VFC LEVEL 112' - 7 1/2"

VFC LEVEL 223' - 8 1/2"

VFC LEVEL 334' - 5 1/2"

123456789101112131415

T.O. MECH53' - 3 1/2"

CONCOURSE LEVEL16' - 3 1/2"

6.4 3.5

A201

1

A201

2

6.11617 0.9

114114

VFC LEVEL 112' - 7 1/2"

VFC LEVEL 223' - 8 1/2"

VFC LEVEL 334' - 5 1/2"

VFC BASEMENT1' - 6 1/2"

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

T.O. MECH53' - 3 1/2"

FIELD LEVEL0' - 0"

CONCOURSE LEVEL16' - 3 1/2"

A202

1

A202

2

16 170.9

Copyright HNTB 2015

23456789101112131415

A

B

C

D

E

F

G

H

J

K

L

M

N

P

Q

R

DRAWN BY

PROJECT NO.

CHECKED BY

APPROVED BY

ISSUED FOR:

...

...

...

SHEET TITLE & NUMBER

HNTB Oregon Architecture, P.C.HNTB Oregon Architecture, P.C.HNTB Oregon Architecture, P.C.HNTB Oregon Architecture, P.C.

One Bunker Hill601 West Fifth Street, Suite 1000Los Angeles, CA 90071(213) 403-1000 / Fax (213) 403-1001

1

OR

EG

ON

ST

AT

E U

NIV

ER

SIT

YC

OR

VA

LLI

S, O

RE

GO

N

DATE

STRUCTURAL:KPFF Consulting Engineers111 SW Fifth Avenue, Suite 2500Portland, OR 97204PH (503) 227-3251/FAX (503) 227-7980

CIVIL:KPFF Consulting Engineers111 SW Fifth Avenue, Suite 2500Portland, OR 97204PH (503) 542-3251/FAX (503) 274-4681

LANDSCAPE:Mayer / Reed319 SW Washington Street, Suite 820Portland, OR 97204PH (503) 223-5953/FAX (503) 223-8076

SIGNAGE & GRAPHIC:Mayer / Reed319 SW Washington Street, Suite 820Portland, OR 97204PH (503) 223-5953/FAX (503) 223-8076

MECHANICAL & PLUMBING:Systems West Engineers411 High StreetEugene, OR 97401PH (541) 342-7210/FAX (541) 342-7220

ELECTRICAL & LIGHTING:Stantec733 SW Oak Street, Suite 200Portland, OR 97205PH (503) 273-0064

FIRE PROTECTION & CODE:FP&C Consultants inc.One Ward Parkway, Suite 200Kansas City, MO 64112PH (816) 931-3377/FAX (816) 931-3378

SOUND/ AV/ TEL:WJHW3424 Midcourt Rd, Suite 124Carrollton, TX 75006PH (972) 934-3700/FAX (972) 934-3720

ELEVATOR CONSULTING:ECS15600 NE 8th Street, Suite B1, PMB 148Bellevue, WA 98008PH (425) 957-4641

OVERALL BUILDINGELEVATIONS -

NORTH & SOUTH

A200

60562

12.09.2015

PKG-3 NORTH END ZONE & VFCRENOVATION

PKG-3 NORTH END

ZONE & VFC

RENOVATION

12.0

9.20

15P

KG

-3 N

OR

TH

EN

D Z

ON

E &

VF

C R

EN

OV

AT

ION

VA

LLE

Y F

OO

TB

ALL

CE

NT

ER

/N

OR

TH

EN

D Z

ON

E R

EN

OV

AT

ION

1/16" = 1'-0"A200

1 NORTH ELEVATION

1/16" = 1'-0"A200

2 SOUTH ELEVATION

1 3 5 7 10 1513

A

C

E

G

H

J

KEY PLAN

1

2

REFERENCE KEYNOTE

SPEC.# DESCRIPTION

SHEET NOTES

114 NORTH ENTRANCE ARCH, STRUCT,& M.E.P. SCOPEWILL BE ISSUED AS PART OF PKG-5 - NORTHENTRANCE.

# DATE DESCRIPTION

Page 4: Gill and Reser Building Drawings - Oregon State University

VFC LEVEL 112' - 7 1/2"

VFC LEVEL 223' - 8 1/2"

VFC LEVEL 334' - 5 1/2"

VFC BASEMENT1' - 6 1/2"

1 2 3 4 5 6 7

T.O. MECH53' - 3 1/2"

FIELD LEVEL0' - 0"

CONCOURSE LEVEL16' - 3 1/2"

6.43.5

FIELD PADDING ON CONCRETEWALL AT PERIMETER TYP.

EXISTING WALL FINISH TO BEPAINTED : ADD ALTERNATE 4SEE SHEET G001

LOWER BOWL SEATING

18' -

10"

10' -

9"

11' -

1"

11' -

1"

1' -

6 9

/16"

53' -

3 9

/16"

136' - 0"

24' - 0" 28' - 0" 12' - 6" 15' - 6" 12' - 0" 20' - 0" 9' - 0" 15' - 0"

LOCKER ROOM-0' - 6"

EXISTING SCOREBOARD

CONCRETE WALL GLASS GUARDRAILSYSTEM W/ 2" DIA. RAIL &1/2" THK. TEMP. GLASSEXPOSED CMU

BURNISHED FINISH

GLASS GUARDRAIL SYSTEMW/ 2" DIA. RAIL & 1/2" THK.TEMP. GLASS

LOCATION OF CAMERAPLATFORM (N.I.C.)

FIELD LIGHT POLES

CENTRIA (OR SIMILAR) INTERCEPTMODULAR METAL PANEL SYSTEM(LIMESTONE COLOR) OVER COLDMETAL STUDS FRAME & RIGIDINSULATION

0.9

VFC LEVEL 112' - 7 1/2"

VFC LEVEL 223' - 8 1/2"

VFC LEVEL 334' - 5 1/2"

VFC BASEMENT1' - 6 1/2"

8 9 10 11 12 13 14 15

T.O. MECH53' - 3 1/2"

FIELD LEVEL0' - 0"

CONCOURSE LEVEL16' - 3 1/2"

7.1

18' -

10"

10' -

9"

11' -

1"

11' -

1"

1' -

6 9

/16"

3' -

7 1

5/16

"

53' -

3 9

/16"

9' - 0" 20' - 0" 12' - 0" 16' - 0" 16' - 0" 24' - 0" 24' - 0" 20' - 0"

EXISTING ROOFING AND FASCIAPANEL TO BE PAINTED A DIFFERENTCOLOR : ADD ALTERNATE 3 SEESHEET G001

FIELD PADDING ON CONCRETE WALLAT PERIMETER TYP.

EXISTING WINDOW TOREMAIN

EXISTING WALL FINISH TO BEPAINTED : ADD ALTERNATE 4SEE SHEET G001

GLASS GUARDRAIL SYSTEMW/ 2" DIA. RAIL & 1/2" THK.TEMP. GLASS

METAL PANEL OVER STUDFRAMING & RIGID INSULATIONTYP.

STOREFRONT GLAZING SYSTEM

EXPOSED CMU WITHBURNISHED FINISH TYP.

CENTRIA (OR SIMILAR) INTERCEPTMODULAR METAL PANEL SYSTEM(LIMESTONE COLOR) OVER COLDFORMED METAL STUDS FRAME FORELEVATOR ENCLOSURE / ADJACENTSTAIR TO BE OPEN

FIELD LIGHT POLE

16 17

METAL WALL PANELS074213

PIPE GUARDRAILS AT BRIDGE. GALV.& PTD. BY METAL STAIRCONTRACTOR

WALL SECTIONS & DETAILS GENERAL NOTES:

1. REFER TO SHEET A___ FOR CURTAIN /STOREFRONT TYPES SCHEULE & GLASS TYPESSCHEDULE

2. THE BRICK MASONRY CONTRACTOR SHALLDESIGN, ENGINEER, FABRICATE, ASSEMBLE ANDINSTALL ALL COMPONENTS OF THE BRICKMASONRY WALL INCLUDING BUT NOT LIMITED TOTHE FULL FACE BRICK TIES, LEDGER/RELIEFANGLES AS SPECIFIED PER SECTION 01 62 11 -DELEGATED DESIGN REQUIREMENTS.

3. THE CONTRACTOR SHALL ENGINEER ANDINSTALL METAL FRAMING AS SPECIFIED IN THEDELEGATED DESIGN REQUIREMENTS OFSPECIFCATIONS.

4. ALL EXTERIOR EXPOSED STRUCTURAL AND NONSTRUCTURAL METAL FRAMING SHALL HAVE PAINTFINISH.

Copyright HNTB 2015

23456789101112131415

A

B

C

D

E

F

G

H

J

K

L

M

N

P

Q

R

DRAWN BY

PROJECT NO.

CHECKED BY

APPROVED BY

ISSUED FOR:

...

...

...

SHEET TITLE & NUMBER

HNTB Oregon Architecture, P.C.HNTB Oregon Architecture, P.C.HNTB Oregon Architecture, P.C.HNTB Oregon Architecture, P.C.

One Bunker Hill601 West Fifth Street, Suite 1000Los Angeles, CA 90071(213) 403-1000 / Fax (213) 403-1001

1

OR

EG

ON

ST

AT

E U

NIV

ER

SIT

YC

OR

VA

LLI

S, O

RE

GO

N

DATE

STRUCTURAL:KPFF Consulting Engineers111 SW Fifth Avenue, Suite 2500Portland, OR 97204PH (503) 227-3251/FAX (503) 227-7980

CIVIL:KPFF Consulting Engineers111 SW Fifth Avenue, Suite 2500Portland, OR 97204PH (503) 542-3251/FAX (503) 274-4681

LANDSCAPE:Mayer / Reed319 SW Washington Street, Suite 820Portland, OR 97204PH (503) 223-5953/FAX (503) 223-8076

SIGNAGE & GRAPHIC:Mayer / Reed319 SW Washington Street, Suite 820Portland, OR 97204PH (503) 223-5953/FAX (503) 223-8076

MECHANICAL & PLUMBING:Systems West Engineers411 High StreetEugene, OR 97401PH (541) 342-7210/FAX (541) 342-7220

ELECTRICAL & LIGHTING:Stantec733 SW Oak Street, Suite 200Portland, OR 97205PH (503) 273-0064

FIRE PROTECTION & CODE:FP&C Consultants inc.One Ward Parkway, Suite 200Kansas City, MO 64112PH (816) 931-3377/FAX (816) 931-3378

SOUND/ AV/ TEL:WJHW3424 Midcourt Rd, Suite 124Carrollton, TX 75006PH (972) 934-3700/FAX (972) 934-3720

ELEVATOR CONSULTING:ECS15600 NE 8th Street, Suite B1, PMB 148Bellevue, WA 98008PH (425) 957-4641

ENLARGEDELEVATION -

SOUTH

A202

60562

12.09.2015

PKG-3 NORTH END ZONE & VFCRENOVATION

PKG-3 NORTH END

ZONE & VFC

RENOVATION

12.0

9.20

15P

KG

-3 N

OR

TH

EN

D Z

ON

E &

VF

C R

EN

OV

AT

ION

VA

LLE

Y F

OO

TB

ALL

CE

NT

ER

/N

OR

TH

EN

D Z

ON

E R

EN

OV

AT

ION

1 3 5 7 10 1513

A

C

E

G

H

J

KEY PLAN

1/8" = 1'-0"A202

2 SOUTH ELEVATION

1/8" = 1'-0"A202

1 SOUTH ELEVATION

12

REFERENCE KEYNOTE

SPEC.# DESCRIPTION

074213 METAL WALL PANELS

SHEET NOTES

# DATE DESCRIPTION