Page 1: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

Technical Seminar

Mike O’Connor

Columbus Marriot NorthwestMarch 28, 2014

Page 2: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

DOT 49 CFR 192.353 Meter Protection & Location

Current Designs & Standards by Current Gas Provider

Steel Bollards

Bolt Down Bollards

Bendable Bollards

Page 3: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

Pipeline and Hazardous Materials Safety

Administration

Pipeline Safety Regulations

DOT 49 CFR Section § 192.353 Customer Meters and Regulators: Location

Each meter and service regulator, whether inside or outside a building, must be installed in a readily accessible location and protected from corrosion and other damage, including, vehicular damage that may be anticipated. However, the upstream regulator in a series may be buried.

Each service regulator installed within a building must be located as near as practical to the point of service line entrance.

Each meter installed within a building must be located in a ventilated place and not less than 3’ from any source of ignition or heat.

Where feasible, the upstream regulator in a series must be located outside the building, unless located in a separate metering or regulating building.

Page 4: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

This gas standard provides guidelines and instructions for

selecting and installing new and retrofitted gas meter

guards for residential and commercial meters subject to

vehicular traffic

These meter guards are designed to protect against

incidental bump damage during typical low-speed

maneuvering

Purpose & Scope

References: Gas Meter Locations J-15; Electric and Gas Service Requirements, MeterProtection; California Fire Code, Section 1106, Gas Meters and Piping; DOT 49 CFR Section192.353; American Welding Society, Safety and Health Fact Sheet No. 25: Metal Fume Fever

Page 5: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

Type 1 Locations -

Residential

Within 3’ of the following:

A single-family driveway/parking area

A roadway, street, alley, or driveway

with a curb

Within 8’ of the following:

A roadway, street, alley, or driveway

without a curb

A multi-family driveway/parking area

Type 2 Locations -

Commercial

Within 3’ of the following:

A commercial refuse container

location

Within 8’ of the following:

A commercial or industrial

driveway/parking area

A loading dock/freight handling area

Physical protection must be provided for any

gas meter set located in one of the areas

described below:

Page 6: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

If a risk of vehicular damage exists at a location,

the meter should be protected by barrier posts:

When field conditions do not permit exact compliance with these

requirements, alternatives may be proposed. Alternative meter guard

arrangements must sufficiently protect the meter set and ensure

adequate distance for maintenance and meter reading.

Residential areas require a minimum 2” diameter Schedule 40 (0.154” thickness) steel post.

Commercial and industrial areas require a concrete-filled, minimum 4” diameter Schedule 40 (0.237” thickness) steel post.

Page 7: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

High quality domestic steel

Prime painted recommended

Wide variety of standard thicknesses

and sizes

Coatings: galvanized, powder coated,

painted

Shapes: square, rectangular, round

A500B structural pipe recommended

Depth is a function of frost line

Core Drilled

Page 8: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

Diameter Schedule Wall Thickness O.D.

4" 10 0.130 4.5"

4" 40 0.237 4.5"

4" 80 0.337 4.5"

6" 10 0.134 6.625

6" 40 0.280 6.625

6" 80 0.432 6.625

8" 20 0.250 8.625

8" 40 0.322 8.625

8" 80 0.500 8.625

10" 20 0.250 10.75

10" 40 0.365 10.75

10" XHD 0.500 10.75

Structural Pipe A500B Common Sizes

Page 9: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

Strength Levels Yield Strength Min. 42,000 PSI

Tensile Strength Min. 58,000 PSI

Elongation % Min. 23

Lengths Tube Production Up to 74”

Tolerances O.D. Size +/- 0.75%

Wall Thickness +/- 10%

Chemistry Low C, Mn, P, S, and residual elements for

superior weld-ability

Size Availability 28 sizes Range 1.900” O.D. to 16.000” O.D.

Gauge

Availability

Standard sizes 0.125”, 0.188”, 0.250”, 0.313”, 0.375”, 0.438”,

0.500”, 0.625”

Straightness 1/8” x length (ft) divided by five

Page 10: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

Great looking protection at low cost

Improves property appearance/visibility

Crack & fade-resistant HDPE Plastic

Optional 3M reflective stripes

Adhesive free installation

Comes in many colors & sizes

Page 11: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

Designed for all weather conditions

No more scraping & painting

Reduces dings & dents

Easy to clean with any abrasive cleaning agent

Before

After

Page 12: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

Easy installation

No core drilling or

excavation

Cost effective

Schedule 40 Steel

Safety Yellow Powder

Coated

Weld on cap recommended

Optional reflective tape

4" x 36"

4" x 42“

6" x 42"

Recommended Design

½ ” thick base plate:

4” dia. = 8” x 8”6” dia. = 10” x 10”

¾ ” anchor holes

Page 13: GUARD YOUR EQUIPMENT - Ohio Gas Association€¦ · Strength Levels Yield Strength Min. 42,000 PSI Tensile Strength Min. 58,000 PSI Elongation % Min. 23 Lengths Tube Production Up

No moving parts

Flexes on impact

Returns to height & shape

Elastomeric polymer material

Available as bolt down, core drilled, or removable bollard

Becoming standard in Europe