GENERAL PURPOSE DISTRIBUTION TRANSFORMERS 600 Volt Class and below Single Phase and Three Phase Single Phase, Aluminum & Copper Features ................ 174 Single Phase Aluminum Selection Tables ..................... 175 Single Phase Copper Selection Tables .......................... 177 Three Phase, Aluminum & Copper Features ................. 184 Three Phase Aluminum Selection Tables ...................... 185 Three Phase Copper Selection Tables ........................... 189 Specification Guide and Quote Form ............................ 193 Termination Details ............................................... 271 & 272 Accessories - Sprinkler Hoods & Wall Mounting Kits ....................... 273 SECTION 8

Upload: others

Post on 24-Jul-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

GENERAL PURPOSE

DISTRIBUTION TRANSFORMERS

600 Volt Class and below

Single Phase and Three Phase

Single Phase, Aluminum & Copper Features ................ 174

Single Phase Aluminum Selection Tables ..................... 175

Single Phase Copper Selection Tables .......................... 177

Three Phase, Aluminum & Copper Features ................. 184

Three Phase Aluminum Selection Tables ...................... 185

Three Phase Copper Selection Tables ........................... 189

Specifi cation Guide and Quote Form ............................ 193

Termination Details ............................................... 271 & 272

Accessories - Sprinkler Hoods & Wall Mounting Kits ....................... 273

SECTION 8

Page 2: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

174Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

ALUMINUM & COPPER WOUND SINGLE PHASE FEATURES

600 VOLT CLASS DISTRIBUTION TRANSFORMERS

Other voltages not listed in this section are available upon request for both aluminum and copper wound units. Please contact customer service for details, price and availability.

‘E’ Style Enclosure‘M’ Style Enclosure

50 to 750VA 1000 to 5000VANEMA 3R Style Enclosures

15 to 333 kVA

UL Listed File: E50394 File: E50394 File: E112313

CSA Certifi ed File: LR3902 File: LR3902 File: LR3902

Frequency 60 Hz 60 Hz 60 Hz

Insulation System 50 to 250VA = 105°C (55°C rise) 130°C (80°C rise) 220°C (150°C rise) 500 to 750VA = 130°C (80°C rise) optional: 115°C (80°C rise)

Enclosure Rugged Type 1 Enclosure Rugged Type 1 Enclosure Heavy Duty Ventilated (M style) with one end bell. (E style) - no end bells. NEMA Type 3R

Enclosure Finish Black Black ANSI 61 Grey

Termination Separate terminal compartment Separate terminal compartment Front accessible separate high and with 19” leads for lead termination. with 19” leads for lead termination. low voltage terminals; connectors (up to 340A) suitable for aluminum are provided for easy cable installation.

Conduit Knock-Outs Standard on all units. Standard on all units. Standard on 15 to 150kVA units.

Impedance Typically 5 to 9%. Typically 3 to 7%. Typically 4 to 6%.

Mounting Designed for vertical or horizontal Designed for vertical or horizontal Standard Floor Mounting mounting. mounting. Optional wall mounting kits are available on 15 to 50kVA units.

FEATURE 50 to 750VA 1000 to 3000VA 5000 to 10,000VA

General purpose distribution transformers are rated for 600 volts and below. They are generally used for

supplying appliance, lighting, motorized machine and power loads from electrical distribution systems. They are

either ventilated or totally enclosed, and are available in standard ratings from 50 VA up to 750 kVA.

Hammond shielded distribution transformers provide a copper electrostatic shield between the primary and

secondary windings. The shield is grounded and thus shunts most noise and transients to the ground path rather

than passing them through to the secondary. Applications for shielded transformers are similar to those above,

and they are ideal for commercial or electrical installations where electronic circuitry operating at low voltage DC

is present and is very sensitive to ‘noise’.

Page 3: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

175

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

ALUMINUM WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

* OPTIONAL WALL MOUNTING KIT REQUIRED.

208 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 198-207)

15 MF015BE UH5 13.00 14.00 23.00 170 F or W* SCD 20 25 MF025BE UH6 16.00 19.00 31.00 220 F or W* SCD 6 37.5 MF037BE UH6 16.00 19.00 31.00 260 F or W* SCD 6 50 MF050BE UH6 16.00 19.00 31.00 375 F or W* SCD 6 75 MF075BE UH7 19.50 21.00 35.00 500 F SCD 6 100 MF100BE UH8 24.00 25.00 39.00 650 F SCD 6 150 MF150BE UH9 26.00 26.50 44.00 850 F SCD 6 167 MF167BE UH9 26.00 26.50 44.00 950 F SCD 6

For shielded units, please add the suffi x “S” to the above part numbers.

240 X 480 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MF015LE UH5 13.00 14.00 23.00 170 W or F SCD 5 25 MF025LE UH6 16.00 19.00 31.00 220 W or F SCD 19 37.5 MF037LE UH6 16.00 19.00 31.00 260 W or F SCD 19 50 MF050LE UH6 16.00 19.00 31.00 370 W or F SCD 19 75 MF075LE UH7 19.50 21.00 35.00 500 F SCD 19 100 MF100LE UH8 24.00 25.00 39.00 650 F SCD 19 150 MF150LE UH9 26.00 26.50 44.00 850 F SCD 19 167 MF167LE UH9 26.00 26.50 44.00 900 F SCD 19

For shielded units, please add the suffi x “S” to the above part numbers. *OPTIONAL WALL MOUNTING KIT REQUIRED.

277 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MF015FE UH5 13.00 14.00 23.00 170 F or W* SCD 20 25 MF025FE UH6 16.00 19.00 31.00 260 F or W* SCD 6 37.5 MF037FE UH6 16.00 19.00 31.00 400 F or W* SCD 6 50 MF050FE UH6 16.00 19.00 31.00 450 F or W* SCD 6 75 MF075FE UH7 19.50 21.00 35.00 650 F SCD 6 100 MF100FE UH8 24.00 25.00 39.00 700 F SCD 6 150 MF150FE UH9 26.00 26.50 44.00 830 F SCD 6 167 MF167FE UH9 26.00 26.50 44.00 880 F SCD 6

* OPTIONAL WALL MOUNTING KIT REQUIRED.For shielded units, please add the suffi x “S” to the above part numbers.

Note: For smaller kVA units, please see single phase copper units on pages 179 and 180, or single phase copper Encapsulated units in Section 12 on page 219.

Page 4: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

176Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

ALUMINUM WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

416 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MF015HE UH5 13.00 14.00 23.00 220 F or W* SCD 20 25 MF025HE UH6 16.00 19.00 31.00 220 F or W* SCD 6 37.5 MF037HE UH6 16.00 19.00 31.00 260 F or W* SCD 6 50 MF050HE UH6 19.50 21.00 35.00 400 F or W* SCD 6 75 MF075HE UH7 19.50 21.00 35.00 480 F SCD 6 100 MF100HE UH8 24.00 25.00 39.00 650 F SCD 6 150 MF150HE UH9 26.00 26.50 44.00 850 F SCD 6 167 MF167HE UH9 26.00 26.50 44.00 900 F SCD 6

* OPTIONAL WALL MOUNTING KIT REQUIRED.For shielded units, please add the suffi x “S” to the above part numbers.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

600 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MF015PE UH5 13.00 14.00 23.00 220 F or W* SCD 20 25 MF025PE UH6 16.00 19.00 31.00 220 F or W* SCD 6 37.5 MF037PE UH6 16.00 19.00 31.00 260 F or W* SCD 6 50 MF050PE UH6 19.50 21.00 35.00 400 F or W* SCD 6 75 MF075PE UH7 19.50 21.00 35.00 480 F SCD 6 100 MF100PE UH8 24.00 25.00 39.00 650 F SCD 6 150 MF150PE UH9 26.00 26.50 44.00 850 F SCD 6 167 MF167PE UH9 26.00 26.50 44.00 900 F SCD 6

*OPTIONAL WALL MOUNTING KIT REQUIRED.For shielded units, please add the suffi x “S” to the above part numbers.

190/200/208/220/380/400/416/440 Primary Volts 120/240 Secondary Volts 50/60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MF015XE UH6 16.00 19.00 31.00 190 F or W* SCD 46 25 MF025XE UH6 16.00 19.00 31.00 240 F or W* SCD 46 37.5 MF037XE UH6 16.00 19.00 31.00 300 F or W* SCD 46 50 MF050XE UH7 19.50 21.00 35.00 390 F or W* SCD 46 75 MF075XE UH7 19.50 21.00 35.00 540 F SCD 46 100 MF100XE UH8 24.00 25.00 39.00 700 F SCD 46 150 MF150XE CONSULT FACTORY F SCD 46 167 MF167XE CONSULT FACTORY F SCD 46

*OPTIONAL WALL MOUNTING KIT REQUIRED.For shielded units, please add the suffi x “S” to the above part numbers.

SINGLE PHASE, EXPORT MODEL

Note: For smaller kVA units, please see single phase copper units on pages 181 and 183, or single phase copper Encapsulated units in Section 12.

Page 5: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

177

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

COPPER WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MF015BEC UH5 13.00 14.00 23.00 180 F or W* SCD 20 25 MF025BEC UH6 16.00 19.00 31.00 240 F or W* SCD 6 37.5 MF037BEC UH6 16.00 19.00 31.00 300 F or W* SCD 6 50 MF050BEC UH6 16.00 19.00 31.00 375 F or W* SCD 6 75 MF075BEC UH7 19.50 21.00 35.00 525 F SCD 6 100 MF100BEC UH8 24.00 25.00 39.00 650 F SCD 6 150 MF150BEC UH9 26.00 26.50 44.00 900 F SCD 6 167 MF167BEC UH9 26.00 26.50 44.00 1000 F SCD 6

120 Primary Volts 120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05AACB M01 2.5 3.37 4.06 3.4 W SCD 39 0.1 FC10AACB M02 2.5 3.37 4.56 4.2 W SCD 39 0.15 FC15AACB M11 3.13 4.00 4.63 5.8 W SCD 39 0.2 FC20AACB M13 3.13 4.00 5.38 7.6 W SCD 39 0.25 FC25AACB M13 3.13 4.00 5.38 7.6 W SCD 39 0.35 FC35AACB M21 3.75 4.75 4.56 9 W SCD 39 0.5 FC50AACB M23 3.75 4.75 5.56 13.1 W SCD 39 0.75 FC75AACB M31 4.31 5.5 7.41 21.1 W SCD 39

* OPTIONAL WALL MOUNTING KIT REQUIRED.

208 Primary Volts 120/240 Secondary Volts 60 Hz

208 Primary Volts 120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05BACB M01 2.5 3.37 4.06 3.4 W SCD 40 0.1 FC10BACB M02 2.5 3.37 4.56 4.2 W SCD 40 0.15 FC15BACB M11 3.13 4.00 4.63 5.8 W SCD 40 0.2 FC20BACB M13 3.13 4.00 5.38 7.6 W SCD 40 0.25 FC25BACB M13 3.13 4.00 5.38 7.6 W SCD 40 0.35 FC35BACB M21 3.75 4.75 4.56 9 W SCD 40 0.5 FC50BACB M23 3.75 4.75 5.56 13.1 W SCD 40 0.75 FC75BACB M31 4.31 5.5 7.41 21.1 W SCD 40

Note: For single phase copper Encapsulated units, please refer to Section 12.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

Page 6: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

178Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

COPPER WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

208/416 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05B1ECB M01 2.5 3.37 4.06 3.4 W SCD 1 0.1 FC10B1ECB M02 2.5 3.37 4.56 4.2 W SCD 1 0.15 FC15B1ECB M11 3.13 4.00 4.63 5.8 W SCD 1 0.2 FC20B1ECB M13 3.13 4.00 5.38 7.6 W SCD 1 0.25 FC25B1ECB M13 3.13 4.00 5.38 7.6 W SCD 1 0.35 FC35B1ECB M21 3.75 4.75 4.56 9 W SCD 1 0.5 FC50B1ECB M23 3.75 4.75 5.56 13.1 W SCD 1 0.75 FC75B1ECB M31 4.31 5.5 7.41 21.1 W SCD 1

240 Primary Volts 120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05DACB M01 2.5 3.37 4.06 3.4 W SCD 41 0.1 FC10DACB M02 2.5 3.37 4.56 4.2 W SCD 41 0.15 FC15DACB M11 3.13 4.00 4.63 5.8 W SCD 41 0.2 FC20DACB M13 3.13 4.00 5.38 7.6 W SCD 41 0.25 FC25DACB M13 3.13 4.00 5.38 7.6 W SCD 41 0.35 FC35DACB M21 3.75 4.75 4.56 9 W SCD 41 0.5 FC50DACB M23 3.75 4.75 5.56 13.1 W SCD 41 0.75 FC75DACB M31 4.31 5.5 7.41 21.1 W SCD 41

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

Page 7: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

179

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

COPPER WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

240 X 480 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05LECB M01 2.5 3.37 4.06 3.4 W SCD 1 0.1 FC10LECB M02 2.5 3.37 4.56 4.2 W SCD 1 0.15 FC15LECB M11 3.13 4.00 4.63 5.8 W SCD 1 0.2 FC20LECB M13 3.13 4.00 5.38 7.6 W SCD 1 0.25 FC25LECB M13 3.13 4.00 5.38 7.6 W SCD 1 0.35 FC35LECB M21 3.75 4.75 4.56 9 W SCD 1 0.5 FC50LECB M23 3.75 4.75 5.56 13.1 W SCD 1 0.75 FC75LECB M31 4.31 5.5 7.41 21.1 W SCD 1 1 F1C0LECB E32 4.31 5.5 7.91 23.6 W SCD 1 1.5 F1C5LECF E01 5.31 9 6.75 34 W SCD 1 2 F002LECF E02 5.31 10 6.75 48 W SCD 1 3 F003LECF E11 6.25 10.5 8 65 W SCD 1 5 F005LECF E21 7.5 10.75 9.5 102 W SCD 1 7.5 7.5 kVA is only available in an Encapsulated version. Please refer to Section 12 for specifi cations. 10 10 kVA is only available in an Encapsulated version. Please refer to Section 12 for specifi cations. 15 MF015LEC UH5 13.00 14.00 23.00 180 F or W* SCD 5 25 MF025LEC UH6 16.00 19.00 31.00 240 F or W* SCD 19 37.5 MF037LEC UH6 16.00 19.00 31.00 300 F or W* SCD 19 50 MF050LEC UH6 16.00 19.00 31.00 375 F or W* SCD 19 75 MF075LEC UH7 19.50 21.00 35.00 525 F SCD 19 100 MF100LEC UH8 24.00 25.00 39.00 650 F SCD 19 150 MF150LEC UH9 26.00 26.50 44.00 900 F SCD 19 167 MF167LEC UH9 26.00 26.50 44.00 1000 F SCD 19

*OPTIONAL WALL MOUNTING KIT REQUIRED.For shielded units, please replace the suffi x “C” with a ‘K’ on the above part numbers. Not applicable on the ‘FC’ or ‘F’ units.

Note: For single phase copper Encapsulated units, please refer to Section 12.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

Page 8: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

180Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

COPPER WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

277 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05FECB M01 2.5 3.37 4.06 3.4 W SCD 4 0.1 FC10FECB M02 2.5 3.37 4.56 4.2 W SCD 4 0.15 FC15FECB M11 3.13 4.00 4.63 5.8 W SCD 4 0.2 FC20FECB M13 3.13 4.00 5.38 7.6 W SCD 4 0.25 FC25FECB M13 3.13 4.00 5.38 7.6 W SCD 4 0.35 FC35FECB M21 3.75 4.75 4.56 9 W SCD 4 0.5 FC50FECB M23 3.75 4.75 5.56 13.1 W SCD 4 0.75 FC75FECB M31 4.31 5.5 7.41 21.1 W SCD 4 1 F1C0FECB M32 4.31 5.5 7.91 23.6 W SCD 4 1.5 F1C5FECF E01 5.31 9 6.75 34 W SCD 4 2 F002FECF E02 5.31 10 6.75 48 W SCD 4 3 F003FECF E11 6.25 10.5 8 65 W SCD 4 5 F005FECF E21 7.5 10.75 9.5 102 W SCD 4 7.5 7.5 kVA is only available in an Encapsulated version. Please refer to Section 12 for specifi cations. 10 10 kVA is only available in an Encapsulated version. Please refer to Section 12 for specifi cations. 15 MF015FEC UH5 13.00 14.00 23.00 180 F or W* SCD 20 25 MF025FEC UH6 16.00 19.00 31.00 240 F or W* SCD 6 37.5 MF037FEC UH6 16.00 19.00 31.00 300 F or W* SCD 6 50 MF050FEC UH6 16.00 19.00 31.00 375 F or W* SCD 6 75 MF075FEC UH7 19.50 21.00 35.00 525 F SCD 6 100 MF100FEC UH8 24.00 25.00 39.00 650 F SCD 6 150 MF150FEC UH9 26.00 26.50 44.00 900 F SCD 6 167 MF167FEC UH9 26.00 26.50 44.00 1000 F SCD 6

For shielded units, please replace the suffi x “C” with a ‘K’ on the above part numbers. Not applicable on the ‘FC’ or ‘F’ units. *OPTIONAL WALL MOUNTING KIT REQUIRED.

347 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05G1ECB M01 2.5 3.37 4.06 3.4 W SCD 4 0.1 FC10G1ECB M02 2.5 3.37 4.56 4.2 W SCD 4 0.15 FC15G1ECB M11 3.13 4.00 4.63 5.8 W SCD 4 0.2 FC20G1ECB M13 3.13 4.00 5.38 7.6 W SCD 4 0.25 FC25G1ECB M13 3.13 4.00 5.38 7.6 W SCD 4 0.35 FC35G1ECB M21 3.75 4.75 4.56 9 W SCD 4 0.5 FC50G1ECB M23 3.75 4.75 5.56 13.1 W SCD 4 0.75 FC75G1ECB M31 4.31 5.5 7.41 21.1 W SCD 4

Note: For single phase copper Encapsulated units, please refer to Section 12.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

Page 9: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

181

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

COPPER WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

380 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05GECB M01 2.5 3.37 4.06 3.4 W SCD 4 0.1 FC10GECB M03 2.5 3.37 4.81 5 W SCD 4 0.15 FC15GECB M12 3.13 4.00 4.88 6.4 W SCD 4 0.2 FC20GECB M13 3.13 4.00 5.38 10.7 W SCD 4 0.25 FC25GECB M13 3.13 4.00 5.38 11.4 W SCD 4 0.35 FC35GECB M22 3.75 4.75 4.81 14.2 W SCD 4 0.5 FC50GECB M24 3.75 4.75 5.81 18.3 W SCD 4 0.75 FC75GECB M32 4.31 5.5 7.41 24.8 W SCD 4

416 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05HECB M01 2.5 3.37 4.06 3.4 W SCD 4 0.1 FC10HECB M02 2.5 3.37 4.56 4.2 W SCD 4 0.15 FC15HECB M11 3.13 4.00 4.63 5.8 W SCD 4 0.2 FC20HECB M13 3.13 4.00 5.38 7.6 W SCD 4 0.25 FC25HECB M13 3.13 4.00 5.38 7.6 W SCD 4 0.35 FC35HECB M21 3.75 4.75 4.56 9 W SCD 4 0.5 FC50HECB M23 3.75 4.75 5.56 13.1 W SCD 4 0.75 FC75HECB M31 4.31 5.5 7.41 21.1 W SCD 4 1 F1C0HECB M32 4.31 5.5 7.91 23.6 W SCD 4 1.5 F1C5HECF E01 5.31 9 6.75 34 W SCD 4 2 F002HECF E02 5.31 10 6.75 48 W SCD 4 3 F003HECF E11 6.25 10.5 8 65 W SCD 4 5 F005HECF E21 7.5 10.75 9.5 102 W SCD 4 7.5 7.5 kVA is only available in an Encapsulated version. Please refer to Section 12 for specifi cations. 10 10 kVA is only available in an Encapsulated version. Please refer to Section 12 for specifi cations. 15 MF015HEC UH5 13.00 14.00 23.00 180 F or W* SCD 20 25 MF025HEC UH6 16.00 19.00 31.00 240 F or W* SCD 6 37.5 MF037HEC UH6 16.00 19.00 31.00 300 F or W* SCD 6 50 MF050HEC UH6 16.00 19.00 31.00 375 F or W* SCD 6 75 MF075HEC UH7 19.50 21.00 35.00 525 F SCD 6 100 MF100HEC UH8 24.00 25.00 39.00 650 F SCD 6 150 MF150HEC UH9 26.00 26.50 44.00 900 F SCD 6 167 MF167HEC UH9 26.00 26.50 44.00 1000 F SCD 6

For shielded units, please replace the suffi x “C” with a ‘K’ on the above part numbers. Not applicable on the potted ‘FC’ or ‘F’ units. *OPTIONAL WALL MOUNTING KIT REQUIRED.

Note: For single phase copper Encapsulated units, please refer to Section 12.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

Page 10: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

182Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

COPPER WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

480 Primary Volts 120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05KACB M01 2.5 3.37 4.06 3.4 W SCD 43 0.1 FC10KACB M02 2.5 3.37 4.56 4.2 W SCD 43 0.15 FC15KACB M11 3.13 4.00 4.63 5.8 W SCD 43 0.2 FC20KACB M13 3.13 4.00 5.38 7.6 W SCD 43 0.25 FC25KACB M13 3.13 4.00 5.38 7.6 W SCD 43 0.35 FC35KACB M21 3.75 4.75 4.56 9 W SCD 43 0.5 FC50KACB M23 3.75 4.75 5.56 13.1 W SCD 43 0.75 FC75KACB M31 4.31 5.5 7.41 21.1 W SCD 43

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

600 Primary Volts 120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05PACB M01 2.5 3.37 4.06 3.4 W SCD 43 0.1 FC10PACB M02 2.5 3.37 4.56 4.2 W SCD 43 0.15 FC15PACB M11 3.13 4.00 4.63 5.8 W SCD 43 0.2 FC20PACB M13 3.13 4.00 5.38 7.6 W SCD 43 0.25 FC25PACB M13 3.13 4.00 5.38 7.6 W SCD 43 0.35 FC35PACB M21 3.75 4.75 4.56 9 W SCD 43 0.5 FC50PACB M23 3.75 4.75 5.56 13.1 W SCD 43 0.75 FC75PACB M31 4.31 5.5 7.41 21.1 W SCD 43

Note: For single phase copper Encapsulated units, please refer to Section 12.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

Page 11: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

183

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

COPPER WOUND, SINGLE PHASE, NEMA 3R STYLE ENCLOSURE

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

600 Primary Volts 120/240 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

0.05 FC05PECB M01 2.5 3.37 4.06 3.4 W SCD 4 0.1 FC10PECB M02 2.5 3.37 4.56 4.2 W SCD 4 0.15 FC15PECB M11 3.13 4.00 4.63 5.8 W SCD 4 0.2 FC20PECB M13 3.13 4.00 5.38 7.6 W SCD 4 0.25 FC25PECB M13 3.13 4.00 5.38 7.6 W SCD 4 0.35 FC35PECB M21 3.75 4.75 4.56 9 W SCD 4 0.5 FC50PECB M23 3.75 4.75 5.56 13.1 W SCD 4 0.75 FC75PECB M31 4.31 5.5 7.41 21.1 W SCD 4 1 F1C0PECB M32 4.31 5.5 7.91 23.6 W SCD 4 1.5 F1C5PECF E01 5.31 9 6.75 34 W SCD 4 2 F002PECF E02 5.31 10 6.75 48 W SCD 4 3 F003PECF E11 6.25 10.5 8 65 W SCD 4 5 F005PECF E21 7.5 10.75 9.5 102 W SCD 4 7.5 7.5 kVA is only available in an Encapsulated version. Please refer to Section 12 for specifi cations. 10 10 kVA is only available in an Encapsulated version. Please refer to Section 12 for specifi cations. 15 MF015PEC UH5 13.00 14.00 23.00 180 F or W* SCD 20 25 MF025PEC UH6 16.00 19.00 31.00 240 F or W* SCD 6 37.5 MF037PEC UH6 16.00 19.00 31.00 300 F or W* SCD 6 50 MF050PEC UH6 16.00 19.00 31.00 375 F or W* SCD 6 75 MF075PEC UH7 19.50 21.00 35.00 525 F SCD 6 100 MF100PEC UH8 24.00 25.00 39.00 650 F SCD 6 150 MF150PEC UH9 26.00 26.50 44.00 900 F SCD 6 167 MF167PEC UH9 26.00 26.50 44.00 1000 F SCD 6

*OPTIONAL WALL MOUNTING KIT REQUIRED.For shielded units, please replace the suffi x “C” with a ‘K’ on the above part numbers. Not applicable on the potted ‘FC’ or ‘F’ units.

190/200/208/220/380/400/416/440 Primary Volts 120/240 Secondary Volts 50/60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MF015XEC UH6 16.00 19.00 31.00 220 F or W* SCD 46 25 MF025XEC UH6 16.00 19.00 31.00 240 F or W* SCD 46 37.5 MF037XEC UH6 16.00 19.00 31.00 300 F or W* SCD 46 50 MF050XEC UH7 19.50 21.00 35.00 410 F or W* SCD 46 75 MF075XEC UH7 19.50 21.00 35.00 540 F SCD 46 100 MF100XEC UH8 24.00 25.00 39.00 700 F SCD 46 150 MF150XEC CONSULT FACTORY F SCD 46 167 MF167XEC CONSULT FACTORY F SCD 46

*OPTIONAL WALL MOUNTING KIT REQUIRED.

SINGLE PHASE, EXPORT MODEL

Note: For single phase copper Encapsulated units, please refer to Section 12.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

The above type ‘FC’ units are not available with a shield and are available in a NEMA 1 enclosure only.

Page 12: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

184Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

ALUMINUM & COPPER WOUND THREE PHASE FEATURES

UL Listed File: E112313

CSA Certifi ed File: LR3902

Frequency 60 Hz

Insulation System 220°C (150°C rise)

(optional: 115°C or 80°C rise)

Enclosure Type Heavy Duty Ventilated

NEMA Type 3R

Enclosure Finish ANSI 61 Grey

Standard Primary Taps Refer to wiring diagrams for details.

Termination Front accessible separate high

and low voltage terminals;

connectors (up to 165A) suitable

for aluminum are provided for easy

cable installation.

Conduit Knock-Outs Standard on 9 to 150kVA units.

Impedance Typically 4 to 6%.

Mounting Standard Floor Mounting.

Optional wall mounting kits are

available on 9 to 75 kVA.

THREE PHASE FEATURES NEMA 3R

FEATURE 9 to 750 kVA

600 VOLT CLASS DISTRIBUTION TRANSFORMERS

Other voltages not listed in this section are available upon request for both aluminum and copper wound units. Please contact customer service for details, price and availability.

9 to 750 kVA

Page 13: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

185

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

ALUMINUM WOUND, THREE PHASE, NEMA 3R STYLE ENCLOSURE

208 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009BB UH1 16.75 14 22 140 F or W* SCD 33 15 MK015BB UH1 16.75 14 22 180 F or W* SCD 33 30 MK030BB UH2 21.5 19.5 29 300 F or W* SCD 9 45 MK045BB UH2 21.5 19.5 29 400 F or W* SCD 9 75 MK075BB UH3 26 21 38 575 F or W* SCD 9 112.5 MK112BB UH3 26 21 38 750 F SCD 9 150 MK150BB UH4 30 24 39 900 F SCD 9 225 MK225BB UJ1 39.5 30 50 1350 F SCD 9 300 MK300BB UJ1 39.5 30 50 1550 F SCD 9 500 MK500BB UJ2 48.5 34 59 2400 F SCD 33 750 MK750BB UJ3 51.5 39 66 3450 F SCD 33

208 Delta Primary Volts 480Y/277 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MK015BK UH1 16.75 14 22 180 F or W* SCD 26 30 MK030BK UH2 21.5 19.5 29 300 F or W* SCD 34 45 MK045BK UH2 21.5 19.5 29 400 F or W* SCD 34 75 MK075BK UH3 26 21 38 575 F or W* SCD 34 112.5 MK112BK UH3 26 21 38 750 F SCD 34 150 MK150BK UH4 30 24 39 900 F SCD 34 225 MK225BK UJ1 39.5 30 50 1350 F SCD 34 300 MK300BK UJ1 39.5 30 50 1550 F SCD 34 500 MK500BK UJ2 48.5 34 59 2400 F SCD 26 750 MK750BK UJ3 51.5 39 66 3450 F SCD 26

240 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009DB UH1 16.75 14 22 140 F or W* SCD 33 15 MK015DB UH1 16.75 14 22 180 F or W* SCD 33 30 MK030DB UH2 21.5 19.5 29 300 F or W* SCD 9 45 MK045DB UH2 21.5 19.5 29 400 F or W* SCD 9 75 MK075DB UH3 26 21 38 575 F or W* SCD 9 112.5 MK112DB UH3 26 21 38 750 F SCD 9 150 MK150DB UH4 30 24 39 900 F SCD 9 225 MK225DB UJ1 39.5 30 50 1350 F SCD 9 300 MK300DB UJ1 39.5 30 50 1550 F SCD 9 500 MK500DB UJ2 48.5 34 59 2400 F No Taps 750 MK750DB UJ3 51.5 39 66 3450 F No Taps

*OPTIONAL WALL MOUNTING KIT REQUIRED.

For shielded units, please add the suffi x “S” to the above part numbers.

For shielded units, please add the suffi x “S” to the above part numbers.

For shielded units, please add the suffi x “S” to the above part numbers.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

Note: For three phase copper Encapsulated units, please refer to Section 12.

Page 14: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

186Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

ALUMINUM WOUND, THREE PHASE, NEMA 3R STYLE ENCLOSURE

240 Delta Primary Volts 480Y/277 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MK015DK UH1 16.75 14 22 180 F or W* SCD 26 30 MK030DK UH2 21.5 19.5 29 300 F or W* SCD 34 45 MK045DK UH2 21.5 19.5 29 400 F or W* SCD 34 75 MK075DK UH3 26 21 38 575 F or W* SCD 34 112.5 MK112DK UH3 26 21 38 750 F SCD 34 150 MK150DK UH4 30 24 39 900 F SCD 34 225 MK225DK UJ1 39.5 30 50 1350 F SCD 34 300 MK300DK UJ1 39.5 30 50 1550 F SCD 34 500 MK500DK UJ2 48.5 34 59 2400 F SCD 26 750 MK750DK UJ3 51.5 39 66 3450 F No Taps

480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009KB UH1 16.75 14 22 140 F or W* SCD 33 15 MK015KB UH1 16.75 14 22 180 F or W* SCD 33 30 MK030KB UH2 21.5 19.5 29 300 F or W* SCD 21 45 MK045KB UH2 21.5 19.5 29 400 F or W* SCD 21 75 MK075KB UH3 26 21 38 575 F or W* SCD 21 112.5 MK112KB UH3 26 21 38 750 F SCD 21 150 MK150KB UH4 30 24 39 900 F SCD 21 225 MK225KB UJ1 39.5 30 50 1350 F SCD 21 300 MK300KB UJ1 39.5 30 50 1550 F SCD 21 500 MK500KB UJ2 48.5 34 59 2400 F SCD 10 750 MK750KB UJ3 51.5 39 66 3450 F SCD 10

480 Delta Primary Volts 240 Delta/120 CT1 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009KD UH1 16.75 14 22 140 F or W* SCD 13 15 MK015KD UH1 16.75 14 22 180 F or W* SCD 13 30 MK030KD UH2 21.5 19.5 29 300 F or W* SCD 23 45 MK045KD UH2 21.5 19.5 29 400 F or W* SCD 23 75 MK075KD UH3 26 21 38 575 F or W* SCD 23 112.5 MK112KD UH3 26 21 38 750 F SCD 23 150 MK150KD UH4 30 24 39 900 F SCD 23 225 MK225KD UJ1 39.5 30 50 1350 F SCD 23 300 MK300KD UJ1 39.5 30 50 1550 F SCD 23 500 MK500KD UJ2 48.5 34 59 2400 F SCD 15 750 MK750KD UJ3 51.5 39 66 3450 F SCD 15

*OPTIONAL WALL MOUNTING KIT REQUIRED.

For shielded units, please add the suffi x “S” to the above part numbers.

For shielded units, please add the suffi x “S” to the above part numbers.

For shielded units, please add the suffi x “S” to the above part numbers.1 No center tap is provided on the 9kVA unit. The 120V lighting tap is limited to 5% of nameplate rating.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

Note: For three phase copper Encapsulated units, please refer to Section 12.

Page 15: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

187

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

ALUMINUM WOUND, THREE PHASE, NEMA 3R STYLE ENCLOSURE

480 Delta Primary Volts 480Y/277 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009KK UH1 16.75 14 22 140 F or W* SCD 33 15 MK015KK UH1 16.75 14 22 180 F or W* SCD 33 30 MK030KK UH2 21.5 19.5 29 300 F or W* SCD 21 45 MK045KK UH2 21.5 19.5 29 400 F or W* SCD 21 75 MK075KK UH3 26 21 38 575 F or W* SCD 21 112.5 MK112KK UH3 26 21 38 750 F SCD 21 150 MK150KK UH4 30 24 39 900 F SCD 21 225 MK225KK UJ1 39.5 30 50 1350 F SCD 21 300 MK300KK UJ1 39.5 30 50 1550 F SCD 21 500 MK500KK UJ2 48.5 34 59 2400 F SCD 10 750 MK750KK UJ3 51.5 39 66 3450 F SCD 10

600 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009PB UH1 16.75 14 22 140 F or W* SCD 10 15 MK015PB UH1 16.75 14 22 180 F or W* SCD 10 30 MK030PB UH2 21.5 19.5 29 300 F or W* SCD 9 45 MK045PB UH2 21.5 19.5 29 400 F or W* SCD 9 75 MK075PB UH3 26 21 38 575 F or W* SCD 9 112.5 MK112PB UH3 26 21 38 750 F SCD 9 150 MK150PB UH4 30 24 39 900 F SCD 9 225 MK225PB UJ1 39.5 30 50 1350 F SCD 9 300 MK300PB UJ1 39.5 30 50 1550 F SCD 9 500 MK500PB UJ2 48.5 34 59 2400 F SCD 10 750 MK750PB UJ3 51.5 39 66 3450 F SCD 10

*OPTIONAL WALL MOUNTING KIT REQUIRED.

For shielded units, please add the suffi x “S” to the above part numbers.

For shielded units, please add the suffi x “S” to the above part numbers.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

Note: For three phase copper Encapsulated units, please refer to Section 12.

Page 16: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

188Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

600Y Primary Volts 240 Delta Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009PD UH1 16.75 14 22 140 F or W* SCD 47 15 MK015PD UH1 16.75 14 22 180 F or W* SCD 47 30 MK030PD UH2 21.5 19.5 29 300 F or W* SCD 17 45 MK045PD UH2 21.5 19.5 29 400 F or W* SCD 17 75 MK075PD UH3 26 21 38 575 F SCD 17 112.5 MK112PD UH3 26 21 38 750 F SCD 17 150 MK150PD UH4 30 24 39 900 F SCD 17 225 MK225PD UJ1 39.5 30 50 1350 F SCD 17 300 MK300PD UJ1 39.5 30 50 1550 F SCD 17 500 MK500PD UJ2 48.5 34 59 2400 F SCD 47 750 MK750PD UJ3 51.5 39 66 3450 F SCD 47

600 Delta Primary Volts 480Y/277 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009PK UH1 16.75 14 22 140 F or W* SCD 10 15 MK015PK UH1 16.75 14 22 180 F or W* SCD 10 30 MK030PK UH2 21.5 19.5 29 300 F or W* SCD 9 45 MK045PK UH2 21.5 19.5 29 400 F or W* SCD 9 75 MK075PK UH3 26 21 38 575 F SCD 9 112.5 MK112PK UH3 26 21 38 750 F SCD 9 150 MK150PK UH4 30 24 39 900 F SCD 9 225 MK225PK UJ1 39.5 30 50 1350 F SCD 9 300 MK300PK UJ1 39.5 30 50 1550 F SCD 9 500 MK500PK UJ2 48.5 34 59 2400 F SCD 10 750 MK750PK UJ3 51.5 39 66 3450 F SCD 10

ALUMINUM WOUND, THREE PHASE, NEMA 3R STYLE ENCLOSURE

For shielded units, please add the suffi x “S” to the above part numbers.

For shielded units, please add the suffi x “S” to the above part numbers.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

Note: For three phase copper Encapsulated units, please refer to Section 12.

Page 17: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

189

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

208 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009BBCF UH1 16.75 14 22 170 F or W* SCD 33 15 MK015BBCF UH1 16.75 14 22 200 F or W* SCD 33 30 MK030BBC UH2 21.5 19.5 29 300 F or W* SCD 9 45 MK045BBC UH2 21.5 19.5 29 400 F or W* SCD 9 75 MK075BBC UH3 26 21 38 580 F or W* SCD 9 112.5 MK112BBC UH3 26 21 38 750 F SCD 9 150 MK150BBC UH4 30 24 39 1000 F SCD 9 225 MK225BBC UJ1 39.5 30 50 1450 F SCD 9 300 MK300BBC UJ1 39.5 30 50 1700 F SCD 9 500 MK500BBC UJ2 48.5 34 59 2630 F SCD 33 750 MK750BBC UJ3 51.5 39 66 3500 F SCD 33

208 Delta Primary Volts 480Y/277 Secondary Volts 60 Hz

240 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009DBCF UH1 16.75 14 22 170 F or W* SCD 33 15 MK015DBCF UH1 16.75 14 22 200 F or W* SCD 33 30 MK030DBC UH2 21.5 19.5 29 300 F or W* SCD 9 45 MK045DBC UH2 21.5 19.5 29 400 F or W* SCD 9 75 MK075DBC UH3 26 21 38 580 F or W* SCD 9 112.5 MK112DBC UH3 26 21 38 750 F SCD 9 150 MK150DBC UH4 30 24 39 1000 F SCD 9 225 MK225DBC UJ1 39.5 30 50 1450 F SCD 9 300 MK300DBC UJ1 39.5 30 50 1700 F SCD 9 500 MK500DBC UJ2 48.5 34 59 2630 F No Taps 750 MK750DBC UJ3 51.5 39 66 3500 F No Taps

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MK015BKCF UH1 16.75 14 22 200 F or W* SCD 26 30 MK030BKC UH2 21.5 19.5 29 300 F or W* SCD 34 45 MK045BKC UH2 21.5 19.5 29 400 F or W* SCD 34 75 MK075BKC UH3 26 21 38 580 F or W* SCD 34 112.5 MK112BKC UH3 26 21 38 750 F SCD 34 150 MK150BKC UH4 30 24 39 1000 F SCD 34 225 MK225BKC UJ1 39.5 30 50 1450 F SCD 34 300 MK300BKC UJ1 39.5 30 50 1700 F SCD 34 500 MK500BKC UJ2 48.5 34 59 2630 F SCD 26 750 MK750BKC UJ3 51.5 39 66 3500 F SCD 26

COPPER WOUND, THREE PHASE, NEMA 3R STYLE ENCLOSURE

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

Note: For three phase copper Encapsulated units, please refer to Section 12.

Page 18: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

190Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

240 Delta Primary Volts 480Y/277 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

15 MK015DKCF UH1 16.75 14 22 200 F or W* SCD 26 30 MK030DKC UH2 21.5 19.5 29 300 F or W* SCD 34 45 MK045DKC UH2 21.5 19.5 29 400 F or W* SCD 34 75 MK075DKC UH3 26 21 38 580 F or W* SCD 34 112.5 MK112DKC UH3 26 21 38 750 F SCD 34 150 MK150DKC UH4 30 24 39 1000 F SCD 34 225 MK225DKC UJ1 39.5 30 50 1450 F SCD 34 300 MK300DKC UJ1 39.5 30 50 1700 F SCD 34 500 MK500DKC UJ2 48.5 34 59 2630 F SCD 26 750 MK750DKC UJ3 51.5 39 66 3500 F No Taps

480 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009KBCF UH1 16.75 14 22 170 F or W* SCD 33 15 MK015KBCF UH1 16.75 14 22 200 F or W* SCD 33 30 MK030KBC UH2 21.5 19.5 29 300 F or W* SCD 21 45 MK045KBC UH2 21.5 19.5 29 400 F or W* SCD 21 75 MK075KBC UH3 26 21 38 580 F or W* SCD 21 112.5 MK112KBC UH3 26 21 38 750 F SCD 21 150 MK150KBC UH4 30 24 39 1000 F SCD 21 225 MK225KBC UJ1 39.5 30 50 1450 F SCD 21 300 MK300KBC UJ1 39.5 30 50 1700 F SCD 21 500 MK500KBC UJ2 48.5 34 59 2630 F SCD 10 750 MK750KBC UJ3 51.5 39 66 3500 F SCD 10

480 Delta Primary Volts 240 Delta/120 CT1 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009KDCF UH1 16.75 14 22 170 F or W* SCD 13 15 MK015KDCF UH1 16.75 14 22 200 F or W* SCD 13 30 MK030KDC UH2 21.5 19.5 29 300 F or W* SCD 23 45 MK045KDC UH2 21.5 19.5 29 400 F or W* SCD 23 75 MK075KDC UH3 26 21 38 580 F or W* SCD 23 112.5 MK112KDC UH3 26 21 38 750 F SCD 23 150 MK150KDC UH4 30 24 39 1000 F SCD 23 225 MK225KDC UJ1 39.5 30 50 1450 F SCD 23 300 MK300KDC UJ1 39.5 30 50 1700 F SCD 23 500 MK500KDC UJ2 48.5 34 59 2630 F SCD 15 750 MK750KDC UJ3 51.5 39 66 3500 F SCD 15

*OPTIONAL WALL MOUNTING KIT REQUIRED.

COPPER WOUND, THREE PHASE, NEMA 3R STYLE ENCLOSURE

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.1 No center tap is provided on the 9kVA unit. The 120V lighting tap is limited to 5% of nameplate rating.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

Note: For three phase copper Encapsulated units, please refer to Section 12.

Page 19: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

191

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

480 Delta Primary Volts 480Y/277 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009KKCF UH1 16.75 14 22 170 F or W* SCD 33 15 MK015KKCF UH1 16.75 14 22 200 F or W* SCD 33 30 MK030KKC UH2 21.5 19.5 29 300 F or W* SCD 21 45 MK045KKC UH2 21.5 19.5 29 400 F or W* SCD 21 75 MK075KKC UH3 26 21 38 580 F or W* SCD 21 112.5 MK112KKC UH3 26 21 38 750 F SCD 21 150 MK150KKC UH4 30 24 39 1000 F SCD 21 225 MK225KKC UJ1 39.5 30 50 1450 F SCD 21 300 MK300KKC UJ1 39.5 30 50 1700 F SCD 21 500 MK500KKC UJ2 48.5 34 59 2630 F SCD 10 750 MK750KKC UJ3 51.5 39 66 3500 F SCD 10

600 Delta Primary Volts 208Y/120 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009PBCF UH1 16.75 14 22 170 F or W* SCD 10 15 MK015PBCF UH1 16.75 14 22 200 F or W* SCD 10 30 MK030PBC UH2 21.5 19.5 29 300 F or W* SCD 9 45 MK045PBC UH2 21.5 19.5 29 400 F or W* SCD 9 75 MK075PBC UH3 26 21 38 580 F or W* SCD 9 112.5 MK112PBC UH3 26 21 38 750 F SCD 9 150 MK150PBC UH4 30 24 39 1000 F SCD 9 225 MK225PBC UJ1 39.5 30 50 1450 F SCD 9 300 MK300PBC UJ1 39.5 30 50 1700 F SCD 9 500 MK500PBC UJ2 48.5 34 59 2630 F SCD 10 750 MK750PBC UJ3 51.5 39 66 3500 F SCD 10

*OPTIONAL WALL MOUNTING KIT REQUIRED.

COPPER WOUND, THREE PHASE, NEMA 3R STYLE ENCLOSURE

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

Note: For three phase copper Encapsulated units, please refer to Section 12.

Page 20: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

192Data subject to change without notice.

SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

COPPER WOUND, THREE PHASE, NEMA 3R STYLE ENCLOSURE

600Y Primary Volts 240 Delta Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009PDCF UH1 16.75 14 22 140 F or W* SCD 47 15 MK015PDCF UH1 16.75 14 22 180 F or W* SCD 47 30 MK030PDC UH2 21.5 19.5 29 300 F or W* SCD 17 45 MK045PDC UH2 21.5 19.5 29 400 F or W* SCD 17 75 MK075PDC UH3 26 21 38 575 F or W* SCD 17 112.5 MK112PDC UH3 26 21 38 750 F SCD 17 150 MK150PDC UH4 30 24 39 900 F SCD 17 225 MK225PDC UJ1 39.5 30 50 1350 F SCD 17 300 MK300PDC UJ1 39.5 30 50 1550 F SCD 17 500 MK500PDC UJ2 48.5 34 59 2400 F SCD 47 750 MK750PDC UJ3 51.5 39 66 3450 F SCD 47

600 Delta Primary Volts 480Y/277 Secondary Volts 60 Hz Catalog Case Approx. Dimensions Approx. Mtg Type Wiring kVA Number Style (Inches) Weight W - Wall Diagram (Pages 254-257) Width Depth Height (Lbs.) F - Floor (Pages 258-269)

9 MK009PKCF UH1 16.75 14 22 140 F or W* SCD 10 15 MK015PKCF UH1 16.75 14 22 180 F or W* SCD 9 30 MK030PKC UH2 21.5 19.5 29 300 F or W* SCD 9 45 MK045PKC UH2 21.5 19.5 29 400 F or W* SCD 9 75 MK075PKC UH3 26 21 38 575 F or W* SCD 9 112.5 MK112PKC UH3 26 21 38 750 F SCD 9 150 MK150PKC UH4 30 24 39 900 F SCD 9 225 MK225PKC UJ1 39.5 30 50 1350 F SCD 9 300 MK300PKC UJ1 39.5 30 50 1550 F SCD 9 500 MK500PKC UJ2 48.5 34 59 2400 F SCD 10 750 MK750PKC UJ3 51.5 39 66 3450 F SCD 10

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

For shielded units, please replace the suffi x “C” with “K” on the above part numbers.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

*OPTIONAL WALL MOUNTING KIT REQUIRED.

Products listed on this page are available as ‘CE Mark’ products. Please consult our sales offi ce.

Note: For three phase copper Encapsulated units, please refer to Section 12.

Page 21: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.

SECTION 1SECTION 8 GENERAL PURPOSE DISTRIBUTION TRANSFORMERS

193

SE

CT

ION

8

FOR ACCESSORIES SEE PAGE 273.FOR TERMINATION DETAILS SEE PAGE 271 AND 272.

© Hammond Power Solutions Inc.

Please complete the following Specifi cation Guide/Quote Form for Hammond General Purpose Transformers and fax to: Canada: (519) 822-9688 or U.S.: (608) 356-2080 or contact Hammond Quotations Department directly by calling: Canada: 1-888-798-8882 or U.S.: 1-800-537-0500.

Company Name: _______________________________________________ Date: ________________

Address: ____________________________________________________________________________

City: _________________________ State/Prov.: _____________ Zip/Postal: ____________

Contact Name: ______________________________ Phone #: __________________________

Fax Number: __________________________ E-Mail Address: ___________________________

General Purpose Transformer Specification Guide and Quote Form

PERFORMANCE REQUIREMENTS: (please complete the following) Customer P.O. # :

Quantity: Power Rating (kVA): Phase: Single Three Phase

Frequency: 50 Hz 60 Hz 50/60 Hz

Type: General Purpose Shielded K-Factor 4 K-Factor 13 K-Factor 20 Energy Effi cient

Hazardous Location (potted) Drive Isolation

Open Core & Coil Only: Enclosure: EEMAC Type 1 2 3R 4 4X 12

Insulation Class: Class 150 (B) Class 180 (F) Class 220 (H)

Windings: Copper Aluminum

Primary Volts: ____________V Connection: Standard Other

Primary Taps: Standard Special

Secondary Volts:___________V Connection: Standard Other

Sound Level at No Load: Standard CSA/ANSI Special

Accessories: Sprinkler Kit

Special Paint __________________

Wall Mounting Brackets

Thermostat

Dial Type Thermometers: 2 contact 3 contact

Anti-Vibration Pads Anti-Vibration Isolators

NOTE: See Page 273 for General Purpose Transformer Accessories

(Temp. Rise) 80°C Rise 115°C Rise 150°C Rise

Custom Features: (please list)

Quote # : ______________ Quoted By: __________________________ Date: _______________

Page 22: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

254Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

A

G*PM

C

B

Lifting Provision on UH1, UH2, UH5, UH6 only.

D

H

E

NF*1.00

0.56 Dia (4)

1.75 Typ.

K K,O, (2)Typical perside onEncl. style

FRONT VIEWSIDE VIEW

* Cable Entrance Area in Bottom (F X G)

A

C

G*

P

M

1 3/4 Typ. B

K 3 1/22

J

HV

LV

H1 1/2

E

D

1 F*

N

9/16Dia.(4)

Cable EntranceArea in Sides

* Cable Entrance Areain Bottom (F X G)

E

D

E

A

H

F

C

if wallmounted

B0.5 Typ.

M

L

N

F

R Dia.A Style = 4B Style = 6

P (K.O.)

G

K

FRONT VIEW SIDE VIEW

S

SIDE VIEW WITHOPTIONAL SPRINKLER HOOD

Case Dimensions in Inches Style A B C D E F G H K L M N P R S

A1* 12.00 7.00 10.20 10.00 11.40 5.00 0.50 0.50 0.60 5.50 1.60 1.00 0.5 X 0.75 0.31 10.00 A2* 17.25 11.25 14.00 14.75 16.50 7.00 0.90 0.90 0.40 9.50 2.00 1.00 0.75 X 1.0 0.40 13.25 H1 19.50 16.50 19.00 16.50 18.50 10.00 2.00 3.25 2.50 10.00 2.00 2.50 1.0 X 1.25 0.56 22.50 H2 24.50 20.50 24.50 21.50 23.50 10.00 2.00 3.25 2.50 12.00 2.50 2.50 1.0 X 2.0 0.56 26.50 H3 30.00 24.00 32.50 27.00 29.00 16.00 2.00 3.25 2.50 13.00 3.00 3.00 1.5 X 2.5 0.56 30.00 H4 33.00 26.00 36.00 30.00 32.00 16.00 2.00 3.25 2.50 13.00 3.00 3.00 1.5 X 2.5 0.56 32.00 H5 16.00 16.50 18.00 13.00 15.00 10.00 2.00 3.25 2.50 7.50 2.00 2.50 1.0 X 1.25 0.56 22.50 H6 21.25 20.00 28.00 18.25 20.25 10.00 2.00 3.25 2.50 12.50 3.00 2.50 1.5 X 2.5 0.56 26.00 H7 24.00 26.00 30.00 21.00 23.00 16.00 2.00 3.25 2.50 13.00 3.00 3.00 1.5 X 2.5 0.56 32.00 H8 27.00 26.00 36.00 24.00 26.00 16.00 2.00 3.25 2.50 13.00 3.00 3.00 1.5 X 2.5 0.56 32.00

Case Dimensions in Inches Style A B C D E F G H K M N P

UH1 16.75 14.00 22.00 11.00 2.50 2.25 9.00 6.00 1.38 X 1.75 19.25 9.00 18.25 UH2 21.50 19.50 29.00 15.00 2.50 3.25 14.00 6.00 1.38 X 2.50 24.00 14.50 23.00 UH3 26.00 21.00 38.00 24.00 3.00 4.75 18.00 8.00 2.00 X 3.00 28.50 16.00 27.50 UH4 30.00 24.00 39.00 24.00 3.00 3.75 20.00 9.00 2.00 X 3.00 32.50 19.00 31.50 UH5 13.00 14.00 23.00 10.00 2.50 2.25 6.00 6.00 1.38 X 1.75 15.50 9.00 14.50 UH6 16.00 19.00 31.00 15.00 2.50 2.75 7.00 6.00 2.00 X 3.00 18.50 14.00 17.50 UH7 19.50 21.00 35.00 20.00 3.00 5.25 10.00 8.00 2.00 X 3.00 22.00 16.00 21.00 UH8 24.00 25.00 39.00 24.00 3.00 4.75 11.00 9.00 2.00 X 3.00 26.50 20.00 25.50 UH9 26.50 26.00 44.00 5.00 4.00 5.00 22.50 4.50 10.00 28.50 21.50 27.50 UH10 34.00 30.00 44.00 5.00 6.00 6.00 26.50 5.00 10.00 32.50 29.00 31.50

DIMENSIONAL DRAWINGS‘UH’ SERIES ENCLOSURES

‘A’ & ‘H’ SERIES ENCLOSURES

Note: J dimension for UH9 = 3.50”. J dimension for UH10 = 4.00”

* No ventilation slots in rear.

UH9 AND UH10 SIDE & FRONT VIEWS

Page 23: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.255

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

A

P

C

B

4.0

2.0

.69 Dia. (4)

M

N 1.0

8.0

D

1.50G

K

H

1.50

1.75 Typ.3.5

Cable Entry Location

BA

CK

FRONT VIEW SIDE VIEW

F

E

2.0

CableEntryLocation

BOTTOM VIEW

A

E K

C

4.0

0.69 Dia. (4)F

B

1.0

L

0.5

D

FRONT VIEW SIDE VIEW

H

SIDE VIEW WITHOPTIONAL SPRINKLER HOOD

Case Dimensions in Inches Style A B C D E F H K L

J1 39.72 37.00 50.00 34.25 24.00 35.00 40.00 7.75 2.00 J2 48.75 41.00 59.00 38.25 27.50 39.00 44.00 10.50 2.00 J3 51.75 46.00 66.00 43.25 34.00 44.00 49.00 8.75 2.00 J4 32.25 35.00 50.00 32.25 22.00 33.00 38.00 5.00 2.00 J5 36.00 33.00 44.00 29.50 24.00 31.00 35.50 6.00 2.25 J6 64.00 43.50 68.00 40.00 40.00 41.50 46.00 12.00 2.25

Case Dimensions in Inches Style A B C D E F G H K M N P

UJ1 39.50 30.00 50.00 10.00 7.50 21.50 8.00 6.50 13.50 34.00 32.00 24.00 UJ2 48.50 34.00 59.00 13.00 8.50 25.00 9.00 8.50 15.50 38.00 36.00 27.50 UJ3 51.50 39.00 66.00 16.00 9.50 31.50 10.00 11.50 18.00 43.00 41.00 34.00 UJ4 32.00 28.50 50.00 10.00 8.50 19.50 9.00 6.50 12.75 32.50 30.50 22.00 UJ5 36.00 29.50 44.00 5.00 6.50 21.50 10.00 6.50 12.75 33.00 31.00 24.00 UJ6 64.00 40.00 68.00 16.00 10.50 37.50 11.00 11.50 18.00 43.50 41.50 40.00

DIMENSIONAL DRAWINGS‘UJ’ SERIES ENCLOSURES

‘J’ SERIES ENCLOSURES

Page 24: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

256Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

A

G

C

B

3.50

Lifting HolesM Dia. (2)

J

K (K.O.)

D

H

0.25

K (K.O.)

Wall Mtg. HolesN Dia. (4)D/2

FE

Front and bottom pannelsare removable for accessto terminals.

Note:Center mountinghole not availableon L0, L1, F0, F3and F4 styles.

A

G

C

B

3.50

Lifting HolesM Dia. (2)

J

K (K.O.)

D

H

0.25

K (K.O.)

Wall Mtg. HolesN Dia. (4)D/2

FE

Front and bottom pannelsare removable for accessto terminals.

Note:Center mountinghole not availableon L0, L1, F0, F3and F4 styles.

Ventilation

DIMENSIONAL DRAWINGS‘F’ & ‘L’ SERIES ENCLOSURES

‘L6 to L13’ SERIES ENCLOSURES

Case Dimensions in Inches Style A B C D E F G H J K M N

L6 6.75 4.75 14.38 4.00 13.63 12.00 1.38 1.50 - 0.5 X 0.75 0.75 0.312 L7 6.75 6.25 14.38 4.00 13.63 12.00 1.38 1.50 - 0.5 X 0.75 0.75 0.312 L8 9.00 7.25 17.25 6.25 16.50 15.00 2.38 1.25 - 0.5 X 0.75 0.75 0.312 L9 9.00 8.50 18.25 6.25 17.50 16.00 2.75 2.25 - 0.5 X 0.75 0.75 0.312 L10 11.50 7.50 20.75 8.75 20.00 18.44 - - - - 0.75 0.312 L11 11.50 9.00 20.75 8.75 20.00 18.44 - - - - 0.75 0.312 L12 13.00 12.00 20.50 10.28 19.44 17.44 - - - - 0.75 0.406 L13 15.00 12.00 25.00 12.50 23.94 21.92 - - - - 0.75 0.406

Case Dimensions in Inches Style A B C D E F G H J K M N

L0 7.00 7.00 14.75 4.50 13.00 11.13 1.50 2.50 - .50 X .75 0.75 0.265 L1 9.00 8.50 17.50 5.50 15.75 13.88 2.00 1.50 7.00 .75 X 1.0 0.75 0.265 L2 12.50 8.00 23.00 9.00 21.25 19.38 2.00 1.50 6.88 .75 X 1.0 0.75 0.265 L3 12.50 6.00 16.50 9.00 14.75 12.88 2.00 1.50 4.50 .75 X 1.0 0.75 0.265 L4 16.50 6.00 19.00 13.00 17.25 15.38 1.50 2.00 4.50 1.0 X 1.25 0.75 0.265 L5 7.50 7.75 15.94 5.50 14.20 12.80 1.50 2.50 - 0.5 X 0.75 0.75 0.265 F0 8.00 7.50 15.00 5.50 14.20 12.50 1.50 2.75 - .75 X 1.0 0.75 0.312 F1 8.75 9.00 15.50 5.75 14.68 13.13 2.00 3.50 - .75 X 1.0 0.75 0.312 F2 10.75 8.50 16.50 7.50 15.68 14.13 2.00 3.50 - .75 X 1.0 0.75 0.312 F3 11.75 8.13 19.50 8.75 18.68 17.13 2.00 3.50 - 1.0 X 2.0 0.75 0.375 F4 13.50 9.44 21.75 10.50 21.00 19.38 2.00 4.00 - 1.0 X 2.0 0.75 0.437

Page 25: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.257

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

A

G

C

B

CJ

L (K.O.)

D

H

0.88" x 1.25" Slot

FRONT VIEWG1 - G4G6 - G7

FRONT VIEWG5

Wall Mtg. Holes0.56" Dia. (4)

FE

Front and bottom pannelsare removable for accessto terminals.

K (K.O.)

N

AM

Wall Mtg. Holes0.56" Dia. (4)

A

D

B

C

K

FRONT VIEW SIDE VIEW

E

M

G X H (4 slots)

F

A

B

C

G

H E

D

M

K

DIMENSIONAL DRAWINGS‘G’ SERIES ENCLOSURES

Case Dimensions in Inches Style A B C D E F G H J K L M N

G1 17.44 7.00 21.50 8.31 20.00 17.50 2.25 1.63 4.88 1.0 X 1.25 0.75 X 1.0 - - G2 17.44 8.50 21.50 8.50 20.00 17.50 2.25 1.88 5.63 1.0 X 1.25 0.75 X 1.0 - - G3 19.44 9.50 26.50 10.00 25.00 22.50 2.50 2.63 6.88 1.5 X 2.0 1.0 X 1.25 - - G4 22.94 10.25 30.00 13.81 28.50 25.00 2.75 2.63 7.38 1.5 X 2.0 1.0 X 1.25 - - G5 16.50 12.75 27.50 - - 24.40 1.50 2.50 8.50 1.0 X 1.25 1.0 X 1.25 14.60 12.50 G6 18.00 14.00 35.00 10.00 32.50 30.00 2.75 3.25 9.25 1.5 X 2.0 1.0 X 1.25 - - G7 33.75 13.00 35.00 20.00 32.75 30.00 2.75 2.25 8.75 1.0 X 1.25 2.0 X 2.0 -

Case Dimensions in Inches Knockout

Style A B C D E F G X H K M

M01 2.5 3.37 4.06 2.00 3.16 4.19” .20 X .56 1.25 .50 M02 2.5 3.37 4.56 2.00 3.66 4.69 .20 X .56 1.25 .50 M11 3.13 4.00 4.63 2.25 3.88 4.50 .25 X .50 1.25 .50 M12 3.13 4.00 4.88 2.25 4.13 4.50 .25 X .50 1.25 .50 M13 3.13 4.00 5.38 2.25 4.63 5.25 .25 X .50 1.25 .50 M21 3.75 4.75 4.56 2.75 3.56 4.28 .25 X .50 1.25 .50 X .75 M22 3.75 4.75 4.81 2.75 3.81 4.28 .25 X .50 1.25 .50 X .75 M23 3.75 4.75 5.56 2.75 4.56 5.28 .25 X .50 1.25 .50 X .75 M24 3.75 4.75 6.06 2.75 4.81 5.28 .25 X .50 1.25 .50 X .75 M31 4.31 5.50 7.41 3.25 5.58 6.75 .31 X .63 1.00 .50 X .75 M32 4.31 5.50 7.91 3.25 6.08 7.25 .31 X .63 1.25 .50 X .75

‘M’ SERIES ENCLOSURES

‘E’ SERIES ENCLOSURES

Case Dimensions in Inches Knockout

Style A B C D E F G X H K M

E01 5.31 9.50 6.75 4.25 7.50 - .31 X .63 1.25 .50 X .75 E02 5.31 10.50 6.75 4.25 8.50 - .31 X .63 1.25 .50 X .75 E11 6.25 10.50 8.00 5.00 9.00 - .31 X .63 1.25 .50 X .75 E21 7.5 10.75 9.50 6.00 9.25 - .38 X .75 1.25 .75 X 1.00

Page 26: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

258Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

H1 H3 H2 H4

X4 X2 X3 X1

H1 H2

X4 X2 X3 X1

3 421

H1 H4H2H3

X4 X1X3X2

5 64213

H1 H2

X4 X3X2 X1

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Primary Volts Connect lines to Inter-connect

208 277 347 380 416 600 H1, H2 ---

SCHEMATIC CONNECTIONS

SCD 4

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3

Primary Volts Connect lines to Inter-connect

504 H1, H4 1-H2, 2-H3, H2-H3 492 H1, H4 2-H3, 3-H2, H2-H3 480 H1, H4 3-H2, 4-H3, H2-H3 468 H1, H4 4-H3, 5-H2, H2-H3 456 H1, H4 5-H2, 6-H3, H2-H3 252 H1, H4 1-H2, 2-H3, H1-H3, H2-H4 240 H1, H4 3-H2, 4-H3, H1-H3, H2-H4 228 H1, H4 5-H2, 6-H3, H1-H3, H2-H4

SCHEMATIC CONNECTIONS

SCD 3

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3

Primary Volts Connect lines to Inter-connect

480 416 H1, H4 H2-H3 240 208 H1, H4 H1-H3, H2-H4

SCHEMATIC CONNECTIONS

SCD 1

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3

Primary Volts Connect lines to Inter-connect

480 H1, H2 1-2 468 H1, H2 2-3 456 H1, H2 3-4 240 H1, H2 H1-2, H2-1 228 H1, H2 H1-4, H2-3

SCHEMATIC CONNECTIONS

SCD 2

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3

Page 27: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.259

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

H1 H2

X4 X3X2 X1

3 421

H1

5 64213

H2

X4 X3X2 X1

H2

H3

H1 X1

X2

X0

X3

12

3

H2X2

X0

X3H3H1

X1

42

13

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Primary Volts Connect lines to Inter-connect

208 240 277 416 480 600 H1, H2 1-2 198 228 263 395 456 570 H1, H2 2-3 187 216 249 374 432 540 H1, H2 3-4 120 208 240 H1, H2 H1-2, H2-1 108 187 216 H1, H2 H1-4, H2-3

SCHEMATIC CONNECTIONS

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3

Primary Volts Connect lines to Inter-connect

218 291 437 504 630 2520 4368 H1, H2 1-2 213 284 426 492 615 2460 4264 H1, H2 2-3 208 277 416 480 600 2400 4160 H1, H2 3-4 203 270 406 468 585 2340 4056 H1, H2 4-5 198 263 395 456 570 2280 3952 H1, H2 5-6

SCHEMATIC CONNECTIONS

SCD 6

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3

Primary Volts Connect lines to Inter-connect

218 252 437 483 504 630 H1, H2, H3 1 208 240 416 460 480 600 H1, H2, H3 2 198 228 395 437 456 570 H1, H2, H3 3

SCHEMATIC CONNECTIONS

SCD 7

Secondary Volts Connect lines to

208 230 240 380 416 460 480 600 X1, X2, X3 120 133 139 220 240 265 277 347 X1, X0 X2, X0 X3, X0

Primary Volts Connect lines to Inter-connect

218 252 437 483 504 630 2520 4368 H1, H2, H3 1-2208 240 416 460 480 600 2400 4160 H1, H2, H3 2-3198 228 395 437 456 570 2280 3952 H1, H2, H3 3-4

SCHEMATIC CONNECTIONS

SCD 8

Secondary Volts Connect lines to

208 230 240 380 416 460 480 600 X1, X2, X3 120 133 139 220 240 265 277 347 X1, X0 X2, X0 X3, X0

SCD 5

Page 28: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

260Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

H2

H1

H3

X1

X2

X0

X3

12

34

5

H2

H1 H3

X0

X1

X2

X3

12

34

56

H2

H1

H3

X2

X1 X3

132

H2 X2

H1 H3 X1 X3

12

3

4

Primary Volts Connect lines to Inter-connect

218 252 437 483 504 630 2520 4368 H1, H2, H3 1 213 246 426 574 492 615 2460 4264 H1, H2, H3 2 208 240 416 460 480 600 2400 4160 H1, H2, H3 3 203 234 406 449 468 585 2340 4056 H1, H2, H3 4 198 228 395 437 456 570 2280 3952 H1, H2, H3 5

Secondary Volts Connect lines to Inter-connect

208 380 416 480 600 X1, X2, X3 - 120 220 240 277 347 X1, X0 - X2, X0 - X3, X0 -

SCHEMATIC CONNECTIONS

SCD 9

SCHEMATIC CONNECTIONS

SCD 10

Secondary Volts Connect lines to Inter-connect

208 380 416 480 600 X1, X2, X3 - 120 220 240 277 347 X1, X0 - X2, X0 - X3, X0 -

Primary Volts Connect lines to Inter-connect

218 252 437 483 504 630 2520 4368 H1, H2, H3 1-2 213 246 426 574 492 615 2460 4264 H1, H2, H3 2-3 208 240 416 460 480 600 2400 4160 H1, H2, H3 3-4 203 234 406 449 468 585 2340 4056 H1, H2, H3 4-5 198 228 395 437 456 570 2280 3952 H1, H2, H3 5-6

Primary Volts Connect lines to Inter-connect

252 504 H1, H2, H3 1 240 480 H1, H2, H3 2 228 456 H1, H2, H3 3

SCHEMATIC CONNECTIONS

SCD 11

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 -

Primary Volts Connect lines to Inter-connect

480 600 H1, H2, H3 1-2 456 570 H1, H2, H3 2-3 432 540 H1, H2, H3 3-4

SCHEMATIC CONNECTIONS

SCD 12

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 -

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Page 29: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.261

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

X2H2

H1 H3 X1 X3X6

12

3

4

120 120

X2H2

H1

H3X1 X3X6

12

34

120 120

5

X2H2

H1 H3 X1 X3X6

12

3

4

120 120

5

6

H2

H3H1

X1

X2

X3

123

Primary Volts Connect lines to Inter-connect

480 600 H1, H2, H3 1-2 456 570 H1, H2, H3 2-3 432 540 H1, H2, H3 3-4

SCHEMATIC CONNECTIONS

SCD 13

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 - 120 X1, X6 - X3, X6 -

Primary Volts Connect lines to Inter-connect

504 H1, H2, H3 1 492 H1, H2, H3 2 480 H1, H2, H3 3 468 H1, H2, H3 4 456 H1, H2, H3 5

SCHEMATIC CONNECTIONS

SCD 14

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 - 120 X1, X6 - X3, X6 -

Primary Volts Connect lines to Inter-connect

504 H1, H2, H3 1-2 492 H1, H2, H3 2-3 480 H1, H2, H3 3-4 468 H1, H2, H3 4-5 456 H1, H2, H3 5-6

SCHEMATIC CONNECTIONS

SCD 15

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 - 120 X1, X6 - X3, X6 -

Primary Volts Connect lines to Inter-connect

218 504 504 630 H1, H2, H3 1 208 480 480 600 H1, H2, H3 2 198 456 456 570 H1, H2, H3 3

SCHEMATIC CONNECTIONS

SCD 16

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Page 30: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

262Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

H2

H3

H1

X1

X2

X3

123

54

H1 H2

X4 X3X2 X1

H2H5

H4H3

HV HVH1 H2 H3 H4 H1 H2 H3 H4

OR

OR

7 8642135 7 8642135

X4 X1X3X2X4 X1X3X2

LV LV LVLV

HV HV

H1 H2H3

H4 H2H3

H4H1

OR

OR X4 X1X3X2X4 X1X3X2

LV LV LV

LV

Primary Volts Connect lines to Inter-connect

504 630 H1, H2, H3 1 492 615 H1, H2, H3 2 480 600 H1, H2, H3 3 468 585 H1, H2, H3 4 456 570 H1, H2, H3 5

SCHEMATIC CONNECTIONS

SCD 17

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3

Primary Volts Connect lines to Inter-connect

218 437 504 630 H1, H6 - 213 426 492 615 H1, H5 - 208 416 480 600 H1, H4 - 203 406 468 585 H1, H3 - 198 395 456 570 H1, H2 -

SCHEMATIC CONNECTIONS

SCD 18

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3

Primary Volts Connect lines to Inter-connect

504 H1, H4 1-H2, 2-H3, H2-H3 492 H1, H4 3-H2, 2-H3, H2-H3 480 H1, H4 3-H2, 4-H3, H2-H3 468 H1, H4 5-H2, 4-H3, H2-H3 456 H1, H4 5-H2, 6-H3, H2-H3 444 H1, H4 7-H2, 6-H3, H2-H3 432 H1, H4 7-H2, 8-H3, H2-H3 252 H1, H4 1-H2, 2-H3, H1-H3, H2-H4 240 H1, H4 3-H2, 4-H3, H1-H3, H2-H4 228 H1, H4 5-H2, 6-H3, H1-H3, H2-H4 216 H1, H4 7-H2, 8-H3, H1-H3, H2-H4

SCHEMATIC CONNECTIONS

SCD 19

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2- X3 120 X1, X2 X1-X3, X2-X4 120/240 X1, X2, X4 X2-X3

Primary Volts Connect lines to Inter-connect

218 252 291 437 504 630 H1, H4 - 208 240 277 416 480 600 H1, H3 - 198 228 263 395 456 570 H1, H2 - 188 216 249 374 432 540 H1, H2 -

SCHEMATIC CONNECTIONS

SCD 20

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120 X1, X2 X1-X3, X2-X4 120/240 X1, X2, X4 X2-X3

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Page 31: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.263

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

X2H2

H1

H3

X1X3

X0

12

34

567

X2H2

H1 H3

X1

X3

X0

86

42

357

1

X2H2

H1

H3X1 X3

X6

12

34

567

120V 120V

Primary Volts Connect lines to Inter-connect

218 504 630 H1, H2, H3 1-H1, 1-H2, 1-H3 213 492 615 H1, H2, H3 2-H1, 2-H2, 2-H3 208 480 600 H1, H2, H3 3-H1, 3-H2, 3-H3 203 468 585 H1, H2, H3 4-H1, 4-H2, 4-H3 198 456 570 H1, H2, H3 5-H1, 5-H2, 5-H3 193 444 556 H1, H2, H3 6-H1, 6-H2, 6-H3 188 432 542 H1, H2, H3 7-H1, 7-H2, 7-H3

SCHEMATIC CONNECTIONS

SCD 21

Secondary Volts Connect lines to Inter-connect

208 480 X1, X2, X3 - 120 277 X1, X0 - X2, X0 - X3, X0 -

Primary Volts Connect lines to Inter-connect

218 504 H1, H2, H3 1-2 213 492 H1, H2, H3 2-3 208 480 H1, H2, H3 3-4 203 468 H1, H2, H3 4-5 198 456 H1, H2, H3 5-6 193 444 H1, H2, H3 6-7 188 432 H1, H2, H3 7-8

SCHEMATIC CONNECTIONS

SCD 22

Secondary Volts Connect lines to Inter-connect

208 X1, X2, X3 - 120 X1, X0 - X2, X0 - X3, X0 -

Primary Volts Connect lines to Inter-connect

504 H1, H2, H3 1-H1, 1-H2, 1-H3 492 H1, H2, H3 2-H1, 2-H2, 2-H3 480 H1, H2, H3 3-H1, 3-H2, 3-H3 468 H1, H2, H3 4-H1, 4-H2, 4-H3 456 H1, H2, H3 5-H1, 5-H2, 5-H3 444 H1, H2, H3 6-H1, 6-H2, 6-H3 432 H1, H2, H3 7-H1, 7-H2, 7-H3

SCHEMATIC CONNECTIONS

SCD 23

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 - 120 X1, X6 - X3, X6 -

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Page 32: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

264Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

X2H2

H1 H3 X1 X3X6

120V 120V

86

42

357

1

H2

H3

H1

X1

X2

X3

123

H0

H2X2

H1

H3X1

X3

12

3

4

H0

H2X2

H1

H3X1

X3

1237

H0

5 64

Primary Volts Connect lines to Inter-connect

504 H1, H2, H3 1-2 492 H1, H2, H3 2-3 480 H1, H2, H3 3-4 468 H1, H2, H3 4-5 456 H1, H2, H3 5-6 444 H1, H2, H3 6-7 432 H1, H2, H3 7-8

SCHEMATIC CONNECTIONS

SCD 24

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 - 120 X1, X6 - X3, X6 -

Primary Volts Connect lines to Inter-connect

208 230 240 X1, X2, X3 1-X1, 1-X2, 1-X3 198 218 228 X1, X2, X3 2-X1, 2-X2, 2-X3 188 207 216 X1, X2, X3 3-X1, 3-X2, 3-X3

SCHEMATIC CONNECTIONS

SCD 25

Secondary Volts Connect lines to

230 260 460 480 H1, H2, H3 133 139 265 277 H1, H0 H2, H0 H3, H0

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Primary Volts Connect lines to Inter-connect

208 240 X1, X2, X3 1-2 198 228 X1, X2, X3 2-3 188 216 X1, X2, X3 3-4

SCHEMATIC CONNECTIONS

SCD 26

Secondary Volts Connect lines to

230 260 460 480 H1, H2, H3 133 139 265 277 H1, H0 H2, H0 H3, H0

Primary Volts Connect lines to Inter-connect

218 X1, X2, X3 1-X1, 1-X2, 1-X3 213 X1, X2, X3 2-X1, 2-X2, 2-X3 208 X1, X2, X3 3-X1, 3-X2, 3-X3 203 X1, X2, X3 4-X1, 4-X2, 4-X3 198 X1, X2, X3 5-X1, 5-X2, 5-X3 193 X1, X2, X3 6-X1, 6-X2, 6-X3 188 X1, X2, X3 7-X1, 7-X2, 7-X3

SCHEMATIC CONNECTIONS

SCD 27

Secondary Volts Connect lines to

208 230 240 480 H1, H2, H3 120 133 133 277 H1, H0 H2, H0 H3, H0

Page 33: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.265

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

H2X2

H1

H3X1

X3

12

37

H0

5

648

X2H2

H1

H3X1 X3

12

34

567

X2H2

H1 H3 X1 X3

86

42

357

1

X2H2

H1

H3

X1

X3H0/X0

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Primary Volts Connect lines to Inter-connect

218 X1, X2, X3 1-2 213 X1, X2, X3 2-3 208 X1, X2, X3 3-4 203 X1, X2, X3 4-5 198 X1, X2, X3 5-6 193 X1, X2, X3 6-7 188 X1, X2, X3 7-8

SCHEMATIC CONNECTIONS

SCD 28

Secondary Volts Connect lines to

208 240 480 H1, H2, H3 120 133 277 H1, H0 H2, H0 H3, H0

Primary Volts Connect lines to Inter-connect

504 H1, H2, H3 1-H1, 1-H2, 1-H3 492 H1, H2, H3 2-H1, 2-H2, 2-H3 480 H1, H2, H3 3-H1, 3-H2, 3-H3 468 H1, H2, H3 4-H1, 4-H2, 4-H3 456 H1, H2, H3 5-H1, 5-H2, 5-H3 444 H1, H2, H3 6-H1, 6-H2, 6-H3 432 H1, H2, H3 7-H1, 7-H2, 7-H3

SCHEMATIC CONNECTIONS

SCD 29

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 -

Primary Volts Connect lines to Inter-connect

504 H1, H2, H3 1-2 492 H1, H2, H3 2-3 480 H1, H2, H3 3-4 468 H1, H2, H3 4-5 456 H1, H2, H3 5-6 444 H1, H2, H3 6-7 432 H1, H2, H3 7-8

SCHEMATIC CONNECTIONS

SCD 30

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3 -

Connect to Step Down Step Up Lines from Supply H1, H2, H3 X1, X2, X3

Lines to Load X1, X2, X3 H1, H2, H3 Neutral X0 H0

SCHEMATIC CONNECTIONSSCD 31

Page 34: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

266Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

H2

H3

H1 X1

X2

X0

X3

12

3

H2X2

X0

X3H3H1

X1

42

13

H2X2

H1

H3X1

X3

123

H0

54

H2X2

H1

H3X1

X3

12

3

H0

5

64

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

SCHEMATIC CONNECTIONS

SCD 34

Secondary Volts Connect lines to Inter-connect

460 480 600 X1, X2, X3 - 265 277 347 X1, X0 X2, X0 X3, X0 -

Primary Volts Connect lines to Inter-connect

218 252 H1, H2, H3 1 213 246 H1, H2, H3 2 208 240 H1, H2, H3 3 203 234 H1, H2, H3 4 198 228 H1, H2, H3 5

Primary Volts Connect lines to Inter-connect

208 240 416 480 600 H1, H2, H3 1 198 228 395 456 570 H1, H2, H3 2 187 216 374 432 540 H1, H2, H3 3

SCHEMATIC CONNECTIONS

SCD 32

Secondary Volts Connect lines to

208 230 240 380 416 460 480 600 X1, X2, X3 120 133 139 220 240 265 277 347 X1, X0 X2, X0 X3, X0

SCHEMATIC CONNECTIONS

SCD 33

Primary Volts Connect lines to Inter-connect

208 240 416 480 600 H1, H2, H3 1-2 198 228 395 456 570 H1, H2, H3 2-3 187 216 374 432 540 H1, H2, H3 3-4

Secondary Volts Connect lines to Inter-connect

208 380 416 480 600 X1, X2, X3 - 120 220 240 277 347 X1, X0 X2, X0 X3, X0 -

SCHEMATIC CONNECTIONS

SCD 35

Primary Volts Connect lines to Inter-connect

218 252 H1, H2, H3 1-2 213 246 H1, H2, H3 2-3 208 240 H1, H2, H3 3-4 203 234 H1, H2, H3 4-5 198 228 H1, H2, H3 5-6

Secondary Volts Connect lines to Inter-connect

460 480 600 X1, X2, X3 - 265 277 347 X1, X0 X2, X0 X3, X0 -

Page 35: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.267

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

H2

H3

H1

X1

X2

X3

123

H0

H2X2

H1

H3X1

X3

12

3

4

H0

H1 120V

120VX2 X1

H2

X2H2

H1

H3

X1

X3H0/X0

ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS

Primary Volts Connect lines to Inter-connect

218 252 X1, X2, X3 1-X1, 1-X2, 1-X3 208 240 X1, X2, X3 2-X1, 2-X2, 2-X3 198 228 X1, X2, X3 3-X1, 3-X2, 3-X3

SCHEMATIC CONNECTIONS

SCD 36

Secondary Volts Connect lines to Inter-connect

480 H1, H2, H3 - 277 H1, H0 - H2, H0 - H3, H0 -

Primary Volts Connect lines to Inter-connect

218 252 X1, X2, X3 1-2 208 240 X1, X2, X3 2-3 198 228 X1, X2, X3 3-4

SCHEMATIC CONNECTIONS

SCD 37

Secondary Volts Connect lines to Inter-connect

480 H1, H2, H3 - 277 H1, H0 - H2, H0 - H3, H0

Primary Volts Connect lines to Inter-connect

120 H1, H2 ---

SCHEMATIC CONNECTIONS

SCD 39

Secondary Volts Connect lines to Inter-connect

120 X1, X2 ---

Connect to Step Down Step Up Lines from Supply H1, H2, H3 X1, X2, X3

Lines to Load X1, X2, X3 H1, H2, H3 Neutral X0 H0

SCHEMATIC CONNECTIONSSCD 38

Page 36: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

268Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

H2

H3

H1

X1

X2

X3

1

42

3

H1 208V

120VX2 X1

H2

H1 240V

120VX2 X1

H2

H1 480V

120VX2 X1

H2

H1 600V

120VX2 X1

H2

Primary Volts Connect lines to Inter-connect

208 H1, H2 ---

SCHEMATIC CONNECTIONS

SCD 40

Secondary Volts Connect lines to Inter-connect

120 X1, X2 ---

Primary Volts Connect lines to Inter-connect

240 H1, H2 ---

SCHEMATIC CONNECTIONS

SCD 41

Secondary Volts Connect lines to Inter-connect

120 X1, X2 ---

Primary Volts Connect lines to Inter-connect

630 H1, H2, H3 1-2 600 H1, H2, H3 2-3 570 H1, H2, H3 3-4

SCHEMATIC CONNECTIONS

SCD 42

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3

Primary Volts Connect lines to Inter-connect

480 H1, H2 ---

SCHEMATIC CONNECTIONS

SCD 43

Secondary Volts Connect lines to Inter-connect

120 X1, X2 ---

Primary Volts Connect lines to Inter-connect

600 H1, H2 ---

SCHEMATIC CONNECTIONS

SCD 44

Secondary Volts Connect lines to Inter-connect

120 X1, X2 ---

Page 37: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.269

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

H2

H3

H1

X1

X2

X3

1

642

35

HV HVH1 H2 H3 H4 H1 H2 H3 H4

OR

OR

7 8642135 7 8642135

X4 X1X3X2X4 X1X3X2

LV LV LVLV

H1 H2H3

H4 H6H8

H9H7H5 H10

X4 X3 X2 X1

Primary Volts Connect lines to Inter-connect

440 H1, H10 H5-H6 416 H1, H9 H4-H6 400 H1, H8 H3-H6 380 H1, H7 H2-H6 220 H1, H10 H1-H6, H5-H10 208 H1, H9 H1-H6, H4-H9 200 H1, H8 H1-H6, H3-H8 120 H1, H7 H1-H6, H2-H7

SCHEMATIC CONNECTIONS

SCD 45

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2-X3 120/240 X1, X2, X4 X2-X3 120 X1, X4 X2-X4, X1-X3

Primary Volts Connect lines to Inter-connect

440 H1, H4 1-H2, 2-H3, H2-H3 416 H1, H4 3-H2, 4-H3, H2-H3 400 H1, H4 5-H2, 6-H3, H2-H3 380 H1, H4 7-H2, 8-H3, H2-H3 220 H1, H4 1-H2, 2-H3, H1-H3, H2-H4 208 H1, H4 3-H2, 4-H3, H1-H3, H2-H4 200 H1, H4 5-H2, 6-H3, H1-H3, H2-H4 190 H1, H4 7-H2, 8-H3, H1-H3, H2-H4

SCHEMATIC CONNECTIONS

SCD 46

Secondary Volts Connect lines to Inter-connect

240 X1, X4 X2- X3 120 X1, X2 X1-X3, X2-X4 120/240 X1, X2, X4 X2-X3

Primary Volts Connect lines to Inter-connect

630 504 H1, H2, H3 1-2 615 492 H1, H2, H3 2-3 600 480 H1, H2, H3 3-4 585 468 H1, H2, H3 4-5 570 456 H1, H2, H3 5-6

SCHEMATIC CONNECTIONS

SCD 47

Secondary Volts Connect lines to Inter-connect

240 X1, X2, X3

Page 38: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

270Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

TERMINATION DETAILS - For NEMA 1 Style TransformersIncludes: Autotransformers (Section 13) and Medium Voltage Transformers (Section 14).

SINGLE PHASE TERMINATION - AWG(MCM) OR PADS kVA VOLTAGE 120/240 277 416 480 600 2400 4160

0.25 Leads Leads Leads Leads Leads - - 0.5 Leads Leads Leads Leads Leads - - 0.75 Leads Leads Leads Leads Leads - - 1 Leads Leads Leads Leads Leads - - 1.5 Leads Leads Leads Leads Leads - - 2 Leads Leads Leads Leads Leads - - 3 Leads Leads Leads Leads Leads - - 5 Leads Leads Leads Leads Leads - - 7.5 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 - - 10 #4-#14 #6-#14 #6-#14 #6-#14 #6-#14 - - 15 #2-#14 #2-#14 #4-#14 #4-#14 #4-#14 #6-#14 #6-#14 25 #2/0-#6 #2/0-#6 #2-#14 #2-#14 #2-#14 #6-#14 #6-#14 37.5 #250-#6 #250-#6 #2/0-#6 #2/0-#6 #2-#14 #6-#14 #6-#14 50 #600-#2 #350-#6 #250-#6 #2/0-#6 #2/0-#6 #6-#14 #6-#14 75 2X#350-#4 #600-#2 #350-#6 #250-#6 #250-#6 #6-#14 #6-#14 100 Diagram 1D Diagram 1D #600-#2 #600-#2 #350-#6 #2-#14 #6-#14 150 Diagram 2 Diagram 1D Diagram 1D 2X#350-#4 #600-#2 #2-#14 #2-#14 167 Diagram 2 Diagram 2 Diagram 1D Diagram 1D 2X#350-#6 #2-#14 #2-#14 250 Diagram 2 Diagram 2 Diagram 2 Diagram 1D Diagram 1D #2/0-#6 #2-#14 333 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 #250-#6 #2/0-#6

THREE PHASE TERMINATION - AWG(MCM) OR PADS kVA VOLTAGE 208 230 240 380 416 480 600 2400 4160

2 Leads Leads Leads Leads Leads Leads Leads - - 3 Leads Leads Leads Leads Leads Leads Leads - - 6 Leads Leads Leads Leads Leads Leads Leads - - 9 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 15 #4-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 30 #2/0-#6 #2/0-#14 #2/0-#14 #2-#14 #4-#14 #4-#14 #4-#14 #6-#14 #6-#14 45 #250-#6 #250-#6 #250-#6 #2-#14 #2-#14 #2-#14 #4-#14 #6-#14 #6-#14 75 #600-#2 #350-#4 #350-#4 #250-#6 #2/0-#6 #2/0-#6 #2/0-#6 #6-#14 #6-#14 112.5 2X#350-#4 #600-#2 #600-#2 #350-#4 #250-#6 #250-#6 #2/0-#6 #6-#14 #6-#14 150 Diagram 1D Diagram 1D Diagram 1D #600-#2 #600-#2 #350-#4 #250-#6 #6-#14 #6-#14 225 Diagram 2 Diagram 2 Diagram 1D Diagram 1D 2X#350-#4 #600-#2 #600-#2 #2-#14 #6-#14 300 Diagram 2 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1D 2X#350-#4 #2/0-#6 #2-#14 500 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 1D #250-#6 #2-#14 600 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 #250-#6 #2/0-#6 750 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 #350-#4 #2/0-#6

1A - 0.281” Dia.1B - 0.343” Dia.1C - 0.437” Dia.1D - 0.560” Dia.

DIAGRAM 1

0.56” x 1.0 Slot (Qty. 4) or0.56” Diameter (Qty. 4)

DIAGRAM 2

Page 39: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.271

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

TERMINATION DETAILS - NEMA 3R, ALUMINUM WOUNDIncluding: Drive Isolation (Section 4), General Purpose Distribution (Section 8), K-Factor (Section 9), Energy Effi cient (Section 10) and Low Temperature Rise (Section 11).

THREE PHASE, ALUMINUM TERMINATION - AWG(MCM) OR PADS kVA VOLTAGE 208 230 380 416 480 600 2400 4160

2 Leads Leads Leads Leads Leads Leads - - 3 Leads Leads Leads Leads Leads Leads - - 6 Leads Leads Leads Leads Leads Leads - - 9 #4-#14 #4-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 15 #4-#14 #4-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 #6-#14 30 #2/0-#6 #2-#14 #2-#14 #4-#14 #4-#14 #4-#14 #6-#14 #6-#14 45 #250-#6 #250-#6 #2-#14 #2-#14 #2-#14 #4-#14 #6-#14 #6-#14 75 Diagram 1C Diagram 1C #2/0-#6 #2/0-#6 #2/0-#6 #2/0-#14 #6-#14 #6-#14 112.5 Diagram 1D Diagram 1D Diagram 1C #250-#6 #250-#6 #250-#6 #6-#14 #6-#14 150 Diagram 1D Diagram 1D Diagram 1C Diagram 1C Diagram 1C #250-#6 #6-#14 #6-#14 225 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1C Diagram 1C #2-#14 #2-#14 300 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1D Diagram 1D #2/0-#6 #2-#14 500 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 1D #2/0-#6 #2-#14 600 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 #250-#6 #2/0-#6 750 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 1C #2/0-#6

SINGLE PHASE, ALUMINUM TERMINATION - AWG(MCM) OR PADS kVA VOLTAGE 120/240 277 416 480 600 2400 4160

0.25 Leads Leads Leads Leads Leads - - 0.5 Leads Leads Leads Leads Leads - - 0.75 Leads Leads Leads Leads Leads - - 1 Leads Leads Leads Leads Leads - - 1.5 Leads Leads Leads Leads Leads - - 2 Leads Leads Leads Leads Leads - - 3 Leads Leads Leads Leads Leads - - 5 Leads Leads Leads Leads Leads - - 7.5 #4-#14 #4-#14 #4-#14 #4-#14 #4-#14 #6-#14 #6-#14 10 #4-#14 #4-#14 #4-#14 #4-#14 #4-#14 #6-#14 #6-#14 15 Diagram 1A #2-#14 #4-#14 #4-#14 #4-#14 #6-#14 #6-#14 25 Diagram 1A #2/0-#6 #2-#14 #2-#14 #2-#14 #6-#14 #6-#14 37.5 Diagram 1B #250-#6 #2/0-#6 #2/0-#6 #2-#14 #6-#14 #6-#14 50 Diagram 1C Diagram 1C #250-#6 #2/0-#6 #2/0-#6 #6-#14 #6-#14 75 Diagram 1D Diagram 1C Diagram 1C #250-#6 #250-#6 #6-#14 #6-#14 100 Diagram 1D Diagram 1D Diagram 1C Diagram 1C Diagram 1C Diagram 1A Diagram 1A 150 Diagram 2 Diagram 1D Diagram 1D Diagram 1D Diagram 1C Diagram 1A Diagram 1A 167 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1D Diagram 1A Diagram 1A 250 Diagram 2 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1A Diagram 1A 333 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 1B Diagram 1A

1A - 0.281” Dia.1B - 0.343” Dia.1C - 0.437” Dia.1D - 0.560” Dia.

DIAGRAM 1

0.56” x 1.0 Slot (Qty. 4) or0.56” Diameter (Qty. 4)

DIAGRAM 2

Page 40: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

272Data subject to change without notice.

GENERAL INFORMATIONG

EN

ER

AL

IN

FO

RM

AT

ION

© Hammond Power Solutions Inc.

SINGLE PHASE, COPPER TERMINATION - AWG(MCM) OR PADS kVA VOLTAGE 120/240 277 416 480 600 2400 4160

0.25 Leads Leads Leads Leads Leads - - 0.5 Leads Leads Leads Leads Leads - - 0.75 Leads Leads Leads Leads Leads - - 1 Leads Leads Leads Leads Leads - - 1.5 Leads Leads Leads Leads Leads - - 2 Leads Leads Leads Leads Leads - - 3 Leads Leads Leads Leads Leads - - 5 Leads Leads Leads Leads Leads - - 7.5 Diagram 1A #4-#14 #4-#14 #4-#14 #4-#14 Diagram 1A Diagram 1A 10 Diagram 1A #4-#14 #4-#14 #4-#14 #4-#14 Diagram 1A Diagram 1A 15 Diagram 1A Diagram 1A #4-#14 #4-#14 #4-#14 Diagram 1A Diagram 1A 25 Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A 37.5 Diagram 1B Diagram 1B Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A 50 Diagram 1C Diagram 1C Diagram 1B Diagram 1A Diagram 1A Diagram 1A Diagram 1A 75 Diagram 1D Diagram 1C Diagram 1C Diagram 1B Diagram 1B Diagram 1A Diagram 1A 100 Diagram 1D Diagram 1D Diagram 1C Diagram 1C Diagram 1C Diagram 1A Diagram 1A 150 Diagram 2 Diagram 1D Diagram 1D Diagram 1D Diagram 1C Diagram 1A Diagram 1A 167 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1D Diagram 1A Diagram 1A 250 Diagram 2 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1A Diagram 1A 333 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 1B Diagram 1A

THREE PHASE, COPPER TERMINATION - AWG(MCM) OR PADS kVA VOLTAGE 208 230 380 416 480 600 2400 4160

2 Leads Leads Leads Leads Leads Leads - - 3 Leads Leads Leads Leads Leads Leads - - 6 Leads Leads Leads Leads Leads Leads - - 9 #4-#14 #4-#14 #6-#14 #6-#14 #6-#14 #6-#14 Diagram 1A Diagram 1A 15 #4-#14 #4-#14 #6-#14 #6-#14 #6-#14 #6-#14 Diagram 1A Diagram 1A 30 Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A 45 Diagram 1B Diagram 1B Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A 75 Diagram 1C Diagram 1C Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A Diagram 1A 112.5 Diagram 1D Diagram 1D Diagram 1C Diagram 1B Diagram 1B Diagram 1B Diagram 1A Diagram 1A 150 Diagram 1D Diagram 1D Diagram 1C Diagram 1C Diagram 1C Diagram 1B Diagram 1A Diagram 1A 225 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1C Diagram 1C Diagram 1A Diagram 1A 300 Diagram 2 Diagram 2 Diagram 1D Diagram 1D Diagram 1D Diagram 1D Diagram 1A Diagram 1A 500 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 1D Diagram 1A Diagram 1A 600 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 1B Diagram 1A 750 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 2 Diagram 1C Diagram 1A

1A - 0.281” Dia.1B - 0.343” Dia.1C - 0.437” Dia.1D - 0.560” Dia.

DIAGRAM 1

0.56” x 1.0 Slot (Qty. 4) or0.56” Diameter (Qty. 4)

DIAGRAM 2

TERMINATION DETAILS - NEMA 3R, COPPER WOUNDIncluding: Drive Isolation (Section 4), General Purpose Distribution (Section 8), K-Factor (Section 9), Energy Effi cient (Section 10), Low Temperature Rise (Section 11) and Encapsulated (Section 12).

Page 41: GENERAL PURPOSE DISTRIBUTION TRANSFORMERSGeneral purpose distribution transformers are rated for 600 volts and below. They are generally used for supplying appliance, lighting, motorized

Data subject to change without notice.273

GE

NE

RA

L

INF

OR

MA

TIO

NGENERAL INFORMATION

© Hammond Power Solutions Inc.

ACCESSORIES - GENERAL PURPOSE TRANSFORMERSSPRINKLER HOODS (NEMA TYPE 2 ENCLOSURE)

Sprinkler hoods can easily be

fi eld installed to protect a trans-

former from water falling at an angle

up to 75° from verticle. A NEMA

Type 1 enclosure with a properly

installed sprinkler hood will meet

NEMA Type 2 requirements.

Use the selection table to the

right to select the appropriate sprin-

kler hood kit. Each kit comes with

either 2 or 4 hoods, depending on

the case style, to fi t on transformer

enclosure.

For overall dimensions of the

enclosures with a sprinkler hood

installed, please refer to the enclo-

sure dimensional drawings on

pages 254 thru 257.

Factory installed NEMA Type

2 enclosures are also available.

Please contact the nearest Ham-

mond Sales Offi ce for details.

Note: UH style enclosures do not

require sprinkler hood kits.

If wall mounting is desired for

a transformer fi tted with sprinkler

hoods, optional wall mounting

brackets can be ordered separately.

Use the selection table to the

right to select the appropriate kit.

One kit is required for each trans-

former.

WALL MOUNTING KITS (Used with Sprinkler Hoods)

SPRINKLER HOOD KIT AND WALL MOUNTING BRACKET KIT PART NO.’S

All standard transformers are

supplied with installed internal

vibration absorbing pads to

minimize noise during operation.

Optional external “anti-vibra-

tion pads” and “vibration isolators”

(for higher noise dampening) are

available, and can be used to reduce

operating noise even further.

Both kits are resistant to

industrial contaminants like oils,

acids and alkalies.

ANTI-VIBRATION PADS AND ISOLATORS

ANTI-VIBRATION PADS

Part No. Case Style Description

P1 A1 - A2 Rubber and steel washer H1 - H8 assemblies which replace the UH1 - UH8 standard steel washers P2 J1 - J6 UJ1-UJ6

VIBRATION ISOLATORS Part Transformer Description No. Weight (lb)

NMP1 up to 380 Moulded neoprene and steel NMP2 381 - 760 plate assemblies to virtually NMP3 761 - 1040 eliminate vibration noise from the NMP4 1041 - 1880 transformer to the mounting NMP5 1881 - 2880 surface. NMP6 2881 - 4880

Sprinkler Wall Hood Kit Mounting Case Part No. Part No. Style

DHA1 WB2 A1 DHA2 WB2 A2 DHH1 WB2 H1 DHH2 WB2 H2 DHH3 N/A H3 DHH4 N/A H4 DHH5 WB2 H5 DHH6 WB2 H6 DHH7 N/A H7 DHH8 N/A H8 DHJ1 N/A J1 DHJ2 N/A J2 DHJ3 N/A J3 DHJ4 N/A J4 DHJ5 N/A J5 DHJ6 N/A J6 N/A W1 UH1 N/A W2 UH2&3 N/A W1 UH5 N/A W2 UH6