GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat panels These instructions must be left on site with the person responsible for the fire alarm system. This publication covers the: GENT range XEN1, XEN2, XEN4 and XEN8 fire alarm control panels. GENT XEN RPT fire alarm repeat panel. Design and installation Specifications 2 System design 5 Cables 8 Notes to the Installer 9 Panel fixing 10 Commissioning Commissioning 13 Installed system tests 14 Access levels 2 & 3 15 System test functions 16 Panel configuration functions 17 Operation User responsibility 19 Fault indications 21 Operating instructions 23 Parts list 25 Figure 1 Fire alarm control / repeat panel cdm64 4188-410 Issue 1 1 8/97

Upload: others

Post on 15-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

GENT Xenex range of

1,2,4 and 8 zone fire Control and Repeat panels

These instructions mustbe left on site with theperson responsible forthe fire alarm system.

This publication covers the:

GENT range XEN1, XEN2,XEN4 and XEN8 fire alarm control panels.

GENT XEN RPT fire alarm repeat panel.

Design and installationSpecifications 2

System design 5

Cables 8

Notes to the Installer 9

Panel fixing 10

CommissioningCommissioning 13

Installed system tests 14

Access levels 2 & 3 15

System test functions 16

Panel configuration functions 17

OperationUser responsibility 19

Fault indications 21

Operating instructions 23

Parts list 25

Figure 1 Fire alarm control / repeat panelcdm64

4188-410 Issue 1 1 8/97

Page 2: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Specification for the Control panelUK Model No. (with batteries) XEN1 XEN2 XEN4 XEN8

Number of Zone (detection) circuits 1 - Zone 2 - Zone 4 - Zone 8 - Zone

Zone circuit load (maximum) 2mA per zone

Number of Sounder circuits 2 2 4 8

Sounder circuit (shared load) 1A at 24V d.c. nominal 1.5A at 24V d.c. nominal

End-of-line unit Zone circuit: Capacitor (diode) unit Sounder circuit: 22K ohms resistor

Standards EN54 : Parts 2 & 4

Flush fixing kit 3 3 3 3

Colour Front cover - Grey RAL 7000 (standard)

Assembled panel size (in mm) 395 wide x 274 high x 87 deep

Weight (with batteries) 5.1Kg 5.1Kg 6.6Kg 6.6Kg

Operating temperature and humidity 0 - 40oC low to +95% RH non condensing

Storage temperature and humidity -5oC to +50oC low to +95% RH condensing

Approvals LPCB approval to be acquired

Emission BS EN50081-1:1992: Part 1 Residential, Commercial & Light industry Class B limits

Immunity BS EN50130-4: 1995: Part 4 Alarm systems : Electromagnetic compatibilityProduct family standard: Immunity requirements for components of fire, intruder

and social alarm systems

IP rating (BS5490) IP31 (indoor)

Mains operating voltage 230V ac +10% -6% 50Hz

Knock-In cable entry points 13 - top & 13 - back

Terminal size 2.5mm2 maximum

Battery supply (sealed lead acid) 2-off12V 2.1Ah 2-off12V 2.8Ah

Battery standby with 1mA load perzone and 1A total sounder alarm load 72hr standby plus 0.5hr with alarm load

Auxiliary contacts(operates with fire)

Pair of normally closed (NC) and a pair of normally open (NO) contacts rated1A @ 24V dc resistive load (Maximum 100m cable distance)

Common Fault Open collector - normally On (with 1K ohms limiting resistor)

Common Fire Open collector - normally Off (with 1K ohms limiting resistor)

Class change Normally open push button, up to 100m cable distance away from the panel

24V Power supply(with foldback current limit)

100mA maximum at 24V d.c. nominal 250mA maximum at 24V d.c. nominal

User access: By means of code entryvia numeric key pad(AL1 Authorised user - No code isrequired)

AL2 Site security 3 digit code - 123AL3 Site engineering 3 digit code - 321

Key pad button controls Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric keypad.

Buzzer for local audible indications Fire & System Fault - continuous sound Fault - intermittent sound (via piezoelectric buzzer operating at 2KHz 70dB(A) at 1m)

Visual indications FIRE & ZONES-fire (Red LEDs ‘lights’)ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power,Access/Function (Yellow LEDs ‘lights’)Power on (Green LED ‘light’)

Repeat panel connections Serial port , see also repeat panel specification

Specifications GENT Xenex fire panels

8/97 2 4188-410 Issue 1

Page 3: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Specification for the Repeat panelUK Model number XEN RPT

Number of Zones 8 - Zone (standard size)

Standard EN54 : Parts 2 & 4

Flush fixing kit 3

Colour Front cover - Grey RAL 7000

Assembled panel size (in mm) 395 wide x 274 high x 87 deep

Weight (with batteries) 5.1Kg

Operating temperature and humidity 0 - 40oC low to +95% RH non condensing

Storage temperature and humidity -5oC to +50oC low to +95% RH condensing

Approvals LPCB approval to be acquired

Emission BS EN50081-1:1992: Part 1 Residential, Commercial & Lightindustry

Class B limits

Immunity BS EN50130-4: 1995: Part 4 Alarm systems : Electromagneticcompatibility Product family standard: Immunity requirements for

components of fire, intruder and social alarm systems

IP rating (BS5490) IP31 (indoor)

Mains operating voltage 230V ac +10% -6% 50Hz

Knock-In cable entry points Top & back entries

Terminal size 2.5mm2 maximum

Battery supply (sealed lead acid) 2-off12V 2.1Ah

Standby duration 72hr standby

User access: By means of code entryvia numeric key pad(AL1 Authorised user - No code isrequired)

AL2 Site security 3 digit code - 123AL3 Site engineering 3 digit code - 321NOTE: Only a limited number of functions are accessible at therepeat panel.

Key pad button controls Sound alarm, Silence alarm, System Reset & Cancel buzzer &numeric keypad.

Buzzer for local audible indications Fire & System Fault - continuous sound Fault - intermittent sound(via piezoelectric buzzer operating at 2KHz 70dB(A) at 1m)

Visual indications FIRE & ZONES-fire (Red LEDs ‘lights’)ZONES-fault, Fault, System, Power, Earth, Sounder, Disable,Test, Power, Access/Function (Yellow LEDs ‘lights’)Power on (Green LED ‘light’)

Repeat panel (standard 8 zone) A maximum of up to 6 repeat panels connected in series to thecontrol panel

Repeat panel connections Serial port

GENT Xenex fire panels Specifications

4188-410 Issue 1 3 8/97

Page 4: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Zone circuit products (24Vdc) See control panel specification for zone circuit loading.

Part number Product Operating voltage Quiescentcurrent

Alarmcurrent

17640-01 Optical smoke detector

16V dc to 32Vdc

90uA10mA

Maximumcan be

upto 65mAlimited bythe control

panel

17630-01 Ionisation smoke detector 50uA

17650-01 Fixed temperature heat detector 45uA

17660-01 Rate of rise heat detector 45uA

17670-01 High temperature heat detector 90uA

17615-01 Duct detector 90uA

17906-49 Remote external LED for detector -

07011-31 Beam detector see note

14112-08 Manual call point (surface) 470R n/a As perdetectors14112-18 Manual call point (flush) 470R n/a

NOTE: If the beam detector is used then it must be powered from an external power supply.

Sounder circuit products (24Vdc) See control panel specification sounder circuit loading.

Part number Product Alarm current

12511-37 Electronic sounder (red) 20mA

12511-52 Electronic sounder (grey) 20mA

12141-04 Electronic bell (red) IP40 30mA

12141-54 Electronic bell (grey) IP40 30mA

02601-31 Sounder 18mA

02300-01 Xenon flasher (red) 125mA

02300-01 Xenon beacon (red) 45mA

Door holders

NOTE: The door holder circuit should be controlled by the control panel’s auxiliary contacts, using externalpower supply.

Part number Product Current

04390-31 Door holder (24Vdc) 22mA

04390-55 Door holder (240Vac) 17.5mA

Specifications GENT Xenex fire panels

8/97 4 4188-410 Issue 1

Page 5: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

System designThe design of the fire detectionand alarm system should be to BS 5839:Part 1:1988 Code ofPractice for system designinstallation and servicing.Supplemented with customerrequirements.

Mains Supply Connection

The mains supply to the controlpanel should be via a fused spurunit rated: 5A for 1 & 2 Zone panel7A for 4 & 8 Zone panel

Standby Supply

With the recommended batterythe control panel will provide astandby supply under mainsfailure conditions, for a period of72 hours followed by 30 minutesof alarm load, see specification.

24V supply

The power supply terminals ‘24+and 0’ may drive external ancillaryequipment and is designed to beused in conjunction with auxiliarycontacts and common fire andfault outputs, see control panelspecification.

NOTE: The use of the 24Vsupply will affect the panelstandby capability.

Figure 2 System schematiccdm65

GENT Xenex fire panels System design

4188-410 Issue 1 5 8/97

Page 6: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Fire Detection (Zone Circuits)See parts list for compatible parts.

Each zone circuit can have up to2mA load. An end-of-linecapacitor unit is required for zonecircuit monitoring, which must befitted after the last detector ormanual call point on the circuit.All manual call points usedmust have a 470 ohms seriesresistor.

NOTE: If a Beam detector isused, then it must be poweredfrom an independent supply.

Where a zone circuit is not beingused, the end-of-line capacitorunit must be fitted across itsterminals in the panel.

Alarm (Sounder circuits)

NOTE: All sounder circuits(sectors) will always operatetogether in the event of a firecondition.

See parts list for compatible parts.

To comply with the requirementsof BS 5839: Part 1:1988, aminimum of two alarm soundercircuits should be used on allinstallations.

1 & 2 ZonePanel

4 & 8 ZonePanel

1A maximumAlarm sounderload per panel

1.5A maximumAlarm sounderload per panel

The load must be shared betweenthe sounder circuits.

The alarm sounder circuits areregularly pulse monitored forfailure. It is important that the lastalarm sounder is fitted with a 22KOhm end-of-line resistor.

Where a sounder circuit is notbeing used, the end-of-lineresistor must be fitted across itsterminals in the control panel.

Figure 3 Zone circuit connectionscdm68

Figure 4 Alarm sounder connectionscdm67

System design GENT Xenex fire panels

8/97 6 4188-410 Issue 1

Page 7: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Auxiliary ContactsThese are normally open (NO)and normally closed (NC)contacts that switch over whenthe panel goes into a fire condition.

The contacts are rated at 24V d.c.1A for a resistive load and shouldnot be used to switch voltages inexcess of 50V.

The auxiliary circuits should bepowered from an independentpower supply.

Class ChangeA pair of unmonitored terminalsallow only the system alarmsounders to be actuated from aremote position. It is consideredthat the major use for these will befor class change functions inschools and colleges.

NOTE: There is no indicationat the panel of class changepush button operation.

Common Fire and faultThe common fault output is anormally closed electronic switch,which opens with a fault condition,this is for a fail safe operation.

The common fire output isnormally open electronic switchthat closes with a fire condition.

NOTE: Each electronic switchhas an in-line 1K ohms resistor.

The +24V & 0V is a power supplyfor use with auxiliary contacts,common fire and common faultcircuits, see specification.

Repeat PanelThere can be up to 6 repeatpanels series connected from thecontrol panel. A repeat panelduplicates fire and faultindications together with systemcontrols.

Figure 5 Auxiliary contact circuitcdm72

Figure 6 Class change circuitcdm73

Figure 7 Fire fault & 24V outputscdm74

Figure 8 Control to repeat panel connectionscdm75

GENT Xenex fire panels System design

4188-410 Issue 1 7 8/97

Page 8: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

CablesFor the wiring of:

The guidance of BS5839 : Part 1: 1988 should befollowed.

The use of cables, such as (MICCor Belden) are recommended.

Generally available electricalinstallation cable may be used,providing the cable is:

to BS6387

with no more than 2 - cores

each core having no less than1.5mm2 cross section area

with an inherent or through metal conduit screen for earthcontinuity in order to produceelectrical protection and screening

having protection from heat andmechanical damage

Power supply cord

This should be a 3-core cordhaving a rated current of:

5A with a nominal core cross sectional area of 0.75mm2 provided the length of the corddoes not exceed 2m.

Length per circuit Type of circuit Recommended cables, also see BS5839:Part 1 guidance

2m Mains power supply cord see power supply cord

1Km Zone circuit

See BS5839:Part 1 guidance1Km Sounders circuit

100m Auxiliary circuit

100m Common fire and fault circuit

100m Class change circuit

500m Repeat panel link Belden type screened 2-core twisted pair

Figure 9 Panel cable entry and earth pointscdm158

Cables GENT Xenex fire panels

4188-410 Issue 1 8 8/97

Page 9: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Notes to the installerChecks

The power-up and commissioning is done by theservicing organisation.

The wires between the termination point and terminalsshould be short and straightas possible.

The cables of the fire detectionand alarm system and othersystems should usually beseparated by at least 160mm,unless dedicated conduit orducting is used.

Do not use any part of buildingstructure for earthing.

The cable length between theRepeat LED unit and respectivefire detector where used ,should not exceed 10m

Cable Glands should be usedon the equipment for the mainssupply cable.

Unused knockouts on productenclosure that have been removed, should not be leftopen.

Requirements

It is recommended that theinstaller follow the generalrequirements of:

• BS5839:Part 1:1988, which isthe code of practice relating tothe fire detection and alarmsystems for buildings.

• the relevant parts of the BS7671 Requirements forElectrical Installation Institute ofElectrical Engineers WiringRegulations 16th edition.

Second fix installation

To prevent the possibility ofdamage or dirt degrading theperformance or appearance of theSystem products:

the installation of second fix itemsshould be delayed until all majorbuilding work in the area iscomplete.

Fixtures and fittings

It is the installers responsibility toprovide:

• adequate fixtures and fittingsfor the type of constructionsurface onto which a productis to be installed.

• as an aid to this decision, theweight and overall size ofeach full assembly togetherwith implications on cableentries and routing should betaken into consideration.

NOTE: All these proceduresassume that the cable, gland,steel box (BESA box) andother related accessories areprovided by the installer.

As fitted wiring drawings

The installer should acquire:

• site specific information fromthe interested parties, fordetails on the location ofproducts for installation

• the acquired informationtogether with this guide andthe relevant standards shouldbe used to assist the work.

Earth continuity

To maintain earth continuity, thecable screen must be continuedthrough each system device,whether the earth is connected toa device or not.

GENT Xenex fire panels Notes to the installer

8/97 9 4188-410 Issue 1

Page 10: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Panel fixinga) Remove panel from its

packing, but retain the cartonfor storage of spare parts andloose items.

b) Remove the top and bottominner plates, see Figure 10.

c) Check the spares partssupplied with those listed inTable 1. If replacement partsare required at any time, onlyspares that are of the samespecification should be used.

d) Remove the transformer andearth connections from theelectronic assembly, and thenremove the electronicassembly from the panel, see Figure 11. Store the electronicassembly in a safe place untilrequired.

e) Remove the appropriateknock-in on the panel case forcable entry.

f) Hold the panel on the wall inthe desired mounting positionand mark the positions of thefixing holes. See Figure 11 forcase fixing details.

g) Secure the panel to the wallusing suitable fixing such thatadequate support is providedto the control panel assembly.A top centre keyhole fixing isprovided on the case to allowthe panel to be hooked whilstthe bottom two fixing pointsare located.

h) Connect the mains supplycable to the panel.The cable:

• must be through one of thededicated cable entry into thepanel

• via an unswitched fusedspur unit, rated 5A for the1&2 Zone Control and Repeatpanels and 7A for 4&8 Zonepanels.

The fused spur isolator covershould be red and marked:FIRE ALARM - DO NOT SWITCHOFF

The fused spur units must befed from a dedicated switch orprotective device at the localmains supply distributionboard.

DescriptionFor fuses alsosee Figure 12

Quantity supplied with controlpanel

Repeatpanel

1 -zone

2 -zone

4 -zone

8 -zone

8 - zoneonly

22K end-of-line resistor 2 2 4 8

Capacitor unit 1 2 4 8

End-of-line label 3 4 8 16

Fuse 5A 20mm x 5mm AS (mains terminal block)

1 1

Fuse 3.15A 20mm x 5mmAS (mains terminal blockand power 1 & 2 - F1 &F2)

2 2 2 2 2

Fuse 5A 20mm x 5mm QB(battery F3)

1 1 1 1 1

Fuse 0.5A 20mm x 5mm QB(sector)

2 2 2 2

Fuse 0.16A 20mm x 5mmQB (sector)

2 6

Battery link 1 1 1 1 1

Zone designation label 1 1 1 1 1

Table 1 Spare parts supplied with each panel

Figure 10 How to remove the outer coverscdm77

Panel fixing GENT Xenex fire panels

4188-410 Issue 1 10 8/97

Page 11: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

i) Wire the system. With theexception of mains cable, allother cables should remainunconnected at the panel.

For the unconnected cableleave 300mm tail wire lengthand mark each core identifyingits final point of connection.

The system wiring can betested whilst not connected tothe respective terminals ateach system equipment.

CAUTION: DO NOTundertake high voltageinsulation tests WITH THECABLES CONNECTED totheir terminals. Such a testmay damage the electroniccircuitry in the systemequipment.

j) Refit the electronic assemblyinto the panel and connect thetransformer and earth cablespreviously removed, see Figure 11.

NOTE: Each terminal in apanel will accept a maximumconductor size of 2.5mmsquare.

NOTE: The installation of alloutstanding parts are usuallycarried out duringCommissioning of the System.

Store all spare parts and loosecomponents including thebatteries inside the panelcarton and keep in a safeplace until required.

Figure 11 Panel fixingscdm69

GENT Xenex fire panels Panel fixing

8/97 11 4188-410 Issue 1

Page 12: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Figure 12 Panel terminals and fusescdm70

Panel fixing GENT Xenex fire panels

4188-410 Issue 1 12 8/97

Page 13: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

CommissioningThe total system should be testedin accordance with thecommissioning requirements ofBS5839:Part 1:1988 or otherstandard specified by the systempurchaser.

NOTE: The commissioningprocedures assume that thesystem has been installed asper instructions in this booklet.

System checksAcquire as fitted drawings

check the system has been in-stalled to the project require-ments.

if appropriate, action the in-staller to carry out changes tothe system.

Initial power upa) Disconnect cables to terminals

of zone, sounder, classchange, auxiliary, common fireand fault circuits. Ensure eachcable is marked forreconnection to respectiveterminals later.

b) Connect end-of-line units tozones and sounder circuits forinitial power up.

c) Check mains connection andswitch on the mains power tothe control panel.

d) Now connect the batterysupply, see Figure 13.

e) Check the panel provides anormal healthy indication, withthe green light lit.

Zone circuit testsa) Transfer the end-of-line

capacitor unit to the last device(detector or manual call point)on a zone circuit.

b) Connect the zone cable to thezone circuit terminals.

c) Carry out zone open circuitand short circuit tests andcheck appropriate indicationsare given.

d) Repeat the above for otherzone circuits.

Sounder circuit testsa) Transfer the end-of-line

resistor unit to the last deviceon a sounder circuit.

b) Connect the sounder circuitcable to the sounder circuitterminals.

c) Carry out sounder open andshort circuit tests and checkappropriate indications aregiven.

d) Repeat the above for othersounder circuits.

Figure 13 Battery installationcdm71

GENT Xenex fire panels Commissioning

4188-410 Issue 1 13 8/97

Page 14: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Installed system testsThe fire detection and alarmsystem should be tested to ensureit operates to meet the standardsand project requirements.

Configuration

The control and repeat panels arefactory set to the requirements of EN54 Parts 2 and 4.

The operation of the control andrepeat panels and the systemmay be re-configured to sitespecific needs, see system testfunctions and Panel configurationfunctions.

CAUTION: Any specialconfigurations may cause thesystem and equipment tooperate outside therequirements of Europeanstandards.

Test mode A or B operationTo facilitate tests on the firedetection and alarm system thecontrol panel can be set tooperate in a test mode, seeSystem test functions.

With Test mode A or B active: atriggered manual call point or firedetector in the test zone will give:

NOTE: A detector that is stillfull of smoke or heat willretrigger into a fire conditionuntil the smoke or heat in thearea is cleared.

Repeat panel configuration

There can be up to 6 repeatpanels connected in series to thethe control panel.

Each repeat panel connected tothe system is required to be givenan address at both the controland repeat panels, see Panelconfiguration section.

Sound level test

Sound level tests should beconducted to standardrequirements and to customersatisfaction.

Other equipment tests

Where external equipment isconnected to the control panelusing auxiliary, common fire andfault terminals, then these mustbe tested to project requirements.

Zone designation labela) Write on to the zone

designation label the namethat identifies the areaprotected by each zone circuit.

b) Fix the label over the zonedesignation part of the lowerinner plate, see figure 13.

Log book

Fill in system details on the firstthree pages of the log book.

On completion

Ensure the persons responsiblefor the system are made aware of

• system operation

• access codes to controls

• basic controls

• their responsibility

• and the need to log systemevents in the log book.

Test A Test B

Fireindication for 10 secondsdurationfollowed by asystem reset

System alarmsounds for thefirst 2 secondsand at the sametime a Fireindication isgiven for 10 secondsdurationfollowed by asystem reset

Table 2 Test mode operation

Installed system tests GENT Xenex fire panels

8/97 14 4188-410 Issue 1

Page 15: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Access levels 2 and 3The control and repeat panelsprovides system security bycoded password entry to controls.

There are three coded accesslevels to user controls, also see Table 3.

Access level 1 (AL1) is for authorised user.

Access level 2 (AL2) is for site security.

Access level 3 (AL3) is for site engineer.

Access codesThe factory set codes for:

AL1 - No code required

AL2 - is 123 (default)

AL3 - is 321 (default)

The AL2 and AL3 are 3-digitcodes.

NOTE: The standard AL2 andAL3 access codes are factoryset. These codes may bechanged to user defined codes.

Access Levels->

What is accessible

AL1 AL2Code:*123

AL3Code:*321

Cancel buzzer (fire and fault) *3­ 3 3

System Reset 3 3

Sound alarms 3* 3*

Silence alarms 3 3

Disable / Enable sounders 3 3

Disable / Enable zone(s) 3 3

Zone(s) only Test A *3¬ 3

Zone(s) with sounders Test B *3¬ 3

Cancel Test A / Test B *3¬ 3

Display test *3­ 3 3

All indications 3 3 3

Zone designations (located behind lower cover) 3 3 3

Instructions (located behind lower cover) 3 3 3

Change to AL2 and AL3 user password 3

Repeat panel address 3

A Shaded option is not applicable to the repeat panel.

¬ This option may be moved to AL3, see Panel configuration section­ This option may be moved to AL2, see Panel configuration section* factory setting

Table 3 Controls accessible at various user levels

GENT Xenex fire panels Access levels 2 and 3

4188-410 Issue 1 15 8/97

Page 16: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

System test functionsTo ease the testing of the systemit is necessary to gain access tosome of these functions.

NOTE: It is only necessary toenter the access code once,provided the 2 minute timeoutis not exceeded betweenbutton presses.

Access code

AL2 Code : 123 may be usedto gain access to the testfunctions. Depending on how thesystem is configured it may benecessary to use AL3 code321instead of AL2 code.

The factory set AL2 and AL3codes are 123 and 321respectively on first power-up. Ifthe codes are changed at anytime then the power-up codes arenot applicable.

NOTE: It is important to leavethe system in a normaloperating condition oncompletion of commissioning.

How to Controls Result

How to do a Display test Enter the 3 digit code then:

press shift and display buttons

All indicators are lit (flashingindication for zone fire/fault) andthe buzzer sounds for 10 secondsduration

How to set the panelto operate Test mode A

Enter the 3 digit code then:

press ③ and the respective zone ➀ - ➇

This will allow the zone circuit(s) tobe tested without an alarm of fire.

How to set the panelto operate Test mode B

Enter the 3 digit code then:

Press ➃ and the respective zone ➀ - ➇

This will allow the zone circuit(s) tobe tested with 2 second alarm offire.

How to Cancel Testmode A/B Enter the 3 digit code then:

Press ➄ and the respective zone ➀ - ➇

This will cancel any active Testmode, either A or B.

How to Disable azone Enter the 3 digit code then:

Press ➀ and the respective zone ➀ - ➇

A fired detector in disabled zone(s)will not cause the panel to go into afire condition.

How to Enable azone Enter the 3 digit code then:

Press ➁ and the respective zone ➀ - ➇

This will re-enable all previouslydisabled zone circuit(s).

How to Disablesounders Enter the 3 digit code then:

Press ➀ and followed by

This will disable the Soundercircuits operation.

How to Enablesounders Enter the 3 digit code then:

Press ➁ and

This will re-enable previouslydisabled sounder circuits.

How to change AL2 password Enter the AL3 3-digit code

then: Press ➈ ➀ followed by the new

3-digit code and

This will allow a previous AL2password to be changed to a new3-digit code

How to change AL3password Enter the AL3 3-digit code

then press ➈ ➁ followed by the new

3-digit code and

This will allow a previous AL3password to be changed to a new3-digit code

How to exit from AL2,AL3 or AL4 to AL1 Press This will exit the current access

level and return to AL1

System test functions GENT Xenex fire panels

4188-410 Issue 1 16 8/97

Page 17: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Panel configuration functionsTo ease the commissioning of thesystem it is necessary to gainaccess to some of these functions.

NOTE: It is only necessary toenter the access code once,provided the 2 minute timeoutis not exceeded betweenbutton presses.

Access code

AL3 Code : 321 may be usedto gain access to thesecommissioning functions.

The AL3 code is: 321 on firstpower-up. If the code is changedat any time then the power-upcode is not applicable.

NOTE: It is important to leavethe system in a normaloperating condition oncompletion of commissioning.

How to: Controls Result Factorydefault

How to terminate theEEPROM programmingmode

Press Shift followed by ➈ This will terminate theprogramming mode at anystage, and return theEEPROM to a protectedstate.

How to set a repeatpanel address at thecontrol panel

There can be up to 6repeat panels in asystem.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➇ and the repeat panel

address ➀ and then .

At the Control panellocation 038 an entry ismade of the first repeatpanel address 001

Depending on the numberof repeat panels used,similarly at locations 039,040, 041, 042 and 043enteries are made of the2nd, 3rd, 4th, 5th and 6threpeat panel addresses,which may be 002, 003,004, 005 and 006respectively.

Repeatpaneladdressis 000

How to set a repeatpanel address at therepeat panel

There can be up to 6repeat panels in asystem.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➇ and repeat panel

address ➀ and .

At the Repeat panellocation 038 an entry ismade of the repeat paneladdress, in this case it is001. Other repeat panelscan be given an addressfrom the range 002 to006, which must beentered in location 038..

Repeatpaneladdressis 001

How to move ‘Cancelbuzzer’ from accesslevel AL1 to AL2

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➁,and data ➀ and .

This will move the Cancelbuzzer button access tolevel 2.

How to move ‘Cancelbuzzer’ from accesslevel AL2 to AL1

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➁, and data

and .

This will move the ‘Cancelbuzzer’ button access tolevel 1.

GENT Xenex fire panels Panel configuration functions

4188-410 Issue 1 17 8/97

Page 18: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

How to: Controls Result Factorydefault

How to move ‘Test A&B’and Cancel Test fromaccess level AL3 to AL2

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➃, and data

➀ and .

This action will move the‘Test A&B and Canceltest’ functions from AL3 toAL2.

How to move ‘Test A&B’and Cancel test fromAL2 to AL3

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➃, and data

and .

This action will move the‘Test A&B and Canceltest’ functions from AL2 toAL3.

How to set the mostrecent fire as a steadyindication.

Enter the AL3 3-digit code

then: Press ➈

followed by location ➂➄, data

and .

This will result in the mostrecent fire being displayedas a steady indication.

How to set the mostrecent fire as a pulsingindication.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➄, data

➀ and .

This will result in the mostrecent fire being displayedas a pulsing indication.

How to set the auxiliaryrelay to operate(energise) with soundalarms.

Enter the AL3 3-digit code

then: Press ➈

followed by location ➂➆ data

➀ and .

This will result in theauxiliary relay activationwith sounders.

How to set the auxiliaryrelay to operate(energise) with firecondition.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➆ data

and .

This will result in theauxiliary relay activationwith a fire condition.

How to move ‘Displaytest’ from access levelAL2 to AL1.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➂ data

➀ and .

This will move the ‘Displaytest’ button access to AL1.

How to move ‘Displaytest’ from access levelAL1 to AL2.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➂ data

and ..

This will move the ‘Displaytest’ button access to AL2.

Panel configuration functions GENT Xenex fire panels

19/8/97 18 4188-410 Issue 1

Page 19: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

User ResponsibilityIt is recommended that thepersons responsible for the firealarm system, should becomefamiliar with the procedures onhow to operate the controls andinterpret indications given at thecontrol and repeat panels.Adequate training should alsohave been given from appointedpersonnel.

DailyThe British Standard code ofpractice for Fire detection andalarm systems for buildings, BS 5839:Part1:1988, states thatthe system should be inspecteddaily to ensure that a normalindication is given at the controland indicating equipment and thatany previously indicated faultcondition has receivedappropriate attention.

a) It recommends entry into theLog Book provided of all thesystem events for futurereference.

b) The person inspecting theprotected premises can ensurethat the use of the area(s)inspected has not changedsuch that the detection andalarm devices have becomeinappropriate.

c) The area(s) can be inspectedto check that no unsafepractices that could lead to fireare being undertaken.

WeeklyAt Weekly intervals a differentFire detector or Manual CallPoint of the system should betested to ensure the system iscapable of operating under alarmcondition.

a) The operation of the alarmsounders should be checked,which also provides a regularreminder to those occupyingthe premises that there is a firealarm system with a particularcharacteristic sound.

b) The test should be performedat a regular time to avoidconfusion between a test anda genuine fire alarm.

QuarterlyAt quarterly intervals the systemshould be inspected and any worknecessary should be performedby trained maintenance engineer.

Battery Replacement

NOTE: Any servicing work onthe System must be carriedout by servicing organisation.

Under normal operatingconditions the maintenance freelead acid batteries in the Controland Repeat panels can have auseful life of up to 5 years fromthe date of manufacture.

NOTE: It is recommended thatthese batteries are replaced at4 Yearly intervals from thedate the System is firstcommissioned.

User Responsibility GENT Xenex fire panels

4188-410 Issue 1 19 8/97

Page 20: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Testing a Manual Call PointPush the test key through the holein the underside of the call point toengage the test cam mechanismand push to operate the cammechanism.

At this point the test key isretained in the call point andpulling it out will reset the glass.

NOTE: The alarm sounders inthe system will be activated bythis test. To silence alarmsand reset the system, seeoperating instructions.

Replacing a broken Glass

WARNING: Takeappropriate precautionswhen clearing broken glassto prevent injury.

NOTE: A weather resistantversion of manual call pointswill have two gaskets, aCover/glass gasket and aSpacer/cover gasket, whichmust be installed in theirrespective position.

These procedures assume thecover on the manual call point isopen and any broken glass hasbeen cleared.

a) Feed the glass upward to pushthe cams down and fit underslider, locate bottom of glassinto recess.

b) Hold the bottom of glass inposition and rotate thethumbwheel quadrant to raisethe top of the glass.

c) Fit the call point cover byhooking it into the top of theunit and making sure that theglass is properly seated (helddown) tighten the cover fixingscrew.

Figure 15 Replacing a broken MCP glassemfl216

GENT Xenex fire panels User Responsibility

8/97 20 4188-410 Issue 1

Page 21: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Fault indications

All fault repairs should becarried out by the servicingorganisation.

In a fault condition:

• the common Fault lightis lit

• appropriate fault light isalso lit

• internal Fault Buzzer soundsintermittent tone

• Multiple faults aresimultaneously annunciatedwhen this does not causeconfusion.

NOTE: Normally the fault lightswill be automaticallyextinguished once the faultcondition is rectified.

NOTE: If the system detects afire during a fault condition thefault indicators may beextinguished.

How to silence the faultbuzzer

Press the 3 digit code

if required and

then press Cancel Buzzer .

Notice the buzzer is silencedbut visual indications remainactive.

NOTE: The sounder circuitsare pulse monitored for failure.The monitoring signal is onlyapplied to the circuits for ashort duration at regularintervals.

Figure 14 Fault indicatorscdm95

Faults Cause

What is a Zonefault?

A zone fault occurs when a zone circuit cable is opencircuit or short circuit, or the end-of-line capacitor unithas been disconnected or a detector has beenremoved.

What is aSounder fault?

A sounder fault occurs when a sounder circuit cableis open circuit or short circuit, or the end-of-lineresistor unit has been disconnected.

What is a Mainspower fault?

A mains failure occurs when the mains power supplyto the panel is removed. This can occur on mainsfuse failure or mains supply disconnection.

What is a Batterypower fault?

A battery supply failure occurs when the batterysupply to the panel has failed (due to aging process)or is disconnected or the battery fuse has failed.

What is an Earthfault?

An earth fault occurs when there is an electrical pathfor current flow from the system to earth connections.

What is a Repeatpanel link fault?

A repeat panel link fault occurs when there is acommunication failure between the control andrepeat panels.

What is a SystemFault?

A system fault occurs in the event themicroprocessor failure.

Table 4 Types of faults

Fault indications GENT Xenex fire panels

4188-410 Issue 1 21 8/97

Page 22: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

GENT Xenex fire panels Fault indications

8/97 22 4188-410 Issue 1

Page 23: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Operating instructions

Normal indicationsUnder normal condition the panelshould give a healthy indication,

with only the green Powerlight lit.

The control panel provides systemsecurity by password entry tocontrols.

Fire ConditionIn the event of an automatic firedetection the indications given are:

FIRE light is lit.

Zones-fire light is lit.

buzzer sounds continuous tone.

system alarm sounders are activated

if applicable, auxiliary equip-ment is actuated

if applicable, automatic link tothe Fire Brigade is initiated.

After the emergency is overAfter emergency is over silencethe alarms and reset the system:

a) Enter the 3 digit code

to gain access tothe controls.

b) Press the Silence Alarms

button.

Notice the system alarmsounders are silenced andlocal buzzer soundsintermittent tone.

b) After the cause of the alarmhas been investigated, ensuresmoke and excess heat havehad time to clear fromautomatic detectors andbroken manual call pointglasses have been replacedwhere necessary. Press the

System Reset button.Notice the indications return totheir pre fire status.

Figure 16 Controls and indicationscdm66

Operating instructions GENT Xenex fire panels

4188-410 Issue 1 23 8/97

Page 24: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

To Sound AlarmsTo re-sound the alarm soundersduring a fire condition:

a) Enter the 3 digit code

to gain access tothe controls.

b) Press the Sound Alarms

button. Notice the system alarmSounders are activated.

To Silence AlarmsTo silence system alarm soundersafter they have been actuated:

a) Enter the 3 digit code

to gain access tothe controls.

b) Press the Silence Alarms

button. Notice the system alarmSounders are silenced.

To carry out a lamp testa) Enter the 3 digit code

to gain access tothe controls.

b) Press the ‘shift‘ button and

then the display button. Notice the all indicators are litand the buzzer soundscontinuous for 12 seconds.

Fault ConditionIn the event of an automatic faultdetection the indications given are:

Fault light is lit

fault indicators are lit(except for system fault whichis a contineous sound)

buzzer sounds intermittent.

To Cancel fault buzzera) Enter the 3 digit code

to gain access tothe controls.

b) b) After investigating fault, press

the Buzzer button. Noticethe buzzer is silenced butother indications remain active.

The fault indications arenormally automaticallyextinguished once the faultcondition has been rectified.

Action to rectify faultSuggested action to rectify faultcondition:

NOTE: All fault rectificationwork must be done by theservicing organisation.

The fault indicators may beextinguished during a firecondition.

See commissioning section. Themains failure condition overridesall other fault indications in orderto preserve battery standbycapacity.

GENT Xenex fire panels Operating instructions

8/97 24 4188-410 Issue 1

Page 25: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Parts listXenex Panels

Part number DescriptionXEN1 1 Zone control panel

XEN2 2 Zone control panel

XEN4 4 Zone control panel

XEN8 8 Zone control panel

XENRPT Repeat panel

Fire DetectorsPart number Description17640-01 Optical smoke

17630-01 Ionisation smoke

17650-01 Fixed temperature heat

17660-01 Rate of rise heat

17670-01 High temperature heat

17601-01 Base (BS5839:Part1)

17615-01 Duct detector

07011-31 Beam detector

NOTE: The beam detectorshould be powered from anindependent power supply.

Manual call points (MCP)Part number Description14112-08 Manual call point

(surface)Red 470R

14112-45 Manual call point(surface)Red 470Rc/w cover

14112-08 Manual call point flush (red) 470R

14112-58 Manual call point flush (red) 470Rc/w cover

14112-19 MCP Surface water resistant kit

14112-09 Pack of 10 glasses14115-08 Keyswitch

(red) surface 470R

Parts list GENT Xenex fire panels

4188-410 Issue 1 25 8/97

Page 26: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

14115-18 Keyswitch (red) flush 470R

24Vdc Sound signalsPart number Description12511-37 Electronic sounder (red)

12511-52 Electronic sounder (grey)

12511-19 Water resistant kit for 2511 sounders

12143-04 Electronic bell (red) IP55

12141-54 Electronic bell (Grey)

02601-31 Sounder 6-28V

02300-01 Xenon flahser (red) - 125mA

02300-01 Xenon beacon(red) - 45mA

24Vdc Ancilliary

Part number Description04390-31 Magnetic Door holder

- 22mA

04390-92 Door holder floor plate

04390-99 Door bracket

NOTE: The door holdersshould be powered from anindependent power supply.

AccessoriesPart number Description4015-502 12V 2.1Ah battery

(2-off required for 1 & 2 zone panelplus repeat panel)

4015-509 12V 2.8Ah battery(2-off requiredfor 4 & 8 zone panel)

2534-142 Spares pack for XEN12534-143 Spares pack for XEN22534-144 Spares pack for XEN42534-145 Spares pack for XEN82534-146 Spares pack - XENRPT

.

GENT Xenex fire panels Parts list

8/97 26 4188-410 Issue 1

Page 27: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

NOTES

Parts list GENT Xenex fire panels

4188-410 Issue 1 27 8/97

Page 28: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

NOTES

GENT Xenex fire panels Parts list

8/97 28 4188-410 Issue 1

Page 29: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Log Book

To comply with therequirements of BS5839 : Part 1 : 1988and to allow thoseconcerned with the firedetection and alarmsystems to monitor thelong term performanceof the system, it isimportant that a log iskept which includes allthe events relating tothe performance of thesystem.

SITE ADDRESS____________________________________________________________

____________________________________________________________

____________________________________________________________

GENT Contract No.____________________________________________

Site ID:______________________________________________________

For ServiceNormal Hours Mon-Fri__________________________________________

Tel._________________________________________________________

Outside Normal Hours__________________________________________

Tel._________________________________________________________

Manned Centre Telephone_______________________________________

Manned Centre Code No.________________________________________

Responsible Persons on SITE:____________________________________

A Log of systemevents MUST bekept by theresponsiblepersons on siteand must beavailable at alltimes togetherwith the systemaccess codes.

For each zone record the location description.

Zone number Description of the zonal location

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

Zone 7

Zone 8

AL2 password AL3 password

Log book for 4188-410 Issue 1 1 8/97

Page 30: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

System configuration recordThis information will assist the servicing organisation to keep a record of how the system is configured.

Mark in the table below any deviation(s) from the standard factory settings.

Detection and zone circuit configuration

Zone number 1 2 3 8 5 6 7 8

Normal zone operation (factory setting)

Non latching zone operation

First fire to be a pulsing indication (factory setting) Detection band A (factory setting)

First fire to be a steady indication Detection Band B

Detection Band C

Zone short circuit to give a fault (factory setting)

Zone short circuit to give a fire

Sounders and system reset configuration

Silence alarms and reset to operate independently (factory setting)

Silence alarms and reset to operate as per BS5839: Part 4

Reset to also action the silence alarms

Sound alarms to operate in fire condition only (factory setting)

Sound alarms to operate at any time

Auxiliary relay to energise with fire (factory setting)

Auxiliary relay to energise with sound alarms

Access level

Access levels AL1 AL2 AL3

Cancel buzzer (AL1 - factory setting) N/A

Test A & B mode, Cancel Test (AL2 - factory setting) N/A

Display test (AL1 - factory setting) N/A

Repeat panel information

Repeat panel EEPROMlocation

EEPROMData (address)

Name of the area where the panelis installed on site

1st Repeat panel

2nd Repeat panel

3rd Repeat panel

4th Repeat panel

5th Repeat panel

6th Repeat panel

GENT Xenex fire panels Log book

8/97 2 Log book for 4188-410 Issue 1

Page 31: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Location of system devicesMake copies of this page to record details of the system.This information will assist the servicing organisation to keep a record of how the system is configured.

Zone

Type of system device Location 1 2 3 4 5 6 7 8

Log book GENT Xenex fire panels

Log book for 4188-410 Issue 1 3 8/97

Page 32: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

GENT Xenex fire panels Log book

8/97 4 Log book for 4188-410 Issue 1

Page 33: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

Log book GENT Xenex fire panels

Log book for 4188-410 Issue 1 5 8/97

Page 34: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

GENT Xenex fire panels Log book

8/97 6 Log book for 4188-410 Issue 1

Page 35: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

Log book GENT Xenex fire panels

Log book for 4188-410 Issue 1 7 8/97

Page 36: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

GENT Xenex fire panels Log book

8/97 8 Log book for 4188-410 Issue 1

Page 37: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

Log book GENT Xenex fire panels

Log book for 4188-410 Issue 1 9 8/97

Page 38: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

GENT Xenex fire panels Log book

8/97 10 Log book for 4188-410 Issue 1

Page 39: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

Log book GENT Xenex fire panels

Log book for 4188-410 Issue 1 11 8/97

Page 40: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

GENT SALES & SERVICECENTRES

Head OfficeWaterside RoadHamilton Industrial ParkLeicester, LE5 1TNTelex: 342367Fax: 0116 246 2300Tel: 0116 246 2000

International divisionWaterside Road, Hamilton Ind.Park, Leicester, LE5 1TN, UKTelephone: (44) 116 246 2200Fax: (44) 116 246 2018Telex: 342367 GENT G

South EastTelephone: 0181 300 7784 Fax: 0181 302 7739

South WestTelephone: 0117 961 8340 Fax: 0117 961 8292

MidlandsTelephone: 0116 246 2400Telex:342367 Fax: 0116 246 2017

NorthTelephone: 01204 531155 Fax: 01204 531177

ScotlandTelephone: 0141 429 5446 Fax: 0141 420 1731

Northern IrelandTaylorThe Mount2 Woodstock LinkBelfastBT6 8DDTelephone: 01232 730 150 Fax: 01232 730 199

GENT Xenex fire panels Log book

8/97 12 Log book for 4188-410 Issue 1

Page 41: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

GENT Xenex range of

1,2,4 and 8 zone fire Control and Repeat panels

This publication is forinternal use only.

This publication covers the:

GENT range XEN1, XEN2,XEN4 and XEN8 fire alarm control panels.

GENT XEN RPT fire alarm repeat panel.

Design and installationSpecifications 2

System design 5

Cables 8

Notes to the Installer 9

Panel fixing 10

CommissioningCommissioning 13

Installed system tests 14

Access levels 2 & 3 15

System test functions 16

Panel configuration functions 17

Servicing organisation’saccess codes 19

Factory functions 20

OperationUser responsibility 21

Fault indications 24

Operating instructions 26

Parts list 28

Log book 31

Figure 1 Fire alarm control / repeat panelcdm64

4188-416 Issue 1 1 8/97

Page 42: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Specification for the Control panelUK Model No. (with batteries) XEN1 XEN2 XEN4 XEN8

Number of Zone (detection) circuits 1 - Zone 2 - Zone 4 - Zone 8 - Zone

Zone circuit load (maximum) 2mA per zone

Number of Sounder circuits 2 2 4 8

Sounder circuit (shared load) 1A at 24V d.c. nominal 1.5A at 24V d.c. nominal

End-of-line unit Zone circuit: Capacitor (diode) unit Sounder circuit: 22K ohms resistor

Standards EN54 : Parts 2 & 4

Flush fixing kit 3 3 3 3

Colour Front cover - Grey RAL 7000 (standard)

Assembled panel size (in mm) 395 wide x 274 high x 87 deep

Weight (with batteries) 5.1Kg 5.1Kg 6.6Kg 6.6Kg

Operating temperature and humidity 0 - 40oC low to +95% RH non condensing

Storage temperature and humidity -5oC to +50oC low to +95% RH condensing

Approvals LPCB approval to be acquired

Emission BS EN50081-1:1992: Part 1 Residential, Commercial & Light industry Class B limits

Immunity BS EN50130-4: 1995: Part 4 Alarm systems : Electromagnetic compatibilityProduct family standard: Immunity requirements for components of fire, intruder

and social alarm systems

IP rating (BS5490) IP31 (indoor)

Mains operating voltage 230V ac +10% -6% 50Hz

Knock-In cable entry points 13 - top & 13 - back

Terminal size 2.5mm2 maximum

Battery supply (sealed lead acid) 2-off12V 2.1Ah 2-off12V 2.8Ah

Battery standby with 1mA load perzone and 1A total sounder alarm load 72hr standby plus 0.5hr with alarm load

Auxiliary contacts(operates with fire)

Pair of normally closed (NC) and a pair of normally open (NO) contacts rated1A @ 24V dc resistive load (Maximum 100m cable distance)

Common Fault Open collector - normally On (with 1K ohms limiting resistor)

Common Fire Open collector - normally Off (with 1K ohms limiting resistor)

Class change Normally open push button, up to 100m cable distance away from the panel

24V Power supply(with foldback current limit)

100mA maximum at 24V d.c. nominal 250mA maximum at 24V d.c. nominal

User access: By means of code entryvia numeric key pad(AL1 Authorised user - No code isrequired)

AL2 Site security 3 digit code - 123AL3 Site engineering 3 digit code - 321AL4 Engineers 4 digit code - 7426Servicing organisation 4 digit code - 4083Reset AL2 & AL3 codes 4 digit code - 2623

Key pad button controls Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric keypad.

Buzzer for local audible indications Fire & System Fault - continuous sound Fault - intermittent sound (via piezoelectric buzzer operating at 2KHz 70dB(A) at 1m)

Visual indications FIRE & ZONES-fire (Red LEDs ‘lights’)ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power,Access/Function (Yellow LEDs ‘lights’)Power on (Green LED ‘light’)

Repeat panel connections Serial port , see also repeat panel specification

Specifications GENT Xenex fire panels

8/97 2 4188-416 Issue 1

Page 43: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Specification for the Repeat panelUK Model number XEN RPT

Number of Zones 8 - Zone (standard size)

Standard EN54 : Parts 2 & 4

Flush fixing kit 3

Colour Front cover - Grey RAL 7000

Assembled panel size (in mm) 395 wide x 274 high x 87 deep

Weight (with batteries) 5.1Kg

Operating temperature and humidity 0 - 40oC low to +95% RH non condensing

Storage temperature and humidity -5oC to +50oC low to +95% RH condensing

Approvals LPCB approval to be acquired

Emission BS EN50081-1:1992: Part 1 Residential, Commercial & Lightindustry

Class B limits

Immunity BS EN50130-4: 1995: Part 4 Alarm systems : Electromagneticcompatibility Product family standard: Immunity requirements for

components of fire, intruder and social alarm systems

IP rating (BS5490) IP31 (indoor)

Mains operating voltage 230V ac +10% -6% 50Hz

Knock-In cable entry points Top & back entries

Terminal size 2.5mm2 maximum

Battery supply (sealed lead acid) 2-off12V 2.1Ah

Standby duration 72hr standby

User access: By means of code entryvia numeric key pad(AL1 Authorised user - No code isrequired)

AL2 Site security 3 digit code - 123AL3 Site engineering 3 digit code - 321AL4 Engineers 4 digit code - 7426Servicing organisation 4 digit code - 4083Reset AL2 & AL3 codes 4 digit code - 2623NOTE: Only a limited number of functions are accessible at therepeat panel.

Key pad button controls Sound alarm, Silence alarm, System Reset & Cancel buzzer &numeric keypad.

Buzzer for local audible indications Fire & System Fault - continuous sound Fault - intermittent sound(via piezoelectric buzzer operating at 2KHz 70dB(A) at 1m)

Visual indications FIRE & ZONES-fire (Red LEDs ‘lights’)ZONES-fault, Fault, System, Power, Earth, Sounder, Disable,Test, Power, Access/Function (Yellow LEDs ‘lights’)Power on (Green LED ‘light’)

Repeat panel (standard 8 zone) A maximum of up to 6 repeat panels connected in series to thecontrol panel

Repeat panel connections Serial port

GENT Xenex fire panels Specifications

4188-416 Issue 1 3 8/97

Page 44: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Zone circuit products (24Vdc) See control panel specification for zone circuit loading.

Part number Product Operating voltage Quiescentcurrent

Alarmcurrent

17640-01 Optical smoke detector

16V dc to 32Vdc

90uA10mA

Maximumcan be

upto 65mAlimited bythe control

panel

17630-01 Ionisation smoke detector 50uA

17650-01 Fixed temperature heat detector 45uA

17660-01 Rate of rise heat detector 45uA

17670-01 High temperature heat detector 90uA

17615-01 Duct detector 90uA

17906-49 Remote external LED for detector -

07011-31 Beam detector see note

14112-08 Manual call point (surface) 470R n/a As perdetectors14112-18 Manual call point (flush) 470R n/a

NOTE: If the beam detector is used then it must be powered from an external power supply.

Sounder circuit products (24Vdc) See control panel specification sounder circuit loading.

Part number Product Alarm current

12511-37 Electronic sounder (red) 20mA

12511-52 Electronic sounder (grey) 20mA

12141-04 Electronic bell (red) IP40 30mA

12141-54 Electronic bell (grey) IP40 30mA

02601-31 Sounder 18mA

02300-01 Xenon flasher (red) 125mA

02300-01 Xenon beacon (red) 45mA

Door holders

NOTE: The door holder circuit should be controlled by the control panel’s auxiliary contacts, using externalpower supply.

Part number Product Current

04390-31 Door holder (24Vdc) 22mA

04390-55 Door holder (240Vac) 17.5mA

Specifications GENT Xenex fire panels

8/97 4 4188-416 Issue 1

Page 45: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

System designThe design of the fire detectionand alarm system should be to BS 5839:Part 1:1988 Code ofPractice for system designinstallation and servicing.Supplemented with customerrequirements.

Mains Supply Connection

The mains supply to the controlpanel should be via a fused spurunit rated: 5A for 1 & 2 Zone panel7A for 4 & 8 Zone panel

Standby Supply

With the recommended batterythe control panel will provide astandby supply under mainsfailure conditions, for a period of72 hours followed by 30 minutesof alarm load, see specification.

24V supply

The power supply terminals ‘24+and 0’ may drive external ancillaryequipment and is designed to beused in conjunction with auxiliarycontacts and common fire andfault outputs, see control panelspecification.

NOTE: The use of the 24Vsupply will affect the panelstandby capability.

Figure 2 System schematiccdm65

GENT Xenex fire panels System design

4188-416 Issue 1 5 8/97

Page 46: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Fire Detection (Zone Circuits)See parts list for compatible parts.

Each zone circuit can have up to2mA load. An end-of-linecapacitor unit is required for zonecircuit monitoring, which must befitted after the last detector ormanual call point on the circuit.All manual call points usedmust have a 470 ohms seriesresistor.

NOTE: If a Beam detector isused, then it must be poweredfrom an independent supply.

Where a zone circuit is not beingused, the end-of-line capacitorunit must be fitted across itsterminals in the panel.

Alarm (Sounder circuits)

NOTE: All sounder circuits(sectors) will always operatetogether in the event of a firecondition.

See parts list for compatible parts.

To comply with the requirementsof BS 5839: Part 1:1988, aminimum of two alarm soundercircuits should be used on allinstallations.

1 & 2 ZonePanel

4 & 8 ZonePanel

1A maximumAlarm sounderload per panel

1.5A maximumAlarm sounderload per panel

The load must be shared betweenthe sounder circuits.

The alarm sounder circuits areregularly pulse monitored forfailure. It is important that the lastalarm sounder is fitted with a 22KOhm end-of-line resistor.

Where a sounder circuit is notbeing used, the end-of-lineresistor must be fitted across itsterminals in the control panel.

Figure 3 Zone circuit connectionscdm68

Figure 4 Alarm sounder connectionscdm67

System design GENT Xenex fire panels

8/97 6 4188-416 Issue 1

Page 47: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Auxiliary ContactsThese are normally open (NO)and normally closed (NC)contacts that switch over whenthe panel goes into a fire condition.

The contacts are rated at 24V d.c.1A for a resistive load and shouldnot be used to switch voltages inexcess of 50V.

The auxiliary circuits should bepowered from an independentpower supply.

Class ChangeA pair of unmonitored terminalsallow only the system alarmsounders to be actuated from aremote position. It is consideredthat the major use for these will befor class change functions inschools and colleges.

NOTE: There is no indicationat the panel of class changepush button operation.

Common Fire and faultThe common fault output is anormally closed electronic switch,which opens with a fault condition,this is for a fail safe operation.

The common fire output isnormally open electronic switchthat closes with a fire condition.

NOTE: Each electronic switchhas an in-line 1K ohms resistor.

The +24V & 0V is a power supplyfor use with auxiliary contacts,common fire and common faultcircuits, see specification.

Repeat PanelThere can be up to 6 repeatpanels series connected from thecontrol panel. A repeat panelduplicates fire and faultindications together with systemcontrols.

Figure 5 Auxiliary contact circuitcdm72

Figure 6 Class change circuitcdm73

Figure 7 Fire fault & 24V outputscdm74

Figure 8 Control to repeat panel connectionscdm75

GENT Xenex fire panels System design

4188-416 Issue 1 7 8/97

Page 48: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

CablesFor the wiring of:

The guidance of BS5839 : Part 1: 1988 should befollowed.

The use of cables, such as (MICCor Belden) are recommended.

Generally available electricalinstallation cable may be used,providing the cable is:

to BS6387

with no more than 2 - cores

each core having no less than1.5mm2 cross section area

with an inherent or through metal conduit screen for earthcontinuity in order to produceelectrical protection and screening

having protection from heat andmechanical damage

Power supply cord

This should be a 3-core cordhaving a rated current of:

5A with a nominal core cross sectional area of 0.75mm2 provided the length of the corddoes not exceed 2m.

Length per circuit Type of circuit Recommended cables, also see BS5839:Part 1 guidance

2m Mains power supply cord see power supply cord

1Km Zone circuit

See BS5839:Part 1 guidance1Km Sounders circuit

100m Auxiliary circuit

100m Common fire and fault circuit

100m Class change circuit

500m Repeat panel link Belden type screened 2-core twisted pair

Figure 9 Panel cable entry and earth pointscdm158

Cables GENT Xenex fire panels

4188-416 Issue 1 8 8/97

Page 49: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Notes to the installerChecks

The power-up and commissioning is done by theservicing organisation.

The wires between the termination point and terminalsshould be short and straightas possible.

The cables of the fire detectionand alarm system and othersystems should usually beseparated by at least 160mm,unless dedicated conduit orducting is used.

Do not use any part of buildingstructure for earthing.

The cable length between theRepeat LED unit and respectivefire detector where used ,should not exceed 10m

Cable Glands should be usedon the equipment for the mainssupply cable.

Unused knockouts on productenclosure that have been removed, should not be leftopen.

Requirements

It is recommended that theinstaller follow the generalrequirements of:

• BS5839:Part 1:1988, which isthe code of practice relating tothe fire detection and alarmsystems for buildings.

• the relevant parts of the BS7671 Requirements forElectrical Installation Institute ofElectrical Engineers WiringRegulations 16th edition.

Second fix installation

To prevent the possibility ofdamage or dirt degrading theperformance or appearance of theSystem products:

the installation of second fix itemsshould be delayed until all majorbuilding work in the area iscomplete.

Fixtures and fittings

It is the installers responsibility toprovide:

• adequate fixtures and fittingsfor the type of constructionsurface onto which a productis to be installed.

• as an aid to this decision, theweight and overall size ofeach full assembly togetherwith implications on cableentries and routing should betaken into consideration.

NOTE: All these proceduresassume that the cable, gland,steel box (BESA box) andother related accessories areprovided by the installer.

As fitted wiring drawings

The installer should acquire:

• site specific information fromthe interested parties, fordetails on the location ofproducts for installation

• the acquired informationtogether with this guide andthe relevant standards shouldbe used to assist the work.

Earth continuity

To maintain earth continuity, thecable screen must be continuedthrough each system device,whether the earth is connected toa device or not.

GENT Xenex fire panels Notes to the installer

8/97 9 4188-416 Issue 1

Page 50: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Panel fixinga) Remove panel from its

packing, but retain the cartonfor storage of spare parts andloose items.

b) Remove the top and bottominner plates, see Figure 10.

c) Check the spares partssupplied with those listed inTable 1. If replacement partsare required at any time, onlyspares that are of the samespecification should be used.

d) Remove the transformer andearth connections from theelectronic assembly, and thenremove the electronicassembly from the panel, see Figure 11. Store the electronicassembly in a safe place untilrequired.

e) Remove the appropriateknock-in on the panel case forcable entry.

f) Hold the panel on the wall inthe desired mounting positionand mark the positions of thefixing holes. See Figure 11 forcase fixing details.

g) Secure the panel to the wallusing suitable fixing such thatadequate support is providedto the control panel assembly.A top centre keyhole fixing isprovided on the case to allowthe panel to be hooked whilstthe bottom two fixing pointsare located.

h) Connect the mains supplycable to the panel.The cable:

• must be through one of thededicated cable entry into thepanel

• via an unswitched fusedspur unit, rated 5A for the1&2 Zone Control and Repeatpanels and 7A for 4&8 Zonepanels.

The fused spur isolator covershould be red and marked:FIRE ALARM - DO NOT SWITCHOFF

The fused spur units must befed from a dedicated switch orprotective device at the localmains supply distributionboard.

DescriptionFor fuses alsosee Figure 12

Quantity supplied with controlpanel

Repeatpanel

1 -zone

2 -zone

4 -zone

8 -zone

8 - zoneonly

22K end-of-line resistor 2 2 4 8

Capacitor unit 1 2 4 8

End-of-line label 3 4 8 16

Fuse 5A 20mm x 5mm AS (mains terminal block)

1 1

Fuse 3.15A 20mm x 5mmAS (mains terminal blockand power 1 & 2 - F1 &F2)

2 2 2 2 2

Fuse 5A 20mm x 5mm QB(battery F3)

1 1 1 1 1

Fuse 0.5A 20mm x 5mm QB(sector)

2 2 2 2

Fuse 0.16A 20mm x 5mmQB (sector)

2 6

Battery link 1 1 1 1 1

Zone designation label 1 1 1 1 1

Table 1 Spare parts supplied with each panel

Figure 10 How to remove the outer coverscdm77

Panel fixing GENT Xenex fire panels

4188-416 Issue 1 10 8/97

Page 51: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

i) Wire the system. With theexception of mains cable, allother cables should remainunconnected at the panel.

For the unconnected cableleave 300mm tail wire lengthand mark each core identifyingits final point of connection.

The system wiring can betested whilst not connected tothe respective terminals ateach system equipment.

CAUTION: DO NOTundertake high voltageinsulation tests WITH THECABLES CONNECTED totheir terminals. Such a testmay damage the electroniccircuitry in the systemequipment.

j) Refit the electronic assemblyinto the panel and connect thetransformer and earth cablespreviously removed, see Figure 11.

NOTE: Each terminal in apanel will accept a maximumconductor size of 2.5mmsquare.

NOTE: The installation of alloutstanding parts are usuallycarried out duringCommissioning of the System.

Store all spare parts and loosecomponents including thebatteries inside the panelcarton and keep in a safeplace until required.

Figure 11 Panel fixingscdm69

GENT Xenex fire panels Panel fixing

8/97 11 4188-416 Issue 1

Page 52: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Figure 12 Panel terminals and fusescdm70

Panel fixing GENT Xenex fire panels

4188-416 Issue 1 12 8/97

Page 53: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

CommissioningThe total system should be testedin accordance with thecommissioning requirements ofBS5839:Part 1:1988 or otherstandard specified by the systempurchaser.

NOTE: The commissioningprocedures assume that thesystem has been installed asper instructions in this booklet.

System checksAcquire as fitted drawings

check the system has been in-stalled to the project require-ments.

if appropriate, action the in-staller to carry out changes tothe system.

Initial power upa) Disconnect cables to terminals

of zone, sounder, classchange, auxiliary, common fireand fault circuits. Ensure eachcable is marked forreconnection to respectiveterminals later.

b) Connect end-of-line units tozones and sounder circuits forinitial power up.

c) Check mains connection andswitch on the mains power tothe control panel.

d) Now connect the batterysupply, see Figure 13.

e) Check the panel provides anormal healthy indication, withthe green light lit.

Zone circuit testsa) Transfer the end-of-line

capacitor unit to the last device(detector or manual call point)on a zone circuit.

b) Connect the zone cable to thezone circuit terminals.

c) Carry out zone open circuitand short circuit tests andcheck appropriate indicationsare given.

d) Repeat the above for otherzone circuits.

Sounder circuit testsa) Transfer the end-of-line

resistor unit to the last deviceon a sounder circuit.

b) Connect the sounder circuitcable to the sounder circuitterminals.

c) Carry out sounder open andshort circuit tests and checkappropriate indications aregiven.

d) Repeat the above for othersounder circuits.

Figure 13 Battery installationcdm71

GENT Xenex fire panels Commissioning

4188-416 Issue 1 13 8/97

Page 54: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Installed system testsThe fire detection and alarmsystem should be tested to ensureit operates to meet the standardsand project requirements.

Configuration

The control and repeat panels arefactory set to the requirements of EN54 Parts 2 and 4.

The operation of the control andrepeat panels and the systemmay be re-configured to sitespecific needs, see system testfunctions and Panel configurationfunctions.

CAUTION: Any specialconfigurations may cause thesystem and equipment tooperate outside therequirements of Europeanstandards.

Test mode A or B operationTo facilitate tests on the firedetection and alarm system thecontrol panel can be set tooperate in a test mode, seeSystem test functions.

With Test mode A or B active: atriggered manual call point or firedetector in the test zone will give:

NOTE: A detector that is stillfull of smoke or heat willretrigger into a fire conditionuntil the smoke or heat in thearea is cleared.

Repeat panel configuration

There can be up to 6 repeatpanels connected in series to thethe control panel.

Each repeat panel connected tothe system is required to be givenan address at both the controland repeat panels, see Panelconfiguration section.

Sound level test

Sound level tests should beconducted to standardrequirements and to customersatisfaction.

Other equipment tests

Where external equipment isconnected to the control panelusing auxiliary, common fire andfault terminals, then these mustbe tested to project requirements.

Zone designation labela) Write on to the zone

designation label the namethat identifies the areaprotected by each zone circuit.

b) Fix the label over the zonedesignation part of the lowerinner plate, see figure 13.

Log book

Fill in system details on the firstthree pages of the log book.

On completion

Ensure the persons responsiblefor the system are made aware of

• system operation

• access codes to controls

• basic controls

• their responsibility

• and the need to log systemevents in the log book.

Test A Test B

Fireindication for 10 secondsdurationfollowed by asystem reset

System alarmsounds for thefirst 2 secondsand at the sametime a Fireindication isgiven for 10 secondsdurationfollowed by asystem reset

Table 2 Test mode operation

Installed system tests GENT Xenex fire panels

8/97 14 4188-416 Issue 1

Page 55: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Access levels 2 and 3The control and repeat panelsprovides system security bycoded password entry to controls.

There are three coded accesslevels to user controls, also see Table 3.

Access level 1 (AL1) is for authorised user.

Access level 2 (AL2) is for site security.

Access level 3 (AL3) is for site engineer.

Access codesThe factory set codes for:

AL1 - No code required

AL2 - is 123 (default)

AL3 - is 321 (default)

The AL2 and AL3 are 3-digitcodes.

NOTE: The standard AL2 andAL3 access codes are factoryset. These codes may bechanged to user defined codes.

Access Levels->

What is accessible

AL1 AL2Code:*123

AL3Code:*321

Cancel buzzer (fire and fault) *3­ 3 3

System Reset 3 3

Sound alarms 3* 3*

Silence alarms 3 3

Disable / Enable sounders 3 3

Disable / Enable zone(s) 3 3

Zone(s) only Test A *3¬ 3

Zone(s) with sounders Test B *3¬ 3

Cancel Test A / Test B *3¬ 3

Display test *3­ 3 3

All indications 3 3 3

Zone designations (located behind lower cover) 3 3 3

Instructions (located behind lower cover) 3 3 3

Change to AL2 and AL3 user password 3

Repeat panel address 3

A Shaded option is not applicable to the repeat panel.

¬ This option may be moved to AL3, see Panel configuration section­ This option may be moved to AL2, see Panel configuration section* factory setting

Table 3 Controls accessible at various user levels

GENT Xenex fire panels Access levels 2 and 3

4188-416 Issue 1 15 8/97

Page 56: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

System test functionsTo ease the testing of the systemit is necessary to gain access tosome of these functions.

NOTE: It is only necessary toenter the access code once,provided the 2 minute timeoutis not exceeded betweenbutton presses.

Access code

AL2 Code : 123 may be usedto gain access to the testfunctions. Depending on how thesystem is configured it may benecessary to use AL3 code321instead of AL2 code.

The factory set AL2 and AL3codes are 123 and 321respectively on first power-up. Ifthe codes are changed at anytime then the power-up codes arenot applicable.

NOTE: It is important to leavethe system in a normaloperating condition oncompletion of commissioning.

How to Controls Result

How to do a Display test Enter the 3 digit code then:

press shift and display buttons

All indicators are lit (flashingindication for zone fire/fault) andthe buzzer sounds for 10 secondsduration

How to set the panelto operate Test mode A

Enter the 3 digit code then:

press ③ and the respective zone ➀ - ➇

This will allow the zone circuit(s) tobe tested without an alarm of fire.

How to set the panelto operate Test mode B

Enter the 3 digit code then:

Press ➃ and the respective zone ➀ - ➇

This will allow the zone circuit(s) tobe tested with 2 second alarm offire.

How to Cancel Testmode A/B Enter the 3 digit code then:

Press ➄ and the respective zone ➀ - ➇

This will cancel any active Testmode, either A or B.

How to Disable azone Enter the 3 digit code then:

Press ➀ and the respective zone ➀ - ➇

A fired detector in disabled zone(s)will not cause the panel to go into afire condition.

How to Enable azone Enter the 3 digit code then:

Press ➁ and the respective zone ➀ - ➇

This will re-enable all previouslydisabled zone circuit(s).

How to Disablesounders Enter the 3 digit code then:

Press ➀ and followed by

This will disable the Soundercircuits operation.

How to Enablesounders Enter the 3 digit code then:

Press ➁ and

This will re-enable previouslydisabled sounder circuits.

How to change AL2 password Enter the AL3 3-digit code

then: Press ➈ ➀ followed by the new

3-digit code and

This will allow a previous AL2password to be changed to a new3-digit code

How to change AL3password Enter the AL3 3-digit code

then press ➈ ➁ followed by the new

3-digit code and

This will allow a previous AL3password to be changed to a new3-digit code

How to exit from AL2,AL3 or AL4 to AL1 Press This will exit the current access

level and return to AL1

System test functions GENT Xenex fire panels

4188-416 Issue 1 16 8/97

Page 57: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Panel configuration functionsTo ease the commissioning of thesystem it is necessary to gainaccess to some of these functions.

NOTE: It is only necessary toenter the access code once,provided the 2 minute timeoutis not exceeded betweenbutton presses.

Access code

AL3 Code : 321 may be usedto gain access to thesecommissioning functions.

The AL3 code is: 321 on firstpower-up. If the code is changedat any time then the power-upcode is not applicable.

NOTE: It is important to leavethe system in a normaloperating condition oncompletion of commissioning.

How to: Controls Result Factorydefault

How to terminate theEEPROM programmingmode

Press Shift followed by ➈ This will terminate theprogramming mode at anystage, and return theEEPROM to a protectedstate.

How to set a repeatpanel address at thecontrol panel

There can be up to 6repeat panels in asystem.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➇ and the repeat panel

address ➀ and then .

At the Control panellocation 038 an entry ismade of the first repeatpanel address 001

Depending on the numberof repeat panels used,similarly at locations 039,040, 041, 042 and 043enteries are made of the2nd, 3rd, 4th, 5th and 6threpeat panel addresses,which may be 002, 003,004, 005 and 006respectively.

Repeatpaneladdressis 000

How to set a repeatpanel address at therepeat panel

There can be up to 6repeat panels in asystem.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➇ and repeat panel

address ➀ and .

At the Repeat panellocation 038 an entry ismade of the repeat paneladdress, in this case it is001. Other repeat panelscan be given an addressfrom the range 002 to006, which must beentered in location 038..

Repeatpaneladdressis 001

How to move ‘Cancelbuzzer’ from accesslevel AL1 to AL2

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➁,and data ➀ and .

This will move the Cancelbuzzer button access tolevel 2.

How to move ‘Cancelbuzzer’ from accesslevel AL2 to AL1

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➁, and data

and .

This will move the ‘Cancelbuzzer’ button access tolevel 1.

GENT Xenex fire panels Panel configuration functions

4188-416 Issue 1 17 8/97

Page 58: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

How to: Controls Result Factorydefault

How to move ‘Test A&B’and Cancel Test fromaccess level AL3 to AL2

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➃, and data

➀ and .

This action will move the‘Test A&B and Canceltest’ functions from AL3 toAL2.

How to move ‘Test A&B’and Cancel test fromAL2 to AL3

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➃, and data

and .

This action will move the‘Test A&B and Canceltest’ functions from AL2 toAL3.

How to set the mostrecent fire as a steadyindication.

Enter the AL3 3-digit code

then: Press ➈

followed by location ➂➄, data

➀ and .

This will result in the mostrecent fire being displayedas a steady indication.

How to set the mostrecent fire as a pulsingindication.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➄, data

➀ and .

This will result in the mostrecent fire being displayedas a pulsing indication.

How to set the auxiliaryrelay to operate(energise) with soundalarms.

Enter the AL3 3-digit code

then: Press ➈

followed by location ➂➆ data

➀ and .

This will result in theauxiliary relay activationwith sounders.

How to set the auxiliaryrelay to operate(energise) with firecondition.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➆ data

and .

This will result in theauxiliary relay activationwith a fire condition.

How to move ‘Displaytest’ from access levelAL2 to AL1.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➂ data

➀ and .

This will move the ‘Displaytest’ button access to AL1.

How to move ‘Displaytest’ from access levelAL1 to AL2.

Enter the AL3 3-digit code

then: Press ➈ followed

by location ➂➂ data

and ..

This will move the ‘Displaytest’ button access to AL2.

Panel configuration functions GENT Xenex fire panels

19/8/97 18 4188-416 Issue 1

Page 59: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Servicing organisationaccess codes

CAUTION: Under normalcircumstances the factorysettings must not be altered.

NOTE: The Access level 4code, Servicing organisation’sengineers code and the Resetcodes are for servicingorganisation use only.

The control and repeat panelsprovides system security bycoded password entry to controls.

Other access levelsThere are four coded accesslevels to controls.

Access level 1 (AL1) is for authorised user.

Access level 2 (AL2) is for site security.

Access level 3 (AL3) is for site engineer.

Access level 4 (AL4) is forservicing organisation.

Access codesThe factory set codes for:

AL1 - No code required

AL2 - is 123 (factory set)

AL3 - is 321 (factory set)

AL4 - is 7426

Servicing organisation’s engineers code - is 4083

The AL2 and AL3 are 3-digitcodes that may be changed touser defined ones. Onceredefined the factory codes arenot applicable.

Reset code - is 2623

The Reset code allows the userdefined AL2 and AL3 codes to bereset to their default factorysettings.

Access Levels->

What is accessibleAL4

Code:7426

ServiceOrganisation’s

EngineersCode:4083

ResetCode:*2623

All access level 2 (AL2)and access level 3 (AL3) functions,see Access levels 2 & 3 section

3 3

Reset AL2 and AL3 password tofactory settings

3

Factory settings 3

Access code 2623 will reset AL2 and AL3 passwords to their factory default setting.

* - Note the European practice is to Sound Alarms in fire condition only

* factory setting

Table 4 Servicing organisation access levels

GENT Xenex fire panels Servicing organisation access codes

4188-416 Issue 1 19 8/97

Page 60: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Factory functions

NOTE: It is only necessary toenter the access code once,provided the 2 minute timeoutis not exceeded betweenbutton presses.

AL4 Code : 7426 may be usedto gain access to change thefactory settings.

CAUTION: On entering thismode to make changes thefactory settings, the EEPROMremains unprotected, ensurethe EEPROM protection isreinstated.

The system fault light will indicatewhen the EEPROM protection isremoved.

Press Shift followed by ➈to terminate the configurationmode at any stage, and return theEEPROM to a protected state.

How to change control panel zone and alarm circuit operation

Selections Controls Result Factorydefault

Silence alarms + Reset tooperate as BS5839:Part4

Enter the AL4 4-digit code

then: Press ➈ followed

by location ➀➄➇ and data

XXX and .

See How to work out the XXX number.

The Silence alarms buttonmust be pressed beforeReset button.

Silence alarms + Reset tooperate independently

The Silence alarms buttonand reset button operateindependently.

Reset system buttonoperation also actionsSilence alarms

The Reset button will alsoaction the Silence alarmbutton.

Sound alarms in fire only The Sound alarms button willonly operate in fire condition.

Sound alarms at any time. The Sound alarm button willoperate at any time.

Zone short circuit is a fault A short circuit on a zone willcause a zone fault.

Zone short circuit is a fire A short circuit on a zone willcause a zone fire.

Detection band A See devices in parts list ✔

Detection band B tba

Detection band C tba

How to work out the XXX number

Bits 7 6 5 4 3 2 1 0 The default decimalnumber is 20.Therefore the XXXnumber is 020.Note the shaded cellsare factory defaults.

Example: If we need: Band A As BS 5839 Part 4 Sound alarm at any time and zone short equals fire.

Then the Byte requiredwill be:= 00100000which is decimal 32

therefore the XXXnumber required is 032.

DetectionBand

A 0 0

B 0 1

C 1 0

Silencealarms &Resetbuttonoperation

As BS5839:Part4 0 0

both independent 0 1

Reset actions Silence alarms 1 0

Soundalarms

At any time 0

In fire condition 1

ZoneShortcircuit

Fault 0

Fire 1

Default byte required 0 0 0 1 0 1 0 0

Decimal number of each bit 128 64 32 16 8 4 2 1

Factory functions GENT Xenex fire panels

8/97 20 4188-416 Issue 1

Page 61: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Panel zone operation

How to: Controls Result Factorydefault

How to set latching andnon latching zones Enter the AL4 4-digit code

then: Press ➈ followed

by location ➀➄➆ and data YYY and . See How to work out the YYY number.

This will cause fired zoneto clear automatically if thezone circuit returns to anormal operating condition

allzonesare setforlatchedoperation

How to work out the YYY number

Control panel zone number 8 7 6 5 4 3 2 1 The corresponding bit of the databyte that relates to a system zoneis set to ‘0’ for normal operation,which is the factory setting.Therefore the YYY number is 000.

To set a system zone fornon-latching operating therespective zone bit must be set to‘1’ to give the required decimalnumber.

For Example:If zones 1 and 4 are required tooperate in a non-latching modethen the binary number will be00001001, which is a decimal 9.Therefore the decimal number is009.

Bit number of the data byte 7 6 5 4 3 2 1 0

Factory setting of the bits 0 0 0 0 0 0 0 0

Decimal equivalent 128 64 32 16 8 4 2 1

How to set the zone capacity of a control and repeat panel

How to: Controls Result Factorydefaults

How to set the zonecapacity of the controland repeat panels.

Enter the AL4 4-digit code

then: Press ➈ followed by

location ➀➄➅ and data ZZZ and

.

The zzz number can be selected from:1 zone Control panel - 0012 zone Control panel - 0024 zone Control panel - 0048 zone Control panel - 008 Repeat panel - 000

A 1,2,4 or 8 zone controlpanel data will be 001,002, 004 or 008respectively.

The repeat panel data willalways be 000

GENT Xenex fire panels Factory functions

4188-416 Issue 1 21 8/97

Page 62: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

User ResponsibilityIt is recommended that thepersons responsible for the firealarm system, should becomefamiliar with the procedures onhow to operate the controls andinterpret indications given at thecontrol and repeat panels.Adequate training should alsohave been given from appointedpersonnel.

DailyThe British Standard code ofpractice for Fire detection andalarm systems for buildings, BS 5839:Part1:1988, states thatthe system should be inspecteddaily to ensure that a normalindication is given at the controland indicating equipment and thatany previously indicated faultcondition has receivedappropriate attention.

a) It recommends entry into theLog Book provided of all thesystem events for futurereference.

b) The person inspecting theprotected premises can ensurethat the use of the area(s)inspected has not changedsuch that the detection andalarm devices have becomeinappropriate.

c) The area(s) can be inspectedto check that no unsafepractices that could lead to fireare being undertaken.

WeeklyAt Weekly intervals a differentFire detector or Manual CallPoint of the system should betested to ensure the system iscapable of operating under alarmcondition.

a) The operation of the alarmsounders should be checked,which also provides a regularreminder to those occupyingthe premises that there is a firealarm system with a particularcharacteristic sound.

b) The test should be performedat a regular time to avoidconfusion between a test anda genuine fire alarm.

QuarterlyAt quarterly intervals the systemshould be inspected and any worknecessary should be performedby trained maintenance engineer.

Battery Replacement

NOTE: Any servicing work onthe System must be carriedout by servicing organisation.

Under normal operatingconditions the maintenance freelead acid batteries in the Controland Repeat panels can have auseful life of up to 5 years fromthe date of manufacture.

NOTE: It is recommended thatthese batteries are replaced at4 Yearly intervals from thedate the System is firstcommissioned.

User Responsibility GENT Xenex fire panels

4188-416 Issue 1 22 8/97

Page 63: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Testing a Manual Call PointPush the test key through the holein the underside of the call point toengage the test cam mechanismand push to operate the cammechanism.

At this point the test key isretained in the call point andpulling it out will reset the glass.

NOTE: The alarm sounders inthe system will be activated bythis test. To silence alarmsand reset the system, seeoperating instructions.

Replacing a broken Glass

WARNING: Takeappropriate precautionswhen clearing broken glassto prevent injury.

NOTE: A weather resistantversion of manual call pointswill have two gaskets, aCover/glass gasket and aSpacer/cover gasket, whichmust be installed in theirrespective position.

These procedures assume thecover on the manual call point isopen and any broken glass hasbeen cleared.

a) Feed the glass upward to pushthe cams down and fit underslider, locate bottom of glassinto recess.

b) Hold the bottom of glass inposition and rotate thethumbwheel quadrant to raisethe top of the glass.

c) Fit the call point cover byhooking it into the top of theunit and making sure that theglass is properly seated (helddown) tighten the cover fixingscrew.

Figure 15 Replacing a broken MCP glassemfl216

GENT Xenex fire panels User Responsibility

8/97 23 4188-416 Issue 1

Page 64: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Fault indications

All fault repairs should becarried out by the servicingorganisation.

In a fault condition:

• the common Fault lightis lit

• appropriate fault light isalso lit

• internal Fault Buzzer soundsintermittent tone

• Multiple faults aresimultaneously annunciatedwhen this does not causeconfusion.

NOTE: Normally the fault lightswill be automaticallyextinguished once the faultcondition is rectified.

NOTE: If the system detects afire during a fault condition thefault indicators may beextinguished.

How to silence the faultbuzzer

Press the 3 digit code

if required and

then press Cancel Buzzer .

Notice the buzzer is silencedbut visual indications remainactive.

NOTE: The sounder circuitsare pulse monitored for failure.The monitoring signal is onlyapplied to the circuits for ashort duration at regularintervals.

Figure 14 Fault indicatorscdm95

Faults Cause

What is a Zonefault?

A zone fault occurs when a zone circuit cable is opencircuit or short circuit, or the end-of-line capacitor unithas been disconnected or a detector has beenremoved.

What is aSounder fault?

A sounder fault occurs when a sounder circuit cableis open circuit or short circuit, or the end-of-lineresistor unit has been disconnected.

What is a Mainspower fault?

A mains failure occurs when the mains power supplyto the panel is removed. This can occur on mainsfuse failure or mains supply disconnection.

What is a Batterypower fault?

A battery supply failure occurs when the batterysupply to the panel has failed (due to aging process)or is disconnected or the battery fuse has failed.

What is an Earthfault?

An earth fault occurs when there is an electrical pathfor current flow from the system to earth connections.

What is a Repeatpanel link fault?

A repeat panel link fault occurs when there is acommunication failure between the control andrepeat panels.

What is a SystemFault?

A system fault occurs in the event themicroprocessor failure.

Table 5 Types of faults

Fault indications GENT Xenex fire panels

4188-416 Issue 1 24 8/97

Page 65: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

GENT Xenex fire panels Fault indications

8/97 25 4188-416 Issue 1

Page 66: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Operating instructions

Normal indicationsUnder normal condition the panelshould give a healthy indication,

with only the green Powerlight lit.

The control panel provides systemsecurity by password entry tocontrols.

Fire ConditionIn the event of an automatic firedetection the indications given are:

FIRE light is lit.

Zones-fire light is lit.

buzzer sounds continuous tone.

system alarm sounders are activated

if applicable, auxiliary equip-ment is actuated

if applicable, automatic link tothe Fire Brigade is initiated.

After the emergency is overAfter emergency is over silencethe alarms and reset the system:

a) Enter the 3 digit code

to gain access tothe controls.

b) Press the Silence Alarms

button.

Notice the system alarmsounders are silenced andlocal buzzer soundsintermittent tone.

b) After the cause of the alarmhas been investigated, ensuresmoke and excess heat havehad time to clear fromautomatic detectors andbroken manual call pointglasses have been replacedwhere necessary. Press the

System Reset button.Notice the indications return totheir pre fire status.

Figure 16 Controls and indicationscdm66

Operating instructions GENT Xenex fire panels

4188-416 Issue 1 26 8/97

Page 67: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

To Sound AlarmsTo re-sound the alarm soundersduring a fire condition:

a) Enter the 3 digit code

to gain access tothe controls.

b) Press the Sound Alarms

button. Notice the system alarmSounders are activated.

To Silence AlarmsTo silence system alarm soundersafter they have been actuated:

a) Enter the 3 digit code

to gain access tothe controls.

b) Press the Silence Alarms

button. Notice the system alarmSounders are silenced.

To carry out a lamp testa) Enter the 3 digit code

to gain access tothe controls.

b) Press the ‘shift‘ button and

then the display button. Notice the all indicators are litand the buzzer soundscontinuous for 12 seconds.

Fault ConditionIn the event of an automatic faultdetection the indications given are:

Fault light is lit

fault indicators are lit(except for system fault whichis a contineous sound)

buzzer sounds intermittent.

To Cancel fault buzzera) Enter the 3 digit code

to gain access tothe controls.

b) b) After investigating fault, press

the Buzzer button. Noticethe buzzer is silenced butother indications remain active.

The fault indications arenormally automaticallyextinguished once the faultcondition has been rectified.

Action to rectify faultSuggested action to rectify faultcondition:

NOTE: All fault rectificationwork must be done by theservicing organisation.

The fault indicators may beextinguished during a firecondition.

See commissioning section. Themains failure condition overridesall other fault indications in orderto preserve battery standbycapacity.

GENT Xenex fire panels Operating instructions

8/97 27 4188-416 Issue 1

Page 68: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Parts listXenex Panels

Part number DescriptionXEN1 1 Zone control panel

XEN2 2 Zone control panel

XEN4 4 Zone control panel

XEN8 8 Zone control panel

XENRPT Repeat panel

Fire DetectorsPart number Description17640-01 Optical smoke

17630-01 Ionisation smoke

17650-01 Fixed temperature heat

17660-01 Rate of rise heat

17670-01 High temperature heat

17601-01 Base (BS5839:Part1)

17615-01 Duct detector

07011-31 Beam detector

NOTE: The beam detectorshould be powered from anindependent power supply.

Manual call points (MCP)Part number Description14112-08 Manual call point

(surface)Red 470R

14112-45 Manual call point(surface)Red 470Rc/w cover

14112-08 Manual call point flush (red) 470R

14112-58 Manual call point flush (red) 470Rc/w cover

14112-19 MCP Surface water resistant kit

14112-09 Pack of 10 glasses14115-08 Keyswitch

(red) surface 470R

Parts list GENT Xenex fire panels

4188-416 Issue 1 28 8/97

Page 69: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

14115-18 Keyswitch (red) flush 470R

24Vdc Sound signalsPart number Description12511-37 Electronic sounder (red)

12511-52 Electronic sounder (grey)

12511-19 Water resistant kit for 2511 sounders

12143-04 Electronic bell (red) IP55

12141-54 Electronic bell (Grey)

02601-31 Sounder 6-28V

02300-01 Xenon flahser (red) - 125mA

02300-01 Xenon beacon(red) - 45mA

24Vdc Ancilliary

Part number Description04390-31 Magnetic Door holder

- 22mA

04390-92 Door holder floor plate

04390-99 Door bracket

NOTE: The door holdersshould be powered from anindependent power supply.

AccessoriesPart number Description4015-502 12V 2.1Ah battery

(2-off required for 1 & 2 zone panelplus repeat panel)

4015-509 12V 2.8Ah battery(2-off requiredfor 4 & 8 zone panel)

2534-142 Spares pack for XEN12534-143 Spares pack for XEN22534-144 Spares pack for XEN42534-145 Spares pack for XEN82534-146 Spares pack - XENRPT

GENT Xenex fire panels Parts list

8/97 29 4188-416 Issue 1

Page 70: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

This page has been intentionally left blank.

Parts list GENT Xenex fire panels

4188-416 Issue 1 30 8/97

Page 71: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Log Book

To comply with therequirements of BS5839 : Part 1 : 1988and to allow thoseconcerned with the firedetection and alarmsystems to monitor thelong term performanceof the system, it isimportant that a log iskept which includes allthe events relating tothe performance of thesystem.

SITE ADDRESS____________________________________________________________

____________________________________________________________

____________________________________________________________

GENT Contract No.____________________________________________

Site ID:______________________________________________________

For ServiceNormal Hours Mon-Fri__________________________________________

Tel._________________________________________________________

Outside Normal Hours__________________________________________

Tel._________________________________________________________

Manned Centre Telephone_______________________________________

Manned Centre Code No.________________________________________

Responsible Persons on SITE:____________________________________

A Log of systemevents MUST bekept by theresponsiblepersons on siteand must beavailable at alltimes togetherwith the systemaccess codes.

For each zone record the location description.

Zone number Description of the zonal location

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

Zone 7

Zone 8

AL2 password AL3 password

Log book for 4188-416 Issue 1 31 8/97

Page 72: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

System configuration recordThis information will assist the servicing organisation to keep a record of how the system is configured.

Mark in the table below any deviation(s) from the standard factory settings.

Detection and zone circuit configuration

Zone number 1 2 3 8 5 6 7 8

Normal zone operation (factory setting)

Non latching zone operation

First fire to be a pulsing indication (factory setting) Detection band A (factory setting)

First fire to be a steady indication Detection Band B

Detection Band C

Zone short circuit to give a fault (factory setting)

Zone short circuit to give a fire

Sounders and system reset configuration

Silence alarms and reset to operate independently (factory setting)

Silence alarms and reset to operate as per BS5839: Part 4

Reset to also action the silence alarms

Sound alarms to operate in fire condition only (factory setting)

Sound alarms to operate at any time

Auxiliary relay to energise with fire (factory setting)

Auxiliary relay to energise with sound alarms

Access level

Access levels AL1 AL2 AL3

Cancel buzzer (AL1 - factory setting) N/A

Test A & B mode, Cancel Test (AL2 - factory setting) N/A

Display test (AL1 - factory setting) N/A

Repeat panel information

Repeat panel EEPROMlocation

EEPROMData (address)

Name of the area where the panelis installed on site

1st Repeat panel

2nd Repeat panel

3rd Repeat panel

4th Repeat panel

5th Repeat panel

6th Repeat panel

GENT Xenex fire panels Log book

8/97 32 Log book for 4188-416 Issue 1

Page 73: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Location of system devicesMake copies of this page to record details of the system.This information will assist the servicing organisation to keep a record of how the system is configured.

Zone

Type of system device Location 1 2 3 4 5 6 7 8

Log book GENT Xenex fire panels

Log book for 4188-416 Issue 1 33 8/97

Page 74: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

GENT Xenex fire panels Log book

8/97 34 Log book for 4188-416 Issue 1

Page 75: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Event logMake copies of this page to record details of system events.

Date Time Events Action Datecomplete

Name

Log book GENT Xenex fire panels

Log book for 4188-416 Issue 1 35 8/97

Page 76: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

GENT SALES & SERVICECENTRES

Head OfficeWaterside RoadHamilton Industrial ParkLeicester, LE5 1TNTelex: 342367Fax: 0116 246 2300Tel: 0116 246 2000

International divisionWaterside Road, Hamilton Ind.Park, Leicester, LE5 1TN, UKTelephone: (44) 116 246 2200Fax: (44) 116 246 2018Telex: 342367 GENT G

South EastTelephone: 0181 300 7784 Fax: 0181 302 7739

South WestTelephone: 0117 961 8340 Fax: 0117 961 8292

MidlandsTelephone: 0116 246 2400Telex:342367 Fax: 0116 246 2017

NorthTelephone: 01204 531155 Fax: 01204 531177

ScotlandTelephone: 0141 429 5446 Fax: 0141 420 1731

Northern IrelandTaylorThe Mount2 Woodstock LinkBelfastBT6 8DDTelephone: 01232 730 150 Fax: 01232 730 199

GENT Xenex fire panels Log book

8/97 36 Log book for 4188-416 Issue 1

Page 77: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

GENT 1,2,4 and 8 Zone Model 3260 Fire Alarm Control Panel

Also refer to the ElectromagneticCompatibility (EMC) and Low voltagedirective (LVD) leaflet.

1 IntroductionThe fire alarm control panel has beendesigned to comply with the requirementsof BS 5839:Part 4:1988 for use insystems complying with the requirementsof BS 5839:Part 1:1988 which are theBritish Standards for fire detection andalarm systems in buildings. Theseinstructions should provide sufficientinformation to install the product and thencheck the performance of the installedsystem. It is however important that thoseresponsible for the design, installation andcommissioning of the system should havea good working knowledge of therequirements of installed systems,particularly BS 5839:Part 1:1988 Code ofPractice for system design installationand servicing.

2 Fire Detection and AlarmSystem DesignThe following design information isintended to provide guidance on aspectsof system design, specifically related tothe use of the control panel. Beforedesigning any fire alarm system, referenceshould be made to the BS 5839 Part1:1988 which is the Code normallyapplicable in the U.K., but this may besupplemented by additional requirementsto suit individual user needs.

2.1 Mains Supply ConnectionThe mains supply to the Control Panelshould be a 230Vac +10% -6% 50Hzsingle phase. Its connection to the panelshould be made via a 3A (5A for 8 ZonePanel) fused spur unit reserved solely tofeed the Control Panel.

2.2 Standby SupplyThe Control Panel will provide a standbysupply, under mains failure conditions,for a period of 72 hours followed by 30minutes of full alarm load, with anaverage detector load of 1mA per zoneand a total sounder load of 1A.

2.3 Fire Detection Circuits(Zone Circuits)The control panel include fire detectioncircuits, also referred to as zone circuits,for the connection of fire detectors andmanual call points. It is important toensure that the detectors and call pointsused are compatible with the controlpanel. Only the recommended devicesshould be used. It is important that allcall points are fitted with a 470 ohmsseries resistor. Failure to follow thisrecommendation may lead to inferiorperformance of the system.

Note: The maximum line loopresistance of a fire detection circuitshould not exceed 100 Ohms.

The recommended devices for firedetection circuit are:

• GENT 7630 Ionisation smoke detector

• GENT 7640 Optical smoke detector

• GENT 7650 Fixed temperature heatdetector

• GENT 7660 Rate of rise heat detector

• GENT 7670 High temperature heatdetector

• GENT 7610 Duct detector 24Vd.c.

• GENT 1195-OR Manual call point

• GENT 7011 Beam detector (only oneper zone allowed. Plus a seperatepower supply is required.

2.4 Monitoring Fire DetectionCircuitsEffective monitoring of the fire detectioncircuits relies on the end-of-line capacitorunit being present. A capacitor unit mustbe fitted after the last detector or manualcall point on a fire detection circuit, seeFigure 1. As the end-of-line capacitor unitis connected to prevent a fault conditionbeing annunciated any fire detectioncircuits not being used should beterminated in, or adjacent to, the controlpanel with an end-of-line capacitor unit.

Notice: A fire detection circuit wiringmust be one continuous circuit with nospur circuits being permitted.

Notice: The use of capacitor(s) and anassociated monitoring circuit is thesubject of British Patent 2101784.Foreign filing has also been undertaken.

CDM26Figure 1 Typical Fire Detection & Alarm System Schematic

FL121

Figure 2

To permit the removal of a plug-in firedetector to be annunciated as an open-circuitfault but prevent subsequent detectors or callpoints from being disconnected, each firedetector base should be wired with a diode.

10\96 Page 1 4188-285 Issue 8

Page 78: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

2.5 Alarm Sounder CircuitsTo comply with the requirements of BS5839: Part 1:1988, it is important thatboth alarm sounder circuits are used on allinstallations. Each alarm sounder circuitfor the 1,2 and 4 zone control panel israted at 24V 750mA, with a maximumalarm sounder current of 1 A distributedbetween the two alarm sounder circuits.The 8 zone control panel has each alarmsounder circuit rated at 24V 1.5A, with amaximum alarm sounder current of 2Adistributed between the two alarm soundercircuits.

The recommended devices for use are:

• GENT 2511 Electronic Sounder 24Vdc.

• GENT 2141 Electronic Bell

2.6 Monitoring of AlarmSounder CircuitsEach alarm sounder circuit is monitoredfor both short and open circuit wiringfault. This requires that the remote end ofeach alarm sounder circuit is fitted with a22K Ohm end-of-line resistor. An alarmsounder circuit wiring must be onecontinuous circuit with no spur circuitsbeing permitted. Also to allow themonitoring function to operate effectively,it is important that all sounders include aseries blocking diode that will only allowcurrent to flow through the sounders whenthe supply is polarised in accordance withthe terminal markings on the control panelprinted circuit board. For monitoringpurposes, each alarm sounder circuit isfed with a reversed polarity supply whichonly permits current to flow through theend-of-line resistor.

2.7 Class Change CircuitA pair of unmonitored terminals areprovided to permit the system alarmsounders to be actuated from a remoteposition. It is considered that the majoruse for these will be for class changefunctions in schools and colleges. Thewiring connecting these terminals to thenormally open initiating contacts is notmonitored for an open circuit fault. Cablelength is 100m maximum.

2.8 Auxiliary Relay ContactsA set of normally open contacts and anisolated set of normally closed contactshave been provided for triggeringauxiliary circuits. These contacts arerated at 24V d.c. 1A for a resistive load.These contacts should not be used toswitch voltages in excess of extra lowvoltage of 50V. Any auxiliary circuitsshould be powered from an independentpower supply and should not use thepower of the control panel as this mayhave a detrimental affect on batterystandby capability of the control panel.For the 1 and 2 zone control panel,these contacts operate with systemalarm sounders , whereas for the 4 and8 zone panel the contacts operate withonly the fire condition.

2.9 Repeat Panel Connections(Applicable for 4 & 8 ZoneControl Panels Only)The control panel include terminals forthe connection of a repeat panel to permitduplicate common fire and fault, togetherwith associated fire zone indications. The24V positive supply connection to therepeat panel is protected by a 1A fuse onthe printed circuit board in the controlpanel. The power supply is not intendedto be a source of power for other ancillarydevices.

3 Installation InstructionsIt is recommended thatthe installation bedelayed until all buildingwork has beencompleted in the vicinityof the control panelposition. This willprevent the possibility ofdirt degrading theperformance orappearance of the controlpanel.

a) Remove control panelfrom its packing butretain the carton forstorage of spare partsand loose items.

b) Open control panelfront cover using the keyprovided and ifnecessary remove doorby extracting the hingefixing.

c) Remove the innercover of the controlpanel by removing itsfasteners.

d) Check the spares parts supplied withthose listed in Table 1. If replacementparts are required at any time, only sparesthat are of the same specification shouldbe used.

e) Remove the appropriate knock-outs onthe control panel case for cable entry. The4 or 8 zone control panel case hasknockouts provided to allow rear cableentry.

f) Hold the control panel on the wall inthe desired mounting position and markthe positions of the fixing holes. SeeFigure 3 for case fixing details.

g) Secure the control panel to the wallusing suitable fixing such that adequatesupport is provided to the control panelassembly. A top centre keyhole fixing isprovided on the case to allow the panel tobe hooked whilst the bottom two fixingpoints are located.

h) Terminate the cables into theappropriate terminal blocks on the printedcircuit board.

Note: Each customer terminal on theprinted circuit board would accept amaximum conductor size of 2.5mmsquare.

i) If it is not intended that the system becommissioned at this stage, the innercover and the front cover should berefitted and the system left without power.

j) Store spare parts and loose componentsincluding the batteries inside the controlpanel carton and keep in a safe place untilrequired.

FL123Figure 3 Case Fixing Details

Control Panel Sizes 1 Zone 2 Zone 4 Zone 8 Zone

Main Panel assembly 1 1 1 1Batteries 12V 2 2 2 2Instructions log book & Card 1 1 1 1Keys(Pack of 2) 1 1 1 1End-of-line Resistor 22k 2 2 2 2End-of-line Capacitor Unit 1 2 4 8End-of-line Label 3 4 6 10Shorting Link 1 1 1 1Fuse 800mA (Quick blow type) 1 1 1 -Fuse 2A(Quick blow type) - - - 1Fuse 2.5A(Quick blow type) 1 1 - -Fuse 3.15A (Quick blow type) 1 1 1 1Fuse 5A (Quick blow type) - - 1 1Zone designation label - 1 1 1Battery wire link 1 1 1 1Battery support bracket 1 1 2 2

Table 1 Part List

4188-285 Issue 8 Page 2 10\96

Page 79: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

4 One Man Commissioningand TestThe total system should be tested inaccordance with the commissioningrequirements of BS5839:Part 1:1988 orother standard specified by the systempurchaser.

a) When the system is to becommissioned, the batteries should beconnected as shown in Figure 4 and themains power supply connected. Ensurethe batteries are placed on the support(s)provided and securely fixed to the back ofthe case by using the sticky backed pads.

b) With the power supplied, the controlpanel should now be operational and thegreen power on lamp should beilluminated.

c)To facilitate commissioning and testingof this control panel, by one manservicing, a four way connector has beenincluded on the printed circuit boarddesignated P4 for the 1 and 2 zone controlpanels, and P7 for the 4 and 8 zonecontrol panels. A small black shorting linkis supplied to enable the control panel intoeither commissioning or test mode.

Test mode

To enable the control panel into the testmode, fit the shorting link across the twopins of connector P4 or P7 as shown inFigure 5. The fire detection circuit(s) willthen appear disabled. However, in thismode any detector operated will be reset,automatically, after approximately sevenseconds, without giving any indication onthe control panel or starting the alarmsounders.

Commissioning mode

To enable the control panel into theCommissioning mode, fit the shorting linkacross the two pins of connector P4 or P7as shown in Figure 5. The fire detectioncircuit(s) will then appear disabled.However, in this mode any detector ormanual call point made active will causesystem alarm sounders to signal for twoseconds and subsequently a panel reset isperformed automatically afterapproximately seven seconds.

d) After each zone circuit has beencommissioned or tested it can be enabledseparately to operate as normal, seesection 5.5.

Important:The shorting link MUST BEREMOVED from connector P4 or P7to restore the control panel to thenormal mode.

e) Write zone identification name onto thezone designation label, if provided, suchthat the name is adjacent to the respectivezone Fire and Fault lamps on the innercover of the control panel.

f) The label backing should then be peeledoff and label stuck onto the inner cover toallow appropriate zone indicator lamps toappear through cutout of the label.

g) Arrangements should now be made tothe ongoing maintenance of theinstallation as required by BS5839:Part1:1988 . GENT will provide a quotationfor this service upon request.

Note: The batteries supplied with thispanel have a self-dischargingcharacteristic during storage. If anypanels are put into service after theBattery Storage Expiry Date and whenpowered up a “Battery Fault” condition isinitiated, please contact the StockistRepresentative or Internal Sales Engineerat your local GENT office.

Under normal operating conditions thebatteries can have a useful life of up to 5Years from the date of their manufacture.The REPLACE BY DATE shown on thebattery label is calculated at 4 Years frommanufacture and it is stronglyrecommended that the batteries are changedby this date.

5 Operating Instructions The control panel provides systemsecurity by virtue of the lockable door andprovides clear indication of the indicatorlamps and easily readable instructions forthe system operator.

The automatic functions of the controlpanel, includes the annunciation of fireand fault conditions of the fire detectionand alarm system, without the need tooperate any of the push buttons control.Silencing of alarm sounders and the faultbuzzer, re-sounding of the alarm soundersand the operation of the test functions dorequire the operation of push buttons andthese are protected against unauthorisedactuation by the lockable hinged frontcover of the control panel. Once this coveris lowered, all push buttons are exposed,as are the basic instructions required bythe operator.

5.1Fire Condition• Common fire lamps are on

• Appropriate zone fire lamps are on, ifapplicable

• Internal fire buzzer is actuated

• System alarm sounders are actuated

• Any auxiliary equipment is actuated

• Any automatic link to the Fire Brigadeis initiated

Suggested action tosilence alarms andreset the system:

a) Press SILENCEALARMS push afteremergency is over.Notice the systemalarm Sounders aresilenced and internalfire buzzer changes tofault/supervisorybuzzer output. Allother fire conditionstatus remain active.

b) Press RESET pushafter the cause of thealarm has beeninvestigated, ensuresmoke and excess heathave had time to clear

cdm27 Figure 4 Fuses and Battery Connections

TEST COMMS

COMMS TEST

Link P4

Link P7

1 & 2 ZONE PANEL

4 & 8 ZONE PANEL

FL119

Figure 4 Commissioning and Test ModeLink Configurations

FL120

Figure 5 PushButton Controls

10\96 Page 3 4188-285 Issue 8

Page 80: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

from automatic detectors and brokenmanual call point glasses have beenreplaced where necessary. All the controlpanel indications and outputs will returnto their normal condition.

5.2 To Sound AlarmsIf it is necessary to actuate the alarmsounders when there is no fire indicated,or to re-sound the alarm sounders afterthey have been cancelled during a firecondition, for this the SOUND ALARMSpush should be pressed. The alarmsounders are then cancelled by pressingthe SILENCE ALARMS push.

5.3 Fault Condition• Common fault lamp is on

• Appropriate fault indicators are on

• Internal Fault/Supervisory Buzzer isactuated

Suggested action to rectify fault condition:

Press CANCEL FAULT BUZZER pushafter investigating fault. Notice the buzzeris silenced but other indications remainactive.

The fault lamps will be automaticallyextinguished once the fault condition isrectified. If the system detects a fireduring a fault condition the faultindicators may be extinguished. Details ofthe indications relating to specific faultconditions are shown in Table 2. Multiplefaults are simultaneously annunciatedwhen this does not cause confusion.However, a mains failure conditionoverrides all other fault indications inorder to preserve battery standby capacity.

5.4 To Test Lamps and BuzzerPress LAMP TEST push. All lampsshould be illuminated and theFault/Supervisory Buzzer should soundfor a period of approximately 2 seconds.

5.5 To Disable or Enable a FireDetection Zone (Available with4 or 8 zone control panel only)This function may beused for systemmaintenance purpose orfor the prevention ofinadvertent alarms whilethere is generalmaintenance or buildingwork being undertaken inareas protected byautomatic fire detectors.

Zone Disable

a) Press SELECT ZONEpush. This will cause oneof the amber zone faultindicator lamps to be onsteady. Repeatedly press the push until thenew zone lamp associated with the zoneto be disabled is on steady.

b) Press the DISABLE ZONE push untilthe steady indication disappears.

For any disabled zone(s) the indicator willpulse and the zone disabled warning lampwill be on. Also the fault/supervisorybuzzer will be on and will not cancel untilall zones are re-enabled.

Zone Enable

a) Press the RESET push.

b) Press the SELECT ZONE push untilthe appropriate zone indicator lamp is onsteady.

c) Press the ENABLE ZONE push and thezone will be enabled. Repeatedly press theSELECT ZONE push until the steadyindication disappears.

6 Routine TestingDailyThe British Standard Code of Practice forFire Detection and Alarm Systems forbuildings, BS 5839:Part 1:1988, statesthat the system should be inspected dailyto ensure that it is indicating a normalcondition and that any previouslyindicated Fault and Warning condition hasreceived appropriate attention. Itrecommends entry into the log bookprovided of all system events for futurereference.

WeeklyAt weekly intervals a different firedetector or manual call point of thesystem should be tested. The test shouldbe performed at regular time to avoidconfusion between a test and a genuinealarm. This would also provide a regularreminder to those occupying the premisesthat there is a fire alarm system with aparticular characteristic sound.

QuarterlyAt quarterly intervals the system shouldbe inspected and any work necessaryshould be performed by a trained engineerresponsible for the system.

6.1 Log BookTo comply with the requirements of BS5839:Part 1:1988 and to allow thoseconcerned with the fire detection andalarm systems to monitor the long termperformance of the system, it is importantthat a log is kept which includes all theevents relating to the performance of thesystem.

DISABLEZONE

ENABLEZONE

SELECTZONE

FL118

Figure 7 ZoneDisable/Enable

Controls

Visual Indications AudibleSounder Pro- Warning Indication

Com. Com. Zone Zone /Earth cessor Power ZoneFire Fault Fire Fault Fault Fault ON Disabled Buzzer CONDITION PROBABLE CAUSESred amber red amber amber amber green amber sound ANNUNCIATED

- - - - - - ON - - Normal Condition System is operating correctly

ON - ON/ - - - ON - ON Fire Condition An automatic fire detector- - PULSE - - - - - - or call point has operated

- - - ON& - - ON ON ON Disabled Zone Fire detection circuit hasPULSE been disabled by Engineer to

prevent inadvertent alarms.

- ON - ON - - ON - ON Zone Circuit A fire detector has been removedFault or detection circuit wiring

has open or short circuited.

- ON - - ON - ON - ON Alarm Sounder An alarm sounder circuit wiringCircuit Fault has open or short circuited or

its protection fuse has ruptured.

- ON - - ON& - ON - ON Earth Fault A part of the system has anPULSE electrical leakage path to earth.

- ON& - - - - ON - ON& Battery The battery or its wiring hasPULSE PULSE Disconnection failed, or its protection

fuse has ruptured.

- ON& - - - - - - ON& Mains Supply The Mains Supply to the panel isPULSE PULSE or Charger Fault faulty or the Regulated Supply

Fuse has ruptured or theBattery Charger has failed.

- ON& - - - - ON - ON& High Supply Regulated Supply voltage isPULSE PULSE Fault incorrect.

- - - - - ON ON - ON Processor The panels micro-computer hasFailure malfunctioned.

(ON&PULSE)=ON AND PULSING (ON/PULSE)=ON OR PULSING-if it is a recently activated zone.Note:The visual indications of zone fire and zone fault are not applicable to the 1 zone control panel. The zone disable warning indications are only applicable to the 4 and 8 zone control panels .

Table 2 Fault chart

4188-285 Issue 8 Page 4 10\96

Page 81: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Fire/Fault Interface Unit (for 3260 4/8 Zone Control Panel) 1. INTRODUCTIONThis leaflet provides sufficient information toinstall the 3260 Fire/Fault Interface Unit, code13260-41, and connect it to a 3260 (4/8Zone) Control Panel. This Interface Unit isintended to allow a 3260 Control Panel tolink with another fire detection system.

2. INSTALLATIONMount the Unit using the four holes locatedat each corner of the container.

Place the unit in the desired position and markthe four fixing holes onto the surface to whichthe unit is to be mounted.

Drill the four fixing holes and mount the uniton the surface with suitable fixings such thatadequate support is provided.

Terminate the cable at entry points andconnect the ends into the appropriateterminals on the printed circuit board, seeFigure 1.

CAUTION: Failure to make theconnections correctly can result in damageto the unit.

CAUTION: It is important NOT toundertake insulation tests of wiring withthe wires connected into their intendedterminals. THE ELECTRONICCOMPONENTS MAY BE SERIOUSLYDAMAGED.

PCB Connection details

The 4/8 Zone Panels have terminals providedfor a repeat indicator and these are used formaking connections to the Interface board, seeFigure 1 and Table 1.

External connections can bealtered by changing the links:

For signalling fire and fault toa zone of 3250,3260 or 3440fit X1, X4 (EOL Cap unit isalready fitted to Interface PCB).

For Signalling fire and fault tozone of 3228/3280 fit X2,X3,X4(EOL 2K2 resistor is alreadyfitted to Interface PCB).

For Separate SPCO contactsfor fire and fault fit X3 only.

Note - The on board alarmrelay for connection to aremote sounder circuit ispolarised and suppressed. If itis used at the end of amonitored circuit a suitablemonitoring component must beadded across the AS+, AS-terminals.

3260 ZONE PCBfl43

Figure 1 Wiring Diagram

Function 4/8 Zone

24V Supply 24+

0V Supply Z-(any)

Fire Signal CR

Fault Signal CF

Sounders CC1

Sounders CC2

Table 1 3260 Connection Points

8/95 4188-351 Issue 4

Page 82: GENT Xenex range of 1,2,4 and 8 zone fire Control and Repeat … · 2017-02-13 · manual call point on the circuit. All manual call points used must have a 470 ohms series resistor

Zonal Fire/Fault Interface Unit (for 3260 4/8 Zone Panel)1. INTRODUCTIONThis leaflet provides sufficient information toinstall the 3260 Interface Unit and connectionsto a 3260 (4/8 zone) Control Panel. TheseInterface Units are intended to allow 3260(4/8 zone) Control Panel to provide zonal firecontacts and a common fault signal to otherequipment such as multiplexers or datacollection systems.

13260-38 - 8 way Fire/Fault Interface PCB.

2. INSTALLATIONMount the Unit using the four holes locatedat each corner of the container.

Place the unit in the desired position and markthe four fixing holes onto the surface to whichthe unit is to be mounted.

Drill the four fixing holes and mount the uniton the surface with suitable fixings such thatadequate support is provided.

Terminate the cable at entry points andconnect the ends into the appropriate terminalson the printed circuit board. See Figure 1.

CAUTION: Failure to make theconnections correctly can result in damageto the unit.

CAUTION: It is important NOT toundertake insulation tests of wiring withthe wires connected into their intendedterminals. THE ELECTRONICCOMPONENTS MAY BE SERIOUSLYDAMAGED.

4/8 Zone 3260 Panels These panels have terminals provided for arepeat indicator and these are used formaking connections to the Interface Unit, seeTable 1 and Figure 1.

External Connections

The Interface Unit PCB has three links, formost applications all three are removed.

Fitting LK1 - Connects contact common withthe positive supply.

Fitting LK2 - Connects contact common withthe negative supply.

Fitting LK3 - Connects the sounder controlrelay coil to the common terminal. (Relayoperated by supply between B and Common).

CAUTION: LK1 and LK2 should NEVERbe fitted at the same time.

fl158

Figure 1 Connections for 8 Way Unit

Function 4/8 Zone

24V+ Supply 24+

0V Supply z-(any)

Common Fire CR

Zone 1 Fire R1

Zone 2 Fire R2

Zone 3 Fire R3

Zone 4 Fire R4

Zone 5 Fire R5

Zone 6 Fire R6

Zone 7 Fire R7

Zone 8 Fire R8

Fault CF

Sounders CC1

Sounders CC2

Table 1 3260 ConnectionPoints

7/95 4188-352 Issue 4