ground reference transformer sizing

Upload: mehrbloorgmailcom

Post on 04-Jun-2018

1.503 views

Category:

Documents


114 download

TRANSCRIPT

  • 8/13/2019 Ground Reference Transformer Sizing

    1/5

     Ground Reference Transformer Sizing

    Example 1:

    1. Objective: The three-phase fault duty at a Wind Farm facility is 5kA (299 MVA) on the

    ungrounded 34.5 kV system. It is required to ground this system using a zigzag groundingtransformer and limit the ground-fault current to 400 A. the objective of this study is specifying thegrounding transformer.

    2.  Input Data

    a. System Voltage:  34.5kV, 3phase, 3Wire 

    b. System Grounding:  Ungrounded 

    c. Type of required grounding Source:  c1: zigzag transformer

    c2: wye-delta 

    d. Neutral ground current that groundingtransformer shall carry under fault:  400A 

    3.  Calculation: 

    a.  Transformer Impedance

    Use 100 MVA Base (100000 kVA)

    Rated Voltage = 34.5 kV

    Base Ohms = (1000) (kV)2/KVA=1000 (34.5)

    2/100000= 11.9 Ω 

    Base Amps = KVA/(KV × √3)= 100000/(34.5 x √3)= 1673 A

     Z 1 = Z 2 = 100/299 = 0.334 per unit (p.u.)

    Positive

    sequence0.334 p.u.

    Negative

    sequence0.334 p.u..

    Zerosequence Z0 

    IG = 400/1673= 0.24 p.u. A

    I0 = 0.24/3= 0.08 p.u. A

     Z total = 1/0.08= 12.5 p.u. Ω 

  • 8/13/2019 Ground Reference Transformer Sizing

    2/5

     Z total  – 2 Z 1 = 12.5 – 0.334 – 0.334= 11.832 p.u. Ω 

     Z 0 = 11.9 × 11.832= 140.8 Ω/phase for grounding transformer

    b.  Transformer short time kVA rating 

    i.  For a zigzag grounding transformer, since both windings are active in the primary circuit,

    the actual (short-time) rating in kilovoltamperes is:

    kVA= (Line-to-Line kV)(Neutral Amps)/3= (34.5 x 400)/3=4600 kVA

    ii.  For a wye-delta grounding transformer, the actual (short-time) rating in kilovoltamperes

    is:

    kVA= (Line-to-Line kV)(Neutral Amps)/√3= (34.5 x 400)/√3=7967 kVA (8 MVA)

    Because a grounding transformer is a short-time device, its size and cost are less than for a

    continuous duty transformer of equal kVA rating. The reduced size can be established in

    terms of an “equivalent two-winding 55 C kVA” kVAx, by applying a reduction factor K to the

    short-time rated kVA of the grounding transformer, and this reduced kVA can be used for a

    price estimate.Since a grounding transformer is a short-time device and normally only required to carry

    short-circuit ground current until the circuit breakers clear the fault, it is common to rate it

    on a reduced time such as 10 s or 1 minute. Under these circumstances the physical size (and

    resulting cost) is considerably reduced. The reduced size can be established in terms of an

    “equivalent two-winding 55 C kVA” kVA reduced, by applying a reduction factor K to the short-

    time rated kVA of the grounding transformer.

    Values for K are listed in Table 1 below for various types and classes of grounding

    transformers;

    Table 1- K FACTORS FOR DETERMINING EQUIVALENT TWO-WINDING 56 C KVA OF

    GROUNDING TRANSFORMERS

  • 8/13/2019 Ground Reference Transformer Sizing

    3/5

     

    Since in wind farms the 34.5 kV system could be subjected to more than one faults in quick

    succession 1 minute rating is preferable.

    i.  The zigzag grounding transformer is required to continuously carrying the 34.5

    kV line to-ground charging current and the unbalanced current (if any).

    As per IEEE 32, the continuous current for a zigzag grounding transformer with a 1minute

    time-rating is equal to the 7% of the ground fault current i.e.

    Icontinuous= (7/100) x 400= 28 A

    Continuous kVA rating= (34.5 x 28)/3=322 kVA

    4.  Proposed Zigzag Grounding transformer

    Technical Requirement for the Proposed Grounding Transformer

    Cooling ONAN

    Installation Outdoor

    Winding Configuration Zigzag

    Rated Voltage 34.5 kV

    Rated BIL 200 kV

    Continuous Neutral Current 28 A

    Rated Neutral Fault Current 400 A for 1 minute

    Zero sequence impedance 140.8 Ω 

    Temperature Copper: 55⁰C, oil: 50⁰C at 40⁰C ambient temperature 

    Standard CAN/CSA C88-M90 (R2009)

    Accessories

    Normal Special

  • 8/13/2019 Ground Reference Transformer Sizing

    4/5

    1 Conservator with liquid drain valve and

    filling valve

    1 Buchholtz relay

    2 Breather 2 Winding temperature indicator

    3 Liquid level indicator 3 Conservator magnetic liquid level indicator

    4 Liquid draining and sampling valve 4 Anti-condensate heater

    5 Top oil thermometer 5 Pressure relief device

    6 Lifting, moving detanking & jacketing

    facilities6 4 CTs, 600/5A, C50, B0.5

    7 Name plate 7 Control box

    8 Grounding pad

    5.  Evaluation of Proposed Zigzag Grounding transformer

    To examine the proposed grounding transformer is suitable it has to be shown that:

    Z0 ≤ XC0 

    Where,

    Z0 = Zero sequence impedance, and

    XC0= line-to-ground capacitive reactance of the system

    Or in another way, the current in the zero sequence impedance IG during a line-to-earth fault

    must be equal to or greater than three times the line-to-earth system charging current, 3IC0 

    IG ≥ 3IC0

    3IC0 could be calculated from below formula:

    3IC0 = (√3) *(2 xπ x f x C 0 x V L-L ) /103 ] Amperes

    Where,

    VL-L = system line-to-line voltage in kilovolts,

    C0 = zero sequence capacitance of the system,

    f = system frequency 

    The zero sequence capacitance of any type of cable can be calculated using the following

    formula:

    C 0 = (0.02415 x SIC)/log (D/d) µF/ km

    Where,

    SIC = dielectric constant,

    D = the diameter of cables over the insulation shield,

    d = the diameter of the conductor,

    The zero sequence capacitance of transformer is negligible. However, for overhead lines, zero

    sequence capacitance can be high if considerable lengths are involved.

  • 8/13/2019 Ground Reference Transformer Sizing

    5/5

    As a general rule, the following approximate capacitance values could be used:

    Transformer C0 = 0.01 µF/transformer

    Overhead line C0 = 0.00625 µF/ km

    Note: the given admittance of collector system, i.e. YC =170.5 micro-mho does not seem reliable;

    however it meets the above mentioned requirement.

    It is recommended to verify the line-to-ground capacitive reactance of the collector system

    based on the formulas given above.

    Mehrdad Boloorchi, P.Eng.

    Associate, Senior Systems Engineer