grx-ci-prg programming control interface programming control interface description • integrates a...

6
® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: GRX-CI-PRG Control Interfaces 369363 Rev. B 1 06.02.11 GRX-CI-PRG Programming Control Interface Description • Integrates a GRAFIK Eye® lighting control system with a PC or other digital equipment that supports RS232 and TCP/IP communication. • Provides a basic serial string command set that allows a PC to monitor and control lighting. • Built-in astronomic timeclock provides ability to schedule lighting events. Example: Lobby lights turn on to scene 1 at 7:30 a.m. or 10 minutes after sunrise. • Enables use of a PC to set up GRX-3500 and GRX-4500 control units. • Comes with easy-to-use, “point-and-click” Windows®-compatible LIAISONTM software for scheduling the astronomic timeclock and using the programmer Interface. • Functionality is selected using DIP switches. • Operates with or without a PC connected. • May be programmed to control any combination of one to eight GRAFIK Eye® 3000 or 4000 series control units. • GRX-3100, GRX-4100, and GXI-3100 control units may utilize the astronomic timeclock function of the GRX-CI-PRG. • GRX-3500, GRX-4500, and GXI-3500 control units may utilize all functions of the GRX-CI-PRG.

Upload: trinhtuyen

Post on 29-May-2018

240 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GRX-CI-PRG Programming Control Interface Programming Control Interface Description • Integrates a GRAFIK Eye

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GRX-CI-PRG Control Interfaces

369363 Rev. B 1 06.02.11

GRX-CI-PRG Programming Control Interface

Description

•IntegratesaGRAFIKEye®lightingcontrolsystemwithaPCorotherdigitalequipmentthatsupportsRS232andTCP/IPcommunication.

•ProvidesabasicserialstringcommandsetthatallowsaPCtomonitorandcontrollighting.

•Built-inastronomictimeclockprovidesabilitytoschedulelightingevents.Example:Lobbylightsturnontoscene1at7:30a.m.or10minutesaftersunrise.

•EnablesuseofaPCtosetupGRX-3500andGRX-4500controlunits.

•Comeswitheasy-to-use,“point-and-click”Windows®-compatibleLIAISONTMsoftwareforschedulingtheastronomictimeclockandusingtheprogrammerInterface.

•FunctionalityisselectedusingDIPswitches.•OperateswithorwithoutaPCconnected.•MaybeprogrammedtocontrolanycombinationofonetoeightGRAFIKEye®3000or4000seriescontrolunits.

•GRX-3100,GRX-4100,andGXI-3100controlunitsmayutilizetheastronomictimeclockfunctionoftheGRX-CI-PRG.

•GRX-3500,GRX-4500,andGXI-3500controlunitsmayutilizeallfunctionsoftheGRX-CI-PRG.

Page 2: GRX-CI-PRG Programming Control Interface Programming Control Interface Description • Integrates a GRAFIK Eye

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GRX-CI-PRG Control Interfaces

369363 Rev. B 2 06.02.11

Specifications

Standards

•CaliforniaEnergyCommission(CEC)Listed

Power

•IECPELV/NEC®Class2•OperatingVoltage:12V 125mA

24V 65mA

Environment

•32to104°F(0to40°C).•Relativehumiditylessthan90%non-condensing.

Basic Command Set

•Monitoring:Sceneselectionandscenestatusupdates.

•Control:Sceneselection,scenelockout,sequencing,zonelockout,zoneraise/lower.

Astronomic Timeclock

•Allowslightingchangestooccurautomaticallybasedontimeofdayand/ordayofweek/month,aswellasrelativetosunriseandsunset.

•Supportsfourscheduleswith60lightingeventsperscheduleandoneSuperSequence.

•Allowsusertostart,pause,andstopschedulesfromaPCoraWallstation.

•Providescommandstosetandmonitorthetimeclock’stime,date,anddayofweek,andreportsunriseandsunset.

•Ifalossofpoweroccurs,theprogrammedschedulesandthetimeofdaywillberetainedforaminimumof10years.

Programmer Interface

PermitscompletesetupofthefollowingonGRX-3500,GRX-4500,orGXI-3500controlunitsviaanIBM®-compatiblePC:

•Scenes,includinglightlevelsin1%incrementsandfadetimes.

•Loadtypesettings.•Tamper-proofprotectionofscenes.•Assignmentofcommunicationbetweencontrolunitsandwallstations.

•Dimmerpanelzoneandloadassignment

AllowsaWindows®-compatiblePCtoqueryGRX-3500,GRX-4500,andGXI-3500controlunitsfortheirsetup,includingtypeofcontrolunitandnumberofzones.

LIAISONTM Software

•ControloverTCP/IPrequiresLIAISONTMversion4.0orlater.

•AllowsuseofaPCtocreatetimeclockschedulesforallGRX-3000,GRX-4000,andGXI-3000seriescontrolunits.

•AllowsuseofaPCtocreatesetupsforGRX-3500,GRX-4500,andGXI-3500controlunits.

•ProvidesdownloadingofschedulesandsetupstoGRX-CI-PRGinterfaceandcontrolunits.

•WorksonanyPCoperatingwithWindows®95Windows®NT4.0,XP,orlater(excludingWindows®VistaandWindows®7).

•SuppliedbyLutron.Updatesareavailableonlineatwww.lutron.com

System Communications and Capacity

•IECPELV/NEC®Class2wiringconnectsGRX-CI-PRGinterfacetocontrolunitsandothercomponents.

•OneGRX-CI-PRGInterfaceperGRAFIKEye®3000or4000orGXI-3000system.Automaticallyoccupieswallstationaddress16.

•50ft(15m)maximumfromGRX-CI-PRGInterfacetoPCorotherRS232source.

•328ft(100m)maximumfromGRX-CI-PRGInterfacetoPCorotherEthernetsource.

Page 3: GRX-CI-PRG Programming Control Interface Programming Control Interface Description • Integrates a GRAFIK Eye

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GRX-CI-PRG Control Interfaces

369363 Rev. B 3 06.02.11

Functions

DIP Switch Function

When set to ON

When set to OFF

1 ZoneLockRetain Ifpowergoesout,lockedzonesstaylockedwhenpowerreturns.

Powercyclingunlockslockedzones.

2 SceneLockRetain Ifpowergoesout,lockedscenesstaylockedwhenpowerreturns.

Powercyclingunlockslockedscenes.

3 SequenceRetain Ifpowergoesout,sequencingresumeswhenpowerreturns.

Powercyclingstopssequencing.

4 SequencingSceneRange Sequencingloopsthroughscenes5to16.

Sequencingloopsthroughscenes1to4.

5 NotUsed DonotsettoOn. Factorypreset;donotchange.

6 ButtonFeedback Interfacereportscontrolunitandwallstationbuttonpresses.

Noreportingonbuttonpresses.

7 SceneStatus Interfacereportsscenechanges. Noreportingonscenechanges.

8 AstronomicTimeclockSchedules

Enablesinternaltimeclock. Disablesinternaltimeclock.

1 2 3 4 5 6 7 8

Page 4: GRX-CI-PRG Programming Control Interface Programming Control Interface Description • Integrates a GRAFIK Eye

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GRX-CI-PRG Control Interfaces

369363 Rev. B 4 06.02.11

Dimensions2.47in

(62.7mm)

3.75in(95.3mm)

4.26in(108.2mm)

5.26in(133.6mm)

1.06in(26.9mm)

Mountingholes

Mounting

1.Mountthecontrolinterfacedirectlyonawall,asshownintheMountingDiagram,usingscrews(notincluded).Whenmounting,providesufficientspaceforconnectingcables.

TheunitcanalsobeplacedintheLUT-19AV-1UAVrackusingthescrewsprovidedwiththeunit.TheLUT-19AV-1Uwillholduptofourunits.

Ifconduitisdesiredforwiring,theLUT-5x10-ENCcanbeusedtomountoneunit.

2.Strip4in(10mm)ofinsulationfromwires.Eachdatalinkterminalwillacceptuptotwo18AWG(1.0mm2)wires.

3.ConnectwiringasshownintheWiringDiagram(nextpage).LED1lightscontinuously(Power)andLED7blinksrapidly(DataLinkRX)whentheIECPELV/NEC®Class2DataLinkisinstalledcorrectly.

LUT-19AV-1U

WireStripLength

4in(10mm)

5.26

4.263.75

2.50

1.06

ControlInterface

Wall

Mounting Diagrams

LUT-5x10-ENC

0.25(6.4)

0.34(8.6)dia.

0.18(4.6)dia.

0.18(4.6)dia.

#6or#8(M3orM4)screwrecommended(notincluded)

Mounting Hole DetailDimensions:in(mm)

Page 5: GRX-CI-PRG Programming Control Interface Programming Control Interface Description • Integrates a GRAFIK Eye

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GRX-CI-PRG Control Interfaces

369363 Rev. B 5 06.02.11

RS232 Link Wiring

1 2 3 4 5 6 71 2 3 4 5 6 7 8

RJ45jack:Ethernetlink(toPCorA/Vequipment)

Ethernetlink/

activity

Ethernetspeed

DataLink(tocontrolunits,processors,andwallstations)

DIPswitches

CAT5Cable:maximum328ft(100m)

ToPCorAVequipment.ForEthernetlink,useaCAT5cabletoconnecttoauxiliaryequipment.TheEthernetlinkLEDwilllightcontinuouslywhenlinkispresentandwillflashwhenthereislinkactivity.AdditionalEthernetnetworkequipmentandcablesprovidedbyothers.

12or24V tooutlet(withoptionaltransformer).Donotwireterminal2onDataLinkwhenusingoptionaltransformer.TopowerseparatelyfromtheDataLink,orderthefollowingLutrontransformermodelnumbers:120V :T120-15DC-9-BL240V :TE240-15DC-9-BL240V (UK):TU240-15DC-9-BL

RS232Cable:maximum50ft(15m)

COM

TxD

RxD

ToPCorAVequipment:UseastandardDB9maletoDB9femalecable,orfollowthechartbelow.

RS232PinConnectWiring

TypicalPCor PinonRS232Interface A/Vequipment 9-pincableCommon Com 5Transmit TxD 3Receive RxD 2

LED1:PowerLED2:EthernetlinkLED3:UnusedLED4:RS232linkTXLED5:RS232linkRXLED6:DatalinkTXLED7:DatalinkRX

Page 6: GRX-CI-PRG Programming Control Interface Programming Control Interface Description • Integrates a GRAFIK Eye

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

GRX-CI-PRG Control Interfaces

369363 Rev. B 6 06.02.11

IEC PELV/NEC® Class 2 Terminal Connections•Installinaccordancewithallapplicableregulations.•Donotconnectlinevoltage/mainspowertodevice.•ThiscontrolcanuseIECPELV/NEC®Class2wiringmethods.Checkwithyourlocalelectricalinspectorforcompliancewithnationalandlocalcodesandwiringpractices.

•Makedaisy-chainconnectionstotheIECPELV/NEC®Class2datalinkterminalsontheendofthecontrolinterface.

•DonotuseT-taps.Runallwiresinandoutoftheterminalblock.•Eachterminalacceptsuptotwo18AWG(1.0mm2)wires.

ZONE 6ZONE 4

HOT/LIVESSA

CU WIRE ONLY

ZONE 2ZONE 3ZONE 5

NEUTRAL

ZONE 1

CLASS 21 2 3 4

USAClass 2IECPELV

4 3 2 1

Toadditionalwallstations/controlinterfaces(16maximum;3poweredfromoneGRAFIKEye® controlunitwithoutexternal12V powersupply;GRX-CI-PRGcountsastwodevicestowardthemaximumofthreeconnectedtooneGRAFIKEye®3000controlunitwhennotusingoptionaltransformer)

Control Interface Wiring: GRX-3000 or GXI-3000 Control Unit

RearViewofGRAFIKEye®ControlUnit(GRX-3106shown)

UseLutronCableGRX-CBL-346Sorequivalent

DataLink

DataLink:

4:MUX

3:MUX

Oneshielded,twistedpair18AWG(1.0mm2)fordatalink(terminals3and4)

IECPELV/NEC®Class2Powerwiring:

2:12V Power1:Common

Two18AWG(1.0mm2)conductorsforCommon(terminal1)and12V (terminal2)

4 3 2 1

IECPELV/NEC®Class2Powerwiring:

1:Common2:24V Power

(2)18AWG(1.0mm2)pigtails,6in(15mm)maximumlengthDonotwirePin2whenusingoptionaltransformer.

D:Drain/Shield

(2)12AWG(2.5mm2)

(2)12AWG(2.5mm2)

DataLink:(1)shielded,twistedpair18AWG(1.0mm2)

4:MUX

3:MUX

Control Interface Wiring: GRX-4000 Control Unit

Note:12AWG(2.5mm2)conductorsforCommon(terminal1)and24V power(terminal2)willnotfitinterminals;use18AWG(1.0mm2)pigtails(<6in/15mm).

Note: Donotconnectdrain/shieldtoground(earth)orwallstation/controlinterfaces.Connectthebaredrainwiresandcutofftheoutsideshield.

UseLutronCableGRX-CBL-46L

ToOutlet(withoptionaltransformer).DonotwirePin2whenusingtransformer.