEE SCHED, SAMEREINF AS
NEIGHBORING WALLTYP, UNO
2#5 CONT
HOOK ALL VERTREINF INTOBOND BEAM
(1) #7 MIN. FULL HT.W/ DOWELS SEE PLAN
7 5/8"
7 5/8"
7 5/8"
7 5/8"
7 5/8"
15 5/8" -
-
SCHED
SEE
SE
E S
CH
ED
ULE
DE
PT
H
SEESCHEDULE
SC
HE
DU
LE
SE
E
NOTES:1. DO NOT USE THIS SCHEDULE IFCONCENTRATED LOAD IS APPLIED TO LINTEL.2. PROVIDE 0'-8"(MIN.) BEARING AT EACH END FORMASONRY.3. PROVIDE CURVED LINTELS AT ALL ARCHEDOPENINGS. SEE ARCH'L DRAWINGS FOR CURVEGEOMETRY AND INFORMATION.4. MASONRY CONTROL JOINTS SHALL NOTOCCUR THROUGH LINTELS.5. PRECAST LINTELS MAY BE USED IN LIEU OFLINTELS SHOWN. PROVIDE SIGNED AND SEALEDDRAWINGS AND CALCS OR MANUFACTURER'STEST RESULTS.
PROVIDE BARS SUPPORTS TOPOSITION BARS TO ALIGN W/ HOLESIN PRECAST LINTELS
WALL
EDGE OFOPENING
GROUT SOLID W/ (2)#7
8" x 16"
CL
2"TYP
"D"
LAP
SE
ES
CH
ED
ULE
* SEE ARCHL FOR WINDOW ROUGHOPENING SIZE. IF "D">16 PROVIDEPRECAST LINTEL, SEE 4/S 06
* PO
UR
DO
WN
FND,SEE PLAN
TIE BEAM SEE PLAN
IF "D">4" PROVIDE #3 SHAPED TIES @8" OC
(2)#4 BOTW/ HK IF "D"<4"
JAMBREINF, SEEPLAN (2)#5 MIN
8" DEEPGROUTED BONDBEAM W/ (1)#6& HK EA END
SILL REINF & CMU OMIT @ DOORS.AT WINDOW SILLS PROVIDE REINFPER SCHED FOR "SILL"
MOSEE ARCHL DWGSFOR DIMENSIONS
8" MINBRG
LAP
SE
ES
CH
ED
ULE
8" CMU WALL SEESCHEDULE FOR
REINFORCEMENT
SLOT BOTTOM OF LINTEL FOR JAMB ORTC REINFORCEMENT TO PASS
PRECAST CONCRETELINTEL SEE SCHEDULE
FOR TOPOF SLAB ELSEE FLR PLAN
VERTICAL REINF OVERLINTEL TO BE SAME SIZEAND SPACING ASADJACENT WALL REINF
JAMB REINF SEE PLAN(2)#5 MIN
TIE COLUMN
STRUCTURAL COLUMN
IF COLUMN IS CAST BEFOREMASONRY WALL IS
RUN UP, USE DOVETAIL ANCHORS
GALVANIZED LADDER-TYPEJOINT REINFORCING@ 16" OC
DOVETAIL ANCHOR SLOT NO. 100 BY HECKMAN(OR ENGINEER APPROVED SUBSTITUTION)
1" W x 16 GA. GALVANIZED DOVETAIL ANCHOR @16" OC NO. 106 BY HECKMAN (OR ENGINEERAPPROVED SUBSTITUTION)
GROUT FILLED CELL
#5 MIN.
GALVANIZED LADDER-TYPE JOINTREINFORCING @ 16" OC
GROUT FILLED CELL
0.145"ø POWDER ACTUATED FASTENER W/ 1"EMBED. DO NOT DISTURB ANY COLUMN
REINFORCEMENT DURING INSTALLATION.
1" W x 16 GA. GALVANIZED DOVETAIL ANCHOR AT16" O.C. NO. 106 BY HECKMAN (OR ENGINEERAPPROVED SUBSTITUTION)
#5 MIN.
CO
VE
R1 1
/2"
CLR
7 1/2"±
7 1/2"±
CMUCONTROL JOINT
RAKED JOINT
TIE BEAM,CONT REINFTHRU JOINT
7S 06
GALV JOINTREINF @ 16" OC.STOP AT CJ
GROUT FILLED CELLW/REINF AT EA SIDE OF JOINT
3/4" RAKED MORTARJOINT W/ CAULKINGEA SIDE OF WALL BUILDING PAPER OR
OTHER BOND BREAKER
BACKER ROD
APPLY SEALANT TOFACES PRIOR TO CAULKING
BACKER ROD
3/4" RAKED MORTAR JOINTW/ CAULKING EA SIDE OF WALL
CONCCOL OR WALL
FILL CORE W/ MORTAR
BUILDERPAPER OROTHER BOND BREAKER
GROUT FILLEDCELL W/ REINF
NOTE: JOINTS IN FINISHMUST ALIGN W/ CMU JOINTS
FILL CORE W/ MORTAR
APPLY SEALANT TO
FACES PRIOR TO CAULKING
NOTE: MAXIMUM ALLOWABLE JOINT SPACING = 50'-0" UNO ON PLAN.
#5 MIN8S 06
LA
P P
ER
SC
HE
D
8" CMU WALLSEE PLAN
SOG SEE PLAN
DOWELS TO MATCHWALL REINF
GROUT FULL EA CELLBELOW SLAB
CONC FTGSEE PLAN
FTG REINFSEE SCHED
3"
CLR
3" CLR
1/2" IJ
SOG SEEPLAN
1/2" IJLA
P P
ER
SC
HE
D
8" CMU WALLSEE PLAN
#4x4'-0" @ 24" O.C.
DOWELS TOMATCH WALL
REINF
GROUT FULL EACELL BELOWSLAB
CONC FTGSEE PLAN
FTG REINFSEE SCHED
(1) #5CONT
EXTERIORVENEER
3" CLR
3"
CLR
SOG SEE PLAN
CMU WALLSEE PLAN
8"x8" CONCHEADER
1#6
CONCRETESLAB
PROVIDECOMPRESSIBLESLEEVE FOR POSSIBLESETTLEMENT, TYP
CONCRETE FTG SEEPLAN
TRENCH BEYOND, POUR CONCRETE WALL 8"AFTER PLUMBING IS INSTALLED & SLEEVED
DOWEL TOMATCH
REINF, TYP
#5@12"OC
LA
P P
ER
SC
HE
DU
LE
FIN FLR
EL=0'-0"
12S 06
CMU WALLSEE PLAN
8"x8" CONCRETEHEADER W/ (1) #6
8" CONCRETEWALL
CONCRETE WALLFOOTING, SEEPLAN
CONCRETETRENCH FOOTING
TRENCH WALLBEYOND
T/SOG
SC
HE
DU
LE
LA
P P
ER
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:4
2 P
M
TYPICAL MASONRY SECTIONS & DETAILS
S 06
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
3/4" = 1'-0"S 06
1 TYPICAL MASONRY WALL CONSTRUCTION 1" = 1'-0"S 06
4
CMU WALL HEAD, JAMB AND SILL REINFORCINGAND SCHEDULE
1 1/2" = 1'-0"S 06
5 WALL OPENING JAMB DETAIL
1/2" = 1'-0"S 06
3 TYP MASONRY DOOR/WINDOW ELEVATION 1/4" = 1'-0"S 06
2 TYP MASONRY OPENING LINTEL DETAIL
1" = 1'-0"S 06
6 COLUMN ANCHORAGE DETAILS
1/2" = 1'-0"S 06
8 SECTION AT MCJ
1" = 1'-0"S 06
7 MASONRY CONTROL JOINT (MCJ)/REINF DETAIL
3/4" = 1'-0"S 06
9 INTERIOR MASONRY WALL SECTION 3/4" = 1'-0"S 06
10 EXTERIOR MASONRY WALL SECTION 1/2" = 1'-0"S 06
11 TRENCH ELEVATION AT EXTERIOR WALL 1/2" = 1'-0"S 06
12
TRENCH WALL SECTIONAT EXTERIOR WALL
3"
HOOK ENDSOF VERT BARS
#3@12"OC
REMOVE EDGE OFPLANKING AS SHOWN
(2)#4CONT
HOLLOW CORE PLANKING
CMU WALL SEE PLAN
10"
CONT #4 IN FULLYGROUTED JOINTS
1/4TIE BMSEE PLAN
L6x6x5/16 x 12" LG @ 4'-0" OC
HOLLOW CORE GALVANIZED WELD PL's BYHOLLOW CORE FABRICATOR, COORDINATEW/ CONN ANGLE TO WALL
NOTE:1. WELD PL's BY HOLLOW COREFABRICATOR, NO SUBSTITUTIONS.
(2) 3/4"øSTAINLESS
STEEL WEDGEBOLTS W/ MIN6" EMBED @ 9
1/2" OC
HOOK ENDSOF VERT
BARS
#4@4'-0" OCGROUTED INSLAB KEYWAY
(2)#4CONT
HOLLOW COREPLANKING
TIE BMSEE PLAN
CMU WALLSEE PLAN
4'-0"
6"
CONT BEARINGPAD, TYP
STD HOOK END OF BAR
#4x4'-0"@4'-0" OC GROUTEDIN SLAB KEYWAY
(1)#4 CONT
HOLLOW COREPLANKING
CONC BMSEE PLAN
GROUTED VOID
CONTBEARINGPAD, TYP
#4x3'-0" LG @ 4'--0" OC GROUTEDIN SLAB KEYWAY, DRILLED &
EPOXY INTO CONC BM
NOTE: BEAMS MAY HAVEPENETRATIONS FOR FIRE SPRINKLERPLUMBING AND CONDUIT. COORDINATELOCATIONS AND SIZES WITH ENGINEERAPPROVED SHOP DRAWINGS ANDELECTRICAL DRAWINGS.
SAW CUT NOTCH IN HOLLOWCORE @ 4'-0", ALTERNATE SIDES
DRILL & EPOXY #4INTO CONC TIE BM W/6" EMBED @ 4'-0" OC
FULLY GROUT NOTCHW/ 5,000 PSI GROUT
CONT #4HOLLOW COREROOF
STD 90° ACI HOOK ATTOP OF VERT REINF
CONC TIE BMSEE PLAN
CMU WALLSEE PLAN
6"
12"
8" CMU NON-BEARINGPARTITION, SEE SCHEDFOR REINF
ROOF HOLLOWCORE, SEE PLAN
CONT DBL COURSEBOND BEAM W/ (1)#6
CONT EA COURSE
T/WALL
SEE ARCH
SLOPE
6"
5'-8
"
HOLLOW COREPLANK, SEE PLAN
CONC BM,SEE PLAN
#5@12" OCHORIZ,CENTERED
6" MIN TAPEREDCONC WINGWALL
PRE-ENGINEEREDCANOPY
CONCCOL, SEE
PLAN
SEE TYP HOLLOW COREPLANK BEARING DETAIL
S 072
NOTE: REFER TO ARCH DWGSFOR WATERPROOFINGDETAILS.
NOTE: SEE ARCH DRAWINGSFOR DIMENSIONS
SLOPE
6"
7'-4
"
CONC BM,SEE PLAN
#5@12" OCHORIZ,CENTERED
6" MIN TAPEREDCONC WINGWALL
CONCCOL, SEE
PLAN
#5@12" OCVERT,CENTERED
4'-0"
CONCCOL, SEE
PLAN
#5@12" OCEW BOTT
NOTE: REFER TO ARCHDWGS FORWATERPROOFING DETAILS.
NOTE: SEE ARCH DRAWINGSFOR DIMENSIONS
8"
1 1/2"1"
4" 1 1/2"
10"
6"
BASE PLATE 3/4"x10"x0'-10"
CL
CL
1 1
/2"
EQ
EQ
1 1
/2"
5/8" DIA THREADED RODFOR HVAC UNITS
WASHER PLATE1/4x4x4
20 GA. METAL STRAPSGROUTED IN SLAB JOINTFOR LIGHT GYO. CEILINGSAND DUCT WORK
TOGGLE BOLT-ONLY FORVERTICAL LOADS,
PLUMBING PIPES, ETC
EXPANSION BOLT- ONLYWITH SUFFICIENT BOTTOM
THICKNESS
OVERHEAD DOOR JAMBCONCRETE COLUMNSEE PLAN
STAINLESS STEEL MC8x8.5FROM SLAB ON GRADE TOBOTTOM OF HEADER BEAM W/3/4"x6" HS@18" OC
JOINTFILLER
SAWCUT
#6x1'-4"@12" OCWWR
15 MILVAPORRETARDER
SAWCUT AS SOON ASPOSSIBLEWITHOUT RAVELINGCONCRETE(4 TO 6 HOURS AFTERPOUR)
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:4
3 P
M
TYPICAL HOLLOW CORE & CONCRETE SECTIONS &DETAILS
S 07
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
3/4" = 1'-0"S 07
1
10" HOLLOW CORE EDGE DETAIL AT ROOF(PARALLEL)
1 1/2" = 1'-0"S 07
2
10" HOLLOW CORE EDGE DETAIL AT ROOF(PERPENDICULAR)
3/4" = 1'-0"S 07
3 10" HOLLOW CORE SECTION AT ROOF 3/4" = 1'-0"S 07
4 HOLLOW CORE PLANK BEARING
1/2" = 1'-0"S 07
5
TYPICAL INTERIOR CMUPARTITION SUPPORT
3/4" = 1'-0"S 07
6 LOUVER EYE BROW 3/4" = 1'-0"S 07
7 ROLL UP DOOR EYE BROW
1 1/2" = 1'-0"S 07
8 STEEL COLUMN BASE PLATE
3/4" = 1'-0"S 07
9 HANGER DETAILS
3/4" = 1'-0"S 07
10 COLUMN PROTECTION SECTION
1 1/2" = 1'-0"S 07
11 TYP CONTROL JOINT IN WORK SHOP SLAB
MW1 8"#6@24"OC CORNERS,
INTERSECTIONS & JAMBS
MW2 8" #5@32"OC
MASONRY WALL SCHEDULEMARK THICKNESS REINFORCING COMMENTS
NOTES:PROVIDE A MINIMUM OF (1)#6 VERT REINF BAR IN A GROUT FILLED CELLAT ALL WALL INTERSECTIONS, CORNERS, AT ENDS OF WALLS AND ATEDGES OF ALLWALL OPENINGS EXCEEDING 2'-0" IN WIDTH. INTERIORWALLS DO NOT REQUIRE ANY ADDITIONAL VERT REINF UNLESSSPECIFICALLY SHOWN OTHERWISE ON PLAN.
8" #4 1'-8"
8" #5 2'-1"
8" #6 3'-7"
8" #7 4'-11"
12" #4 1'-8"
12" #5 2'-1"
12" #6 3'-3"
12" #7 3'-10"
WALL THICKNESS BAR LAP
MASONRY VERTICALREINFORCEMENT LAP
SCHEDULE
#4 1'-4" 1'-4" 1'-4" 1'-4" 1'-4" 1'-4"
#5 1'-7" 1'-5" 1'-4" 1'-4" 1'-4" 1'-4"
#6 1'-10" 1'-8" 1'-7" 1'-5" 1'-4" 1'-4"
#7 2'-9" 2'-5" 2'-3" 2'-1" 1'-11" 1'-10"
#8 3'-1" 2'-9" 2'-7" 2'-4" 2'-3" 2'-1"
#9 3'-8" 3'-3" 3'-0" 2'-9" 2'-7" 2'-6"
#10 4'-6" 4'-1" 3'-9" 3'-5" 3'-3" 3'-0"
#11 5'-3" 4'-8" 4'-3" 3'-11" 3'-8" 3'-6"
COLUMN VERTICAL BAR LAPLENGTH SCHEDULE
BAR 4000 PSI 5000 PSI 6000 PSI 7000 PSI 8000 PSI 9000 PSI
NOTES:1. LAPS SHOWN ARE CLASS "B" TENSION LAPS. FORCLASS "A" LAPS DIVIDE LAP LENGTHS BY 1.3.
STANDARD HOOK LENGTHS
BAR SIZEREINF HOOK STIRRUP & TIE HOOKS
L1 L2 L3
REINF HOOKS STIRRUP & TIE HOOKS
#3 6" 4" 2 1/2"
#4 8" 4 1/2" 3"
#5 10" - -
#6 1'-0" - -
#7 1'-2" - -
#8 1'-4" - -
#9 1'-7" - -
#10 1'-10" - -
#11 2'-0" - -
L1 L2
L3
C1 16 16 (12)#5 #3@12" A
CONCRETE COLUMN SCHEDULE
MARKT
(INCHES)W
(INCHES)VERT
REINFORCINGTIES TYPE
C2 12 16 (10)#5 #3@12" B
TC1 7 5/8 16 (8)#5 #3@8" C
TC2 7 5/8 12 (6)#5 #3@8" D
LAP PER SCHED
CONCRETE COLUMN DETAIL
SLAB OR BEAM,SEE PLAN
HOOK VERTICAL REINFAS SHOWN (UNDER
TOP STEEL)
STD ACI90° HOOK
DOWELS SHALL BETHE SAME SIZE ANDSPACING ASCOLUMN REINF
SLAB OR BEAM,SEE PLAN
SLOPE 1 TO6 MAX (NOTE 1)
PROVIDE (3) TIES @3" OC AT BEND
COLUMN TIESSPACED @ S
PROVIDE 2 TIESIN FOUNDATION
LOOSE DOWELS WHEREREQD (NOTE 1)
COLUMN TIESSPACED @ S
LOWESTREINF LAYER
(NOTE 4)
LOWEST REINF LAYER(NOTE 4)
NOTES:1. WHERE COLUMN FACE IS OFFSET 3" OR GREATER, VERTICAL BARS SHALL NOT BEOFFSET BENT. LOOSE DOWELS SHALL BE PROVIDED.
2. FOR TIE SPACING "S", SEE COLUMN SCHEDULE.
3. WHERE BEAMS FRAME FROM FOUR DIRECTIONS, TERMINATE THE TIES NOT MORETHAN 3" BELOW THE LOWEST HORIZONTAL REINFORCEMENT IN THE SHALLOWESTBEAM.4. ASSUME 1" ABOVE SLAB SOFFIT FOR PT CONSTRUCTION WHERE NO BOTTOM BARSARE PRESENT.
9"
3"
LA
P P
ER
SC
HE
DU
LE
(MA
X)
S/2
S
S
.S
CH
ED
ULE
LA
P P
ER
OFFSET (NOTE 1)
. S/2 MAX (NOTE 2)
.
S/2MAXS
S. S/2 MAX
(NOTE 3)
3"
TY
P3"
CLR
TYP3" CLR
JR1 1#6
MASONRY JAMBREINFORCING SCHEDULE
MARK REINFORCEMENT
JR2 2#7
NOTES:1. JAMB REINFORCEMENT IS CENTERED ON WALL.2. CONTINUE JAMB REINFORCEMENT TO ROOFPARAPET WHERE POSSIBLE.
TYPE A TYPE B TYPE C TYPE D
TYP
a = 7'-6"
3
3
2 1
2
2 3
2
3
NOTE: UPLIFT PRESSURES BASED ON EFFECTIVEAREA OF 10SF.
UPLIFT PRESSURES(GROSS)
ZONE PRESSURE (PSF)
1 -52.0
2 -87.0
3 -131.0
ROOF GROSS WINDUPLIFT PRESSURE
5
4
55
4
5
ϴ a
a
a
a
h
WINDOW & DOOR WIND PRESSUREDIAGRAM
a= 7'-6" TYP
ROOF UPLIFT DIAGRAM
NOTE:POSITIVE PRESSURES ACT TOWARDCOMPONENTS & CLADDING SURFACE ANDNEGATIVE PRESSURES ACT AWAY FROMCOMPONENTS & CLADDING SURFACE
WINDOW & DOOR COMPONENTS& CLADDING WIND PRESSURE
WINDOW & DOOR WIND PRESSURESCOMPONENT & CLADDING
ZONE
4
AREA
47.5/-51.5
20 50 10010
45.4/-49.3 42.6/-46.6 40.5/-44.5
5 47.5/-63.3 45.4/-59.1 42.6/-53.5 40.5/-49.3
a = 7'-6"
NOTE:POSITIVE PRESSURES ACT TOWARD COMPONENTS &CLADDING SURFACE AND NEGATIVE PRESSURES ACT AWAYFROM COMPONENTS & CLADDING SURFACE.
SCHEDULE
BEAM SIZE# ROWS
OF BOLTS
EMBED PL GUSSETPL
THICKNESSL
* LONG DIMENSION VERTICAL
CLEMBEDPL & BM
PL * STUDS
W8, W10, MC8 2 6"
W16 4 12"
2"
TY
P
3/4"ø A325N BOLTS. PROVIDE 1" LONGHORIZ SLOTS IN BEAM WEB. FINGERTIGHTEN NUTS AND PEEN THREADS
1/2" CLR
9" L
3"
TY
P1 1
/2"
TY
P
5/163"
4 1/2"
5/8x10x0'-10"
5/8x10x1'-6"
(4)3/4" DIAx4-7/8" LG 3/8"
3/8"(6)3/4" DIAx4-7/8" LG
'X'#4 OR 'Y'#4(USE LARGER)
SPAN 'X'
'X'/4
SPAN 'Z'SPAN 'Y'
'S2''S1'
Y#3
'S1'
Y#3
6" MIN. 'S1'#2
NOTE 1
CLASS 'A' TENSION LAPAT MIDSPAN UNO INSCHEDULE
ST
D. H
OO
K
BOTTOM BAR
TOP BAR
`C`BAR
ST
D. H
OO
K
`C` BAR
SEE NOTE 6
'M' BARS, WHERE INDICATED INSCHEDULE, TO BE PLACEDBETWEEN T&B BARS EQUALLYSPACED. (CLASS 'B' TENSIONLAP)
STIRRUPS-SEE SCHEDULE FORSPACING, USE 90° END HOOKS,TYP. (USE 135° END HOOKS ATSTIRRUPS MARKED "CLOSED")
TOP BAR
SEENOTE 2
COL, WALL OR PILE
`E` BAR(SEE NOTE7)
'-
/"0 1 25256
0"
2" CLR
' - /"0 11 43 64
' - /"4 0 115 256
BEAM NOTES:
1. START STIRRUP SPACING @ 'S1'/2 FROM FACE OF SUPPORT.2. EXTEND A MINIMUM OF 1/4 OF THE MAXIMUM BOTTOM REINFORCEMENT (2 BAR MINIMUM) TO DEVELOP FULL TENSION CAPACITY & HOOK AT SUPPORT.3. 'S1' AND 'S2' DENOTE STIRRUP SPACING. S2 IS 18" ON CENTER UNLESS NOTED OTHERWISE4. * INDICATES STIRRUP SPACING S1 TO BE MAINTAINED THROUGHOUT SPAN.5. FOR ALL BEAMS OVER 24" DEEP, PROVIDE #7@12" EF "M" BARS.6. ALL BOTTOM REINFORCEMENT TO BE LAPPED WITH A CLASS "A" TENSION LAP SPLICE OR PROVIDE CONTINUOUS BOTTOM BARS.7. 'E' BARS LISTED IN SCHEDULE APPLY TO THE RIGHT HAND SUPPORT OF SPAN.8. FOR TIE BEAM HORIZONTAL REINFORCING DETAIL AT CORNERS AND INTERSECTIONS SEE 1/S 05.
' - /"6 7 189 256 ' - /"1 6 43 256
' - "0 2 ' - /"0 3 33 64
'-
/"0 1 25256
0"
' - /"1 4 127 128' - /"1 4 87 256
' - /"1 5 125 128
' - /"1 4 89 128'Z' OR Y/4 (USE LARGER)UNO IN BEAM SCHEDULE
0"'-
/"0 1 165256 2" CLR
BOTTOM TOP "C" "E"
CB1 24x60 5#9 5#9 5#9 - #3@10" (CLOSED) *
CB2 24x36 5#9 5#9 - - #4@10" (CLOSED) *
CB3 7 5/8x16 (2)#7 (2)#6 - - #3@6" *
TB1 8x16 2#5 2#5 - -#3@24" (CLOSED) *
#3@6" (CLOSED) OVER OPENINGSTIE BEAM
CONCRETE BEAM SCHEDULE
BEAMMARK
BEAMSIZE
(WxD)INCHES
REINFORCINGSTIRRUPS @ SPACING S1 COMMENTS
TB2 7 5/8x20 2#6 2#5 - - #3@6" (CLOSED) * TIE BEAM AT EYE BROWS
(a) ADDED REBAR AROUND HOLES
ADD (3) #4STIRRUPS@ 3" OC EA SIDE
ADD (2) #6 T&B EAEXTEND 2'-0"
BEYOND HOLE
H/4 MAX HOLE THROUGHBEAM STEM
EQ
EQ
H
OF STIRRUPS IN BM SCHEDNOT TO EXCEED SPACING
SLAB
d1
1.5d1
MINd2d1</=d2
BEAMSTEM
(b) HOLES NEXT TO ONE ANOTHER
SLAB
HOLE THROUGHSTEM
(C) HOLES NEXT TO SUPPORTS
H
SPAN/3
FACE OFSUPPORT
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:4
5 P
M
SCHEDULES
S 08
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
FOOTING SCHEDULE
TYPE LENGTH WIDTH THICKNESS
BOTTOMREINFORCING
LW
BOTTOMREINFORCING
SWTOP
REINFORCING COMMENTS
F7 7' - 0" 7' - 0" 2' - 0" 9#6 9#6 -
F12SP 16' - 0" 12' - 0" 2' - 0" 12#8 16#8 -
F15 15' - 0" 15' - 0" 2' - 0" 16#8 16#8 -
WF24 CONT 2' - 0" 1' - 4" 3#5 #5@24"OC -
WF36 CONT 3' - 0" 1' - 4" 4#5 #5@24"OC -
1/8" = 1'-0"S 08
1 CONCRETE COLUMN DETAIL
1" = 1'-0"S 08
2
TYP STEEL BEAM CONNECTION TO CONCRETECOLUMN OR WALL PANEL
3/4" = 1'-0"
TYP BENDING DIAGRAM FOR BEAMS & ONE WAY SLABS
1/4" = 1'-0"S 08
4 PENETRATION THROUGH BEAM
2 1/2" 7" 1 1/2" MIN
3/16
1" GROUT
ELEVATION
PL 1/4" x FLANGEWIDTH
3/16
PL 3/8" x 5 1/2"LENGTH VARIES W/ SLOPE.SLOT 11/16" x 2 1/2" HOLES
ALONG STAIRWAY
(2) 5/8"ø SSADHESIVE ANCHORS
W/ 6" EMBED
1 1/4"
PL 3/8" x 5 1/2"LENGTH VARIES W/ SLOPE.SLOT 11/16" x 2 1/2" HOLESALONG STAIRWAY
SEE PLANS FORSTAIR WIDTH
PL 1/4" x FLANGEWIDTH
1" GROUT
(2) 5/8"ø SSADHESIVEANCHORS
SECTION
NOTES:1. USE BASE PLATE OF SAME METAL AS STRINGER.2. PROVIDE PROTECTION FOR DISSIMILAR METALS AND CONCRETE ASSPECIFIED.3. STAIR HANDRAIL NOT SHOWN.4. ALL HANDRAIL TO BE WELDED JOINTS AT THE HORIZONTAL RAILS ANDVERTICAL POSTS.
TYP UNO11"
1" ±
10" RUN
FO
R H
EIG
HT
TY
P
RIS
ER
, S
EE
DR
AW
ING
S
1"
ALUM STAIR TREAD
STAIRWAYWIDTH
BEARING BARS ALUMTREAD
2'-3" OR LESS 1 1/4" x 3/16"
2'-9" OR LESS 1 1/2" x 3/16"
3'-3" OR LESS 1 3/4" x 3/16"
4'-7" OR LESS 2" x 3/16"
UNO ON PLANS
3'-0"
ALUM STAIRTREAD
2" CLEARFROM ANY OBJECT
. .
NOTES:1. SEE PLANS AND OR SPECIFICATIONS FOR MATERIALSUSED FOR STAIRWAY. USE C10X5.28 ALUM STRINGERSUNLESS NOTED OTHERWISE.2. STAIR TREADS SHALL BE MADE OF SERRATED ALUMGRATING.3. TREAD MANUFACTURER TO VERIFY HOLE LOCATION FORBOLTED CONNECTIONS.4. ALL BOLTS AND CONCRETE ANCHORS SHALL BESTAINLESS STEEL.5. STAIR HANDRAIL NOT SHOWN FOR CLARITY.
TYP UNO11"
1" ±
10" 6"
ALUMINUM STAIR TREAD
ALUMINUM STAIR STRINGER
T/GRATING
RIS
ER
1/2"
C
1 1
/4"
3"
3"
CO
PE
D F
LA
NG
E
1 1
/4"
MIN
AT
(2) 5/8"ø SS BOLTS
L3 1/2x3 1/2 x 5 1/2" MIN W/ (2)5/8"ø SS BOLTS OR WELD TOSTRINGER (TYP)
NOTES:1. FOR CHANNEL SIZES SEE PLAN2. HANDRAIL NOT SHOWN3. COPE STRINGER MINIMUM AS REQUIRED
TYP
G
1 1/2"ø ALUMINUMPIPE
1 1/2"ø ALUMINUMPIPE
SEE MOUNTING OPTIONS FORMEANS OF ATTACHMENT
HANDRAIL SHALL COMPLYW/ OSHA AND FBC
MIN4"
2'-0
"1'-6
"
5'-0" MAX
3'-6
"
MIN
1/4
"
MIN
1 1/2"
HANDRAIL + 6"
1"
MIN
CO
L +
1 1/2"ø HANDRAILSUPPORT COLUMN
CHANNEL FLANGE
CL HANDRAIL
1 1/2"ø HANDRAILSUPPORT COLUMN
CHANNEL FLANGE
MIN
1/2
"
5/8"ø SS W/ LOCK
GUSSET
4"
1 1/2" RAILING POST
T/CONCRETE ORALUMINUM CHANNEL
6" SQUARE STANDARD SLEEVE TYPE SIDEMOUNT FASCIA PLATE BY NORCO, ORAPPROVED EQUAL
3/8"ø FASTENERS
CONC OR ALUMINUM CHANNEL
STANDARD END CAP
(2) 3/4"ø SSTHRU BOLTS
L3x3x1/4 x 5 1/2" LONG W/(2) 3/4"ø SS BOLTS
NOTE:STAGGER BOLTS FOR CHANNELCONNECTION IN OPPOSITE DIRECTION
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:4
5 P
M
STAIR SECTIONS & DETAILS
S 09
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
1" = 1'-0"S 09
1 STAIR BOTTOM TO CONCRETE CONNECTION 1" = 1'-0"S 09
2 STAIR ELEVATION 1" = 1'-0"S 09
3 STAIR CROSS SECTION 1" = 1'-0"S 09
4 STAIR TOP TO CHANNEL CONNECTION
1" = 1'-0"S 09
5 HANDRAIL DETAILS
3" = 1'-0"S 09
6 CHANNEL FLANGE
3" = 1'-0"S 09
7 SIDE MOUNTING BRACKET 1 1/2" = 1'-0"S 09
8
TYPICAL CHANNELCONNECTION TO POST
7
TEMPREINF
12'-8
"
24'-8"
4'-1" 2'-6"
1'-1
"2'-6
"
5S 10
6S 10
7
12S 10
(2)#5B (2)#5B
8
TEMPREINF,
TYP
9
10
3'-1
0"
6"
8'-4
"
7'-4
"6"
4'-1
0"
3'-10" 9'-4" 11'-6"
20'-10" 3'-10"
5S 10
6S 10
10
24'-8"
10
4'-0
"
1'-0" 10" 12'-6" 6" 10'-0" 10"
TYP1'-0"
8"
7'-4
"8"
8'-8
"
5'-3
"
8"
8'-8
"
9'-4
"
10"11 3/4"
1'-0 1/2" **
10'-3 3/4" 8" 10'-0" 10"
8
9
7
9
8" WIDE x 14" DP CONCRETE CURB W/ (2)#5 T&B AND #3 TIES @ 6" OC, TYP (NOTIES REQD OVER WALL)
** COORDINATE W/PROCESS DWGS
8" WIDE x 14" DP CONCRETE CURB W/(2)#5 T&B AND #3 TIES @ 6" OC, TYP(NO TIES REQD OVER WALL)
9
9
TYP
1'-0"10" 4'-0" 6" 3'-0" 6" 3'-0" 10"1'-0"
12'-8"
8'-8
"
8"
10" 4'-0" 6"1'-1 3/8"
9 1/4" **
5'-5 3/8"
8"
9'-4
"
** COORDINATE W/PROCESS DWGS
KJ, WS TYPSEE TYP DETAILSON S 11
12
4'-0" 6'-3"
13'-0
"7'-6
"
20'-6
"
7'-1" 3'-2"
7"
12'-0
"5"
LOWER SLABSEE 7/S 10
7S 10
CJ
CJ
CJ
4"
13
3'-0"
12'-0
"
7S 10
CJ
CJ
1'-6" 1'-0" 1'-6"
1'-0
"
8"
3'-0"
4'-0"
11
13
12
14TEMP REINF,TYP
16
9'-0
"
17'-0"
11S 10
16
16
16
8" 17'-0" 8"
1'-0
"6'-7
5/8
"2'-0
"
8" 10'-2" 8" 3'-2" 8"1'-0"8"
14
16
16
71515
8" 8'-11 1/4" 8"
1'-0
"6'-7
5/8
"2'-0
"
8"
1'-0"
8" 4'-3 1/4" 8"1'-0"8"
14
16
16
715
S 1013
KJ, WS TYPSEE TYPDETAILS ON S11
7
TEMP REINF, TYP
16
8'-1
1"
17'-0"
15
11S 10
10S 10
(2)#5 T&B
16
16
16
13S 10
#5@12" OC
(1)#5 CONT
6" CONC SLAB
SEE PLAN
SLAB REINFSEE PLAN
(2)#6 T&B AROUNDOPENINGS
SLAB REINFSEE PLAN
CURB BEYOND
8"
(2)#5 CONT
2'-0
"
CONC SLABSEE PLAN
SLAB REINFSEE PLAN
(2)#5SLAB REINFSEE PLAN
HATCH WALL BEYONDHATCH WALL
REINF SEE 10/S 10
HATCH WALL
HATCH WALLREINF SEE 10/S 10
8"
GENERAL TANK NOTES:1. SEE TYPICAL DETAILS ON SHEET S 11 FOR WALL & SLAB OPENINGS AND REINFORCING DETAILS.2. TANKS DESIGNED IN ACCORDANCE W/ 2007 FBC W/ 2009 SUPPLEMENTS AND ACI 350 CODE REQUIREMENTS FORENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES AND COMMENTARY.3. ALLOWABLE SOIL BEARING PRESSURE = 2,000 PSFSEE GEOTECHNICAL REPORT PREPARED BY UNIVERSAL ENGINEERING SERVICES DATED APRIL 19, 2010.4. ALL REINFORCING fy=60,000 PSI.
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
1/2
010 1
2:4
3:0
5 P
M
TANK PLANS & SECTIONS
S 10
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
RDJ
R.O. WATER TREATMENT PLANT
09FTM414
1/4" = 1'-0"S 10
2 CHLORINE CONTACT TANK - TOP SLAB
KEYNOTES
KEY# DESCRIPTION
1 CONCRETE HOUSE KEEPING PAD. SEE DETAILSFOR THICKNESS & REINFORCING. SEE SECTIONS13/S 05 & 14/S 05.
2 STAINLESS STEEL MC8x8.5 CONNECTED TO EMBEDPL's. SEE SECTION 2/S 08.
3 STAINLESS STEEL BAR GRATING HEAVY WELDED2"x1/4" SPACED AT 1 3/16" McNICHOLS GHB SERIES19W4 OR ENGINEER APPROVED EQUAL.
4 ALUMINUM BAR GRATING 2"x3/16" SPACED AT 13/16" McNICHOLS GAL SERIES 19SG4 OR ENGINEERAPPROVED EQUAL.
5 L3x3x3/16 CROSS BRACING, TYP
6 ALUMINUM RT3.5x3.5x0.25, TYP
7 8" CONCRETE (5,000 PSI) TOP SLAB REINFORCEDW/ #5 @ 6" OC T&B AND #4 @ 10" OC TEMP T&B.
8 10" CONCRETE (5,000 PSI) BASE SLAB REINFORCEDW/ #6 @ 6" OC T&B AND #4 @ 10" OC TEMP T&B.
9 10" CONCRETE (5,000 PSI) WALLS REINFORCED W/#6 @ 6" OC EF VERT AND #4 @ 10" OC HORIZ TEMPEA FACE.
10 6" CONCRETE (5,000 PSI) WALL W/ #6 @ 6" OC VERTAND #4 @ 12" OC TEMP.
11 12" CONCRETE SLAB (4,000 PSI) W/ #5 @ 12" OC EWT&B.
12 8" MINIMUM CONCRETE SLAB (4,000 PSI) W/ #5 @12" OC EW MID DEPTH.
13 8" CONCRETE SLAB FOUNDATION 2'-6" x 12'-0"(4,000 PSI) W/ #5 @ 12" OC EW MID DEPTH.
14 12" (5,000 PSI) CONCRETE BASE SLAB W/ #6@6" OCT&B AND #4 TEMP REINFORCING @ 12" OC T&B.
15 8" (5,000 PSI) CONCRETE WALLS W/ #5 VERT @ 6"OC EA FACE, #4@12" OC EA FACE HORIZ.
16 8" (5,000 PSI) CONCRETE WALLS W/ #6@6" OC EAFACE VERT, #4@12" OC HORIZ EA FACE.
17 4" (4,000psi) CONCRETE SIDE WALK REINFORCEDW/6x6-W2.0 WWR AT MID DEPTH. SAWCUTCONTROL JOINTS AT 4'-0" OC SEE TYPICAL DETAILON S-05
18 6" CONCRETE SLAB ON GRADE REINFORCEDW/6x6-W2.9xW2.9 WWR SEE HVAC DRAWINGS FORLOCATION & SIZE.
19 (2)#4x4'-0" LG @ 3" OC CENTERED IN SLAB.
1/4" = 1'-0"S 10
1 CHLORINE CONTACT TANK - BASE SLAB
1/4" = 1'-0"S 10
5
CHLORINE CONTACT TANK -LONGITUDINAL SECTION
1/4" = 1'-0"S 10
6 CHLORINE CONTACT TANK - CROSS SECTION
1/4" = 1'-0"S 10
3
HIGH SERVICE PUMP UPPERFOUNDATION PLAN
1/4" = 1'-0"S 10
4
HIGH SERVICE PUMP LOWERFOUNDATION PLAN
1/4" = 1'-0"S 10
7
HIGH SERVICE PUMP FOUNDATION -CROSS SECTION
1/4" = 1'-0"S 10
8 WASTEWATER HOLDING TANK FOUNDATION
1/4" = 1'-0"S 10
11
WASTEWATER HOLDING TANKLONGITUDINAL SECTION
1/4" = 1'-0"S 10
10
WASTEWATER HOLDING TANK CROSSSECTION
1/4" = 1'-0"S 10
9 WASTEWATER HOLDING TANK - TOP SLAB
3/4" = 1'-0"S 10
12 SLAB HATCH CURB DETAIL 3/4" = 1'-0"S 10
13 HATCH WALL DETAIL
SEPT 30 2010
T
11/2 T
LAP
6" W.S. FOR CONST.JT = 1/2 INTO WALL
LEAVE JOINTROUGHENED
ACI 90° HOOKS(CROSSING)
SE
E S
CH
ED
1 1/
2"
6" 2" 2" 6"
IN ADDITION TO TYPBASE SLAB REINF,
PROVIDE (2)#5 TOPON EACH SIDE OFWALL AS SHOWN
NOTE: DOWELSSAME SIZE &SPACING AS WALLREINF
LAP
SE
E S
CH
ED
LAP2'-0" MIN.
0"
0"
ADDITIONAL CORNERREINF. BETWEENCONT. (IF REQ'D)
CORNERREINFORCING TOMATCH CONT. REINF.
CONT. HORIZ.REINF.
CONT. HORIZ.REINF.
LAP
SE
E S
CH
ED
LAPSEE SCHED
0"
0"
ADDITIONAL REINF.BETWEEN CONT. (IFREQ'D)
ADDITIONAL CORNERREINF. BETWEENCONT. (IF REQ'D)
CONT. HORIZ.REINF.
CONT. HORIZ.REINF.
TO MATCH CONT.
2'-6
"
(TY
PIC
AL)
3" CLR ALL AROUND
#5 DIAGONALS @EA. MAT
AREA OF INTERRUPTEDREGULAR REINF. HOOKINTERRUPTED REINF. @OPENING
1. HOOK BARS AT AFFECTED ENDS WHERE BARS CANNOT EXTEND PAST OPENING.2. SHOW OPENINGS ON STEEL PLACING SHOP DRAWINGS WITH ADDED REINFORCING.
AREA OF INTERRUPTEDREGULAR REINF. HOOK
INTERRUPTED REINF. @OPENING
CLR
3"
ADDITIONAL BARS EQUALIN AREA TO 1/2 OFINTERRUPTED BARS MIN(1)#5 TOP & BOTT (SLABS)AND EACH FACE (WALLS)UON IN PLAN
2" CLR. (TYP.) 1" EXP. JT.
1/2" DEEP SEALANTEA. SIDE & TOP BONDBREAKER TAPE @PREMOLDED EXP. MATERIAL
CONT. REINF.STOP @ JOINT
CONT. REINF.STOP @ JOINT
9" RIBBED EXP. JT W.S.
PREMOLDED EXP.MATERIAL EA. SIDE
PROVIDE #7 SLIP DOWELS@ 24" OC, ALTERNATE T&B
SLIP ONE SIDE
2" CLR. (TYP.) 1" EXP. JT.
CONT. REINF.STOP @ JOINT
CONT. REINF.STOP @ JOINT
9" RIBBED EXP. JT W.S.
PREMOLDED EXP.MATERIAL EA. SIDE
1/2" DEEP SEALANTW. BOND BREAKERTAPE @ PREMOLDEDEXP. MATERIAL
PROVIDE #7 SLIPDOWELS @ 24" OC,
ALTERNATE T&B SLIPONE SIDE
LAP
(2'-0" MIN.)
CLOSURE BARS (MATCHSIZE/SPACING HORIZCONT REINF)
CONT BARS
LAP LAP
LAP
SE
E S
CH
ED
SINGLE REINF. MATCENTERED IN WALL
ALTERNATE LEGCONT. REINF.
LAP
LAP
SE
E S
CH
ED
SINGLE REINF. MATCENTERED IN WALL
CONT. REINF.
CORNER BAR TO MATCHCONT HORIZ REINF
11 / 2
"LAP
LEAVE JOINTROUGHENED
ACI 90° HOOKSALTERNATEDIRECTION
6" 2" 2" 6"
IN ADDITION TO TYPBASE SLAB REINF,
PROVIDE (2)#5 TOPON EACH SIDE OFWALL AS SHOWN
6" WS FORKJ=1/2 INTO WALL
NOTE: DOWELSSAME SIZE &SPACING AS WALLREINF
SLOPE 1/8"
t
1/2
t
1/2 t
TYP2" C
LR
"TOP" REINF EWSEE PLAN FOR SIZE & SPACINGALL REINF TO BE CONTINUOUS W/90° HOOK AT BASE SLAB EDGE
NO EARTH FORMINGPERMITTED OF SIDEOF BASE SLABS
ADDITIONAL EDGEREINF SAMESIZE ASNEIGHBORINGREINF"BOT" REINF EW
SEE PLAN FOR SIZE & SPACINGALL REINF TO BE CONTINUOUS
PREPARE SUBGRADE INACCORDANCE W/
GEOTECH REPORT
2" C
LR3"
CLR
2" CLR
3"
#4 2'-4" 1'-11"
#5 2'-11" 2'-4"
#6 3'-6" 2'-10"
#7 4'-1" 3'-3"
#8 4'-8" 3'-9"
#9 5'-3" 4'-2"
BAR SIZE TOP BEAM BAROTHERBARS
LAP SCHEDULE(5,000 PSI CONCRETE)
SLAB REINF,SEE PLAN. PROVIDE 90ºHOOK AT ALL SLAB EDGES
HO
OK
2"
CLR
TO
2"
2"
.
WALL REINFSEE SECTION.
HOOK ALLVERTICAL REINF
SINGLE MAT WALL
SLAB REINF,SEE PLAN. PROVIDE 90ºHOOK AT ALL SLAB EDGES
2"
2"
.
WALL REINF,SEE SECTION.
HOOK ALLVERTICAL REINF
#7-T&BCONT
HO
OK
2"
CLR
TO
#7-T&BCONT
2" CLR
DOUBLE MAT WALL
* 3" WHERE EXPOSED TO SOIL
*
2"
* 3" WHERE EXPOSED TO SOIL
CLR
2"
6"
(1) #7 FOREACH MAT
TYP WALL REINF,SEE SECTION.
SINGLE MAT WALL
(1) #7 FOR EACH MAT(FOR DOUBLE MATPLACE #7 INSIDE MATS)
TYP WALL REINF,SEE SECTION.
DOUBLE MAT WALL
CLR
2"
CERTIFICATE OF AUTHORIZATION NO. 27322
FILE No.
www.trcww.com
- TRC Worldwide Engineering, Inc.All rights reserved.
TO THE BEST OF MY KNOWLEDGE ANDABILITY, THE COMPLETED STRUCTUREDEPICTED ON THESE PLANS COMPLIES
WITH THE APPLICABLEMINIMUM BUILDING CODES.
12550 Professional Park Drive, Suite 7FORT MYERS, FL 33913PHONE: (239) 939-1414
FAX: (239) 278-4289
©
2009.020
AS NOTED
CAD REFERENCE
PROJECT NO.
SHEET NO.
DATE
LETTER REVISIONS DATE
DESIGNED BY
DRAWN BY
CHECKED BY
SCALE
THESE DRAWINGS ARE NOT
APPROVED FOR CONSTRUCTION
UNLESS SIGNED BELOW:
DATE
FL. Lic. #60487
PAUL S MOERSCHEL, P.E.
2010
SCALES INDICATED ONDRAWINGS ARE FORFULL SIZE PRINTS,
SCALES FOR11x17 ARE 50% SCALE
11/1
0/2
010 3
:28:4
8 P
M
TYPICAL DETAILS
S 11
R.O. WATER TREATMENT PLANT
November 2010RDJ
KLI
PSM
R.O. WATER TREATMENT PLANT
09FTM414
3/4" = 1'-0"S 11
4 TYP CONST JT/WS DETAIL WALL AT BASE SLAB 3/4" = 1'-0"S 11
3 TYPICAL HORIZ REINF IN WALLS AT CORNERS 3/4" = 1'-0"S 11
2 TYP. HORIZ REINF IN WALLS AT 'T' INTERSECTION
3/4" = 1'-0"S 11
1 TYP. REINF AT OPENINGS IN SLABS AND WALLS
3/4" = 1'-0"S 11
7 TYPICAL EXPANSION JOINT - WALLS 3/4" = 1'-0"S 11
6 TYPICAL EXPANSION JOINT - BASE SLAB 3/4" = 1'-0"S 11
5
TYPICAL WALL ENDREINF DETAIL
3/4" = 1'-0"S 11
11
TYP HORIZ REINF IN WALLS AT "T" W/SINGLE MAT
3/4" = 1'-0"S 11
10
TYP HORIZ REINF IN WALLS AT CORNERW/ SINGLE MAT
3/4" = 1'-0"S 11
13
TYPICAL CONSTRUCTION JT - SINGLE MATREINFWALL ON BASE SLAB
3/4" = 1'-0"S 11
12
TYPICAL CHANNELCONNECTION TOCONCRETE
1 1/2" = 1'-0"S 11
9 TYP FDN BASE SLAB DETAIL
3/4" = 1'-0"S 11
8 LAP SCHEDULE
3/4" = 1'-0"S 11
14 TYPICAL CAP SLAB CONNECTION TO WALL 3/4" = 1'-0"S 11
15 TYPICAL TOP OF WALL DETAIL
SEPT 30 2010