generators industrial
TRANSCRIPT
© IEEE 2006
Neutral Grounding & Burning Damage Considerations for Industrial Generators
Louie J. Powell, PEEngineering Consultant
Saratoga Springs, [email protected]
© IEEE 2006
Acknowledgement
The presentation is based in part on work done by the Working Group on Generator Grounding of the IEEE Industry Application Society Protection Committee. Membership in the Working Group included:
Eastman ChemicalRalph YoungBeckwith ElectricCharles Mozina
Eaton ElectricalDavid D. ShippConsultantDaniel J. Love
Artwell ElectricNorman T. StringerUniversity of AlabamaJames R. Jones
GE Energy/ConsultantLouie PowellParsons EnergyJay D. Fischer
Kellog-Brown & RootPrafulla PillaiBruce Douglas
Factory Mutual EngineeringAlan PierceBasler ElectricGerald Dalke
Padden EngineeringLorraine PaddenPowell ElectricJim Bowen
International PaperClifford NormandSiemens/ConsultantBruce Bailey
Kocher & Sherra/ConsultantNeil NicholsKBR/ConsultantDavid S. Baker
AffiliationNameAffiliationName
© IEEE 2006
Introduction• “Grounding” encompasses all matters involved in the
connections between an electrical system and earth.• Grounding practices establish critical system design
objectives– Maximum steady-state and transient voltages imposed on
insulation– Maximum currents in conductors and interrupting devices– Maximum potential gradients between components and
structures– Maximum flash energy at the point of an arc
Grounding Decisions Affect Both System Performance and Electrical Safety
© IEEE 2006
System Grounding vs. Equipment Grounding• System Grounding – How is
the electrical neutral connected to earth?
• Equipment Grounding – How is the electrical frame or enclosure connected to earth?
Focused on Different Objectives –Inextricably Linked
© IEEE 2006
Central Station Practice: High-Resistance Grounding
• Generator rating 100 MVA or larger• Dedicated generator step-up transformer• Generator breaker at high-voltage terminals of GSU• Generator neutral grounded through distribution transformer• Ground fault current limited to about 5-7 amperes
Generator
Simple Application – Widely Used
© IEEE 2006
Critical Differences in Industrial Applications
Generator
• Generator rating 10-50MVA • Generator connected to a distribution bus• Distribution feeders at generator terminal
voltage• Supply transformer connected delta at higher
voltage, wye at lower voltage• Generator breaker at generator terminal voltage
Grounding Must Address Application Requirements
© IEEE 2006
• Transient overvoltages• Workplace safety
– Arc-flash (incident) energy– Potential gradients
• Selective ground fault detection and clearing • Burning damage at the point of the fault• Circulation of third-harmonic current • Stator winding mechanical bracing• Unbalanced phase-to-neutral loading
Factors for consideration
Complex Array of Concerns
© IEEE 2006
Traditional Industrial Practice:Low-Resistance Grounding
75+ Year History of Applications
Generator
• Resistor rating: 100 – 1200 a• 400a. Rating is most typical
• Rationale -Enough current for selective protectionMinimizes potential gradientsMinimizes fault-point arcing“Acceptable compromise” between
competing objectives
© IEEE 2006
Reality Strikes: Recent Failures
• Challenged traditional thinking about resistance grounding
• Serious burning damage for internal stator ground faults
• Required extensive stator rebuild
• Generator out of service for months
• Significant replacement energy cost
Stimulated New Thinking About Grounding Practices
© IEEE 2006
The Physics of Stator Ground Faults:• For a ground fault inside the stator winding of a generator
• Two components of fault current– Supplied from the “system” - Is
• Interrupted by opening the generator breaker• Typically interrupted in about 0.1 seconds (6 cycles)
– Supplied by the generator itself - Ig• Opening the generator breaker has no effect• Requires full demagnetization of the generator field
© IEEE 2006
Energy Released at Fault Point
•
• Two critical parameters:1. Magnitude of ground fault current2. Time to interrupt fault current
• Value of k– 2 for resistive heating– 1.5 suggested for low voltage arcing– Subject for further research
dtIt
k∫=0
arc in Energy
Analyze Two Components SeparatelySum Results for Total Energy Released
© IEEE 2006
Case Study – System Current
400A. Low Resistance Grounding Provides Reasonable Damage ControlGenerators on Effectively Grounded Systems Exposed to Serious Jeopardy
0.01 0.1 1 100
5000
1 .104
1.5 .104
2 .104
2.5 .104
3 .104
3.5 .104
4 .104
400 A. Lo-R system5kA Effect. Grd system
Time, seconds
Ener
gy re
leas
ed, w
att-s
econ
ds
© IEEE 2006
Case Study – Generator CurrentTypical medium voltage generator reactances and time constants
0.01 0.1 1 100.1
1
10
100
1 .103
1 .104
400A. LoR ground10A. HiR ground
Time, seconds
Ener
gy re
leas
ed, w
att s
econ
ds
10A. High Resistance Grounding Provides Reasonable Damage Control400A. Grounding Exposes Machines to Jeopardy
τεt
g Ii−
=
© IEEE 2006
The Issue: Fault Current Decrement
• Tripping the generator breaker DOES NOT remove fault current (IG)
• Current persists until field has collapsed
• Single-line-to-ground fault time constant ~ 1 second
0 1 2 3 4 50.01
0.1
1
10
100
1 .103
Time - seconds
Ener
gy re
leas
e, jo
ules
:
Damage is Mainly Self-Inflicted
τεt
g Ii−
=
© IEEE 2006
What has changed?Technical considerations: well, duh?
Economic considerations:
• Generators returned to manufacturer for repair
• Higher cost of replacement energy
New Economic Framework Drives Different Technical Solutions
© IEEE 2006
Evolving New Practices• Dedicated generation systems (with GSU transformer)
– High resistance grounding (< 10a)• Generators embedded in resistance grounded industrial
distribution systems– 10a. High-resistance grounding on generator, 400 a. grounding on
systemIdeal – but not practical in all casesRequires careful consideration of all potential operating modes
– Hybrid grounding
• Predictive diagnostics (eg. partial discharge monitoring)
N:1
R400a.
Neutral switch10a. High resistance package
© IEEE 2006
Further Work: Energy Release Comparison
0
1000
2000
3000
4000
5000
6000
High-resist ance(10a)
Hybrid (2 cycleswit ching)
Hybr id (6 cycleswit ching)
Low resist ance(400a)
Joul
es
• Evaluate potential for switching transients with hybrid grounding
• Enhance understanding of arc-flash burning mechanism– Understand how arc damage occurs– Quantify threshold of safety
• Enhance on-line predictive & diagnostic capabilities
© IEEE 2006
Discussion
© IEEE 2006
References1. IEEE Guide for Generator Ground Protection, IEEE Standard C37.101, 1993. 2. IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems (The Green
Book), IEEE Standard 142, 1991.3. IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power
Systems (The Buff Book), IEEE Standard 242, 2001.4. American National Standard General Requirements for Synchronous Generators, ANSI C50.10, 1990.5. NEMA Standard for Motors and Generators, NEMA Standard MG1-1998 (Rev. 1, 2000).6. P. G. Brown, “Generator Neutral Grounding,” General Electric Co., Schenectady, NY, Application
Engineering Information GET 1941A, p. 5.7. L. J. Powell, “The impact of system grounding practices on generator fault damage,” IEEE Transactions on
Industry Applications, vol. IA-34, , Sept./Oct. 1998, pp. 923-927.8. L. J. Powell, “Stator Fault Damage Considerations for Generators on Solidly Grounded Systems” IEEE
Transactions on Industry Applications, vol. IA-37, Jan/Feb 2001, pp. 218-222.9. IEEE Working Group Report, P. Pillai, Chair, “Grounding and Ground Fault Protection of Multiple-
Generator Installations in Industrial and Commercial Power Systems” (a four-part paper), IEEE Transactions on Industry Applications, vol IA-40-1, Jan/Feb 2004, pp 11-32
10. Moody, D,. V. Beachum, T. Natali, W. Vilcheck and DD Shipp, “Application of a hybrid grounding scheme to a paper mill 13.8kV generator”, Conference Record, 2003 Pulp & Paper Industry Technical Conference, pp 107-116.
11. M. Zielichowski,, “Uszkodzenia zelaza czynnego w stojanie turbogeneratora przy zwarciach doziemnych(Stator core damage due to grounds in a turbine-generator),” Energetika, No 8, pp. 263-267, 1970.
12. L. J. Powell, “Influence of third harmonic circulating currents in selecting neutral grounding devices,” IEEE Transactions on Industry Applications, vol. IA-9, Nov./Dec. 1973, pp. 672-679.
13. E. M. Gulachenski and E. W. Courville, “New England Electric’s 39 years of experience with resonant neutral grounding of unit-connected generators,” IEEE Transactions on Power Delivery, vol. 6, Jul. 1991, pp. 1016-1024.