GENSYS – Documentation technique page 1/1 A40 Z0 9 0020 K-EN Technical documentation April 2009 Generator management module Technical Documentation CRE Technology believes that all information provided herein is correct and reliable and reserves the right to update at any time. CRE Technology does not assume any responsibility for its use unless otherwise expressly undertaken. CRE Technology 130 Allée Charles-Victor Naudin Zone des Templiers - Sophia Antipolis 06410 BIOT - FRANCE Phone: + 33 (0)4.92.38.86.82 - Fax: + 33 (0)4.92.38.86.83 www.cretechnology.com - [email protected] SARL au Capital de 300.000 Euros - RCS Antibes: 7488 625 000 15 N°TVA FR54 488 625 583 GENSYS

Upload: others

Post on 15-Mar-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

  • GENSYS – Documentation technique page 1/1 A40 Z0 9 0020 K-EN Technical documentation

    April 2009

    Generator management module Technical Documentation

    CRE Technology believes that all information provided herein is correct and reliable and reserves the right to update at any time. CRE Technology does not assume any responsibility for its use unless otherwise expressly undertaken.

    CRE Technology 130 Allée Charles-Victor Naudin

    Zone des Templiers - Sophia Antipolis 06410 BIOT - FRANCE

    Phone: + 33 (0)4.92.38.86.82 - Fax: + 33 (0)4.92.38.86.83 www.cretechnology.com - [email protected]

    SARL au Capital de 300.000 Euros - RCS Antibes: 7488 625 000 15 N°TVA FR54 488 625 583

    GENSYS

  • GENSYS – Documentation technique page 2/2 A40 Z0 9 0020 K-EN Technical documentation

    You can download this documentation and the different documentation relating to GENSYS on our web site: http://www.cretechnology.com/ . Documentation list on web site: • GENSYS technical documentation (this manual) • Complete variable list with label, units and limits • GENSYS menu help file (HELP windows file) • Web JAVA machine • CPA technical documentation • GCR technical documentation • C2S/SCR technical documentation

    NOTE : Bureau VERITAS marine approval : The control and monitoring functions must not be undertaken on the same module. The engine securities (min oil pressure, over speed and oil absent) must not be handled by the same module.

    NOTE : Read this entire manual and all other publications pertaining to the work to be performed before installing, operating, or servicing this equipment. Practice all plant and safety instructions and precautions. Failure to follow instructions can cause personal injury and/or property damage. Contact your CRE dealer for course training.

    Date Version Comments Par

    28-10-2008 J Integration of application notes and general reorganization LB

    31-03-2009 K Révision générale et mise à jour JAM

    http://www.cretechnology.com/�

  • GENSYS – Documentation technique page 3/3 A40 Z0 9 0020 K-EN Technical documentation

    Table of contents 1 Overview .............................................................................................................. 9

    1.1 European Union Directive Compliance CE ............................................................ 9 1.2 Environment .............................................................................................................. 9 1.3 Characteristics .......................................................................................................... 9

    2 Description ......................................................................................................... 10 2.1 Front panel .............................................................................................................. 10

    2.1.1 Display panel ................................................................................................................... 10 2.1.2 Service panel ................................................................................................................... 11 2.1.3 Control Panel ................................................................................................................... 11 2.1.4 Upper Panel ..................................................................................................................... 12

    2.2 Rear panel ............................................................................................................... 13 2.2.1 Overview .......................................................................................................................... 13 2.2.2 Inputs/Outputs ................................................................................................................. 13

    3 User interface .................................................................................................... 17 3.1 Internal browser description ................................................................................. 17

    3.1.1 Navigation Mode .............................................................................................................. 17 3.1.2 Input Mode ....................................................................................................................... 18 3.1.3 Save parameters configuration ........................................................................................ 18 3.1.4 Password protection ........................................................................................................ 18

    3.2 PC browser .............................................................................................................. 19 3.2.1 Setting up Windows XP ................................................................................................... 20 3.2.2 View Web Pages from the GENSYS Web Server ........................................................... 31 3.2.3 First level screens ............................................................................................................ 31

    3.3 Screensaver ............................................................................................................ 32 4 Operating modes ............................................................................................... 34

    4.1 Manu mode .............................................................................................................. 34 4.2 Auto mode ............................................................................................................... 34 4.3 Test mode ................................................................................................................ 35 4.4 Semi Auto Mode ..................................................................................................... 35

    5 Typical start sequence for fuel engines .......................................................... 36 6 Predefined configurations ................................................................................ 37

    6.1 Single generator in change-over mode (without paralleling) ............................. 37 6.2 Generators paralleling with inter GENSYS CANbus ........................................... 39 6.3 Generators paralleling with GENSYS and parallel line modules ....................... 40 6.4 Multiple generators with static paralleling ........................................................... 41

    6.4.1 Configuration ................................................................................................................... 41 6.4.2 Sequence: ........................................................................................................................ 41

    6.5 Single generator paralleled with mains (option 2) ............................................... 42 6.5.1 Mains paralleling modes: ................................................................................................. 43

    6.6 Power plant paralleled with mains ........................................................................ 44 6.6.1 Interfacing GENSYS with GCR ....................................................................................... 45

    6.7 Power plant paralleled with several mains .......................................................... 46 7 Installing and commissioning a GENSYS application ................................... 48

  • GENSYS – Documentation technique page 4/4 A40 Z0 9 0020 K-EN Technical documentation

    7.1 Wiring diagram ........................................................................................................ 48 7.2 Installation instructions: ........................................................................................ 48

    7.2.1 Panel cut-out: ................................................................................................................... 49 7.2.2 Mounting: ......................................................................................................................... 49 7.2.3 Earth grounding: .............................................................................................................. 50 7.2.4 Wiring guidelines: ............................................................................................................. 50 7.2.5 Vibrations: ........................................................................................................................ 51 7.2.6 Real time clock battery: .................................................................................................... 51

    7.3 Before commissioning (before going on site) ..................................................... 51 7.4 During commissioning ........................................................................................... 52

    8 Predefined functions ........................................................................................ 58 8.1 Water preheat / Pre-lubrication / Pre-glow functions .......................................... 58

    Auto mode ...................................................................................................................................... 58 Manual mode .................................................................................................................................. 58

    8.2 Crank / Fuel / Starter 2 / Starter 3 functions ......................................................... 58 8.3 Air fans..................................................................................................................... 59

    Auto mode ...................................................................................................................................... 59 Manu mode ..................................................................................................................................... 59

    8.4 Fuel filling / Coolant filling / Oil filling ................................................................... 59 Auto mode ...................................................................................................................................... 60 Manu mode ..................................................................................................................................... 60

    8.5 Configurable I/Os functions ................................................................................... 60 8.5.1 Digital input functions ....................................................................................................... 60 8.5.2 Configurable input label ................................................................................................... 60 8.5.3 Validity .............................................................................................................................. 60 8.5.4 Input functions .................................................................................................................. 60 8.5.5 Direction ........................................................................................................................... 63 8.5.6 Dedicated inputs .............................................................................................................. 63

    8.6 Digital output functions .......................................................................................... 63 8.6.1 Output functions ............................................................................................................... 63 8.6.2 Polarity ............................................................................................................................. 67

    8.7 Use spare analog input for digital input ............................................................... 67 8.7.1 Purpose: ........................................................................................................................... 67 8.7.2 Configuration: ................................................................................................................... 67 8.7.3 Parameters: ..................................................................................................................... 67

    9 Special functions .............................................................................................. 69 9.1 Fuel crank relay function ....................................................................................... 69

    9.1.1 Introduction ...................................................................................................................... 69 9.1.2 Configuration .................................................................................................................... 69

    9.2 Load sharing using a central frequency (de-drooping) ...................................... 70 9.2.1 Introduction ...................................................................................................................... 70 9.2.2 Procedure......................................................................................................................... 70 9.2.3 GCR synchronization & mains paralleling ....................................................................... 71 9.2.4 INTEGRAL INHIBITION ................................................................................................... 71

    9.3 Pulse control calibration procedure ..................................................................... 72 9.3.1 Parameters....................................................................................................................... 74

    9.4 Operator controlled return of mains ..................................................................... 74 9.5 Mains & Generator electrical fault options ........................................................... 74 9.6 GENSYS with external automatic start module ................................................... 77

    9.6.1 Overview .......................................................................................................................... 77

  • GENSYS – Documentation technique page 5/5 A40 Z0 9 0020 K-EN Technical documentation

    9.7 Remote start upon external pulse ......................................................................... 79 9.7.1 Setting external input ....................................................................................................... 79

    9.8 Safety Inhibitions .................................................................................................... 80 9.8.1 Objective .......................................................................................................................... 80 9.8.2 Configuration ................................................................................................................... 80

    9.9 GENSYS with 500Hz PWM (Cat/Perkins) .............................................................. 82 9.9.1 Schematic ........................................................................................................................ 82 9.9.2 Configuration ................................................................................................................... 83

    9.10 GENSYS with BSM II ........................................................................................... 84 9.10.1 Configuration ................................................................................................................... 84 9.10.2 Standard procedure ......................................................................................................... 84 9.10.3 Custom procedure ........................................................................................................... 85

    9.11 GENSYS with Carantec ....................................................................................... 86 9.11.1 Wiring parallel lines: ......................................................................................................... 86 9.11.2 Configuration of GENSYS ............................................................................................... 86

    9.12 GENSYS with TEM compact ............................................................................... 86 9.13 Under voltage trip coil ........................................................................................ 88 9.14 Level -1 (G59 & counters) ................................................................................... 89 9.15 Scada .................................................................................................................... 89 9.16 How to set a GPID ............................................................................................... 89

    9.16.1 Principle ........................................................................................................................... 89 9.16.2 Empirical method settings ............................................................................................... 90

    9.17 Automatic load / unload ...................................................................................... 90 10 GENSYS PLC .................................................................................................. 91

    10.1 Introduction ......................................................................................................... 91 10.2 File description .................................................................................................... 91 10.3 Parameter definition block ................................................................................. 91 10.4 Label definition block ......................................................................................... 92 10.5 Unit definition block ............................................................................................ 92 10.6 Initialization definition block .............................................................................. 93 10.7 Equation definition block ................................................................................... 93 10.8 End of file ............................................................................................................. 93 10.9 PLC programming language .............................................................................. 94

    11 Communication .............................................................................................. 96 11.1 CANBUS GOOD PRACTICES ............................................................................. 96 11.2 COM1: RS232 to PC ............................................................................................ 97 11.3 COM2: CAN bus inter GENSYS .......................................................................... 97

    11.3.1 Wiring ............................................................................................................................... 97 11.3.2 CAN bus fault ................................................................................................................... 98

    11.4 Broadcasting Data between GENSYS units ...................................................... 99 11.4.1 Introduction: ..................................................................................................................... 99 11.4.2 Procedure / Example ....................................................................................................... 99

    11.5 Can Bus Inhibition ............................................................................................. 103 11.5.1 How to set theses functions: .......................................................................................... 103

    11.6 COM3: CANopen remote I/O ............................................................................. 104

  • GENSYS – Documentation technique page 6/6 A40 Z0 9 0020 K-EN Technical documentation

    11.6.1 System configuration ..................................................................................................... 106 11.6.2 Read / write I/O .............................................................................................................. 106

    11.7 COM3: MDEC (MTU) .......................................................................................... 107 11.7.1 Procedure....................................................................................................................... 107

    11.8 COM3: J1939 ...................................................................................................... 111 11.8.1 Configuration .................................................................................................................. 111 11.8.2 J1939 fault...................................................................................................................... 111 11.8.3 Engine Speed ................................................................................................................ 111 11.8.4 Coolant temperature ...................................................................................................... 111 11.8.5 Oil pressure .................................................................................................................... 111 11.8.6 Engine diagnostic ........................................................................................................... 112 11.8.7 J1939 Messages ............................................................................................................ 112 11.8.8 Advanced functions ........................................................................................................ 115 11.8.9 Engine notes .................................................................................................................. 115

    11.9 COM4: MODBUS RTU on serial port RS485 .................................................... 116 12 Troubleshooting ........................................................................................... 119 13 Variables ....................................................................................................... 121 14 Precautions .................................................................................................. 122 15 References ................................................................................................... 124

    15.1 Options ............................................................................................................... 124 15.2 Accessories ....................................................................................................... 124

    16 Company Information .................................................................................. 126

  • GENSYS – Documentation technique page 7/7 A40 Z0 9 0020 K-EN Technical documentation

    List of illustrations Figure 1 - Rear panel ............................................................................................................................ 13 Figure 2- Browser link description ......................................................................................................... 18 Figure 3 - Contextual keys for Input Mode ............................................................................................ 18 Figure 4 - Password input mode display ............................................................................................... 18 Figure 5 - Typical menu page ................................................................................................................ 19 Figure 6 - Typical configuration page .................................................................................................... 20 Figure 7 - GENSYS PC ................................................................................................................... 20 Figure 8 - Tree menu description .......................................................................................................... 32 Figure 9 - State machine ...................................................................................................................... 35 Figure 10 - Typical start sequence for fuel engines .............................................................................. 36 Figure 11 - Power plant in change over mode without paralleling ........................................................ 37 Figure 12 - Power plant with several generators ................................................................................... 39 Figure 13 - Static paralleling with 4 generators coupled together in emergency situation .................... 41 Figure 14 - Example with 4 generators coupled together in emergency situation. ............................... 42 Figure 15- Paralleling with mains .......................................................................................................... 42 Figure 16 - Typical sequence in No Break CO mode............................................................................ 43 Figure 17 - Typical sequence in permanent mode ................................................................................ 44 Figure 18 - Power plant paralleling with mains ..................................................................................... 44 Figure 19 - GCR GENSYS wiring diagram ....................................................................................... 45 Figure 20 - Power plant paralleling with several mains ......................................................................... 46 Figure 21 - Power plant paralleling with several mains configuration ................................................... 47 Figure 22 - Panel cut-out ....................................................................................................................... 49 Figure 23 - Mounting kit ......................................................................................................................... 49 Figure 24 - Mounting brackets on GENSYS ......................................................................................... 49 Figure 25 - Earth grounding .................................................................................................................. 50 Figure 26 - Interconnection of all battery negatives .............................................................................. 51 Figure 27 - Connecting CAN bus with isolators .................................................................................... 51 Figure 28 - Speed output ....................................................................................................................... 53 Figure 29 - Voltage output ..................................................................................................................... 55 Figure 30 - Connections for water preheat, pre lubrication and pre glow ............................................. 58 Figure 31 - Connection for air fans ........................................................................................................ 59 Figure 32 - Connections for filling.......................................................................................................... 59 Figure 33 - Fuel filling diagram .............................................................................................................. 60 Figure 34 - Speed and voltage control with Contact / Pulses (1) .......................................................... 73 Figure 35 - Speed and voltage control with Contact / Pulses (2) .......................................................... 73 Figure 38 - Schematic ........................................................................................................................... 84 Figure 39 - Wiring GENSYS TEM ................................................................................................... 87 Figure 40 - Typical GPID controller ....................................................................................................... 89 Figure 41 - CAN Bus wiring ................................................................................................................... 97 Figure 42 - GENSYS GENSYS ........................................................................................................ 97 Figure 43 - GENSYS GENSYS GENSYS … .......................................................................... 98 Figure 44 - Mobile generator sets ......................................................................................................... 98 Figure 45 - CAN bus inhibition schematic (example) .......................................................................... 103 Figure 46 - Modular remote I/O extension module .............................................................................. 105 Figure 47 - CANopen coupler wiring ................................................................................................... 105 Figure 48 - Wiring diagram for Volvo EMS2 ........................................................................................ 116 Figure 49 - GENSYS GENSYS GENSYS … (MODBUS) ..................................................... 117 Figure 50 - Several generators warning .............................................................................................. 122 Figure 51 - One generator with mains warning ................................................................................... 122 Figure 52 - Standard cables ................................................................................................................ 125 Figure 53 - Access to CRE Technology in Sophia Antipolis ............................................................... 126

  • GENSYS – Documentation technique page 8/8 A40 Z0 9 0020 K-EN Technical documentation

    List of tables Table 1 - GENSYS Front Panel ............................................................................................................. 10 Table 2 - LCD screen characteristics .................................................................................................... 10 Table 3 - Display Panel keys ................................................................................................................. 11 Table 4 - Service Panel keys ................................................................................................................. 11 Table 5 - Control Panel keys ................................................................................................................. 12 Table 6 - Control Panel LEDs ................................................................................................................ 12 Table 7 - Inputs/Outputs description ...................................................................................................... 16 Table 8 - User interface ......................................................................................................................... 17 Table 9 - Screensaver description ......................................................................................................... 33 Table 10- Typical change over mode configuration .............................................................................. 37 Table 11 - Typical sequence in change over mode ............................................................................... 38 Table 12 - Typical basic multi Generator configuration ......................................................................... 39 Table 13 - Generator paralleling with parallel lines ............................................................................... 40 Table 14 - Typical basic configuration for GENSYS with parallel lines modules .................................. 40 Table 15 - Typical basic mains paralleling configuration ....................................................................... 43 Table 16 - Paralleling with mains configuration ..................................................................................... 45 Table 17 - GENSYS /GCR configuration ............................................................................................... 46 Table 18 - Input functions ...................................................................................................................... 63 Table 19 - Wiring GENSYS Auto Start Module ................................................................................ 78 Table 20 - Wiring GENSYS TEM ...................................................................................................... 87 Table 21 - Variables sent by BROADCAST DATA via Inter GENSYS CANbus ................................... 99 Table 22 - Variables received by BROADCAST DATA via Inter GENSYS CANbus .......................... 100 Table 23 - CAN bus inhibition parameters........................................................................................... 104 Table 24 - CANopen configuration example ....................................................................................... 107 Table 25 - MDEC connection .............................................................................................................. 108 Table 26 - Important parameters ......................................................................................................... 108

  • GENSYS – Documentation technique page 9/9 A40 Z0 9 0020 K-EN Technical documentation

    1 Overview

    1.1 European Union Directive Compliance CE The EMC Directive (89/336/EEC) deals with electromagnetic emissions and immunity. This product is tested by applying the standards, in whole or in part, which are documented in the following technical construction file: CEM 2004/108/EC, which replaces directive CEM (89/336/EEC) relative to electromagnetic emissions as from July 20th 2009. This product is developed to respect harmonized norms: EN 55099:2009 EN 55099:2010 EN 55088:2008 2006/95/EC (replaced directive 73/23/EEC since January 16th 2007). SAE J1939/71, /73, /31 Other norms: EN 61326-1: 2006 (Industrial location) EN 55011 EN 61000-3-2 EN 61000-3-3

    1.2 Environment Operating temperature

    A40Z0 0 to 55°C A40Z1 -20 to 70°C A40Z2(GNSS) 0 to 55°C (UL certified) A40B0,B1, B2, B3, B4, B5 5 to 55 °C (Bureau Veritas Marine agreement) Storage temperature -30 to +70°C Humidity 5 to 95% Tropic-proof circuits for normal operation in humid conditions. Front panel: IP54 protection. Back panel: IP20 protection. Altitude: 2000m

    1.3 Characteristics Size 248x197x57mm (9.76x7.76x2.24in) Weight 1.9kg (4.2oz)

  • GENSYS – Documentation technique page 10/10 A40 Z0 9 0020 K-EN Technical documentation

    2 Description

    2.1 Front panel

    Table 1 - GENSYS Front Panel

    The display panel allows setting up and monitoring of the GENSYS configuration and the power plant it controls. It provides a large LCD display and a keypad. See "User interface" chapter, for more details about the functions of LEDs & Keys.

    LCD characteristics Value Unit

    Viewing area 240x128 dot

    114x64 (4.49x2.52) mm (in)

    30x16 Characters

    Character size (small font) 2.7x3.6 (0.1x0.14) mm (in)

    (standard font) 3.6x3.6 (0.14x0.14) mm (in)

    (large font)

    9.45x9.45 (0.37x0.37) mm (in)

    Back light 60 cd/m²

    LCD mode STN

    Table 2 - LCD screen characteristics

    2.1.1 Display panel

    Key Navigation mode Input mode (during parameter modification)

    Navigation bar

    scroll / select menus and parameters

    change parameter value

    Enter

    enter a menu / switch to ‘Input mode’

    Validate parameter and return to ‘Navigation mode’

    Control Panel

    Display Panel

    Service Panel

  • GENSYS – Documentation technique page 11/11 A40 Z0 9 0020 K-EN Technical documentation

    Shift

    Used with other keys only (F1, F2, I). Shift + I saves all parameters.

    Not used.

    F1

    Shortcut to special function Increase speed in manual mode. Increase voltage when associated with Shift key in manual mode.

    F2

    Shortcut to special function Decrease speed in manual mode. Decrease voltage when associated with Shift key in manual mode.

    Esc

    Return to parent menu Discard parameter changes and return to ‘Navigation mode’

    Table 3 - Display Panel keys

    2.1.2 Service panel The five dedicated keys of the service panel allow you to switch to special menus or functions directly. See "User interface" chapter for more details about the functions of LEDs & Keys.

    Key Function

    Buzzer

    This key will stop the buzzer and turn the associated LED off. The associated red LED indicates the status of the buzzer output.

    Fault !

    Direct access to the Fault menu. An associated red LED indicates the Fault status of the generator. Pressing this key will switch to the associated menu, showing active faults. Pressing a second time on the same key will switch back to the menu displayed beforehand.

    Alarm ! Direct access to the Alarm menu. An associated orange LED indicates the Alarm status of the generator. Pressing this key will switch to the associated menu, showing active alarms. Pressing a second time on the same key will switch back to the menu displayed beforehand.

    Info

    1. Direct access to global monitoring page (user configurable). 2. Save parameters in flash storage when pressed with SHIFT: this action is called “SHIFT-I” Pressing this key will switch to the associated menu, which is custom made and contains parameters the user wants to monitor easily. Pressing a second time on the same key will switch back to the menu displayed beforehand.

    Bulb

    LED test: pressing this key will turn on all GENSYS LEDs. It is a simple test to check the LEDs and the keypad.

    Table 4 - Service Panel keys

    2.1.3 Control Panel The control panel allows the user to pilot and control the generator. See "User interface" chapter, page 17, for more details about the functions of LEDs & Keys.

    Key Function

    LED upper right

    This LED is not associated with any key. It is illuminated when a key is pressed and switched off when all keys are released. This LED also stays on during a save parameters command (see SHIFT-I above).

  • GENSYS – Documentation technique page 12/12 A40 Z0 9 0020 K-EN Technical documentation

    Auto

    Switches the system to automatic mode. The associated LED is ON when AUTO mode is activated.

    Test

    Switches the system to test mode. The associated LED is ON when TEST mode is activated.

    Manu

    Switches the system to manual mode. The associated LED is ON when MANU mode is activated.

    Start

    Starts the generator (only available in manual mode).

    Stop

    Stops the generator (only in manual mode).

    O/I

    Closes/opens the generator breaker (only in manual mode).

    O/I

    Closes/opens the mains breaker if available (only in manual mode).

    Table 5 - Control Panel keys

    Led Function

    Engine

    Shows green when engine is running

    Alternator

    Shows green when generator voltage is present

    Genset breaker

    Shows green when generator breaker is closed

    Mains breaker

    Shows green when mains breaker is closed

    Mains / Bus

    voltage

    Shows green when voltage is present at Mains/bus input

    Table 6 - Control Panel LEDs

    2.1.4 Upper Panel The upper panel displays the status of the power supply. See "User interface" chapter for more details about the functions of LEDs & Keys.

  • GENSYS – Documentation technique page 13/13 A40 Z0 9 0020 K-EN Technical documentation

    2.2 Rear panel 2.2.1 Overview

    Figure 1 - Rear panel

    2.2.2 Inputs/Outputs

    Pin nb Description Terminal capacity (mm² / AWG)

    Comment

    A1 Crank relay out 2.5 / 12 Supplied via emergency stop input at battery positive voltage; 16 Amps.

    A2 Fuel relay out 2.5 / 12 Supplied via emergency stop input at battery positive voltage; 16 Amps.

    A3 Emergency stop 2.5 / 12 To battery positive, normally closed; direct supply to crank and fuel relay outputs.

    B1 Generator N 2.5 / 12 Not necessarily connected: if not connected, GENSYS will calculate a virtual neutral voltage.

    B2 Generator L1 2.5 / 12 100 to 480 VAC line to line. Frequency: 50 or 60 Hz. 100 mAmps / 600 VAC fuses. For UL homologation: - 100 to 230VAC line to line - Fuses must be UL 248-14 listed. - Surge protection must be UL1449 listed.

    B3 Generator L2 2.5 / 12

    B4 Generator L3 2.5 / 12

    B5 Mains L1 2.5 / 12 100 to 480 VAC line to line. Frequency: 50 or 60 Hz.

  • GENSYS – Documentation technique page 14/14 A40 Z0 9 0020 K-EN Technical documentation

    B6

    Mains L3 2.5 / 12 100 mAmps / 600 VAC fuses. For UL homologation: - 100 to 230VAC line to line - Fuses must be UL 248-14 listed. - Surge protection must be UL1449 listed.

    C1 to C5

    Output 1 to 5 2.5 / 12 350 mAmp. Over current protected. Reactive load. Each output can be configured with a specific function (see option list in the Z090014.chm file) or programmed with an equation.

    D1 Generator I1- 2.5 / 12 0 to 5 Amps. Maximum rating: 15 Amps during 10s. 1 VA consumption. Each phase is isolated from the others and from the supply voltage. For UL homologation: External current transformer must be UL506 listed.

    D2 Generator I1+ 2.5 / 12

    D3 Generator I2- 2.5 / 12

    D4 Generator I2+ 2.5 / 12

    D5 Generator I3- 2.5 / 12

    D6 Generator I3+ 2.5 / 12

    D7 Mains I1- 2.5 / 12 0 to 5 Amps. Maximum rating: 15 Amps during 10s. 1 VA consumption. Each phase is isolated from the others and from the supply voltage. For UL homologation: External current transformer must be UL506 listed.

    D8

    Mains I1+ 2.5 / 12

    E1 Mains breaker NC 2.5 / 12 230 VAC, 5 Amps. Isolated relay contact. E2 Mains breaker NO 2.5 / 12

    E3 Mains common 2.5 / 12

    E4 Gen breaker NC 2.5 / 12 230 VAC, 5 Amps. Isolated relay contact. E5 Gen breaker NO 2.5 / 12

    E6 Gen common 2.5 / 12

    F1 Engine meas. 1- 2.5 / 12 0 to 10 kOhms resistive sensors with programmable gain. F2 Engine meas. 1+ 2.5 / 12

    F3 Engine meas. 2- 2.5 / 12 0 to 10 kOhms resistive sensors with programmable gain. F4 Engine meas. 2+ 2.5 / 12

    F5 Shield 2.5 / 12

    F6 Water temp meas. - 2.5 / 12 0 to 400 Ohms resistive sensors.

    F7 Water temp meas. + 2.5 / 12

    F8 Oil pressure meas. - 2.5 / 12 0 to 400 Ohms resistive sensors.

    F9 Oil pressure meas. + 2.5 / 12

    G1 0-20 mA + 2.5 / 12 +/- 10 V (20 kOhms input) or +/- 20 mAmps (50 Ohms input). Used as Mains power input with single generator. Used as synchronization input from GCR (terminal 42) when several generators parallel with mains

    G2 Shield 2.5 / 12

    G3 0-20 mA - 2.5 / 12

    G4 Parallel. - 2.5 / 12 5V (10KOhms) Load sharing and power set level (kW only). G5 Shield 2.5 / 12

  • GENSYS – Documentation technique page 15/15 A40 Z0 9 0020 K-EN Technical documentation

    G6

    Parallel. + 2.5 / 12 Compatibility with GCR (CRE product) and with analogue load sharing line. Compatibility with Wheatstone bridge. Only used with GCR or old ILS Isolated.

    G7 Pickup - 2.5 / 12 50 Hz to 10 kHz. Maximum voltage: 40VAC Used for speed regulation, crank drop out and over-speed (see precautions in chapter 4.2.8). If not wired, the speed measurement can be made by the alternator voltage. But pickup is recommended.

    G8 Pickup + 2.5 / 12

    G9 Speed out + 2.5 / 12 G9: +/- 10 V analogue outputs. G11: +/-10V input from speed governor (ESG) Compatibility with most of speed regulators. Independent gain and offset software adjustment (see Z0900014.chm file).

    G10 Shield 2.5 / 12

    G11 Speed ref 2.5 / 12

    H1 Not connected 2.5 / 12

    H2 AVR out + 2.5 / 12 Analogue output. Automatic voltage regulator (AVR) set level (see Z0900014.chm file for further explanations). Stanford, AVK and Leroy Somer automatic voltage regulators already tested. For others, ask your dealer. Isolated.

    H3 Shield 2.5 / 12

    H4 AVR out - 2.5 / 12

    J1 Mains breaker in 2.5 / 12 Digital input with 10 kOhms pull-up.

    Dedicated input for mains breaker feedback. Accepts NO or NC contacts to 0V. Not isolated.

    J2 Gen breaker in 2.5 / 12 Digital input with 10 kOhms pull-up.

    Dedicated input for generator breaker feed back. Accepts NO or NC contacts to 0V. Not isolated.

    J3

    Remote start/stop 2.5 / 12 Digital input with 10 kOhms pull-up. Dedicated input for remote start/stop request in Auto mode. Accepts NO or NC contacts to 0V. Not isolated.

    J4

    Oil pressure 2.5 / 12 Digital input with 10 kOhms pull-up. Dedicated input for oil pressure fault. This sensor is needed to start the engine whatever the mode. Accept s NO or NC contacts to 0V. Not isolated.

    J5 Water temp 2.5 / 12 Digital input with 10 kOhms pull-up.

    Dedicated input for water temperature fault. Accept s NO or NC contacts to 0V. Not isolated.

    J6 to J15

    Input 1 to 10 2.5 / 12 Digital inputs with 10 kOhms pull-up. 10 inputs can be configured with a specific function (see option list in the Z090014.chm file) or programmed with PLC equations. Accept s NO or NC contacts to 0V. Not isolated.

    K1 Reserved 2.5 / 12 Used for 12V power supply backup during crank time. See A40U200000 documentation for more information.

    K2 Power supply + 2.5 / 12 9 to 40 V, 10 Watt consumption (without actuator).

  • GENSYS – Documentation technique page 16/16 A40 Z0 9 0020 K-EN Technical documentation

    K3

    Power supply - 2.5 / 12 Polarity inversion protection. Note: The "Power supply -" must be wired from the speed governor using 4 mm² wires. See "state of the art" rules wiring diagram. 5 Amps / 40 VDC fuse recommended. For UL homologation: Fuse must be UL 248-14 listed.

    K4 Actuator + 2.5 / 12 200 Hz PWM output (6 Amps continuous). Power supply of actuator. Compatibility with most standard electromagnetic actuators. (Barber Colman, GAC, SynchroStart) Needed to activate an OPTION (To be ordered with the product).

    K5

    Actuator - 2.5 / 12

    COM1

    RS232 to PC or modem

    Female DB9

    Straight cable is needed. 19200 bps, 8b, no parity, 1 stop bit. Communication with a local computer. Used for configuration, parameters, file downloading and uploading. Uses a TCP/IP protocol to communicate. Not isolated. Not to be connected while engine running.

    COM2

    CAN1 to other GENSYS

    Male DB9 125 kbaud. Standard CAN© / proprietary protocol. Used to communicate with other GENSYS units (kW, kVAR, dead bus management) and for broadcast data function. Not isolated.

    COM3

    CAN2 to options Male DB9 125 kbaud. Standard CAN© / CANOPEN© protocol. Used to communicate with remote I/O (WAGO) (see remote I/O chapter) or with engine management units (option 4). Not isolated.

    COM4

    RS485 / MODBUS RTU Male DB9 4800, 9600 or 19200 bps. Used to communicate with SCADA. MODBUS RTU slave. Read (04 and 03) and write (06) functions. 2 wires mode.

    Table 7 - Inputs/Outputs description

  • GENSYS – Documentation technique page 17/17 A40 Z0 9 0020 K-EN Technical documentation

    3 User interface

    Table 8 - User interface

    The user interface can be controlled through two different ways: • Directly on local browser using front panel LCD screen and keyboard • Remotely through an internet browser running on a PC

    3.1 Internal browser description GENSYS can be configured and monitored remotely with a Web browser such as Internet Explorer or Netscape Navigator.

    For local usage, GENSYS has an embedded browser which is able to display the same information pages as the remote Web browser.

    The user can navigate through the different menus with the navigation bar and the / keys.

    3.1.1 Navigation Mode The navigation bar provides 5 contextual keys. Depending on the menu displayed, different icons may appear above these keys, allowing the user to scroll up/down the pages or to select a link to a new menu or parameter.

    When the user selects a parameter and presses the ‘ ’ key, the browser switches to the ‘Input mode’.

    The 5 icons above contextual keys will change appearance depending on the type of parameter to change (list of choice, label, numerical value, password...).

    When in ‘Input mode’, the key will discard the parameter changes and return to the ‘Navigation

    mode’. The key will confirm the parameter changes and return to the ‘Navigation mode’.

    The browser displays a white pointer in front of each link or parameter of a menu. A black pointer will indicate the active link or parameter. Figure 2- Browser link description shows these two pointers:

  • GENSYS – Documentation technique page 18/18 A40 Z0 9 0020 K-EN Technical documentation

    Figure 2- Browser link description

    3.1.2 Input Mode

    To change a parameter, first select it with contextual keys and press to switch to ‘Input mode’. New icons will appear above the contextual keys, depending on the kind of parameter selected.

    Label modification:

    Digital value modification:

    List of options modification :

    Figure 3 - Contextual keys for Input Mode

    When the new parameter value is input, the user must press key to store and confirm the new value.

    3.1.3 Save parameters configuration All GENSYS parameters used in configuration are stored in a FLASH memory. When a parameter is changed by the user, the new value is stored in a RAM memory. This new value will be effective as soon as it is entered, but it will be lost if the GENSYS power supply is cut or too low. To save the new

    parameters in FLASH, you must use “SHIFT-I”. The user must press both + keys together. This will start the backup sequence and store all parameters in the FLASH memory. Now, the new parameters will be effective even after a power supply failure.

    3.1.4 Password protection The GENSYS has different password levels, allowing access to more or less critical parameters or

    menus. When the password page is shown on the LCD display, the user must first press on the key (like for other parameters) to switch to the ‘Password Input mode’.

    Figure 4 - Password input mode display

    Three lines of characters (upper case and lower case letters and ‘0’ to ‘9’ characters) will appear along with 5 icons above the contextual keys.

    NOTE:

    Due to the great number of parameters. The back-up procedure may take a few seconds. It is thus essential to save parameters when the motor is stopped. To save all

    parameters, the user must press at the same time on both + keys on the GENSYS front panel. Otherwise, the new parameters will be lost when shutting down the GENSYS.

  • GENSYS – Documentation technique page 19/19 A40 Z0 9 0020 K-EN Technical documentation

    The first four contextual keys allow the user to move the cursor up, down left or right onto the desired character. The last key (OK icon) will validate the selected character and write it in the password line (a * will appear).

    When all characters are entered, another press on the key will validate the password. If it is correct, the main menu will appear on the LCD display. Otherwise, the password page will be displayed again.

    Default settings for the password are:

    • Level 0: no password entered, just press "Enter" key. • Level 1: 1. • Level 2: Only for distributors.

    The password of your level and those lower can be changed in the system menu.

    Note: the menus might differ according to the security level of the password entered.

    3.2 PC browser GENSYS provides an efficient way of configuring your application thanks to its embedded Web server.

    It is thus possible to access the different menus with a simple Web browser such as Netscape Navigator or Internet Explorer. However, it is not recommended to be connected with the PC while the engine is running.

    Before connecting with the GENSYS you have to configure your computer as described in the next chapter ". The next figure show a typical GENSYS menu accessed from a PC Web browser.

    Figure 5 - Typical menu page

    In this page, the user can choose from among 6 submenus (Generator electrical meters for example). It is also possible to scroll up/down the other pages of the menu with the page up > links. The ESC link acts in the same way as the GENSYS ESC key: it will display the parent menu.

    The last 3 links are identical to the Fault / Alarm / Information key on the GENSYS front panel.

    The next figure shows a typical configuration page. The user can change 5 different parameters (in this case, two numerical values and three option lists) and send them to the GENSYS using the [Save] button. Clicking on the [Save] button changes the parameter immediately.

  • GENSYS – Documentation technique page 20/20 A40 Z0 9 0020 K-EN Technical documentation

    Figure 6 - Typical configuration page

    3.2.1 Setting up Windows XP Connecting a GENSYS with a PC is similar to connecting to Internet with a modem. GENSYS works as a modem and the integrated software works as an Internet provider. GENSYS also provides 1 web server. This web server sends HTML pages to your PC, and your PC browser is used to display it. Live data is refreshed with the JAVA applet.

    A40W0

    Figure 7 - GENSYS PC

    Data transfer takes place through a straight serial cable (with 9 wire DB9 connectors), as shown on the figure above.

    A few steps are required to configure a PC before controlling a GENSYS:

    • Install the modem. • Create a Dial-Up Networking Connection. • Check the network properties. • Set-up the internet security properties.

    Communication between the GENSYS and the PC is carried out via a Dial-Up Network.

    NOTE :

    The user must press on both + keys at the same time on the GENSYS front panel to save the parameters permanently. Otherwise, the new parameters will be lost when shutting down the GENSYS.

  • GENSYS – Documentation technique page 21/21 A40 Z0 9 0020 K-EN Technical documentation

    The PC must be configured to communicate with a 19.2K bps modem with TCP/IP networking enabled.

    3.2.1.1 Check the network properties

    Click Start, Settings, and Network Connection.

    Dial-Up Adapter and TCP/IP -> Dial-Up Adapter protocols must be present in the list. If they are not there, create a new connection using the new connection wizard.

    In the New Connection Wizard, select “connect to the network at my work place”. Then, click “Next”.

  • GENSYS – Documentation technique page 22/22 A40 Z0 9 0020 K-EN Technical documentation

    Select “Dial-up connection”. Click on “Next”

    In the next page, select a 19 200 bps modem. Then, click “Next”.

    In the connection name dialog box, in the “Company name” field write “GENSYS”. Click on “Next”

    In the “Phone number to dial” dialog box, in the “Phone number” field, write: “123”. Then click “Next”.

  • GENSYS – Documentation technique page 23/23 A40 Z0 9 0020 K-EN Technical documentation

    The new connection is now installed. Select “Add a shortcut to this connection to my desktop”. Then click on “Finish”.

    3.2.1.2 Install the Modem Click Start, Settings, and Control Panel.

    In the Control Panel, double-click the Modems icon.

    In the Modems Properties dialog box, click Add.

    Double click on “Add hardware” icon.

  • GENSYS – Documentation technique page 24/24 A40 Z0 9 0020 K-EN Technical documentation

    Click on “Next”.

    Choose the “Modem” icon.

    Then, choose “Add a new hardware device”, and click “Next”.

    Select “Yes, I have already installed the hardware”, and click “Next”.

  • GENSYS – Documentation technique page 25/25 A40 Z0 9 0020 K-EN Technical documentation

    Select install the hardware that I manually select from a list (Advanced)”. Then, click “Next”.

    The following dialog box will appear: select option “don’t detect my modem; I will select it from a list”. Then, click “Next”.

    In the next dialog box, under Manufacturers, Standard Model Types should be selected. Under Models, select Standard 19200 bps Modem, then click Next.

    In the next dialog box, select the Communications Port where GENSYS is connected as the port, and then click Next.

  • GENSYS – Documentation technique page 26/26 A40 Z0 9 0020 K-EN Technical documentation

    After Windows installs the modem, click Finish.

    3.2.1.3 Set the Modem Properties Back in the Modem Properties dialog box, select the new modem (Standard 19200 bps Modem) and then click Properties.

    In the “General” tab, check that the port speed is: 19 200 and the flow control is “hardware”.

    In the Advanced parameters, in the “advanced options” tab, ensure that the modem is configured for 8 data bits, no parity, and one stop bit. Then click “OK”.

    Click OK until you exit this dialog box.

    Create a Dial-Up Networking Connection.

    In the Control Panel, select Network Connection.

    Double click on the “GENSYS” icon.

  • GENSYS – Documentation technique page 27/27 A40 Z0 9 0020 K-EN Technical documentation

    In the “Connection to GENSYS dialog box”, click on “Properties”.

    In the “General” tab, ensure that the selected modem is the modem installed in the previous step.

    In the “Option” tab, in the dialling option, select “Display progress while connecting”.

  • GENSYS – Documentation technique page 28/28 A40 Z0 9 0020 K-EN Technical documentation

    In the “Security” tab, select “Typical (recommended settings)”.

    In the “Networking” tab, select “PPP Windows 95/98/NT4/2000, Internet”. Select “Internet Protocol”. Click on “Install”.

    In the “General” tab, select “Use the following IP address” and write: 192.168.11.2. Then select “Advanced”.

  • GENSYS – Documentation technique page 29/29 A40 Z0 9 0020 K-EN Technical documentation

    In the “General” tab, disable every tick box.

    In the “DNS” tab, select “Append primary and connection specific DNS suffixes” and “Append parent suffixes of the primary DNS suffix”.

    In the “WINS” tab, select “enable LMHOSTS lookup” and in the NetBIOS setting, select “enable NetBIOS over TCP/IP. Then, click OK.

  • GENSYS – Documentation technique page 30/30 A40 Z0 9 0020 K-EN Technical documentation

    Back in the “GENSYS properties dialog box”, click on “Advanced tab. In this tab, ensure that every option is disabled. Then, click OK.

    3.2.1.4 Setting the internet security properties • In the Control panel, double-click the Add/Remove program icon. • If present, uninstall the Java sun program. Click OK. • Run the msjavwu_.exe program provided in the CD Rom. • Click Start, Settings, and Control Panel. • In the Control Panel, double-click the Internet Options icon. • Under the Security tab, select Trusted Sites and click on Add Sites…. Check that Require server

    verification (https :) for all sites in the zone is disabled. In the Zone field write "http://GENSYS" and click on Add. Click OK.

    • Under the Security tab, select trusted sites, click on Customize…. In Java (or Java VM for 95, or Microsoft VM for ME) and Java permissions, select Custom. Click on the Java Custom Settings button. Under the Edit permissions tab, enable the Access to all Network Addresses in the Run Unsigned Content part. Click OK. Click OK. If a dialog box appears, click YES.

    • In the Connection tab, click on Never establish connection. Select GENSYS modem in the modem list Click on Settings, Use a proxy server must be disabled. Click OK.

    • Under the Advanced tab, in the Java VM field (Microsoft VM for ME); check that Java JIT enabled is selected. Click OK.

    • Close Control panel. • Copy the file named hosts from the GENSYS CD Rom “C:\WINDOWS\system32\drivers\etc”

  • GENSYS – Documentation technique page 31/31 A40 Z0 9 0020 K-EN Technical documentation

    3.2.1.5 Connect the GENSYS Connect one end of a DB-9 serial cable to the COM1 port of the PC. Connect the other end of the cable to the connector labelled "RS232 to PC or modem" on the GENSYS.

    Double-click on the Shortcut to GENSYS icon. In the Connect to dialog box, click CONNECT. Click close.

    If the connection is OK, an icon (2 small computers) in the bottom right of the screen appears.

    3.2.2 View Web Pages from the GENSYS Web Server After the TCP/IP connection has been established with GENSYS, you can view GENSYS menus with any standard Web browser such as Firefox or Internet Explorer.

    Start the web browser (Internet explorer, Firefox …).

    In the “Location” or “Address” field of the web browser, enter the URL of the GENSYS: http://gensys (CAUTION: host file must be present in “C:\WINDOWS\system32\drivers\etc” and must contain a line such as: « 192.168.11.1 GENSYS » The GENSYS password page should appear in the browser window. Enter your password.

    You can now browse through the different GENSYS menus.

    To close the connection, double-click on the connection icon in the status bar of Windows. In the Connected to GENSYS dialog box, click Disconnect. Close your web browser.

    3.2.3 First level screens Upon power up, GENSYS displays the genset status (if EMERGENCY STOP not connected) or WELCOME SCREEN. The first level menu contains three entries: • Display • Configuration • System

    You can access it with next KEY sequence:

    => => => You then have access to the top level menu:

    => =>

    http://gensys/�

  • GENSYS – Documentation technique page 32/32 A40 Z0 9 0020 K-EN Technical documentation

    Figure 8 - Tree menu description

    See the Help file for the complete description of the tree menus.

    3.3 Screensaver GENSYS has automatic screensavers. They only appear on the GENSYS LCD screen when you press "Esc" in the password page or after an adjustable delay (GENSYS variable 1266). There are four screensavers and the display depends on the mode and state of GENSYS:

    Screensaver Description Display in Auto mode Display in Manu mode

    Customized screen

    4 customized lines Customer Logo Date and time

    In Wait state (engine stopped). In other cases.

    Generator overview

    KW (in large font) Voltage (in large font) Frequency (in big font) Running hours (in large font)

    When the generator breaker is closed.

    When the generator breaker is closed.

    Engine overview

    Crank Relay Output Fuel Relay Output Water Temp Digital Input Oil Pressure Digital Input Emergency Stop Remote start Nb of start attempts Battery voltage (bar graph) Engine speed (bar graph)

    In Start state and fault state. When you press Start or when in fault state.

    Synchronization column

    Frequency difference (bar graph) Voltage difference (bar graph) Phase difference (column)

    In Synchronization state.

    When the generator is ready and the generator breaker is opened.

  • GENSYS – Documentation technique page 33/33 A40 Z0 9 0020 K-EN Technical documentation

    Frequency match (OK / NOK) Voltage match (OK / NOK) Phase match (OK / NOK)

    Table 9 - Screensaver description

  • GENSYS – Documentation technique page 34/34 A40 Z0 9 0020 K-EN Technical documentation

    4 Operating modes With the GENSYS unit, three main operating modes and one special mode are available to allow you to control your generator.

    Modes are:

    • Manual • Automatic • Test Mode

    4.1 Manu mode In manual mode, it is possible to control the generator with the front panel of the GENSYS. All steps from engine start to paralleling are controlled by pushing keys. To start the engine push the [Start] key and hold down until the oil pressure fault disappears. On the front panel, the 2 LEDs above the generator should light up. The left hand LED indicates that a speed greater than zero is measured, whereas the right hand LED indicates that a voltage other than zero is measured.

    If a speed regulator is connected to GENSYS, it is possible to increase the speed with the F1 key, and decrease it with the F2 key.

    If a voltage regulator is connected to GENSYS, it is possible to increase and decrease the voltage with the SHIFT+F1 keys and SHIFT+F2 keys.

    When the generator is synchronized, it is possible to close the breakers with the 0/I keys.

    Important: The internal synch check relay is always active, i.e. it is impossible to close the breaker if the conditions for closing are not met.

    When the breaker is closed the corresponding LED on the front panel should light up.

    As soon as the generator breaker is closed, the GENSYS is switched to droop mode for speed and voltage, i.e. the speed and the voltage will decrease when the load increases.

    To stop the engine, push the Stop key.

    4.2 Auto mode Speed and voltage droop are inhibited in this mode, the system is running isochronously, i.e. the speed and the voltage remain unchanged whatever the load. This mode has 4 main ways of operating: One generator with Change Over:

    The generator starts with a remote start or in the case of mains failure. When the generator is ready (voltage, frequency), the mains breaker is opened and the generator breaker is closed. Should the mains return to normal conditions or remote start is off, after a programmed delay the generator breaker is opened, the mains breaker is closed and the generator set is stopped.

    One generator paralleling with the mains (option 2):

    The generator starts with a remote start or if there is a mains failure. Paralleling depends on configuration: NO CHANGE OVER, CHANGE OVER, NO BREAK CHANGE OVER, or PERMANENT Load sharing can be on a "base load" or "peak shaving" basis. Depending on the configuration, the generator will stop either when there is a remote stop or when mains power returns to a stable level.

    Power plant with several generators without automatic load/unload:

    The generator starts with a remote start signal, and parallels with the bus. If there is a dead bus, GENSYS will check with the other GENSYS units before closing the bus breaker (this depends on the

  • GENSYS – Documentation technique page 35/35 A40 Z0 9 0020 K-EN Technical documentation

    validation of the dead bus management). The load sharing is accomplished via the inter GENSYS CAN© or via the parallel lines. The generators stop with a remote stop signal.

    Power plant with several generators with automatic load/unload:

    The communication between GENSYS units is via the inter GENSYS CANbus and determines which generators start or stop. The number of generators used depends on load requirements (all generators receive the remote start signal but only start if necessary).

    4.3 Test mode This mode tests the Auto mode. When you press the [Test] key, the engine starts as if there was a remote start, and GENSYS will carry out the standard Auto mode sequence. To exit “TEST MODE”, push the [AUTO] key.

    4.4 Semi Auto Mode Similar to Auto Mode, except that to pass from one state to another you press a button. The following illustration shows the various states.

    Figure 9 - State machine

  • GENSYS – Documentation technique page 36/36 A40 Z0 9 0020 K-EN Technical documentation

    5 Typical start sequence for fuel engines During the start sequence protections are inhibited. This concerns all engine protections. When the engine reaches the required state (E2057 = 6, see next figure) the protections are activated. A timer can be added to inhibit protections during the "safety on" delay (E1514). The timer will start when E2057=6.

    SpeedNominal speed (1080 or 1081)

    Idle speed (1079)

    Startrequest

    Crank drop out (1325 or 1326 or 1327)

    Prelub1145

    Preglow1157

    Crank1135

    Crank rest1136

    Preglow1157

    Crank1135

    Warm up1139

    RPM stab1140

    Volt stab1141

    Safety on1514

    Stoprequest

    Cooling1142

    Rest1144

    Running timers

    Engine state (2057) 0 1 12 0109866543212112

    Crank relay out (2018) (Terminal A1)

    Fuel relay out (2019) (Terminal A2)

    Warm up (2214) (Terminal J6 to J15)

    Validation protection (2192)

    Gen. readyEngineready

    Figure 10 - Typical start sequence for fuel engines

  • GENSYS – Documentation technique page 37/37 A40 Z0 9 0020 K-EN Technical documentation

    6 Predefined configurations

    6.1 Single generator in change-over mode (without paralleling)

    Functions:- Manual mode- Auto mode- Test mode- Nb of running hoursAnalog / logical inputs :- Oil Pressure- Water temp- remote start- Emergency stop- Genset breaker aux- Mains breaker aux- Pickup frequency- Spares ...Logical outputs:- Crank- Fuel solenoid- Mains breaker- Genset breaker- SparesAnalog output:- analog signal to speed regulator

    Start/stop

    Alarms ...

    Mains

    - RMS reasurements (three or single phase)- Electrical protections (>V,f,Q, >P,>I, ...)

    Breakersmanagement

    Utility

    LVor

    HV(100-

    480Vac)

    GENSYS

    LVor

    HV(100-

    480Vac)

    LOA

    DC

    onso

    t

    OU

    GEN

    SET

    Pow

    er

    t

    LOA

    DC

    onso

    t

    GEN

    SET

    Pow

    er

    t

    MA

    INS

    Pow

    er

    t

    MA

    INS

    Pow

    er

    t

    Figure 11 - Power plant in change over mode without paralleling

    Variable number Variable label Variable value

    1179 Gen. number 1

    1147 Nb of gen. 1

    1148 Mains parallel ChangeOver

    1153 Mains regul X

    1158 ILS compatible No

    1177 Synchro mode Dynamic

    1515 Deadbus manag. X

    1258 Load/Unl. mode Inhibited

    1846 Break Ma Fault Mains

    1841 Fault start Yes

    Table 10- Typical change over mode configuration

  • GENSYS – Documentation technique page 38/38 A40 Z0 9 0020 K-EN Technical documentation

    In Change over mode, as shown in Table 10- Typical change over mode configuration, the generator starts and takes the load when a mains electrical fault occurs. When mains power returns, the generator breaker is opened and the mains breaker is closed after a pre-set delay. For the generator to start when mains failure occurs, either a protection (mains or other) or a digital input has to be configured as a "Mains electrical fault".

    If remote start is on when mains are present the generator starts, GENSYS opens the mains breaker, then closes the generator breaker and takes the load.

    400 V

    Mains electrical fault

    Mains voltage

    Fastest mainselectrical fault

    E2201

    E1085

    Remote start onterminal J3

    400 V

    Genset voltageGenset ready

    E1142CooldownGenerator CB

    Switchover delayE1459

    Mains CB E1459Swithover delay

    First black

    Second black

    First black

    Second black

    There are 2 blacks

    START FOR EMERGENCYwill only start if a mains protection or a digital input is programmed as

    "Mains electrical Fault".

    START FOR TESTor switch load from mains to genset

    There are 2 blacks

    E0022

    E2002

    E0003

    E2001

    E2000

    triggered by a protection ordigital input set as "Mainselectrical fault"

    Mains backtimer

    E1459Swithover

    delay

    E1459Switchover

    delay

    E1142Cooldown

    Table 11 - Typical sequence in change over mode

    Note: in "No change over" mode (1148) GENSYS only starts upon a remote start demand and doesn't manage the mains breaker.

  • GENSYS – Documentation technique page 39/39 A40 Z0 9 0020 K-EN Technical documentation

    6.2 Generators paralleling with inter GENSYS CANbus

    GENSYS 1 GENSYS nGENSYS 2

    CAN BusKW, KVAR, COS (f), ...

    Utility Figure 12 - Power plant with several generators

    Variable number Variable label Variable value

    1179 Gen. number 1 to n

    1147 Nb of gen. N (>=2)

    1148 Mains parallel No ch.over

    1153 Mains regul X

    1158 ILS compatible No

    1177 Synchro mode Dynamic

    1515 Deadbus manag. Yes

    1258 Load/Unl. mode X

    1020 MA kW 20mA 0

    1021 MA 0kW setting 0

    Table 12 - Typical basic multi Generator configuration

  • GENSYS – Documentation technique page 40/40 A40 Z0 9 0020 K-EN Technical documentation

    6.3 Generators paralleling with GENSYS and parallel line modules

    GENSYS 1 GENSYS nGENSYS 2

    CAN BusKW, KVAR, COS (f), ...

    Utility

    Analog load sharing lines

    ILS PowRcon

    Table 13 - Generator paralleling with parallel lines

    Variable number Variable label Variable value

    1179 Gen. number 1 to n

    1147 Nb of gen. n (>=2)

    1148 Mains parallel No ch.over

    1153 Mains regul X

    1158 ILS compatible Yes

    1177 Synchro mode Dynamic

    1515 Deadbus manag. No

    1258 Load/Unl. mode Inhibited

    Table 14 - Typical basic configuration for GENSYS with parallel lines modules

    When GENSYS is in ILS compatible mode, the active power sharing is handled via the parallel lines. You have to disconnect the AVR output (H2-H4) and have an external device control the reactive power (CT droop...).

  • GENSYS – Documentation technique page 41/41 A40 Z0 9 0020 K-EN Technical documentation

    6.4 Multiple generators with static paralleling This mode is useful as it allows: • Gradual magnetization of the step-up transformers (no transient short-circuit). • Full plant availability in less than 10 seconds.

    6.4.1 Configuration • One GENSYS per genset. • CAN bus must be connected between GENSYS units. • An "Excitation" output (e.g. exit C1) must be configured on each GENSYS unit. • GE breaker must be powered by 24VDC (so as to close without AC). • In the Setup menu / plant overview / sync mode. E1177 must be set as "A stop". • The value of the maximum excitation rpm is set with E1896 (default: 97%). • The alternators must be identical. • Each GENSYS must be equipped with a speed sensor (magnetic sensor / Pick-up).

    Figure 13 - Static paralleling with 4 generators coupled together in emergency situation

    6.4.2 Sequence: • Loss of voltage -> Dead Busbar • Each GENSYS is ordered to start (Terminal J3). • CB1, CB2, CB3 & CB4 close as ordered by the GENSYS units. • DG1, DG2, DG 3, and DG4 start. • All generators reach the speed defined by the E1896 setting (CANBUS synchronization). • All C1outputs close simultaneously to activate excitation (after dialogue between GENSYS

    units). • Alternator voltages increase gradually at the same time. • The plant is available to take up required load. • Breakers are closed when engine is stopped. • There is a residual voltage of 80V.

  • GENSYS – Documentation technique page 42/42 A40 Z0 9 0020 K-EN Technical documentation

    Figure 14 - Example with 4 generators coupled together in emergency situation.

    6.5 Single generator paralleled with mains (option 2)

    GENSYS

    Mains

    CPA2

    Utility Figure 15- Paralleling with mains

    In permanent mode (1148) and peak shaving mode (1153), a mains power measurement is required. Internal via D7-D8 inputs (Mains I1) or external via G1-G3 inputs (0-20 mA).

    Variable number Variable label Variable value

    1179 Gen. number 1

    1147 Nb of gen. 1

    1148 Mains parallel NoBreak CO / Permanent

    1153 Mains regul Base load / Peak shav.

    1500tr/min

    400V

    80V

    Time

    Speed

    9

    Voltage

  • GENSYS – Documentation technique page 43/43 A40 Z0 9 0020 K-EN Technical documentation

    1158 ILS compatible No

    1177 Synchro mode Dynamic

    1515 Deadbus manag. X

    1258 Load/Unl. mode Inhibited

    Table 15 - Typical basic mains paralleling configuration

    In all mains paralleling modes, if a "mains electrical fault" is set (via protections or digital inputs), the generator starts and takes the entire load upon mains loss even if the remote start is off. In all cases, you have to set a mains protection in order to determine the behaviour of your generator when mains power disappears.

    6.5.1 Mains paralleling modes: Choice of mains paralleling mode is configured through parameter E1178.

    No Break CO (No break change over):

    When remote start is on, the generator starts, synchronizes and parallels with the mains, then takes the load (ramps up). Once the mains are unloaded, GENSYS opens the mains breaker. When remote start is off, the mains takes the load in the same way as the generator did previously. If the generator started for a mains failure, when mains power returns the GENSYS synchronizes the load transfer (ramps down), opens the breaker and then stops the generator.

    START FOR EMERGENCYwill only start if a mains protection or a digital input is programmed as

    "Mains electrical Fault".

    START FOR TEST or to transfert load from mains to GE.

    Triggered byfastest "Mainselectrical fault"

    E1142Cooldown

    E1152Unloadramp

    E1151Load ramp

    Syn

    chro

    bac

    k

    Sho

    rt tra

    nsfe

    rt fro

    m G

    Eto

    Mai

    ns

    Sho

    rt tra

    nsfe

    rt fro

    mm

    ains

    to G

    E

    Syn

    chro

    bac

    k

    Sho

    rt tra

    nsfe

    rt fro

    m G

    Eto

    mai

    ns

    E1085Mains back

    timer

    400 V

    Mains electrical fault

    Mains voltage

    E2201

    Remote start onterminal J3

    400 V

    Genset voltage

    Generator CB

    Mains CB

    E0022

    E2002

    E0003

    E2001

    E2000

    Syn

    chro

    E1152Unloadramp

    E1142Cooldown

    There is only 1 black No black

    E1459Swithover

    delay

    GE

    read

    y

    GE

    read

    y

    Firs

    t Bla

    ck

    Figure 16 - Typical sequence in No Break CO mode

    Permanent:

    When the remote start is on, GENSYS starts the generator, synchronizes and parallels with the mains, then ramps up load until it reaches its set point. In base load mode (E1153), the generator has a constant load and the mains take the utility load variations. If the utility load is less than the generator

  • GENSYS – Documentation technique page 44/44 A40 Z0 9 0020 K-EN Technical documentation

    set point, mains are in reverse power. In the peak shaving mode (E1153), the mains have a constant load and the generator takes the utility load variations.

    Cooldown

    Syn

    chro

    Load

    ram

    p

    Bas

    e lo

    ad o

    r pea

    ksh

    avin

    g (C

    HP

    for

    exam

    ple)

    Unl

    oad

    ram

    p

    START FOR EMERGENCYwill only start if a mains protection or a digital input is programmed as

    "Mains electrical Fault".

    START FOR PRODUCTION /base load or peak shaving

    Triggered byfastest "Mainselectrical fault"

    E1142Cooldown

    E1152Unloadramp

    Syn

    chro

    bac

    k

    Tran

    sfer

    t loa

    d fro

    m G

    Eto

    Mai

    ns

    E1085Mains back

    timer

    400 V

    Mains electrical fault

    Mains voltage

    E2201

    Remote start onterminal J3

    400 V

    Genset voltage

    Generator CB

    Mains CB

    E0022

    E2002

    E0003

    E2001

    E2000

    There is only one black

    E1459Swithover

    delay

    E1152Unloadramp

    E1151Load ramp

    GE

    read

    yFi

    rst B

    lack

    No black. Mains CB is always closed

    GE

    read

    y

    Figure 17 - Typical sequence in permanent mode

    6.6 Power plant paralleled with mains

    CAN busKW, KVAR, COS (phi), ...

    CPA2

    GENSYS nGENSYS 2GENSYS 1 GCR

    Mains kW

    Utility

    Analog load sharing lines

    PLC

    Synchronization bus

    Réseau

    Figure 18 - Power plant paralleling with mains

    In this configuration, base load or peak shaving regulation can be selected, depending on GCR configuration. In base load mode, GCR doesn't need CPA.

  • GENSYS – Documentation technique page 45/45 A40 Z0 9 0020 K-EN Technical documentation

    Variable number Variable label Variable value

    1179 Gen. number 1 to n

    1147 Nb of gen. n (>=2)

    1148 Mains parallel No ch.over

    1153 Mains regul X

    1158 ILS compatible Yes

    1177 Synchro mode Dynamic

    1515 Deadbus manag. Yes

    1258 Load/Unl. mode X

    1020 MA kW 20mA 18000

    1021 MA 0kW setting 0

    1461 Ext kW measure +/- 10V

    Table 16 - Paralleling with mains configuration

    To allow Power Factor regulation, the "Mains breaker in" (J1) information to GENSYS must be wired. Power Factor regulation is not an option.

    6.6.1 Interfacing GENSYS with GCR

    Figure 19 - GCR GENSYS wiring diagram

    • GCR (39-40) – GENSYS (G4-G6): parallel lines (0-3V) to control active power.

  • GENSYS – Documentation technique page 46/46 A40 Z0 9 0020 K-EN Technical documentation

    • GCR (42-43) – GENSYS (G1-G3): mains synchronization bus (+/- 3V). • GENSYS (K3): -VBat from speed governor.

    Variable number Variable label Variable value

    1464 Mains kW Meas. External

    1461 Ext kW measure +/- 10V

    1020 MA kW 20mA 20000

    1021 MA 0kW setting 0

    Table 17 - GENSYS /GCR configuration

    6.7 Power plant paralleled with several mains

    CAN bus

    KWKVARCOS (f)...

    GENSYS 1 GENSYS 2 GENSYS n

    CPA

    GCR 1

    GCR n

    GCR 2

    CPA

    CPA

    CPA

    CPA

    CPA

    kW

    Analog load sharing lines

    Utility 1

    Utility 2

    Utility n

    Mains n

    Mains 2

    Mains 1

    PLC

    Synchronization bus

    Figure 20 - Power plant paralleling with several mains

  • GENSYS – Documentation technique page 47/47 A40 Z0 9 0020 K-EN Technical documentation

    For further information concerning managing several mains using GCR, refer to the GCR technical documentation.

    Variable number Variable label Variable value

    1179 Gen. number 1 to n

    1147 Nb of gen. n (>=2)

    1148 Mains parallel No ch.over

    1153 Mains regul X

    1158 ILS compatible Yes

    1177 Synchro mode Dynamic

    1515 Deadbus manag. Yes

    1258 Load/Unl. mode X

    Figure 21 - Power plant paralleling with several mains configuration

  • GENSYS – Documentation technique page 48/48 A40 Z0 9 0020 K-EN Technical documentation

    7 Installing and commissioning a GENSYS application

    7.1 Wiring diagram

    7.2 Installation instructions: The GENSYS module has been designed for front panel mounting.

    Indoor or outdoor installation is possible as long as the following requirements are met:

    • The chosen cabinet must meet the standard safety rules of the workplace.

  • GENSYS – Documentation technique page 49/49 A40 Z0 9 0020 K-EN Technical documentation

    • The chosen cabinet must be closed during normal use to prevent the user from coming into contact with power cables.

    • Only the front panel must be accessible during normal use. • In accordance with the Bureau VERITAS marine agreement, the module must not be installed in

    areas which are exposed to the weather.

    7.2.1 Panel cut-out:

    Figure 22 - Panel cut-out

    Note: Cut-out must be cleaned of any metal dust before mounting.

    7.2.2 Mounting: To secure the GENSYS onto the panel, use the special kit provided with the module. The kit contains 4 screws, 2 brackets and 1 mounting tool.

    Figure 23 - Mounting kit

    1. Remove the connectors.

    2. Pass the module through the panel cut-out. Ensure that the gasket is properly positioned on the panel and that it is flat.

    3. On the rear side of the module, insert the first bracket into the two holes on the upper edge of the module and push it to the left.

    Figure 24 - Mounting brackets on GENSYS

    4. Use the tool which is provided to screw the bracket gently onto the panel (just to hold the module in place)

    5. Insert the second bracket into the two holes on the lower edge of the module and push it to the right.

    6. Use the tool to screw the bracket gently onto the panel.

    7. Tighten brackets gradually until the module is firmly secured.

    8. Plug in the connectors.

    228 mm /8.98 in

    177 mm /6.97 in

  • GENSYS – Documentation technique page 50/50 A40 Z0 9 0020 K-EN Technical documentation

    7.2.3 Earth grounding: Earth grounding of the GENSYS must be made with two M5 screws & fan washers. Use a short 4mm² cable to connect the unit to earth (see below).

    Figure 25 - Earth grounding

    For UL homologation, the screw must be hexagonal with green head.

    7.2.4 Wiring guidelines: The power cable must be kept separate from the communication cable. The communication cable can be installed in the same conduit as the low level DC I/O lines (under 10 volts). If power and communication cables have to cross, they should do so at right angles. Correct grounding is essential to minimise noise from electromagnetic interference (EMI) and is a safety measure in electrical installations. To avoid EMI, shield communication and ground cables appropriately.

    If several GENSYS are used, all the power supply 0V (pin K3) must connected together with mini 10mm².

    WARNING :

    Please read the following recommendations to avoid any hardware damage to the GENSYS CANBUS Driver (not isolated).

    Power supply to circuit breaker Terminal K3 (0V) should never be disconnected. The battery circuit should only be opened using a breaker placed between the battery's positive terminal and the K2 terminal (Power supply +).

    Note: If the K3 (0V) terminal is disconnected and the bus bar voltage is applied to the GENSYS,

    there is the risk of getting AC voltage on the CANBUS terminals.

  • GENSYS – Documentation technique page 51/51 A40 Z0 9 0020 K-EN Technical documentation

    Interconnection of all battery negatives

    Figure 26 - Interconnection of all battery negatives

    Rental fleet & HV generating sets CANBUS isolators are recommended for generating sets used for rental fleet, Marine, or High Voltage switchboards.

    Figure 27 - Connecting CAN bus with isolators

    Note: These isolators are fitted to prevent any damage due to a disconnection of any K3 terminal from the inter-negative connection. These isolators can be supplied by CRE Technology with the reference A40M0.

    7.2.5 Vibrations: In case of excessive vibration, the module must be mounted on suitable anti-vibration mountings.

    7.2.6 Real time clock battery: If the battery is disconnected, remove the rear panel and connect a 3V battery to the ST1 jumper (+battery: ST1 up; -battery: ST1 down). Battery maintenance must be provided separately from the GENSYS