gs33q03k30-31e_010

7
General Specifications <<Contents>> <<Index>> Model LFS1300 Control Function for Standard Field Control Station (for FIO) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel: 81-422-52-5634 Fax: 81-422-52-9802 GS 33Q03K30-31E GS 33Q03K30-31E ©Copyright Jan. 2001 10th Edition Jun. 1, 2006 GENERAL Model LFS1300, Control Function for Standard Field Control Station (for FIO), is installed and runs in any of the following FCS models: AFS30S, AFS30D, AFS40S, AFS40D FUNCTION SPECIFICATIONS Structure of Control Functions The basic control functions are implemented as a two- level hierarchy, described below. Such a hierarchical model facilitates engineering and modification/addition of functions. Function Blocks These are the smallest elements used to perform control and calculation, and are at the bottom of the hierarchy. Control Drawing A control drawing represents the control instruments responsible for overall control of a small section of the plant, and typically contains several function blocks. A control drawing may be used to implement cascade control or combustion fuel/air ratio control, for example. Function Blocks The function blocks are divided into regulatory and sequence control blocks, calculation blocks, faceplate blocks and unit instruments. These function blocks may be combined to configure a control drawing. Regulatory Control Blocks These function blocks are mainly used for feedback control. Input Indicator Blocks: Input indicator, Input indicator with deviation alarm Controller Blocks: PID controller, Sampling PI con- troller, PID controller with batch switch, Two-/Three-position ON/OFF controllers, Time-proportioning ON/OFF controller, PD controller with manual reset, Blending PI controller, Self-tuning PID controller Manual Loader Blocks: Manual loader, Manual loader with input indicator, Manual loader with Auto/Man SW, Two-/Three-position motor control Signal Setter Blocks: Ratio set, 13-zone program set, Flow-totalizing batch set, Weight-to- talizing batch set Signal Limiter Block: Velocity limiter Signal Selector Blocks: Autoselector, Signal selector, Dual-redundant signal selector Signal Distributor Blocks: Cascade signal distributor, Feedforward signal summing, Non-in- terference control output, Control signal splitter Pulse Count Input Block: Pulse count input YS Instrument Blocks: YS controller, YS programma- ble controller, YS programmable control- ler with pulse-width output, YS manual station with SV output, YS manual station with MV output lever, YS ratio set station, YS batch set station, YS blending control- ler, YS batch controller, YS totalizer Sequence Blocks These function blocks are mainly used for interlock and batch control sequences. Sequence Table Blocks: Table type sequence Sequence Table: Standard: Total of 64 input and output signals and 32 rules Expanded sequence table (*1): M-size: Total of 96 signals (32-64 inputs and outputs, respectively) and 32 rules L-size: 64 inputs, 64 outputs, and 32 rules Rule extension table: Each one adds 32 rules to sequence table *1: Use with Migration type (with Expanded Se- quence Table) database. (Supported by R3.01 or later) Logic Chart Block: Interlock block diagram to de- scribe the relationship between input and output signals with logical operators. It consists of 32 inputs, 32 outputs and 64 logical operators. The following logical operators are available: AND, OR, NOT, Set-/Reset-dominant flip-flop with 1 or 2 outputs, Wipeout, ON-/OFF-delay timers, One-shot, Comparator (>, ≥ , =) Switch Instrument Blocks: Mainly used to operate and monitor motors and valves. 1 input, 2 inputs, 1 output, 2 outputs, 1 input 1 output, 1 input 2 outputs, 2 inputs 1 output, 2 inputs 2 outputs, 1 input 2 one- shot outputs, 2 inputs 2 one-shot outputs Sequence Element Blocks: Mainly used to generate input signals for sequence tables. Sequence Elements 1: Timer, Software counter, Pulse train counter, Code input, Code output. Sequence Elements 2: Relational expression, Resource scheduler, Representative alarms, Valve monitor

Upload: tejas-jasani

Post on 13-Apr-2015

9 views

Category:

Documents


1 download

DESCRIPTION

catalogue

TRANSCRIPT

Page 1: GS33Q03K30-31E_010

GeneralSpecifications

<<Contents>> <<Index>>

Model LFS1300Control Function for Standard Field Control Station (for FIO)

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel: 81-422-52-5634 Fax: 81-422-52-9802

GS 33Q03K30-31E

GS 33Q03K30-31E©Copyright Jan. 2001

10th Edition Jun. 1, 2006

GENERALModel LFS1300, Control Function for Standard Field Control Station (for FIO), is installed and runs in any of the following FCS models: AFS30S, AFS30D, AFS40S, AFS40D

FUNCTION SPECIFICATIONS Structure of Control FunctionsThe basic control functions are implemented as a two-level hierarchy, described below. Such a hierarchical model facilitates engineering and modification/addition of functions.

Function BlocksThese are the smallest elements used to perform control and calculation, and are at the bottom of the hierarchy.

Control DrawingA control drawing represents the control instruments responsible for overall control of a small section of the plant, and typically contains several function blocks. A control drawing may be used to implement cascade control or combustion fuel/air ratio control, for example.

Function BlocksThe function blocks are divided into regulatory and sequence control blocks, calculation blocks, faceplate blocks and unit instruments. These function blocks may be combined to configure a control drawing.

Regulatory Control BlocksThese function blocks are mainly used for feedback control.

Input Indicator Blocks: Input indicator, Input indicator with deviation alarm

Controller Blocks: PID controller, Sampling PI con-troller, PID controller with batch switch, Two-/Three-position ON/OFF controllers, Time-proportioning ON/OFF controller, PD controller with manual reset, Blending PI controller, Self-tuning PID controller

Manual Loader Blocks: Manual loader, Manual loader with input indicator, Manual loader with Auto/Man SW, Two-/Three-position motor control

Signal Setter Blocks: Ratio set, 13-zone program set, Flow-totalizing batch set, Weight-to-talizing batch set

Signal Limiter Block: Velocity limiter

Signal Selector Blocks: Autoselector, Signal selector, Dual-redundant signal selector

Signal Distributor Blocks: Cascade signal distributor, Feedforward signal summing, Non-in-terference control output, Control signal splitter

Pulse Count Input Block: Pulse count inputYS Instrument Blocks: YS controller, YS programma-

ble controller, YS programmable control-ler with pulse-width output, YS manual station with SV output, YS manual station with MV output lever, YS ratio set station, YS batch set station, YS blending control-ler, YS batch controller, YS totalizer

Sequence BlocksThese function blocks are mainly used for interlock and batch control sequences.

Sequence Table Blocks: Table type sequence Sequence Table:

Standard: Total of 64 input and output signals and 32 rules

Expanded sequence table (*1):M-size: Total of 96 signals (32-64 inputs and

outputs, respectively) and 32 rulesL-size: 64 inputs, 64 outputs, and 32 rules

Rule extension table: Each one adds 32 rules to sequence table

*1: Use with Migration type (with Expanded Se-quence Table) database. (Supported by R3.01 or later)

Logic Chart Block: Interlock block diagram to de-scribe the relationship between input and output signals with logical operators. It consists of 32 inputs, 32 outputs and 64 logical operators. The following logical operators are available: AND, OR, NOT, Set-/Reset-dominant flip-flop with 1 or 2 outputs, Wipeout, ON-/OFF-delay timers, One-shot, Comparator (>, ≥ , =)

Switch Instrument Blocks: Mainly used to operate and monitor motors and valves.

1 input, 2 inputs, 1 output, 2 outputs, 1 input 1 output, 1 input 2 outputs, 2 inputs 1 output, 2 inputs 2 outputs, 1 input 2 one-shot outputs, 2 inputs 2 one-shot outputs

Sequence Element Blocks: Mainly used to generate input signals for sequence tables.

Sequence Elements 1: Timer, Software counter, Pulse train counter, Code input, Code output.

Sequence Elements 2: Relational expression, Resource scheduler, Representative alarms, Valve monitor

Page 2: GS33Q03K30-31E_010

2

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Q03K30-31E

SFC Blocks: Describe sequences in SFC Graphical Language.

Three-position switch SFC, Pushbutton SFC, Analog SFC.

Foundation Fieldbus Faceplate Blocks: Fieldbus AI blocks, Fieldbus DI blocks, Fieldbus control selector blocks, Fieldbus PID blocks, Fieldbus ratio set blocks, Fieldbus AO blocks, Fieldbus DO blocks, Fieldbus split-range blocks, Fieldbus signal con-verter blocks, Fieldbus integrator blocks, Fieldbus input selector blocks, Fieldbus multi-DI blocks, Fieldbus multi-DO blocks, Fieldbus multi-AI blocks, Fieldbus multi-AO blocks

Calculation Blocks These function blocks are mainly used to perform calculation.

Arithmetic Calculation Blocks: Addition, Averaging, Multiplication, Division.

Analog Calculation Blocks: Square root, Expo-nential, First-order lag, Integration, Derivative, Ramp, Lead/lag, Dead-time, Dead-time compensation, Moving-average,Cumulative-average, Variable line-segment function, Temperature and pressure correction, ASTM correction: Old JIS, ASTM correction: New JIS

General-Purpose Calculation Blocks: General-pur-pose calculation, General-purpose calcu-lation with string I/O

Logic Operation Blocks: AND, OR, NOT, Set-/Re-set-dominant flip-flop with 1 or 2 out-puts, Wipeout, ON-/OFF-delay timers, One-shot, Comparator (>, ≥ , =), bitwise AND/OR/NOT.

Auxiliary Blocks: Three-pole three-position selector switch, One-pole nine-position selector switch, Selector switch for 16 data, Selec-tor switch for 16 string data, Data set, Data set with input indicator, Inter-station Connection.

Batch Data Blocks: One-batch data set, One-batch string data set, Two-batch data set, Two-batch string data set, Batch data acquisi-tion, Batch string data acquisition.

Faceplate BlocksThese faceplate blocks have a human-machine inter-face function that allows several function blocks to be represented by a single tag.

Analog Faceplate Blocks: Groups the control loops of a multi-block configuration as a single tag.

Dual-pointer indicating station: Indicates PVs and sets SVs.

Dual-pointer manual station: Sets SVs and manipu-lated output values.

Triple-pointer manual station: Indicates PVs and sets SVs and manipulated output val-ues.

Sequence Faceplate Blocks: Used for push-button operation from the HIS, and display and operation of sequence processes as a human-machine interface for sequence control function.

Sep. 24, 2003-00

Batch status indicator: Displays sequence process-es and lamps of 3-push-button switch, uses for push-button operation.

Extended 5-push-button switch: Displays five lamps and uses for push-button opera-tion.

Extended 10-push-button switch: Displays ten lamps and used for push-button opera-tion.

Hybrid Faceplate Block: Has the functions of analog and sequence faceplate blocks.

Extended hybrid manual station: Has the functions of triple-pointer operating station and 5-push-button switch.

Enhanced MC/Switch Instrument BlockThese blocks include enhanced versions of functions incorporated in normal ON/OFF controller blocks, motor control blocks, switch instrument blocks to facilitate mi-grating from a competitor’s control systems, or to allow the control of DO blocks (on/off valve, etc.) in a fieldbus device from ON/OFF controller blocks, MC instru-ments, or switch instruments. In addition to functions in normal instruments, the following functions are added. Enhanced MC/Switch Instrument blocks are standard functions and need optional memory areas of 64 KB when they are used.

Foundation Fieldbus Faceplate Block Connectivity: Enhanced function blocks in a field control station for FIO can connect DI and DO blocks in a fieldbus device via a faceplate block.

Individual Wiring: The open/close or open/close/stop signals for 2-position pulsive outputs, or 3-position (pulsive or status) inputs or outputs of a standard function block can only be connected to contiguous terminals on the same module. For an enhanced function block, however, these input and output signals can be independently con-nected to arbitrary terminals.

For migration from other company’s con-trol systems, enhanced ON/OFF control-lers, enhanced motor control blocks, and enhanced switch instrument blocks can be connected without needing rewiring even though cards with open and close signals from different cards are connect-ed.

Masking of Answerback Undefined Alarm (PERR): Checking of the answerback undefined alarm (PERR) is overridden for a preset time after an open or close (or run or stop) action. Where a Foundation fieldbus faceplate block is connected, or where the answerback signals of a field device are input from different modules, the simulta-neity of those answerback signals cannot be assured. In these cases, masking the PERR alarm check will prevent unneces-sary alarms from occurring.

Page 3: GS33Q03K30-31E_010

3<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 33Q03K30-31E Feb. 18, 2005-00

There are the following as Enhanced MC/switch instru-ment block.

Enhanced ON/OFF controller: Two-position en-hanced ON/OFF controller, Three-position enhanced ON/OFF controller.

Enhanced motor control: Enhanced two-position mo-tor control, Enhanced three-position motor control.

Enhanced switch instrument block: Enhanced 1 input, Enhanced 2 input, Enhanced 1 output, Enhanced 2 output, Enhanced 1 input 1 output, Enhanced 1 input 2 output, Enhanced 2 input 1 output, Enhanced 2 input 2 output, Enhanced 1 input 2 one-shot output, Enhanced 2 input 2 one-shot output.

Unit Supervisory FunctionThe devices and instruments used to control a plant can be defined as a single unit for operation and control purposes.

Unit Instruments: analog, 5-push-button switch, 3-position-switch

Operations: SFC, SEBOL, SFC with floating-data parameters, SFC with character-data parameters, SFC with floating/character-data parameters, SFC with integer/char-acter-data parameters, SFC with floating/integer-data parameters

Internal Switch and Message Output Func-tions

The control functions have internal switch and message output functions.

Internal SwitchesUsed as buffers for storing statuses.

Common Status Switches: Accessible within an FCS.

Global Switches: Transmits status data to other sta-tions in the system via V net communica-tion.

Message Output Function This function notifies events from one FCS to another FCS, HIS or computer. Messages are sent by se-quence functions.

Annunciator Message: Has annunciator function of instrument panel.

Sequence Message: Initiates action on HIS or su-pervisory computer — prints messages, displays operator guide messages, or prompts for data entry.

Event Message: Sends signal event messages, SFC/SEBOL return event messages to other functions within the FCS.

Page 4: GS33Q03K30-31E_010

4

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Q03K30-31E Jun. 1, 2006-00

APPLICATION CAPACITYThe “application capacity” represents the number of control functions that can be executed simultaneously.

Item Max. Capacity

AFS30, AFS40 FIO

Tag Names For elements per FCS (*1) 2,000 (*3) For function blocks (*2) 2,500

Process I/O Analog I/O points 1,280 Contact I/O points 4,096

Communication I/O Data volume (in 16 bit units) 4,000

Internal Switches Common switches 4,000 Global switches 256

Message Outputs

Annunciator messages 500 Messages printed 400 Operator guide messages 200 Request messages 200 Event messages 200

Control Functions Ccontrol drawings 200 High-speed Trend Acquisition Acquisition points 256

*1: The number of tag names for elements per FCS indicates the maximum number of a total of contact inputs/outputs (%Z elements), common switches (%SW elements), and communication inputs/outputs (%WB elements) to which tag names can be assigned. However, up to a thousand %WB elements can only be given tag names.

*2: The number of tag names indicates the maximum number of a total of function blocks (%BL elements) and annunciators (%AN elements) to which tag names can be assigned.

*3: Where I/O cards of an existing CENTUM V or CENTUM-XL system are reused for system migration.

Maximum CapacityIndividual control functions may be expanded up to the maximum capacity. The number of process I/O points de-pends on the number of I/O modules installed.

Scan Period The CPU of the FCS can execute the standard control functions in any of three scan periods. One of the three scan periods can be set for each function block.

Standard Scan Period: 1 secMedium Speed Scan Period: Specify 200 or 500 ms. Mainly used for computation and control of analog data.Fast Scan Period: Specify 50, 100, 200 or 500 ms. Mainly used for sequence control.

The above scan periods does not include I/O signal conversion time for nodes, and bus transmission time.

Inter-station ConnectionsNumber of other stations’ data that can be read and written: 512

Page 5: GS33Q03K30-31E_010

5<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 33Q03K30-31E

DatabaseThe number of function blocks is defined for each database type. Select the database type at system generation, ac-cording to your needs. The number of function blocks for each database type is shown below:

Table: Database (1/2)

Item

Database type

General-purpose

General-purpose

(extended elements per FCS)

Continuous monitoring

Regulatory control

Sequence monitoring

Sequence control

(mainly by Sequence Blocks)

Sequence control

(mainly by SFC Blocks)

Node 10 10 10 10 10 10 10 ALF111 16 16 16 16 16 16 16 ALR11, ALE111 6 6 6 6 6 6 6 Regulatory Control Blocks Calculation Blocks (*1) 700 (250) 550 (250) 2000 (250) 800 (250) 300 (250) 400 (250) 300 (250)

Sequence Blocks 450 450 200 300 200 600 200 General-Purpose Calculations 400 450 200 550 200 200 200 SFC Blocks 10 10 0 0 0 10 80 Operation Blocks 0 0 0 0 0 0 20 Switch Instrument Blocks 450 450 450 300 2000 1000 1000 Sequence Elements 1 600 600 450 600 600 600 600 Faceplate Blocks 200 50 200 200 200 200 200 Logic Operation Blocks 150 150 150 100 150 150 150 Sequence Elements 2 150 150 150 150 150 150 150 Batch Data Blocks 200 200 200 300 200 400 50 Unit Instruments 0 0 0 0 0 0 5 Offsite Blocks 0 0 0 0 0 0 0 Valve Pattern Monitors 0 0 0 0 0 0 0 SEBOL Daemon 10 10 0 0 0 10 40 SEBOL User Function 0 0 0 0 0 0 20 Control Recipe Area 0 0 0 0 0 0 0 FCS-C Task/Option Area 64 KB 64 KB 64 KB 64 KB 64 KB 64 KB 64 KB

*1: Figures in parentheses indicate the maximum number of Foundation Fieldbus faceplate blocks definable.

Feb. 18, 2005-00

Page 6: GS33Q03K30-31E_010

6

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 33Q03K30-31E

Table: Database (2/2)

Item

Database type Unit control

(without recipe)

Unit control (with recipe)

Offsite block

Valve pattern monitor

Migration Migration type with expanded sequence table

Sequence control (with Expanded

Sequence Blocks) Node 10 10 10 10 10 10 10 ALF111 2 2 16 2 2 2 2 ALR11, ALE111 6 6 6 6 6 6 6 Regulatory Control Blocks Calculation Blocks (*1) 250 (30) 250 (30) 700 (250) 250 (30) 300 (30) 300 (30) 500 (30)

Sequence Blocks 250 200 350 200 450 Standard: 200 (*2)

M-size: 200 (*3) L-size: 50 (*4)

Standard: 200 (*2) M-size: 100 (*3) L-size: 100 (*4)

General-Purpose Calcula-tions 100 80 400 80 600 600 500

SFC Blocks 10 10 10 10 5 5 20 Operation Blocks 250 200 0 200 0 0 0 Switch Instrument Blocks 500 450 450 450 600 600 600 Sequence Elements1 600 500 600 500 600 600 700 Faceplate Blocks 100 50 200 50 50 50 10 Logic Operation Blocks 100 50 150 50 100 100 100 Sequence Elements2 150 50 150 50 300 300 300 Batch Data Blocks 50 50 200 50 100 100 200 Unit Instruments 30 30 0 30 0 0 0 Offsite Blocks 0 0 80 0 0 0 0 Valve Pattern Monitor 0 0 0 20 0 0 0 SEBOL Daemon 120 100 10 100 5 5 5 SEBOL User Function 70 70 0 70 0 0 20 Control Recipe Area 0 1 MB 0 500 KB 0 0 0 FCS-C Task/Option Area 64 KB 64 KB 128 KB 128 KB 64 KB 64 KB 64 KB

*1: Figures in parentheses indicate the maximum number of Foundation Fieldbus faceplate blocks definable. *2: Standard – Total of 64 input and output signals and 32 rules*3: M-size – Total of 96 signals (32-64 inputs and outputs, respectively) and 32 rules*4: L-size – 64 inputs, 64 outputs, and 32 rules

Feb. 18, 2005-00

Page 7: GS33Q03K30-31E_010

7<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 33Q03K30-31E

OPTIONAL SOFTWARE PACKAGESThe following optional software packages can be used with Control Function for Standard Field Control Station.Memory size in option area required by each package is shown inside parentheses ( ). Items without such descrip-tions do not need memory.When optional software packages are used, the sum of the memory sizes necessary for those optional packages shall not exceed the memory size of option areas of databases. In addition, when using enhanced MC/switch instruments as standard functions, which need an optional memory area of 64 KB, add this to the required memory size.

LFS8620 (80 KB) Off-Site Block PackageLFS3132 (90 KB) Valve Pattern Monitor PackageLFS2410 FA-M3 Communication Package (for ALR111, ALR121)LFS2420 YS Communication Package (for ALR121) (*1)LFS2421 YS Communication Package with direct connection (for ALR121) (*2)LFS2430 MELSEC Communication Package (for ALE111) (*1)LFS2431 FA-M3 Communication Package (for ALE111) (*1)LFS2432 DARWIN/DAQSTATION Communication Package (for ALE111) (*4)LFS2433 PLC-5/SLC 500 Communication Package (for ALE111) (*1)LFS2453 Modbus Communication Package (for ALE111) (*2)LFS2456 SLC 500 Communication Package (for ALR111, ALR121) (*2)LFS2457 PLC-5 Communication Package (for ALR111, ALR121) (*2)LFS2610 Foundation Fieldbus Communication Package (for ALF111)LFS2710 HART Communication Package (for AAI-H) (*1)LFS9153 (30 KB) Modbus Communication Package (for ALR111, ALR121) (*3)LFS9162 MELSEC-A Communication Package (for ALR111, ALR121)

*1: Supported by R3.02 or later versions.*2: Supported by R3.03 or later versions.*3: Memory can be used for dual-redundant use only.*4: Supported by R3.04 or later versions.

OPERATING ENVIRONMENTHardware RequirementsModel LFS1300 Control Function for Standard Field Control Station operate on the following FCS models: AFS30S, AFS30D, AFS40S, AFS40D

MODELS AND SUFFIX CODESModel Description

LFS1300 Control Function for Standard Field Control Station (for FIO)

*1: Specify with suffix codes for FCS.

TRADEMARKS• CENTUM and DARWIN are registered trademarks of Yokogawa Electric Corporation.• Modbus is a registered trademark of Schneider Electric and/or such related companies.• MELSEC-A is a registered trademark of Mitsubishi Electric Corporation.• SYSMAC is a registered trademark of Omron Corporation.• PLC-5 and SLC are trademarks or registered trademarks of Rockwell Automation, inc.• “FOUNDATION” of “FOUNDATION fieldbus” is a registered trademark of Fieldbus Foundation. • Other product and company names appearing in this document are trademarks or registered trademarks of their

respective holders.

Subject to change without notice.Jun. 1, 2006-00