GE Molded Case Circuit Breakers F225 Line Circuit Breakers 70-250 Amperes-TFJ Noninterchangeable Trip 70-225A TFK, THFK Interchangeable Trip 480 or 600 volts ac 250 Volts dc Frame Type TFK Note: All TFJ, TFK and THFK breakers are UL listed as HACR. Type TFJ—Noninterchangeable Trip Includes line and load lugs. Suitable for reverse feed. Rating Adjustable Trip Range Amp Lo Hi Complete Breaker 480 VacMax. Catalog Number List Price, GO-135B Two-Pole 70 80 90 100 110 125 150 175 200 225 250 225NA 600 700 600 600 660 600 700 800 900 1000 1000 - 900 1000 900 1250 1250 1250 1500 1750 2000 2250 2250 - TFJ224070WL TFJ224080WL TFJ224090WL TFJ224100WL TFJ224110WL TFJ224125WL TFJ224150WL TFJ224175WL TFJ224200WL TFJ224225WL TFJ226Y225©®© $1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 803.00 Complete Breaker 600 VacMax. Catalog Number List Price, GO-135B Three-Pole TFJ236070WL TFJ236080WL TFJ236090WL TFJ236100WL TFJ236110WL TFJ236125WL TFJ236150WL TFJ236175WL TFJ236200WL TFJ236225WL TFJ236250WL TFJ236Y225©® $1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 2075.00 1174.00 Copper/ Aluminum Lugs TCAL24 ® TCAL24 Wire Size #4-300 kcmil ® - Types TFK, THFK—Interchangeable Trip Ampere Rating Adjustable Trip Range Amp Lo Hi Complete Circuit Breaker Includes Line and Load Lugs Standard Catalog Number List Price, GO-135B Hi-Break" Catalog Number List Price, GO-135B Trip Unit Only Use with Standard and Hi-Break Frames List Price, GO-135B Frame Only Catalog Number List Price, GO-135B Terminal Lugs for Front Connection (Copper/Aluminum) ® Catalog Number (Order 1 line and 1 load per pole) List Price, GO-135B Wire Size Two-Pole, 480 Volts ac Max., 250 Volts dc Max. 70 80 90 100 110 125 150 175 200 225 225NA 600 700 600 600 660 600 700 800 900 1000 - 900 1000 900 1250 1250 1250 1500 1750 2000 2250 - TFK224070WL TFK224080WL TFK224090WL TFK224100WL TFK224110WL TFK224125VVL TFK224150WL TFK224175WL TFK224200WL TFK224225WL TFK226Y225®©® $1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 1122.00 937.00 THFK224070WL THFK224080WL THFK224090WL THFK224100WL THFK224110WL THFK224125WL THFK224150WL THFK224175WL THFK224200WL THFK224225WL $2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 2315.00 - TFK226T070 TFK226T080 TFK226T090 TFK226T100 TFK226T110 TFK226T125 TFK226T150 TFK226T1 75 TFK226T200 TFK226T225 TFKY2© $337.00 337.00 337.00 337.00 337.00 337.00 337.00 337.00 337.00 337.00 148.00 TFK224FOOO Standard F r ame THFK224FOOO Hi-Break Frame $753.00 1946.00 TCAL24 $8.00 #4-300 kcmil Three-Pole, 600 Volts ac Max., 250 Volts dc Max. 70 80 90 100 110 125 150 175 200 225 225A Mag Only 225NA 600 700 600 600 660 600 700 800 900 1000 600 1000 - 900 1000 900 1250 1250 1250 1500 1750 2000 2250 1400 2250 - TFK236070WL TFK236080WL TFK236090WL TFK236100WL TFK236110WL TFK236125WL TFK236150WL TFK236175WL TFK236200WL TFK236225WL TFK236Y225©© 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 1407.00 . 1174.00 THFK236070WL THFK236080WL THFK236090WL THFK236100WL THFK236110WI THFK236125WL THFK236150WL THFK236175WL THFK236200WL THFK236225WL - 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 2787.00 - TFK236T070 TFK236T080 TFK236T090 TFK236T100 TFK236T110 TFK236T125 TFK236T150 TFK236T1 75 TFK236T200 TFK236T225 TFK236TM1225® TFK236TM2225® TFKY3© 445.00 445.00 445.00 445.00 445.00 445.00 445.00 445.00 445.00 445.00 555.00 555.00 208.00 TFK236FOOO Standard Frame THFK236FOOO . Hi-Break Frame 914.00 2294.00 TCAL24 8.00 #4-300 kcmil © Molded-case switch. Complete switch includes line and load lugs. UL listed only when ordered as a complete switch. Internal accessory installation requires dummy trip unit. See page 4-51 for additional details. (D Not UL listed. @ For optional lugs, see page 4-62. © 600 volts maximum. © TC024 load end. Wire range #4-300 kcmil copper only. Accessories: See pages 4-48 to 4-65. 4-22 1999 Issue Prices and data subject to change without notice

Upload: others

Post on 17-Aug-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GE Molded Case Circuit Breakers F225 Line Circuit Breakers · complete breaker or switch. All devices listed come with Cu/AI line and load lugs. If line lugs are not required on a

GE Molded Case Circuit Breakers

F225 Line Circuit Breakers70-250 Amperes-TFJ Noninterchangeable Trip70-225A TFK, THFK Interchangeable Trip480 or 600 volts ac250 Volts dc

Frame

Type TFK

Note: All TFJ, TFK and THFKbreakers are UL listed asHACR.

Type TFJ—Noninterchangeable TripIncludes line and load lugs. Suitable for reverse feed.

Rating

Adjustable Trip RangeAmp

Lo Hi

Complete Breaker480 Vac Max.

Catalog NumberList

Price,GO-135B

Two-Pole708090

100110125150175200225

250

225NA

600700600600660600700800900

1000

1000

-

9001000900

1250125012501500175020002250

2250

-

TFJ224070WLTFJ224080WLTFJ224090WLTFJ224100WLTFJ224110WLTFJ224125WLTFJ224150WLTFJ224175WLTFJ224200WLTFJ224225WL

TFJ226Y225©®©

$1122.001122.001122.001122.001122.001122.001122.001122.001122.001122.00

803.00

Complete Breaker600 Vac Max.

Catalog NumberList

Price,GO-135B

Three-PoleTFJ236070WLTFJ236080WLTFJ236090WLTFJ236100WLTFJ236110WLTFJ236125WLTFJ236150WLTFJ236175WLTFJ236200WLTFJ236225WL

• TFJ236250WL

TFJ236Y225©®

$1407.001407.001407.001407.001407.001407.001407.001407.001407.001407.00

2075.00

1174.00

Copper/Aluminum

Lugs

TCAL24

®

TCAL24

WireSize

#4-300kcmil

®

-

Types TFK, THFK—Interchangeable Trip

AmpereRating

AdjustableTrip Range

Amp

Lo Hi

Complete Circuit BreakerIncludes Line and Load Lugs

Standard

Catalog NumberList

Price,GO-135B

Hi-Break"

Catalog NumberList

Price,GO-135B

Trip Unit Only

Use withStandard

andHi-BreakFrames

ListPrice,

GO-135B

Frame Only

Catalog NumberList

Price,GO-135B

Terminal Lugs forFront Connection

(Copper/Aluminum) ®

Catalog Number(Order 1 lineand 1 loadper pole)

ListPrice,

GO-135B

WireSize

Two-Pole, 480 Volts ac Max., 250 Volts dc Max.708090

100110125150175200225

225NA

600700600600660600700800900

1000

-

9001000900

1250125012501500175020002250

-

TFK224070WLTFK224080WLTFK224090WLTFK224100WLTFK224110WLTFK224125VVLTFK224150WLTFK224175WLTFK224200WLTFK224225WL

TFK226Y225®©®

$1122.001122.001122.001122.001122.001122.001122.001122.001122.001122.00

937.00

THFK224070WLTHFK224080WLTHFK224090WLTHFK224100WLTHFK224110WLTHFK224125WLTHFK224150WLTHFK2241 75WLTHFK224200WLTHFK224225WL

$2315.002315.002315.002315.002315.002315.002315.002315.002315.002315.00

-

TFK226T070TFK226T080TFK226T090TFK226T100TFK226T110TFK226T125TFK226T150TFK226T1 75TFK226T200TFK226T225

TFKY2©

$337.00337.00337.00337.00337.00337.00337.00337.00337.00337.00

148.00

TFK224FOOOStandardFrame

THFK224FOOOHi-BreakFrame

$753.00

1946.00

TCAL24 $8.00 #4-300kcmil

Three-Pole, 600 Volts ac Max., 250 Volts dc Max.708090

100110125150175200225

225AMagOnly

225NA

600700600600660600700800900

1000

6001000

-

9001000900

1250125012501500175020002250

14002250

-

TFK236070WLTFK236080WLTFK236090WLTFK236100WLTFK236110WLTFK236125WLTFK236150WLTFK236175WLTFK236200WLTFK236225WL

TFK236Y225©©

1407.001407.001407.001407.001407.001407.001407.001407.001407.001407.00

— .—

1174.00

THFK236070WLTHFK236080WLTHFK236090WLTHFK236100WLTHFK236110WITHFK236125WLTHFK236150WLTHFK236175WLTHFK236200WLTHFK236225WL

-

2787.002787.002787.002787.002787.002787.002787.002787.002787.002787.00

-

TFK236T070TFK236T080TFK236T090TFK236T100TFK236T110TFK236T125TFK236T150TFK236T1 75TFK236T200TFK236T225

TFK236TM1225®TFK236TM2225®

TFKY3©

445.00445.00445.00445.00445.00445.00445.00445.00445.00445.00

555.00555.00

208.00

TFK236FOOOStandardFrame

THFK236FOOO .Hi-BreakFrame

914.00

2294.00 TCAL24 8.00 #4-300kcmil

© Molded-case switch. Completeswitch includes line and loadlugs. UL listed only whenordered as a complete switch.

Internal accessory installationrequires dummy trip unit. Seepage 4-51 for additionaldetails.

(D Not UL listed.@ For optional lugs, see page

4-62.© 600 volts maximum.

© TC024 load end. Wire range#4-300 kcmil copper only.

Accessories:See pages 4-48 to 4-65.

4-22 1999 Issue Prices and data subject to change without notice

Page 2: GE Molded Case Circuit Breakers F225 Line Circuit Breakers · complete breaker or switch. All devices listed come with Cu/AI line and load lugs. If line lugs are not required on a

GE Molded Case Circuit Breakers

FeaturesSpectra RMS™ Molded Case Circuit Breakers

SE150, SF250, SG600, and SK1200 circuit breaker frames have adigital, solid-state, rms sensing trip system with field installable,front-mounted rating plugs to establish or change the breakerampere rating. Adjustable instantaneous with tracking short-timeis standard on all frames including SE150. The trip system usesdigital sampling to determine the rms value of sinusoidal andnonsinusoidal currents.

MicroVersaTrip Plus™ Trip Units or MicroVersaTrip PM™Trip UnitsSG600 and SK1200 are optionally available with eitherMicroVersaTrip Plus™ or MicroVersaTrip PMrM trip units which offerexpanded functionality in the same space-saving size of standardSpectra RMS™ breakers. The trip system uses digital sampling todetermine the rms value of sinusoidal and nonsinusoidal currents.

Section 4Molded Case Circuit Breakers

• Spectra RMS™ breakers are ambient insensitive. Trip times willnot vary over the range 10-50°C breaker ambient Refer toGET-7002 for further application information.

• Spectra RMS™ breakers contain no parts that would supportfungus growth and are, therefore, inherently fungusproof.

Other MCCB Features• NEMAAB1-1975• Broad product line to meet virtually any application need.• Reduced downtime. A tripped breaker is easily spotted and can

be immediately reset after the fault has been corrected.• Eliminates single phasing. A common trip bar disconnects all

poles simultaneously on both overloads and short circuits.• Offers application flexibility through the use of a wide variety of

accessory devices and special attachments.• Repetitive operation—no fuses to replace.• Breakers can be repetitively tested. Fuses must be destroyed to

confirm calibration accuracy.

For more information on these products, order publications listedin Sections 21 and 22.

Instruction Books

MicroVersaTrip Plus™ Trip UnitsMicroVersaTrip Plus trip units utilize a digital, LCD display with afour-button keypad to provide local set-up and readout of tripsettings. A 3-phase ammeter and trip indicators are standard, asis a clear plastic cover with provisons for sealing to allow tamper-resistant installation. The trip unit digitally measures the currentwaveform in each phase to determine the true rms value of the Spectra RMS™ Molded-Case Circuit Breakerscurrent, regardless of the waveshape. SE150 & SF250 GEH-5591v/licroVersaTrip Plus trip units provide accurate, predictable SG600 GEH-5663

overload and short-circuit protection for distribution systems that SG600 with MicroVersaTrip Plus andinclude ac and dc variable speed drives, rectifiers, induction MicroVersaTrip PM Trip Units GEH-5959heating, and other loads that cause high harmonic distortion as SK1200 GEH-5592well as standard circuit. They provide maximum breaker-to- SK1200 with MicroVersaTrip Plus andbreaker selectivity and custom load protection. Short-time and MicroVersaTrip PM Trip Units GEH-5960ground fault functions include the flexibility of coordination with or MicroVersaTrip Plus andwithout an I2t ramp. MicroVersaTrip PM Trip UnitsMicroVersaTrip PM Trip Unit Jn SPectr? RM

pf M°lded-Case Circuit Breakers . . . . GEH-5934

8 f MicroVersaTrip Plus andThe MicroVersaTrip PM trip unit adds power management system MicroVersaTrip PM Rating Plugs GEH-5887capability, advanced metering, and protective relays to the basic Standard Rating Plugs GEH-5549functions of the MicroVersaTrip Plus trip unit. The MicroVersaTrip Shunt Trip/UV Release. . GEH-5551PM trip unit communicates directly on the GE POWER LEADER™ Auxiliary Switch/Bell Alarm GEH-5593communication bus. R-Frame Molded-Case Circuit Breakers GEH-5885A complete circuit breaker consists of a UL listed circuit breaker TVPBP Portable Battery Pack DEJ-001frame and a rating plug (UL listed interchangeable trip unit). Voltage Module GEH-6250Terminal lugs for cable connection are available if required. Power Supply Plate GEH-6251• All frames use the same UL listed, field-installable internal Voltage Conditioner Plate 2^'f25?

accessories (auxiliary switch, shunt trip, undervoltage release [~ower =>upply Assembly GEH-6253and bell alarm) Voltage Conditioner Assembly GEH-6254

• All frame sizes have maximum UL listed interrupting ratings of Distribution Cable Harness GEH-6255200 kA @ 240 volts ac and 100 kA @ 480 volts ac with 600 volts Distribution Cable Extension GEH-6256ac ratings to 65 kA depending on frame size. UL listed current Distribution Cable Terminal Block GEH-6257limiting versions are provided through the SG600 frame for the Distribution Cable Junction Box GEH-625865 kA @ 480 volts ac and the 100 kA @ 480 volts ac models,with no increase in physical frame size.

• Spectra RMS™ Mag-Break'5 instantaneous-only motor circuitprotectors also use the same digital, solid-state trip unit andrating plugs as the circuit breakers. The interchangeable ratingplug establishes the instantaneous pickup range (with trackingshort-time) but does not change the frame ampere rating.

• Spectra RMS™ molded-case switches have a fixed, high-setinstantaneous trip (without tracking short-time function) andhave short-circuit withstand ratings equal to their equivalentbreaker frame size interrupting rating in most cases.

Data subject to change without notice 1999 Issue 4-1

Page 3: GE Molded Case Circuit Breakers F225 Line Circuit Breakers · complete breaker or switch. All devices listed come with Cu/AI line and load lugs. If line lugs are not required on a

GE Molded Case Circuit Breakers

Molded Case Circuit BreakersSpectra RMS™, Spectra RMS™ with MicroVersaTrip Plus™ Trip Units, Spectra RMS™ with .MicroVersaTrip PM™ Trip Units, Thermal Magnetic and J/K with MicroVersaTrip® RMS-9 andPower+™ 4 Trip Units

How to OrderQLine• Thermal Magnetic Circuit Breakers• Molded-Case Switches

The catalog number as shown in the following pages includes thecomplete breaker or switch. TQD and TJD breakers are completewith Cu/AI line and load lugs.

Spectra RMS™• Circuit Breakers

Determine the required breaker frame, 1C rating, and loadrequirements. Select frame, trip unit (rating plug), and lug, ifrequired, catalog numbers from the tables on pages 4-18 and4-19. Select field-mounted internal accessory catalog numbers,if required, on page 4-47. Select field-mounted externalaccessory catalog numbers, if required, on pages 4-48 through4-65. Order as separate items. For Spectra breakers withMicroVersaTrip Plus Trip Units or MicroVersaTrip PM Trip Unitsrefer to page 4-26 through 4-35.

• Mag-Break Motor Circuit ProtectorsDetermine the required frame and ampere requirements.Select frame, trip unit (rating plug), and lug, if required, catalognumbers from the table on page 4-42. Select accessories asnoted above for circuit breakers. The same accessories areused with both circuit breakers and motor circuit protectors.Order as separate items.

• Molded-Case SwitchesDetermine the required frame and ampere requirements.Select frame and lug, if required, catalog numbers from the tableon page 4-20. Rating plugs are not used. Select accessories asnoted above for circuit breakers. Internal accessories do notrequire dummy trips. The same accessories are used with bothcircuit breakers and molded-case switches. Order as separateitems.

Unless otherwise noted, all circuit breakers are UL listed in File E-11592.Molded-case switches are UL listed in File E-57546. Field-InstallableInternal Accessories are UL listed in File E-57253. Distribution CableAccessories for MicroVersaTrip Plus Trip Units and MicroVersaTrip PM TripUnits are UL listed in File E-57253.

E150 Line• Thermal Magnetic Circuit Breakers• Magnetic Circuit Breakers• Molded-Case Switches

. The catalog numbers as shown in the following pages include thecomplete breaker or switch. All devices listed come with Cu/AI lineand load lugs. If line lugs are not required on a breaker, eliminate"WL" from catalog number; for molded-case switches see page4-3. Unless otherwise noted, all circuit breakers are UL listed inFile E-11592. Molded-case switches are UL listed in File E-57546.

F 225 Line• Thermal Magnetic Circuit Breakers• Magnetic Circuit Breakers• Molded-Case Switches

These breakers are available with either noninterchangeable trips(designated Type TFJ) or interchangeable trips (designated TypesTFK/THFK). When ordering Type TFJ, catalog number includes

complete breaker, trip unit, Cu/AI line and load lugs factoryassembled. If line lugs are not required on a breaker, eliminate"WL" from catalog number, and subtract price of line lugs fromprice of complete breaker. If interchangeable trip (Types TFK/THFK) is required order one of two ways. "Complete circuitbreaker" price includes frame, trip, Cu/AI line and load lugs. Unitswill be shipped unassembled unless specified on order "must befactory assembled." If line lugs are not required on a breaker,eliminate "WL" from catalog number, and subtract price of linelugs from price of complete breaker. To order the frame, trip, andlugs separately, select the required components from table.Magnetic breakers must be ordered as components. A completebreaker consists of frame, trip unit, one line lug per pole and oneload lug per pole. Price of "Complete Circuit Breaker" vs. orderingframe, trip, and line and load lugs separately is the same.

Molded-case switches can also be ordered as complete units(designated TFK—Y) or as separate components. They are ULlisted only as complete units. To indicate required lugs, seepage 4-3.

Unless otherwise noted, all circuit breakers are UL listed in FileE-11592. Molded-case switches are UL listed in File E-57546.

J 600 Line• Thermal Magnetic Circuit Breakers• Magnetic Circuit Breakers• Molded-Case SwitchesThese breakers are available with either noninterchangeable trip(designated Type TJJ) or interchangeable trip (designated TypeTJK and THJK). Type TJJ catalog numbers include frame, trip,Cu/AI line, and load lugs factory assembled. If line lugs are notrequired on the breaker, eliminate "WL" from catalog number, andsubtract price of line lugs from price of complete breaker.

TJK breakers are available in two frames, 400 ampere frame(125 to 400 amperes) and 600 ampere frame (250 to 600amperes). Trip units are not interchangeable between frames.

"Complete Circuit Breaker" price includes frame, trip unit, Cu/AIline, and load lugs. Unit will be shipped unassembled unless orderspecifies "must be factory assembled." If line lugs are notrequired, eliminate "WL" from catalog number and subtract priceof line lugs from price of complete breaker.

To order the frame, trip, and lugs separately, select the requiredcomponents from table. Magnetic breakers must be ordered ascomponents. A complete breaker consists of frame, trip, and oneline and one load lug per pole.

Price of ordering "Complete Circuit Breaker" vs. frame, trip, andline and load lugs separately is the same.

Molded-case switches can also be ordered as complete units(designated Type TJK—Y) or as separate components. They areUL listed only as complete units. To indicate required lugs, seepage 4-3.

Unless otherwise noted, all circuit breakers are UL listed in FileE-11592. Molded-case switches are UL listed in File E-57546.

(continued on next page)

4-2 1999 Issue Data subject to change without notice

Page 4: GE Molded Case Circuit Breakers F225 Line Circuit Breakers · complete breaker or switch. All devices listed come with Cu/AI line and load lugs. If line lugs are not required on a

GE Molded Case Circuit Breakers

Molded Case Circuit BreakersQuick Reference Guide

Ratings do not apply to molded-case switches.

TJJ, TJK, THJK TFJ, TFK, THFK

E150 (UL File E-11592; Fixed Thermal Magnetic Trip Unit; CSA LR 57114)

CircuitBreaker

Type

TEY®

TEB©

TED®

THED®

TEL©

AmpereRating

15-100

10-100CD

10-100©

15-100

10-150

15-30

15-100

15-100

110-150

15-150

No.Poles

1

2

3

1

2

3

1

2

3

1

2

3

3

MaximumVoltage Rating

ac

277

480Y/277

120

240

277,347®

480

600

277,347®

480

480,600

600

dc

125

250

125

250

-

125

250

500

125

250

-

UL Listed Interrupting Ratings—rms Symmetrical Amps (In Thousands)

ac Voltage

120

65

10

-

-

120/240

-

-

-

100

240

14

65

10

18

65

65

42

100

277

14

14

-

14

65

-

-

480

-

-

10

18

25

65

600

-

-

14

18

25

dc Voltage

125

10 •

10

5

10

20®

-

-

250

-

10

5

-

10

10

20©

10

-

500©

-

-

10

-

Dimensions(In.)

H

51/4

65/l6

65/16

65/l6

6716

w12

3

1%

2%

4'/8

1%

23/4

41/e

1%

4'/8

4'/8

D

31/ia

3%

33/8

3%

32%2

A

-

241/64

241/64

2'11/B4

27/16

B

-

2'%4

215/M

21%4

215/32

c

-

11/16

1I/16

''/IS

"/16

E

-

23/32

2%2

23/32

2%2

Approx.ShipWt./Std. Pack

26 lb/24

24 lb/1 2

28 lb/8

26 lb/24

24lb/12

28 lb/8

26 lb/24

24lb/12

28 lb/8

3'/2 lb/1

225 (UL File E-11592; TFJ, Fixed Thermal Magnetic Trip Unit; TFK, THFK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)

CircuitBreaker

Type

TFJ®

TFK©

THFK®

TFL©

AmpereRating

70-225

70-250

70-225

70-225

70-225

No.Poles

2

3

2

3

2

3

3

MaximumVoltage Rating

ac

480

600

480

600

480

600

600

dc

250

500

250

250

-

UL Listed Interrupting Ratings—rms Symmetrical Amps (In Thousands)

ac Voltage

120

-

-

120/240

-

100

240

25

25

65

100

277

-

480

22

22

25

65

600

18

18

18

25

dc Voltage

125

-

250

10

10®

10

-

20©

-

500®

10

-

Dimensions(In.)

H

l'o'/8

10 '/8

10'/8

10'/8

W

4>/8

4'/8

4'/S

4'/8

D

3'Vie

3i3/ie

313/I6

313/16

A

3%

37/B

3%

3%

B

37/8

3%

37/8

3%

C

1*6

"/1 6

"/16

"/16

E

13/16

13/16

13/16

13/16

ApproxShip Wt./Std. Pack

10 lb/1

12 lb/1

10 lb/1

12 lb/1

10 lb/1

12 lb/1

-

J600 (UL File E-11592; TJJ, Fixed Thermal Magnetic Trip Unit; TJK, THJK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)

TJJTJK4

TJK6

2

3

2

3

2

3

2

3

250

500

250

500

250

- -

250

~

10

20

10

20®

40

-

40

-

20®

20

-

--

-

16 lb/1

1 7V2 lb/1

18 lb/1

20 lb/1

16 lb/1

1 7'/2 lb/1

18 lb/1

20 lb/1

K1200 (UL File E-11592; Interchangeable Thermal Magnetic Trip Unit; CSA LR 40350)

THKM8

THKM12

300-800

600-1200

2

3

2

3

2

3

2

3600

250

500

250

10

20©

40©

22

_

33 lb/1

39 lb/1

38 Ib/f

41 '/? lb/1

33 lb/1

39 lb/1

38 lb/1

411/2lb/1

© UL listed with poles in seriesfor 500 Vdc ungroundedbattery applications.

© All UL listed as HACR type.® 10 amp not UL listed.

UL listed/CSA Certified for10kA (5) 347 Vac (TED) and18kA@ 347V (THED). Alsorated 10kA@ 480V but notUL listed.

© UL listed at 10,000 amps.© Discontinued© Also 10,000 amps at 500 Volts

dc. Not UL listed.

500 Vdc on TJJ only.

(continued on page 4-8)

Data subject to change without notice 1999 Issue 4-7