GENERAL NOTES
FLOOR PLANS WERE PROVIDED BY THE OWNER AND MAY NOT REFLECT REVISIONS MADE DURINGCONSTRUCTION OR RENOVATION MADE AFTERWARDS. INFORMATION SHOWN PERTAINING TO EXISTINGCONDITIONS IS BASED UPON VISUAL INSPECTION AND EXISTING CONSTRUCTION DOCUMENTS USED BYTHE ARCHITECT. ANY DISCREPANCIES DISCOVERED BY OTHERS SHALL BE BROUGHT TO THE ATTENTIONOF THE ARCHITECT PRIOR TO BEGINNING WORK.
2.
ALL INTERIOR DIMENSIONS ON PLAN SHEETS ARE....A: FACE OF STUD TO FACE OF STUD, (EXCLUSIVE OF FINISH MAT'L) UNLESS
OTHERWISE NOTED.B: FACE OF STUD TO FACE OF EXISTING WALL, UNLESS OTHERWISE NOTED.C: ALL INTERIOR STUDS TO BE SPACED @ 1' - 4" o.c. UNLESS OTHERWISE
NOTED.
3.
GC TO COORDINATE ADDITIONAL NOTES AND DIMENSIONS BETWEEN 1/8" SCALE AND ENLARGED PLANS.
4.
SEE LIFE SAFETY PLANS FOR FIRE RATED PARTITIONS.
5.
UNLESS OTHERWISE NOTED, OWNER TO PROVIDE INTERIOR ROOM SIGNAGE. CONTRACTOR TOCOORDINATE INSTALLATION w/SIGN VENDOR.
6.
SEE PLUMBING PLANS FOR FLOOR DRAIN LOCATIONS. PROVIDE POSITIVE DRAINAGE TO FLOORDRAIN. COORDINATE WITH ALL TRADES.
7.
IN THE EVENT OF ANY DISCREPANCIES AND / OR ERRORS FOUND IN THE DRAWINGS, OR IF PROBLEMSARE ENCOUNTERED DURING DEMOLITION. THE CONTRACTOR SHALL BE REQ'D TO NOTIFY THEDESIGNER BEFORE PROCEEDING WITH THE WORK. IF THE DESIGNER IS NOT NOTIFIED, THECONTRACTOR SHALL TAKE RESPONSIBILITY FOR THE COST OF ANY REVISION.
8.
IN THE EVENT THAT THERE ARE QUESTIONS CONCERNING THE HANDLING OF ANY CONTAMINATEDMATERIALS, THE CONTRACTOR SHALL COORDINATE SUCH ISSUES WITH THE OWNERS REPRESENTATIVE.ALL MATERIALS SHALL BE HANDLED FOR DISPOSAL PROPERLY IN ACCORDANCE WITH ALL APPLICABLELAWS AND REGULATIONS AT APPROVED FACILITIES WHICH ARE LICENSED AND / OR APPROVED FOR THEDISPOSAL OF OR HANDLING OF SUCH MATERIALS.
9.
THIS WORK CONSISTS OF CLEARING, REMOVING AND DISPOSING OF ALL BLDG. DEMOLITIONDEBRIS AND UTILITIES NOT REMOVED BY OTHERS THAT ARE WITHIN DESIGNATED PROJECTAREAS EXCEPT FOR SUCH OBJECTS THAT THE DESIGNER DESIGNATES TO REMAIN. THE WORKSHALL ALSO INCLUDE PRESERVING AND PROTECTING FROM INJURY OR DEFACEMENT OF ALLVEGETATION, STRUCTURE & OBJECTS DESIGNATED TO REMAIN.
10.
CONTRACTOR TO COORDINATE ALL UTILITY DEMOLITION AND REMOVAL WITH PROPER AGENCIES.
11.
CONTRACTOR TO COORDINATE WITH THE RESPECTIVE UTILITIES TO HAVE ALL UTILITY SERVICESREMOVED OR DISCONNECTED PRIOR TO THE COMMENCEMENT OF ANY DISCONNECTED, CAPPED OFF,PLUGGED OR OTHERWISE SECURED UTILITIES. CARE SHALL BE EXERCISED SO AS NOT TO DAMAGE ANYMAIN UTILITY LINES DUE TO DEMOLITION ACTIVITIES AND ANY SUCH DAMAGES WILL BE REPAIRED TO THEREQUIREMENTS OF THE RESPECTIVE UTILITY AR THE CONTRACTORS EXPENSE. ASSURE PROPERFUNCTION OF REMAINING UTILITIES UPON COMPLETION & REWORK.
12.
CONTRACTOR SHALL MAKE ALL NOTIFICATIONS AND OBTAIN ALL PERMITS ASSOCIATED WITH THEDEMOLITION / REMOVAL OF BUILDINGS AND ANY RELATED APPURTENANCES.
13.
PRIOR TO DEMOLITION OF ANY EXISTING CONSTRUCTION / ELEMENTS / EQUIPMENT ON ANY TRACT ORLOT, CONTRACTOR SHALL INSURE THAT ANY AND ALL HAZARDOUS MATERIALS INCLUDING BUT NOTLIMITED TO FRIABLE ASBESTOS CONTAINING MATERIAL SHALL BE HANDLED IN ACCORDANCE WITH ALLLOCAL, STATE, AND FEDERAL REQUIREMENTS. THIS INCLUDES ANY NOTIFICATIONS AND PERMITSREQ'D.
14.
ALL WORK SHALL BE IN ACCORDANCE WITH APPLICABLE NATIONAL EMISSION STANDARDS FORHAZARDOUS AIR POLLUTANTS (NESHAP) PROMULGATED BY THE UNITED STATES ENVIRONMENTALPROTECTION AGENCY (USEPA), AND THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA).
15.
CONTRACTOR IS RESPONSIBLE FOR EROSION CONTROL MEASURES NECESSARY TO INCLUDE SILTFENCES AND INLET PROTECTION WHERE WATER DRAINS OFF DISTURBED AREAS, SEDIMENT ANDEROSION CONTROL MEASURES SHALL BE IN PLACE PRIOR TO DEMOLITION OR CONSTRUCTIONACTIVITIES.
16.
CONTRACTOR SHALL NOT DISTURB EXISTING CONDITIONS OUTSIDE LIMITS OF WORK UNLESSOTHERWISE NOTED; ANY DAMAGES INCURRED WILL BE REPAIRED AT CONTRACTOR'S EXPENSE.
17.
THE ABBREVIATION G.C. WHERE SHOWN ON THE DRAWINGS, SHALL MEAN GENERAL CONTRACTOR.
18.
THE G.C. SHALL SEAL ALL OPENINGS AROUND PIPES, DUCTWORK, ETC. THAT PENETRATE PARTITIONSABOVE THE FINISHED CEILING. ALL WORK AND SEALANT MATERIAL SHALL BE APPROVED BYARCHITECT.
19.
THE G.C. SHALL PROVIDE ALL REQUIRED FIRE EXTINGUISHERS.
20.
ALL EXTERIOR WALLS AND INTERIOR PARTITIONS SHALL EXTEND TO UNDERSIDE OF ROOF OR FLOORDECK UNLESS NOTED OTHERWISE.
21.
VERIFY SIZE AND LOCATION OF ALL LOUVERS, OPENINGS, AND CONCRETE PADS REQUIREDBY THE HEATING CONTRACTOR. HEATING CONTRACTOR TO CONDUCT COORDINATIONMEETINGS w/ ALL DISCIPLINES.
22.
EQUIPMENT, CABINETRY AND FURNISHINGS SUPPLIERS SHALL FIELD VERIFY ALL DIMENSIONS FORNEW ITEMS BEFORE FABRICATION AND INSTALLATION. SHOP DRAWING SHALL CONTAIN VERIFIEDDIMENSIONS WHERE POSSIBLE.
23.
G.C. TO INSTALL WOOD OR METAL BLOCKING AS REQUIRED FOR INSTALLATION OF CASEWORK.MILLWORK, GRAB BARS, AND ANY OTHER ITEMS THAT REQUIRE SECURE ATTACHMENT TO WALLSAND/OR CEILINGS.
24.
CONTRACTORS SHALL NOTE THAT MATERIALS CONTAINING ASBESTOS MAY BE ENCOUNTERED WHENWORKING IN THE EXISTING BUILDING. CONTRACTORS SHALL COORDINATE THEIR WORK WITH THE OWNER.ALL ASBESTOS RELATED WORK SHALL BE COMPLETED BY THE ASBESTOS ABATEMENT CONTRACTOR.
1.
PERFORM WORK AS REQ'D FOR PROPER COMPLETION OF THE WORK. THE DRAWINGS MAY NOTSHOW ALL EXISTING ITEMS OR CONDITIONS. CONTRACTOR SHALL NOT REC'V EXTRA PAYMENTFOR REQUIREMENTS WHICH CAN BE INFERRED THROUGH OBSERVATION OF EXISTINGCONDITIONS AT THE SITE. IN THE EVENT CONCEALED CONDITIONS ARE ENCOUNTERED, WHICHMAY VARY SIGNIFICANTLY FROM THOSE INDICATED ON THE DRAWINGS, NOTIFY THE ARCHITECTBEFORE PROCEEDING WITH THE WORK.
DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCEOVER SCALED DIMENSIONS. ENLARGED PLANS SHALL HAVE PRECEDENCE OVER SMALL-SCALE PLANS.CONTRACTOR SHALL FIELD VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS ON THE JOB SITE.
WHERE WORK IS PERFORMED IN EXISTING AREAS, THE EXISTING FINISHED CONDITIONS ARE TO BEREPAIRED OR REPLACED. THESE FINISHED CONDITIONS ARE TO MATCH EXISTING UNLESSOTHERWISE NOTED. WHERE NEW FINISHED CONDITIONS ARE TO BE INSTALLED, EXISTING FINISHEDCONDITIONS ARE TO BE REMOVED BY THE CONTRACTOR AND APPROPRIATE PREPARATION OFSUBSTRATE SHALL BE COMPLETED FOR SPECIFIED FINISH.
ALL INTERIOR FIRE-RATED PARTITIONS SHALL EXTEND TO DECK ABOVE (w/ SMOKE-TIGHT SEAL) ORSHALL TERMINATE AT ASSEMBLIES OF GREATER OR EQUAL RATING. NON FIRE-RATED PARTITIONSSHALL NOT PENETRATE FIRE-RATED PARTITIONS. AT FIRE-RATED AREAS, THE STRUCTURE ORCEILING SYSTEM SHALL BE RATED TO PROVIDE A FIRE-RATED OCCUPIED ENVELOPE.
NEW GYP. BD. ABUTTING OTHER MATERIALS OR EXISTING FINISHES IS TO BE FINISHED w/ METALEDGES.
GYP. BD. @ STL. STUD FURR-OUTS IN AREAS w/ FINISHED CEILING SHOULD EXTEND TO 4-INCHESMINIMUM ABOVE FINISH CEILING AND BE BRACED WITH DIAGONAL MEMBERS SECURED TO STRUCTUREABOVE @ 8FT. o.c. (MIN.)
EXISTING DOORS & FRAMES THAT ARE TO BE REUSED SHALL BE CLEANED AND REFINISHED. ANYEXISTING DOOR THAT IS LABELED AS FIRE-RATED ON THE NEW LIFE SAFETY DWGS. SHALL BE FIELDVERIFIED BY THE CONTRACTOR. IF IT DOES NOT CONFORM TO THE REQUIRED RATING THEN IT IS TO BEREPLACED WITH A NEW DOOR TO MATCH WITH THE APPROPRIATE RATING
25.
26.
27.
28.
29.
30.
31.
EQUIPMENT AND FURNISHINGS SUPPLIERS SHALL FIELD VERIFY ALL DIMENSIONS FOR NEW ITEMSBEFORE FABRICATION AND INSTALLATION. SHOP DRAWINGS SHALL CONTAIN VERIFIED DIMENSIONS.
32.
ALL EXISTING WD. DECK TO BE PAINTED w/ FIRE RETARDANT INTUMESCENT PAINT.33.
ABBREVIATIONS
A.C.T. ACOUSTICAL CEILING TILEADJ. ADJUSTABLE A.F.F. ABOVE FINISH FLOORALT. ALTERNATEALUM. ALUMINUMARCH. ARCHITECTBM. BEAMBLK. BLOCKBLKG. BLOCKINGBLDG. BUILDINGCEM. CEMENTC.F.S. CLEAR FLOOR SPACEC.J. CONTROL JOINTCL CENTER LINECMU CONCRETE MASONRY UNITCLR. CLEARCLG. CEILINGC.O. CASED OPENINGCOL. COLUMNCONC. CONCRETECONSTR. CONSTRUCTIONCONT. CONTINUOUSC.P.C.I. CONTRACTOR PROVIDED, CONTRACTOR INSTALLEDDBL. DOUBLEDET. DETAILDIA. DIAMETERDIAG. DIAGONALDIM. DIMENSIONDWG. DRAWINGEA. EACHEL. ELEVATIONEQ. EQUALEQUIP. EQUIPMENTEXST. EXISTINGEXP. EXPANSIONEXT. EXTERIORF.C. FILE CABINETFEC FIRE EXTINGUISHER CABINETFIN. FINISHFLR. FLOORFRMG. FRAMINGFT. FOOTGA. GAUGEGT. GROUTGYP. GYPSUMGYP. BD. GYPSUM BOARDHAZ. HAZARDOUSHCWD HOLLOW CORE WOOD DOORHDR. HEADERHDW HARDWAREHMD HOLLOW METAL DOORHNDRL. HANDRAILHORIZ. HORIZONTALHT. HEIGHTICR INTERCHANGABLE CLASS ROOMIN. INCHINCL. INCLUDEDINT. INTERIORJAN. JANITORJT. JOINTLAM. LAMINATELAV. LAVATORYLBR. LUMBERLKR. LOCKERLMST. LIMESTONELVR. LOUVERMAT. MATERIALMAX. MAXIMUMMEZZ. MEZZAININEMIN. MINIMUMM.O. MASONRY OPENINGMOD. BIT. MODIFIED BITUMENM.R. MOISTURE RESISTANTMTL. METALMTLR METAL ROOFMWP MEMBRANE WATERPROOFINGN.I.C. NOT IN CONTRACTNOM. NOMINALN.T.S. NOT TO SCALEO.C. ON CENTERO.P.C.I. OWNER PROVIDED, CONTRACTOR INSTALLEDOPNG. OPENINGOPP. OPPOSITEPLAM. PLASTIC LAMINATEPLYWD. PLYWOODPNL. PANELPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHP.T. PRESURE TREATEDR. RADIUSREINF. REINFORCEREQD. REQUIREDREST. RESTROOMRLG. RAILINGRM. ROOMR.O. ROUGH OPENINGRTU ROOF TOP UNITR.V. ROOF VENTS.C. SOLID CORESCHED. SCHEDULESCWD SOLID CORE WOOD DOORSECT. SECTIONSHT. SHEETSIM. SIMILARSPEC. SPECIFICATIONSSTD. STANDARDSTL. STEELSTRUCT. STRUCTURALSQ. SQUARETHK. THICKT.H. THRESHOLDTYP. TYPICALU.N.O. UNLESS NOTED OTHERWISEVERT. VERTICALV.I.F. VERIFY IN FIELDW.P. WATERPROOFWT. WEIGHTW.W.F. WELDED WIRE FABRICW/ WITHWD. WOOD
ADA DISCLAIMER:ALL CONSTRUCTION ACTIVITIES SHALL BE COMPLETED IN FULL COMPLIANCEWITH THE AMERICANS WITH DISABILITIES ACT ("ADA") AND ARCHITECTURALAND TRANSPORTATION BARRIERS COMPLIANCE BOARD, FEDERAL REGISTER36 CFR PARTS 1190 AND 1191, ACCESSIBLE GUIDELINES FOR BUILDINGS ANDFACILITIES; ARCHITECTURAL BARRIERS ACT (ABA) ACCESSIBILITY GUIDELINES;PROPOSED RULE, PUBLISHED IN THE FEDERAL REGISTER ON JULY 23, 2004,AS HAS BEEN ADOPTED BY METRO.
DRAWING INDEX
SHEET NO SHEET NAME CD
03.
18.1
6
RE
VIS
ION
#1
- 04
.01.
16
RE
VIS
ION
#2
- 04
.21.
16
E0.1 ELECTRICAL - LEGEND & SPECS XE0.2 ELECTRICAL - SCHEDULES & RISER XE0.3 ELECTRICAL - PANELBOARDS X XE1.0 LOWER LEVEL - LIGHTING XE1.1 FIRST FLOOR - AREA 'A' LIGHTING XE1.2 FIRST FLOOR - AREA 'B' LIGHTING XE1.3 FIRST FLOOR - AREA 'C' LIGHTING XE2.0 LOWER LEVEL - POWER / SYSTEMS XE2.1 FIRST FLOOR - AREA 'A' POWER / SYSTEMS XE2.2 FIRST FLOOR - AREA 'B' POWER / SYSTEMS XE2.3 FIRST FLOOR - AREA 'C' POWER / SYSTEMS X XE3.0 LOWER LEVEL - HVAC POWER / FA SUSTEMS XE3.1 FIRST FLOOR - AREA 'A' HVAC POWER / FA SYSTEMS XE3.2 FIRST FLOOR - AREA 'B' HVAC POWER / FA SYSTEMS XE3.3 FIRST FLOOR - AREA 'C' HVAC POWER / FA SYSTEMS XE4.1 ELECTRICAL - DETAILS XE4.2 ELECTRICAL - DETAILS X
FP0.1 LEGEND & SCHEDULES - FIRE PROTECTION XFP1.1 LOWER LEVEL DEMOLITION XFP1.2 FIRST FLOOR AREA 'A' RENOVATION XFP1.3 FIRST FLOOR AREA 'B' RENOVATION XFP1.4 FIRST FLOOR AREA 'C' RENOVATION XFP1.5 LOWER LEVEL - RENOVATION XFP2.1 DETAILS - FIRE PROTECTION X
DRAWING INDEX
SHEET NO SHEET NAME CD
03.
18.1
6
RE
VIS
ION
#1
- 04
.01.
16
RE
VIS
ION
#2
- 04
.21.
16
G0.0 COVER SHEET XG0.5 CODE REVIEW X XG1.0 DRAWING INDEX / GENERAL INFO. X X XG1.1 LOWER LEVEL - LIFE SAFETY PLANS X XG1.2 FIRST FLOOR - AREA 'A' LIFE SAFETY PLAN XG1.3 FIRST FLOOR - AREA 'B' LIFE SAFETY PLAN XG1.4 FIRST FLOOR - AREA 'C' LIFE SAFETY PLAN XG1.6 TYP. INTERIOR WALL PARTITIONS X XG1.7 TYP. UL RATING INFO. X
A0.0 EXISTING SITE PLAN - SIDEWALKS X XA1.0 OVERALL PLANS - DEMOLITION XA1.1 OVERALL PLANS - RENOVATION XA1.2 LOWER LEVEL - DEMOLITION X XA1.3 FIRST FLOOR - AREA 'A' DEMOLITION XA1.4 FIRST FLOOR - AREA 'B' DEMOLITION X XA1.5 FIRST FLOOR - AREA 'C' DEMOLITION X XA1.6 LOWER LEVEL - RENOVATION X X XA1.7 FIRST FLOOR - AREA 'A' RENOVATION X X XA1.8 FIRST FLOOR AREA 'B' RENOVATION X X XA1.9 FIRST FLOOR AREA 'C' RENOVATION X X XA1.11 LOWER LEVEL- DIMENSIONED X XA1.12 FIRST FLOOR - AREA 'A' DIMENSIONED XA1.13 FIRST FLOOR - AREA 'B' DIMENSIONED XA1.14 FIRST FLOOR - AREA 'C' DIMENSIONED XA1.16 LOWER LEVEL - RCP X XA1.17 FIRST FLOOR - AREA 'A' RCP XA1.18 FIRST FLOOR - AREA 'B' RCP XA1.19 FIRST FLOOR - AREA 'C' RCP XA2.0 EXTERIOR ELEVATIONS X XA3.0 WALL SECTIONS X XA4.0 ENLARGED PLANS - TOILETS X XA4.2 ENLARGED PLANS - CASEWORK XA4.3 ENLARGED PLANS - CASEWORK XA4.4 STAIR DETAILS XA4.5 ROOF PLAN, DETAILS & MISC. FLASHING DETAILS XA6.0 DOOR SCHEDULES X X XA6.1 DOOR SCHEDULES X X XA6.2 WINDOW SCHEDULE & OPENING DETAILS X XA7.0 LOWER LEVEL FINISH PLAN X XA7.1 FIRST FLOOR AREA 'A' FINISH PLAN X XA7.2 FIRST FLOOR AREA 'B' FINISH PLAN X XA7.3 FIRST FLOOR AREA 'C' FINISH PLAN X X
FS1 FOOD SERVICES - EQUIPMENT PLAN X
S0.1 GENERAL NOTES XS1.1 FOUNDATION PLAN X XS1.2 ROOF PLAN XS2.1 FOUNDATION DETAILS X XS2.2 FOUNDATION DETAILS XS3.1 FRAMING DETAILS X
M0.1 LEGEND & SCHEDULES - HVAC XM0.02 SCHEDULES - HVAC XM1.1 FIRST FLOOR AREA 'A' DEMOLITION XM1.2 FIRST FLOOR AREA 'B' DEMOLITION XM1.3 FIRST FLOOR AREA 'C' DEMOLITION XM1.4 LOWER LEVEL DEMOLITION XM1.5 FIRST FLOOR AREA 'A' RENOVATION XM1.6 FIRST FLOOR AREA 'B' RENOVATION X XM1.7 FIRST FLOOR AREA 'C' RENOVATION XM1.8 LOWER LEVEL - RENOVATION XM2.1 DETAILS - HVAC XM2.2 DETAILS - HVAC XM3.1 SPECIFICATIONS - HVAC X
P0.1 LEGEND & SCHEDULES XP1.1 FIRST FLOOR AREA 'A' DEMOLITION XP1.2 FIRST FLOOR AREA 'B' DEMOILITION XP1.3 FIRST FLOOR AREA 'C' DEMOLITION XP1.4 LOWER LEVEL - DEMOLITION XP1.5 FIRST FLOOR AREA 'A' RENOVATION XP1.6 FIRST FLOOR AREA 'B' RENOVATION XP1.7 FIRST FLOOR AREA 'C' RENOVATION XP1.8 LOWER LEVEL - RENOVATION XP1.9 KITCHEN AREA RENOVATION XP2.1 SPECIFICATIONS - PLUMBING X
ARCHITECTURAL:
GENERAL:
DATE:
PROJECTNUMBER:
DRAWING NUMBER:
SHEET TITLE:
REVISIONS:
PROJECT TITLE:
DRAWN BY:
NASHVILLE * DENVER * SAN ANTONIO
SAN FRANCISCO * PALM BEACH GARDEN
615.254.8500 * GHP1.com
217th FIFTH AVENUE NORTHNASHVILLE, TN. 37219
1
2
3
4
5
E D C B A
E D C B A
1
2
3
4
5
60 MUSIC SQUARE EASTSUITE 300
NASHVILLE, TN 37203PH: 615.383.6949
1162 FOSTER AVENUENASHVILLE, TN 37210
PH: 615.921.2200
G1.0
DRAWING INDEX /GENERAL INFO.
03.18.2016
13093.09
1252 FOSTER AVE,NASHVILLE, TN 37210
STEMPREPARATORYACADEMY
HIGH SCHOOLRENOVATION
C.D.
FOOD SERVICES:
PLUMBING:
ELECTRICAL:
MECHANICAL:
STRUCTURAL:
DRAWING INDEX NOTE: THE FOLLOWING SHEETS HAVE BEEN OMITTED IN ANTICIPATION OF ALTERNATE #1- ADDITION TO BE PUBLISHED IN THE FUTURE: A1.10; A1.15; A1.20; A3.1; A4.1; A7.4 & G1.5
FIRE PROTECTION:
1 REVISION #1 - 04.01.2016
2 REVISION #2 - 04.21.2016
AREA OF WORK
AREA OF WORK
LOWER LEVEL - KEY PLAN
CRAWL SPACE
CR
AW
L S
PA
CE
CRAWL SPACE
STAIRS
101 MECH
003VESTIBULE
004
COPY / WORKAREA
005
I.C.R.
006I.C.R.
007
CORRIDOR
002
VESTIBULE
009
MECH
010
J.C.
011
TLT
012
TLT
013
CORR.
014
MTG. ROOM
015
STAIRS
159
CORR.
016
OFC.
022
OFC.
023
WORK AREA
020
TLT
019
TLT
018
007
006
004
013
012
011
015
018
019
020
022
023
021
024A
01
01
04 05
01
A1
A3.0
P2 P5
P2
P2
P2
P1 P1
P1
P2
P1
P1
P1
P2
P2
P2
P5
VESTIBULE
001
CORRIDOR
008
01
STG
005A
05
005A
P8
P7
I.C.R.
017
I.C.R.
021
I.C.R.
024
017
P1
P1
UP
UP
UP
UP
0303
003
009010
101B
001
002
159A 016A
024B 016C
014
ELECTRICAL
010A
010A
MECH
017A
LOWER LEVEL LIFE SAFETY - WEST
LOWER LEVEL LIFE SAFETY - EAST
09
APPROX. LOCATION OFEXISTING SUMP PUMPS
APPROX. LOCATION OFEXISTING FIRE ENTRANCE
A4.4C1
016B
UP
OFC
005B
005B
05
UP
NEW CODE COMPLIANT HANDRAIL
NEW CODE COMPLIANTHANDRAIL / GUARDRAIL
SEE SHEET A4.0 FOR TYPICALTOILET EQUIPMENT
E
E
SEE SHEET A4.0 FOR TYPICALTOILET EQUIPMENT
P7
11 11
11
11
11
017A
ALT. #3 (SEE SHEET G0.5 FOR ADD'L INFO.)
12
2
GENERAL RENOVATION NOTES:
1. SEE SHEET G1.6 FOR ADD'L INTERIOR PARTITION INFORMATION.
2. SEE SHEET LIFE SAFETY PLANS FOR FIRE RATED PARTITIONS.
3. ALL CMU CORES (NOT FILLED SOLID FOR REINFORCING) SHALL REC'VFOAMED-IN PLACE MASONRY INSULATION. SEE STRUCTURAL FORREINFORCING.
4. ALL WINDOWS ARE TO REC'V NEW WINDOW SHADES AS SPECIFIED. GC TOFIELD VERIFY WINDOW OPENINGS PRIOR TO ORDERING SHADES.
WALL LEGEND:
EXISTING WALL SYSTEM
NEW WALL: 3 5/8" STL. STUDS WITH 5/8" GYP. BD. ON EACH FACE.
NON-RATED SMOKE PARTITION
1 HR RATED PARTITION
SEE SHEET G1.6 TYPICAL INTERIOR WALL PARTITIONS FOR ADD'L INFORMATION
HATCH INDICATESAREA OF NEW CONCRETESEE STRUCTURAL
INDICATES LOCATION OF GAS COCK - SEE SHEET A4.1
RENOVATION KEYNOTES:
01 INFILL EXISTING CMU WALL WHERE EXISTING DOORS & FRAME HAVE BEENREMOVED. INFILL TO MATCH SURROUNDING WALL TYPE AND PAINTED /FINISHED TO MATCH. MASONRY INFILL SHALL BE TOOTHED TOGETHER
02 THIS NOTE OMITTED.
03 ALIGN NEW WALL FLUSH w/ EXISTING WALL.
04 NEW CASED OPENING TO BE FINISHED TO MATCH THE SURROUNDINGCONDITIONS
05 NEW CONCRETE FLOOR SLAB AND FOOTINGS - SEE STRUCTURAL
06 INFILL OPENING IN EXISTING EXTERIOR WALL SYSTEM. MATCHSURROUNDING CONSTRUCTION. BRICK TO BE APPROVED BYARCHITECT PRIOR TO CONSTRUCTION
07 NEW CONCRETE PATIO SLAB - SEE STRUCTURAL
08 EXTERIOR BRICK TO BE CLEANED.
09 PROVIDE NEW STL. LINTEL - SEE STRUCTURAL
10 PROVIDE ATTIC ACCESS. WHERE POSSIBLE SAVE / RELOCATE EXISTINGACCESS LADDERS. SEE SHEET A4.4 FOR NEW LADDER DETAILS
11 PROVIDE MANUAL PROJECTION SCREENS AT THE TEACHING WALL OF EACHCLASSROOM (SEE SPECIFICATIONS)
1
DATE:
PROJECTNUMBER:
DRAWING NUMBER:
SHEET TITLE:
REVISIONS:
PROJECT TITLE:
DRAWN BY:
NASHVILLE * DENVER * SAN ANTONIO
SAN FRANCISCO * PALM BEACH GARDEN
615.254.8500 * GHP1.com
217th FIFTH AVENUE NORTHNASHVILLE, TN. 37219
1
2
3
4
5
E D C B A
E D C B A
1
2
3
4
5
60 MUSIC SQUARE EASTSUITE 300
NASHVILLE, TN 37203PH: 615.383.6949
1162 FOSTER AVENUENASHVILLE, TN 37210
PH: 615.921.2200
A1.6
LOWER LEVEL -RENOVATION
03.18.2016
13093.09
1252 FOSTER AVE,NASHVILLE, TN 37210
STEMPREPARATORYACADEMY
HIGH SCHOOLRENOVATION
C.D.
1/8" = 1'-0"C1 LOWER LEVEL - RENOVATION
NORTH
1 REVISION #1 - 04.01.2016
2 REVISION #2 - 04.21.2016
RE
F.
LOBBY
100
I.C.R.
102
I.C.R.
108
SPEC. ED.
109
BOY'S TLT
107
J.C.
106
GIRL'S TLT
105
I.C.R.
103
STAIRS
101
WORK ROOM /BREAK AREA
118I.C.R.
120
BOY'S TLT
123
J.C.
124
GIRL'S TLT
125
I.C.R.
126
CORR.
122
CORR.
128
I.C.R.
127
I.C.R.
121
I.C.R.
119
MEETING
117
TLT
114
TLT
115
MECH.
112A
MECH.
113A
12312
6
120
118
127
119
107
105
106
109
121
117
114
115
102
108
125
124
103
A4.0E3
Sim
A4.0E3
Sim
A4.0C3
Sim
A4.3E4
0101
01
01
01
01 01
01
0101
01 010101
010101
01
P1
P1
P2
P5
P1
P1
P1P1
P1
P5
P1
P2
P1
P1
P1
P5
P1
P2
CO
RR
IDO
R
104
CORRIDOR
116
P1CORRIDOR
111
RECEPTION
110
ADMIN. / OFC
113
PROFESSIONALDEVELOPMENT
112
112A
112D
113B
113
IT CLST.
113B
UP
UP 101A
101B
104
112B
112C
113A
128A
A4.3B1
10
FILE ROOM
118A
ALL EXTERIOR ELEMENTS OFEXISTING ENTRY ( WALLS, CEILINGSETC.) - PREP & PAINT.
100
118A
INFILL EXISTING WINDOW w/ BRICK& CMU TO MATCH EXISTING
FIELD VERIFY EXACT LOCATIONOF EXISTING WINDOWS TO ENSURENEW WALLS DO NOT CONFLICT w/EXISTING WINDOWS, TYP.
PROVIDE NEW AWNING TOBE SIMILAR IN SIZE w/ EXISTING
DN
SEE SHEET A0.0 FOR ADD'LSIDEWALK / RAMP INFORMATION
11 11
11
11
11
1111
11
11
2
FIRST LEVEL - KEY PLAN
AREA 'A'
GENERAL RENOVATION NOTES:
1. SEE SHEET G1.6 FOR ADD'L INTERIOR PARTITION INFORMATION.
2. SEE SHEET LIFE SAFETY PLANS FOR FIRE RATED PARTITIONS.
3. ALL CMU CORES (NOT FILLED SOLID FOR REINFORCING) SHALL REC'VFOAMED-IN PLACE MASONRY INSULATION. SEE STRUCTURAL FORREINFORCING.
4. ALL WINDOWS ARE TO REC'V NEW WINDOW SHADES AS SPECIFIED. GC TOFIELD VERIFY WINDOW OPENINGS PRIOR TO ORDERING SHADES.
RENOVATION KEYNOTES:
01 INFILL EXISTING CMU WALL WHERE EXISTING DOORS & FRAME HAVE BEENREMOVED. INFILL TO MATCH SURROUNDING WALL TYPE AND PAINTED /FINISHED TO MATCH. MASONRY INFILL SHALL BE TOOTHED TOGETHER
02 THIS NOTE OMITTED.
03 ALIGN NEW WALL FLUSH w/ EXISTING WALL.
04 NEW CASED OPENING TO BE FINISHED TO MATCH THE SURROUNDINGCONDITIONS
05 NEW CONCRETE FLOOR SLAB AND FOOTINGS - SEE STRUCTURAL
06 INFILL OPENING IN EXISTING EXTERIOR WALL SYSTEM. MATCHSURROUNDING CONSTRUCTION. BRICK TO BE APPROVED BYARCHITECT PRIOR TO CONSTRUCTION
07 NEW CONCRETE PATIO SLAB - SEE STRUCTURAL
08 EXTERIOR BRICK TO BE CLEANED.
09 PROVIDE NEW STL. LINTEL - SEE STRUCTURAL
10 PROVIDE ATTIC ACCESS. WHERE POSSIBLE SAVE / RELOCATE EXISTINGACCESS LADDERS. SEE SHEET A4.4 FOR NEW LADDER DETAILS
11 PROVIDE MANUAL PROJECTION SCREENS AT THE TEACHING WALL OF EACHCLASSROOM (SEE SPECIFICATIONS)
1
WALL LEGEND:
EXISTING WALL SYSTEM
NEW WALL: 3 5/8" STL. STUDS WITH 5/8" GYP. BD. ON EACH FACE.
NON-RATED SMOKE PARTITION
1 HR RATED PARTITION
SEE SHEET G1.6 TYPICAL INTERIOR WALL PARTITIONS FOR ADD'L INFORMATION
HATCH INDICATESAREA OF NEW CONCRETESEE STRUCTURAL
INDICATES LOCATION OF GAS COCK - SEE SHEET A4.1
DATE:
PROJECTNUMBER:
DRAWING NUMBER:
SHEET TITLE:
REVISIONS:
PROJECT TITLE:
DRAWN BY:
NASHVILLE * DENVER * SAN ANTONIO
SAN FRANCISCO * PALM BEACH GARDEN
615.254.8500 * GHP1.com
217th FIFTH AVENUE NORTHNASHVILLE, TN. 37219
1
2
3
4
5
E D C B A
E D C B A
1
2
3
4
5
60 MUSIC SQUARE EASTSUITE 300
NASHVILLE, TN 37203PH: 615.383.6949
1162 FOSTER AVENUENASHVILLE, TN 37210
PH: 615.921.2200
A1.7
FIRST FLOOR - AREA'A' RENOVATION
03.18.2016
13093.09
1252 FOSTER AVE,NASHVILLE, TN 37210
STEMPREPARATORYACADEMY
HIGH SCHOOLRENOVATION
C.D.
1/8" = 1'-0"B1 FIRST FLOOR - AREA 'A' RENOVATIONNORTHNORTH
1 REVISION #1 - 04.01.2016
2 REVISION #2 - 04.21.2016
REF.
FIRST LEVEL - KEY PLAN
AREA 'B'
CORR.
139
I.C.R.
140
CORRIDOR
144
I.C.R.
141GIRL'S TLT
143
J.C.
145
BOY'S TLT
146
I.C.R.
142
I.C.R.
147
I.C.R.
148
MECH
149
STG
150
WORK AREA
152
TLT
153
TLT
154
SPEC. ED
151
CORR.
155
SCIENCELECTURE
156
LAB STG
157A
MECH
157B
SCIENCE LAB
157
MECH
157CLOBBY
158
STAIR
159
I.C.R.
161
CORR
164
I.C.R.
162
GIRL'S TLT
163
J.C.
165
BOY'S TLT
166
SPEC. ED.
167
I.C.R.
168
A4.2
E5
E3
A4.2C3
C5
159
151
160
163
165
157E
157A
167
161
168
162
153
154
152
145
140
141
142
148
147
156
166
A4.0E3
Sim
A4.0C3
Sim
A4.0E3
Sim
02
01
01
01
01
01
01
01
0101
0101
01
01
UP
UP
C.O.
139
149
150
157D
157C
164B
ELECTRICAL
150A
150A
INSTRUCTOR'S DESKCS# 6008A
TYP. GAS COCK -SEE SHEET A4.1
A4.3E1
A4.3
D1
157F
MTG. ROOM
158A
158A
IT CLST.
160
10
DN
INSTRUCTOR'S DESKCR# 6008A
ALL EXTERIOR ELEMENTS OF EXISTINGENTRY ( WALLS, CEILINGS ETC.) - PREP& PAINT.
P1P1
P1
P1
P1
P2
P1
158D
159A
143
146
157B
SEE SHEET A0.0 FOR ADD'LSIDEWALK / RAMP INFORMATION
TYP. STUDENT DESKCR# 6510
11
11
11 11
11
11
11
11
11
11
2
2
GENERAL RENOVATION NOTES:
1. SEE SHEET G1.6 FOR ADD'L INTERIOR PARTITION INFORMATION.
2. SEE SHEET LIFE SAFETY PLANS FOR FIRE RATED PARTITIONS.
3. ALL CMU CORES (NOT FILLED SOLID FOR REINFORCING) SHALL REC'VFOAMED-IN PLACE MASONRY INSULATION. SEE STRUCTURAL FORREINFORCING.
4. ALL WINDOWS ARE TO REC'V NEW WINDOW SHADES AS SPECIFIED. GC TOFIELD VERIFY WINDOW OPENINGS PRIOR TO ORDERING SHADES.
RENOVATION KEYNOTES:
01 INFILL EXISTING CMU WALL WHERE EXISTING DOORS & FRAME HAVE BEENREMOVED. INFILL TO MATCH SURROUNDING WALL TYPE AND PAINTED /FINISHED TO MATCH. MASONRY INFILL SHALL BE TOOTHED TOGETHER
02 THIS NOTE OMITTED.
03 ALIGN NEW WALL FLUSH w/ EXISTING WALL.
04 NEW CASED OPENING TO BE FINISHED TO MATCH THE SURROUNDINGCONDITIONS
05 NEW CONCRETE FLOOR SLAB AND FOOTINGS - SEE STRUCTURAL
06 INFILL OPENING IN EXISTING EXTERIOR WALL SYSTEM. MATCHSURROUNDING CONSTRUCTION. BRICK TO BE APPROVED BYARCHITECT PRIOR TO CONSTRUCTION
07 NEW CONCRETE PATIO SLAB - SEE STRUCTURAL
08 EXTERIOR BRICK TO BE CLEANED.
09 PROVIDE NEW STL. LINTEL - SEE STRUCTURAL
10 PROVIDE ATTIC ACCESS. WHERE POSSIBLE SAVE / RELOCATE EXISTINGACCESS LADDERS. SEE SHEET A4.4 FOR NEW LADDER DETAILS
11 PROVIDE MANUAL PROJECTION SCREENS AT THE TEACHING WALL OF EACHCLASSROOM (SEE SPECIFICATIONS)
1
WALL LEGEND:
EXISTING WALL SYSTEM
NEW WALL: 3 5/8" STL. STUDS WITH 5/8" GYP. BD. ON EACH FACE.
NON-RATED SMOKE PARTITION
1 HR RATED PARTITION
SEE SHEET G1.6 TYPICAL INTERIOR WALL PARTITIONS FOR ADD'L INFORMATION
HATCH INDICATESAREA OF NEW CONCRETESEE STRUCTURAL
INDICATES LOCATION OF GAS COCK - SEE SHEET A4.1
EXISTING EXTERIOR WALL
EXISTING CONCRETE SLAB
EXISTING PIPE HANDRAIL (PAINT)
EXISTING STEPS
EXISTING PIPE HANDRAIL (PAINT)
EXISTING CONCRETE SIDEWALK
EXISTING EXTERIOR WALL
1' -
0"
+/-
V.I.
F.
NEW CONCRETE TO PROVIDE5FT MIN. LANDING IN FRONT OFDOOR. FIELD VERIFY WIDTH
NEW CODE COMPLIANT PIPEHANDRAIL (PAINT)
5' -
0"
+/-
C2 / A1.8
11 / S2.1
SEE STRUCTURAL DETAIL 11 / S2.1FOR ADD'L INFORMATION
FIE
LD V
ER
IFY
HG
T.
FT
G.
SEE STRUCT.
EXISTING BLDG
COLD JOINT
EXISTING CONC.STOOP
NEW CONC. DOWELEDINTO EXISTING - SET INEPOXY
EXISTING PIPE HANDRAIL (PAINT)
NEW CODE COMPLIANT PIPEHANDRAIL (PAINT)
SEE STRUCTURAL DETAIL 11 / S2.1FOR ADD'L INFORMATION
GRADE
DATE:
PROJECTNUMBER:
DRAWING NUMBER:
SHEET TITLE:
REVISIONS:
PROJECT TITLE:
DRAWN BY:
NASHVILLE * DENVER * SAN ANTONIO
SAN FRANCISCO * PALM BEACH GARDEN
615.254.8500 * GHP1.com
217th FIFTH AVENUE NORTHNASHVILLE, TN. 37219
1
2
3
4
5
E D C B A
E D C B A
1
2
3
4
5
60 MUSIC SQUARE EASTSUITE 300
NASHVILLE, TN 37203PH: 615.383.6949
1162 FOSTER AVENUENASHVILLE, TN 37210
PH: 615.921.2200
A1.8
FIRST FLOOR AREA'B' RENOVATION
03.18.2016
13093.09
1252 FOSTER AVE,NASHVILLE, TN 37210
STEMPREPARATORYACADEMY
HIGH SCHOOLRENOVATION
C.D.
1/8" = 1'-0"D1 FIRST FLOOR - AREA 'B' RENOVATION
NORTH
1/4" = 1'-0"D2 DOOR STOOP EXPANSION 1/2" = 1'-0"C2 STOOP SECTION
1
1 REVISION #1 - 04.01.2016
2 REVISION #2 - 04.21.2016
AreaOffice
FIRST LEVEL - KEY PLAN
AR
EA
'C'
RA
MP
UP
CORR.
128
CAFE
130
ELEC.
129
KITCHEN
134
STORAGE
132
TLT
133CORR.
139
DISHWASH
131
06
06
06
CAFE CORRIDOR
130A
130A
130B
A
A
A
A
A
NEW WINDOWS TO BECENTERED ON EXISTING WINDOWAS SHOWN, TYP. FIELD VERIFYCONDITIONS
NEW DOORS TO BE CENTERED ONEXISTING WINDOW OPENING ASSHOWN. FIELD VERIFY CONDITIONS
A2.0E4
01
01
07
A1
A2.0
E1
A2.0
E1
A3.0
C1
A2.0
08
08
C.O.
C.O.
C.O.
134A
128B
133
134C
139
10
01
129
PAINT EXISTING CASTIRON SINK
RELOCATE EXISTING HOSEBIBB - SEE PLUMBING
RETURN PASS THRU TO WORKINGORDER SEE SHEET A7.3 FOR ADD'LINFORMATION
P2
P2
P2
NEW CORRIDOR RAMP -SEE DETAIL E4 / A1.9
1' -
0"
MIN
.
LAN
DIN
GLA
ND
ING
LAN
DIN
GR
AM
P U
PR
AM
P U
P
EXISTING CORRIDOR RAMPTO REC'V NEW HANDRAILS
06
06
06
132
130C
SEE SHEET FS1 FOR ADD'LKITCHEN EQUIPMENT
SEE SHEET A0.0 FOR ADD'LSIDEWALK / RAMP INFORMATION
PROVIED COILING COUNTER DOOR ASSPECIFIED.
2
2
2
GENERAL RENOVATION NOTES:
1. SEE SHEET G1.6 FOR ADD'L INTERIOR PARTITION INFORMATION.
2. SEE SHEET LIFE SAFETY PLANS FOR FIRE RATED PARTITIONS.
3. ALL CMU CORES (NOT FILLED SOLID FOR REINFORCING) SHALL REC'VFOAMED-IN PLACE MASONRY INSULATION. SEE STRUCTURAL FORREINFORCING.
4. ALL WINDOWS ARE TO REC'V NEW WINDOW SHADES AS SPECIFIED. GC TOFIELD VERIFY WINDOW OPENINGS PRIOR TO ORDERING SHADES.
RENOVATION KEYNOTES:
01 INFILL EXISTING CMU WALL WHERE EXISTING DOORS & FRAME HAVE BEENREMOVED. INFILL TO MATCH SURROUNDING WALL TYPE AND PAINTED /FINISHED TO MATCH. MASONRY INFILL SHALL BE TOOTHED TOGETHER
02 THIS NOTE OMITTED.
03 ALIGN NEW WALL FLUSH w/ EXISTING WALL.
04 NEW CASED OPENING TO BE FINISHED TO MATCH THE SURROUNDINGCONDITIONS
05 NEW CONCRETE FLOOR SLAB AND FOOTINGS - SEE STRUCTURAL
06 INFILL OPENING IN EXISTING EXTERIOR WALL SYSTEM. MATCHSURROUNDING CONSTRUCTION. BRICK TO BE APPROVED BYARCHITECT PRIOR TO CONSTRUCTION
07 NEW CONCRETE PATIO SLAB - SEE STRUCTURAL
08 EXTERIOR BRICK TO BE CLEANED.
09 PROVIDE NEW STL. LINTEL - SEE STRUCTURAL
10 PROVIDE ATTIC ACCESS. WHERE POSSIBLE SAVE / RELOCATE EXISTINGACCESS LADDERS. SEE SHEET A4.4 FOR NEW LADDER DETAILS
11 PROVIDE MANUAL PROJECTION SCREENS AT THE TEACHING WALL OF EACHCLASSROOM (SEE SPECIFICATIONS)
1
WALL LEGEND:
EXISTING WALL SYSTEM
NEW WALL: 3 5/8" STL. STUDS WITH 5/8" GYP. BD. ON EACH FACE.
NON-RATED SMOKE PARTITION
1 HR RATED PARTITION
SEE SHEET G1.6 TYPICAL INTERIOR WALL PARTITIONS FOR ADD'L INFORMATION
HATCH INDICATESAREA OF NEW CONCRETESEE STRUCTURAL
INDICATES LOCATION OF GAS COCK - SEE SHEET A4.1
LANDING
6' - 0"
RAMP
20' - 7" +/-
LANDING
6' - 0"
RAMP
16' - 5" +/-
LANDING
5' - 0"
LENGTH OF CORRIDOR #139
53' - 11" +/-
1' -
5"
1' -
5"
1' - 0"
1' - 0"
HA
ND
RA
IL
34"
- 3
8"
HA
ND
RA
IL
34"
- 3
8"
10
' - 1
0" +
/-
2' -
10"
1 1/2" Ø HANDRAIL - FIRMLYATTACHED TO WALL
CJCJ
CJ
CJ CJ
CJ
4" CONCRETE RAMP / LANDINGTYP. - SEE STRUCTURAL
4" MIN. COMPACTEDGRAVEL FILL
DATE:
PROJECTNUMBER:
DRAWING NUMBER:
SHEET TITLE:
REVISIONS:
PROJECT TITLE:
DRAWN BY:
NASHVILLE * DENVER * SAN ANTONIO
SAN FRANCISCO * PALM BEACH GARDEN
615.254.8500 * GHP1.com
217th FIFTH AVENUE NORTHNASHVILLE, TN. 37219
1
2
3
4
5
E D C B A
E D C B A
1
2
3
4
5
60 MUSIC SQUARE EASTSUITE 300
NASHVILLE, TN 37203PH: 615.383.6949
1162 FOSTER AVENUENASHVILLE, TN 37210
PH: 615.921.2200
A1.9
FIRST FLOOR AREA'C' RENOVATION
03.18.2016
13093.09
1252 FOSTER AVE,NASHVILLE, TN 37210
STEMPREPARATORYACADEMY
HIGH SCHOOLRENOVATION
C.D.
1/8" = 1'-0"C1 FIRST FLOOR - AREA 'C' RENOVATION
NORTH
1/4" = 1'-0"E5 CORRIDOR #139
1 REVISION #1 - 04.01.2016
2 REVISION #2 - 04.21.2016
GENERAL DOOR NOTES:
1. ALL 7' - 0" TALL DOORS TO RECEIVE (3) HINGES, TYP.
2. DOORS TALLER THAN 7' - 0" TO RECEIVE (4) OR MORE HINGES.
3. AT CENTER LINE OF DOOR, WHERE FLOOR MATERIAL CHANGESPROVIDE DOOR THRESHOLD OR TRANSITION STRIP. SUBMITRECOMMENDED TRANSITION MATERIAL FOR REVIEW & APPROVAL.
4. PROVIDE NEW ALUM. THRESHOLD AT ALL EXTERIOR DOORSUNLESS OTHERWISE NOTED.
5. THIS NOTE OMITTED.
6. PROVIDE NEW WEATHERSTRIPING @ ALL EXTERIOR DOORS.
7. PAINT EXTERIOR H.M. DOORS / FRAMES TO MATCH BRICK COLOR
8. SEE SPECIFICATIONS FOR DOOR FINISH. WOOD DOOR DESIGNATIONON THE DOOR SCHEDULE PERTAINS ONLY TO TYPE OF MATERIALNOT FINISH VENEER.
9. FIRE RATED DOORS REQUIRE EDGE SMOKE SEALING TO COMPLYWITH POSITIVE PRESSURE TEST.
10. FIRE RATED DOORS TO HAVE FIRE RATED FRAMES, HARDWARE,CLOSERS & ACCESSORIES TO MEET UL DESIGN. COORDINATEWITH SPECIFICATIONS.
11. THIS NOTE OMITTED.
12. ANY GLASS IN FIRE-RATED DOORS SHALL BE 1/4" WIRE GLASS
DOOR ABBREVIATIONS:
ALUM. ALUMINUM
HM HOLLOW METAL
F FLUSH
PR PAIR
TEMP'D 1/4" TEMPERED
WG 1/4" WIRE GLASS
WD WOOD
HG HALF GLASS
NV NARROW VIEW
EXIST. EXISTING
PL PLASTIC LAM.
PT PAINT
BL BORROWED LIGHT
FG FULL GLASS
ME MATCH EXISTING
DPS DOOR POSITION SWITCH
DATE:
PROJECTNUMBER:
DRAWING NUMBER:
SHEET TITLE:
REVISIONS:
PROJECT TITLE:
DRAWN BY:
NASHVILLE * DENVER * SAN ANTONIO
SAN FRANCISCO * PALM BEACH GARDEN
615.254.8500 * GHP1.com
217th FIFTH AVENUE NORTHNASHVILLE, TN. 37219
1
2
3
4
5
E D C B A
E D C B A
1
2
3
4
5
60 MUSIC SQUARE EASTSUITE 300
NASHVILLE, TN 37203PH: 615.383.6949
1162 FOSTER AVENUENASHVILLE, TN 37210
PH: 615.921.2200
A6.0
DOOR SCHEDULES
03.18.2016
13093.09
1252 FOSTER AVE,NASHVILLE, TN 37210
STEMPREPARATORYACADEMY
HIGH SCHOOLRENOVATION
C.D.
LOWER LEVEL DOOR SCHEDULE
MARK ROOM NAME
DOORDOORFRAME
FIRERTG HDW COMMENTSPAIR
DOOR SIZEMTL TYPE FINISH GLAZ MTL TYPEWIDTH HGT THK
001 STAIRS / VEST. - 3' - 0" 7' - 0" 1 3/4" - - - - - - 60 MIN 14.0 EXISTING DOOR / NEW HARDWARE002 CORRIDOR - 3' - 0" 7' - 0" 1 3/4" - - - - - - 3.0 EXISTING DOOR / NEW HARDWARE003 MECH - 3' - 0" 7' - 0" 1 3/4" - - - - - - 45 MIN 15.0 EXISTING DOOR / NEW HARDWARE004 VESTIBULE - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 16.0005A COPY / WORK AREA - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 12.0005B OFC - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 2.0006 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0007 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0009 VESTIBULE - 3' - 0" 7' - 0" 1 3/4" - - - - - - 8.0 EXISTING DOOR / NEW HARDWARE010 MECH - 3' - 0" 7' - 0" 1 3/4" - - - - - - 45 MIN 8.0 EXISTING DOOR / NEW HARDWARE010A ELECTRICAL - 3' - 0" 7' - 0" 1 3/4" H.M. F PT - HM A 12.0011 J.C. - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 11.0012 TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 7.0013 TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 7.0014 CORRIDOR - 3' - 0" 7' - 0" 1 3/4" - - - - - - 13.0 EXISTING DOOR / NEW HARDWARE015 MEETING ROOM - 3' - 0" 7' - 0" 1 3/4" H.M. F PT - HM A 2.0016A CRAWL SPACE ACCESS - 3' - 0" 7' - 0" 1 3/4" - - - - - - 9.0 EXISTING DOOR / NEW HARDWARE016B CORRIDOR - 3' - 6" 7' - 0" 1 3/4" SCW F STAIN - HM A 60 MIN 10.0016C CORRIDOR - 3' - 0" 7' - 0" 1 3/4" - - - - - - 3.0 EXISTING DOOR / NEW HARDWARE017 I.C.R. - 3' - 0" 7' - 0" 1 3/4" - - - - - - 5.0 EXISTING DOOR / NEW HARDWARE017A MECH - 3' - 0" 7' - 0" 1 3/4" - - - - - - 15.0 EXISTING DOOR / NEW HARDWARE018 TLT. - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 7.0019 TLT. - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 7.0020 WORK AREA - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 2.0021 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 6.0022 OFC. - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 2.0023 OFC. - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 2.0024A I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 6.0024B I.C.R. - 3' - 0" 7' - 0" 1 3/4" - - - - - - 1.0 EXISTING DOOR / NEW HARDWARE
FIRST FLOOR AREA 'A' - DOOR SCHEDULE
MARK ROOM NAME
DOORDOORFRAME
FIRERTG HDW COMMENTSPAIR
DOOR SIZEMTL TYPE FINISH GLAZ MTL TYPEWIDTH HGT THK
100 LOBBY - 3' - 0" 7' - 0" 1 3/4" - - - - - - - 4.0 EXISTING DOOR / REMOTE ACCESS, PROX READER, KEY FOB101A STAIRS - 3' - 0" 7' - 0" 1 3/4" - - - - - - 45 MIN 14.0 EXISTING DOOR / NEW HARDWARE101B STAIRS - 3' - 0" 7' - 0" 1 3/4" - - - - - - - 3.0 EXISTING DOOR / NEW HARDWARE102 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0103 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0104 CORRIDOR - 3' - 0" 7' - 0" 1 3/4" - - - - - - - 3.0 EXISTING DOOR / NEW HARDWARE105 GIRL'S TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 22.0106 J.C. - 2' - 8" 7' - 0" 1 3/4" HM F PT - HM A 17.0107 BOY'S TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 22.0108 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0109 SPEC. ED. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 6.0112A PROF. DEVELOPMENT - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 19.0112B PROF. DEVELOPMENT - 3' - 0" 7' - 0" 1 3/4" - - - - - - 3.0 EXISTING DOOR / NEW HARDWARE112C PROF. DEVELOPMENT - 2' - 0" 7' - 0" 1 3/4" - - - - - - 18.0 EXISTING DOOR / NEW HARDWARE112D PROF. DEVELOPMENT YES 6' - 0" 7' - 0" 1 3/4" SCW FG STAIN 1/4 TEMP'D HM A 20.0113 ADMIN. / OFC. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 2.0113A MECH - 2' - 0" 7' - 0" 1 3/4" - - - - - - 18.0 EXISTING DOOR / NEW HARDWARE113B IT CLST - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 17.0114 TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 7.0115 TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 7.0117 MEETING - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 2.0118 WORK ROOM - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 2.0118A FILE ROOM - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 21.0119 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0120 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 6.0121 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0123 BOY'S TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 22.0124 J.C. - 2' - 8" 7' - 0" 1 3/4" HM F PT - HM A 17.0125 GIRL'S TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 22.0126 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0127 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0128A CORRIDOR - 3' - 0" 7' - 0" 1 3/4" - - - - - - 3.0 EXISTING DOOR / NEW HARDWARE
1
1
1 REVISION #1 - 04.01.2016
2 REVISION #2 - 04.21.2016
2
2
DOOR ABBREVIATIONS:
ALUM. ALUMINUM
HM HOLLOW METAL
F FLUSH
PR PAIR
TEMP'D 1/4" TEMPERED
WG 1/4" WIRE GLASS
WD WOOD
HG HALF GLASS
NV NARROW VIEW
EXIST. EXISTING
PL PLASTIC LAM.
PT PAINT
BL BORROWED LIGHT
FG FULL GLASS
ME MATCH EXISTING
DPS DOOR POSITION SWITCH
GENERAL DOOR NOTES:
1. ALL 7' - 0" TALL DOORS TO RECEIVE (3) HINGES, TYP.
2. DOORS TALLER THAN 7' - 0" TO RECEIVE (4) OR MORE HINGES.
3. AT CENTER LINE OF DOOR, WHERE FLOOR MATERIAL CHANGESPROVIDE DOOR THRESHOLD OR TRANSITION STRIP. SUBMITRECOMMENDED TRANSITION MATERIAL FOR REVIEW & APPROVAL.
4. PROVIDE NEW ALUM. THRESHOLD AT ALL EXTERIOR DOORSUNLESS OTHERWISE NOTED.
5. THIS NOTE OMITTED.
6. PROVIDE NEW WEATHERSTRIPING @ ALL EXTERIOR DOORS.
7. PAINT EXTERIOR H.M. DOORS / FRAMES TO MATCH BRICK COLOR
8. SEE SPECIFICATIONS FOR DOOR FINISH. WOOD DOOR DESIGNATIONON THE DOOR SCHEDULE PERTAINS ONLY TO TYPE OF MATERIALNOT FINISH VENEER.
9. FIRE RATED DOORS REQUIRE EDGE SMOKE SEALING TO COMPLYWITH POSITIVE PRESSURE TEST.
10. FIRE RATED DOORS TO HAVE FIRE RATED FRAMES, HARDWARE,CLOSERS & ACCESSORIES TO MEET UL DESIGN. COORDINATEWITH SPECIFICATIONS.
11. THIS NOTE OMITTED.
12. ANY GLASS IN FIRE-RATED DOORS SHALL BE 1/4" WIRE GLASS
EXISTING DOOR NOTE:
EXISTING DOORS & FRAMES THAT ARE TO BE REUSED SHALL BECLEANED AND REFINISHED AS SPECIFIED. ANY EXISTING DOOR THATIS LABELED AS FIRE-RATED ON THE NEW LIFE SAFETY DWGS. SHALLBE FIELD VERIFIED BY THE CONTRACTOR. IF IT DOES NOT CONFORMTO THE REQUIRED RATING THEN IT IS TO BE REPLACED WITH A NEWDOOR TO MATCH.
7' -
0"
3' - 0"
2"7'
- 0
"
2"
SCHEDULE
PER 2"
7' -
2"
7' -
0"
3' - 0"
6" 2' - 0" 6"
2' -
10
1/2"
6"
"F"FLUSH
"HG"HALF-GLASS
"A"
7' -
0"
3' - 0"
"F"PAIR OF FLUSH
6' - 0"
7' -
0"
6' - 0"
6" 2' - 0" 6"
2' -
10
1/2"
6"
"HG"PAIR OF HALF-GLASS
2"7'
- 0
"
2"
SCHEDULE
PER 2"
7' -
2"
"B"
7' -
0"
3' - 0"
6" 2' - 0" 6"
"HG2"HALF-GLASS
DATE:
PROJECTNUMBER:
DRAWING NUMBER:
SHEET TITLE:
REVISIONS:
PROJECT TITLE:
DRAWN BY:
NASHVILLE * DENVER * SAN ANTONIO
SAN FRANCISCO * PALM BEACH GARDEN
615.254.8500 * GHP1.com
217th FIFTH AVENUE NORTHNASHVILLE, TN. 37219
1
2
3
4
5
E D C B A
E D C B A
1
2
3
4
5
60 MUSIC SQUARE EASTSUITE 300
NASHVILLE, TN 37203PH: 615.383.6949
1162 FOSTER AVENUENASHVILLE, TN 37210
PH: 615.921.2200
A6.1
DOOR SCHEDULES
03.18.2016
13093.09
1252 FOSTER AVE,NASHVILLE, TN 37210
STEMPREPARATORYACADEMY
HIGH SCHOOLRENOVATION
C.D.
FIRST FLOOR AREA 'B' - DOOR SCHEDULE
MARK ROOM NAME
DOORDOORFRAME
FIRERTG HDW COMMENTSPAIR
DOOR SIZEMTL TYPE FINISH GLAZ MTL TYPEWIDTH HGT THK
139 CORRIDOR - 3' - 0" 7' - 0" 1 3/4" - - - - - - 3.0 EXISTING DOOR / NEW HARDWARE140 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0141 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0142 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0143 GIRL'S TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 22.0145 J.C. - 3' - 0" 7' - 0" 1 3/4" HM F PT - HM A 17.0146 BOY'S TLT - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 22.0147 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0148 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0149 MECH - 2' - 8" 7' - 0" 1 3/4" - - - - - - 45 MIN 8.0 EXISTING DOOR / NEW HARDWARE150 STG - 2' - 8" 7' - 0" 1 3/4" - - - - - - 45 MIN 8.0 EXISTING DOOR / NEW HARDWARE150A ELECTRICAL 3' - 0" 7' - 0" 1 3/4" HM F PT - HM A 12.0151 SPEC. ED. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0152 WORK AREA - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 2.0153 TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 7.0154 TLT - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 7.0156 COMP. LAB. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0157A LAB. STG. - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 26.0157B MECH - 3' - 0" 7' - 0" 1 3/4" HM F PT - HM A 24.0157C MECH - 2' - 8" 7' - 0" 1 3/4" - - - - - - 18.0 EXISTING DOOR / NEW HARDWARE157D SCIENCE LAB - 3' - 0" 7' - 0" 1 3/4" - - - - - - 1.0 EXISTING DOOR / NEW HARDWARE157E SCIENCE LAB - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D WG HM A 45 MIN 5.0157F LAB STG - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 45 MIN 16.0158A MTG. ROOM 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM - 2.0158D LOBBY 3' - 6" 7' - 0" 1 3/4" FG F PT 1/4 TEMP'D HM - 23.0159 STAIRS - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D WG HM A 60 MIN 10.0159A STAIRS - 3' - 0" 7' - 0" 1 3/4" HM F PT - - - 3.0 NEW DOOR - EXISTING FRAME160 IT CLST - 3' - 0" 7' - 0" 1 3/4" HM F PT - HM A 45 MIN 25.0161 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 6.0162 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0163 GIRL'S TLT - 3' - 0" 7' - 0" 1 3/4" SCW F PT - HM A 22.0164B CORRIDOR - 3' - 0" 7' - 0" 1 3/4" - - - - - - 3.0 EXISTING DOOR / NEW HARDWARE165 J.C. - 2' - 8" 7' - 0" 1 3/4" HM F PT - HM A 17.0 ADD DOOR CLOSER 281 P10 AS SPECIFIED166 BOY'S TLT - 3' - 0" 7' - 0" 1 3/4" SCW F PT - HM A 22.0167 SPEC. ED. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 6.0168 I.C.R. - 3' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM A 5.0
FIRST FLOOR AREA 'C' - DOOR SCHEDULE
MARK ROOM NAME
DOORDOORFRAME
FIRE RTG HDW COMMENTSPAIRDOOR SIZE
MTL TYPE FINISH GLAZ MTL TYPEWIDTH HGT THK128B CORRIDOR - 2' - 8" 7' - 0" 1 3/4" - - - - - - 30.0 EXISTING DOOR / NEW HARDWARE129 ELECTRICAL - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - HM A 45 MIN 29.0130A CAFE CORRIDOR YES 6' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D HM B 31.0130B CAFE CORRIDOR YES 6' - 0" 7' - 0" 1 3/4" SCW HG STAIN 1/4 TEMP'D WG HM B 45 MIN 28.0130C CAFE - 3' - 0" 7' - 0" 1 3/4" SCW FG2 STAIN 1/4 TEMP'D - - 3.0 NEW DOOR / EXISTING FRAME132 STORAGE - 3' - 0" 7' - 0" 1 3/4" SCW F STAIN - - - 17.0 NEW DOOR / EXISTING FRAME133 TLT - 2' - 8" 7' - 0" 1 3/4" - - - - - - 7.0 EXISTING DOOR / NEW HARDWARE134A KITCHEN - 2' - 8" 7' - 0" 1 3/4" - - - - - - 45 MIN 32.0 EXISTING DOOR / NEW HARDWARE134C KITCHEN - 3' - 6" 7' - 0" 1 3/4" - - - - - - 27.0 EXISTING DOOR / NEW HARDWARE
1/2" = 1'-0"E1 DOOR & FRAME ELEVATIONS
1
1
1 REVISION #1 - 04.01.2016
2
2
2
2
22
2
2 REVISION #2 - 04.21.2016
COMcheck Software Version 4.0.2.0
Mechanical Compliance Certificate
Project Title:
2012 IECC
Project Type: Alteration
Location: Nashville, TennesseeClimate Zone: 4a
Construction Site:NASHVILLE, TN 37210
Owner/Agent: Designer/Contractor:PMCNASHVILLE, TN
Project Information
Energy Code:
STEM PREPARATORY ACADEMY
Mechanical Systems List
Quantity System Type & Description
Cooling: 1 each - Split System, Capacity = 95 kBtu/h, Air-Cooled Condenser, Air Economizer Proposed Efficiency = 11.20 EER, Required Efficiency = 11.20 EERFan System: FAN SYSTEM 3 | kITCHEN UNIT -- Compliance (Motor nameplate HP method) : Passes
Fans: FAN 3 Supply, Constant Volume, 3000 CFM, 0.5 motor nameplate hp
1 HVAC System (Single Zone):
Gas Instantaneous Water Heater, Capacity: 0 gallons, Input Rating: 199 Btu/h Proposed Efficiency: 0.90 EF, Required Efficiency: 0.67 EF
2 Water Heater 1:
Mechanical Compliance StatementCompliance Statement: The proposed mechanical alteration project represented in this document is consistent with the buildingplans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have beendesigned to meet the 2012 IECC requirements in COMcheck Version 4.0.2.0 and to comply with the mandatory requirementslisted in the Inspection Checklist.
Name - Title Signature Date
Project Title:Data filename:
STEM PREPARATORY ACADEMYM:\2015 Job Numbers\15114 STEM High School\0-General\Basis of Design\COMCHECK\15114MECHANICAL.cck
04/21/16Report date:81 ofPage
Inspection ChecklistRequirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.2.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For eachrequirement, the user certifies that a code requirement will be met and how that is documented, or that an exceptionis being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2012 IECC
Section#
& Req.IDPlan Review Complies? Comments/Assumptions
C103.2[PR2]1
Plans, specifications, and/orcalculations provide all informationwith which compliance can bedetermined for the mechanicalsystems and equipment anddocument where exceptions to thestandard are claimed. Loadcalculations per acceptableengineering standards andhandbooks.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C103.2[PR3]1
Plans, specifications, and/orcalculations provide all informationwith which compliance can bedetermined for the service waterheating systems and equipment anddocument where exceptions to thestandard are claimed. Hot watersystem sized per manufacturer'ssizing guide.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:Data filename:
STEM PREPARATORY ACADEMYM:\2015 Job Numbers\15114 STEM High School\0-General\Basis of Design\COMCHECK\15114MECHANICAL.cck
04/21/16Report date:82 ofPage
Section#
& Req.IDFooting / Foundation Inspection Complies? Comments/Assumptions
C403.2.4.5[FO9]3
Freeze protection and snow/icemelting system sensors for futureconnection to controls.
CompliesDoes NotNot ObservableNot Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:Data filename:
STEM PREPARATORY ACADEMYM:\2015 Job Numbers\15114 STEM High School\0-General\Basis of Design\COMCHECK\15114MECHANICAL.cck
04/21/16Report date:83 ofPage
Section#
& Req.IDMechanical Rough-In Inspection Complies? Comments/Assumptions
C403.2.3[ME55]2
HVAC equipment efficiency verified. CompliesDoes NotNot ObservableNot Applicable
See the Mechanical Systems list for values.
C403.2.5.1[ME59]1
Demand control ventilation providedfor spaces >500 sq.ft. and >25people/1000 sq.ft. occupant densityand served by systems with air sideeconomizer, auto modulating outsideair damper control, or design airflow>3,000 cfm.
CompliesDoes NotNot ObservableNot Applicable
Exception: Systems with energy recovery.
C403.2.7[ME60]2
HVAC ducts and plenums insulated.Where ducts or plenums are installedin or under a slab, verification mayneed to occur during FoundationInspection.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.8[ME61]2
HVAC piping insulation thickness.Where piping is installed in or under aslab, verification may need to occurduring Foundation Inspection.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.8.1[ME7]3
Piping Insulation exposed to weatheris protected from damage (due to sun,moisture, wind, etc.).
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.8[ME41]3
Thermally ineffective panel surfaces ofsensible heating panels haveinsulation >= R-3.5.
CompliesDoes NotNot ObservableNot Applicable
Exception: Requirement does not apply.
C403.2.7[ME10]2
Ducts and plenums sealed based onstatic pressure and location.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.7.1.3[ME11]3
Ductwork operating >3 in. watercolumn requires air leakage testing.
CompliesDoes NotNot ObservableNot Applicable
Exception: Requirement does not apply.
C403.3.1,C403.3.1.1[ME62]1
Air economizers provided whererequired, meet the requirements fordesign capacity, control signal,ventilation controls, high-limit shut-off,integrated economizer control, andprovide a means to relieve excessoutside air during operation.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.2.1[ME53]3
Air outlets and zone terminal deviceshave means for air balancing.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.4.2[ME66]2
VAV fan motors >=7.5 hp to be drivenby variable speed drive, have a vane-axial fan with variable pitch blades, orhave controls to limit fan motordemand.
CompliesDoes NotNot ObservableNot Applicable
Exception: Requirement does not apply.
C403.4.2[ME66]2
VAV fan motors >=7.5 hp to be drivenby variable speed drive, have a vane-axial fan with variable pitch blades, orhave controls to limit fan motordemand.
CompliesDoes NotNot ObservableNot Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:Data filename:
STEM PREPARATORY ACADEMYM:\2015 Job Numbers\15114 STEM High School\0-General\Basis of Design\COMCHECK\15114MECHANICAL.cck
04/21/16Report date:84 ofPage
Section#
& Req.IDMechanical Rough-In Inspection Complies? Comments/Assumptions
C403.2.6[ME57]1
Exhaust air energy recovery onsystems meeting Table C403.2.6
CompliesDoes NotNot ObservableNot Applicable
C403.2.11[ME71]2
Unenclosed spaces that are heateduse only radiant heat.
CompliesDoes NotNot ObservableNot Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:Data filename:
STEM PREPARATORY ACADEMYM:\2015 Job Numbers\15114 STEM High School\0-General\Basis of Design\COMCHECK\15114MECHANICAL.cck
04/21/16Report date:85 ofPage
Section#
& Req.IDFinal Inspection Complies? Comments/Assumptions
C403.2.4.1[FI47]3
Heating and cooling to each zone iscontrolled by a thermostat control.Minimum one humidity control deviceper installedhumidification/dehumidificationsystem.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.4.2[FI38]3
Thermostatic controls have a 5 °Fdeadband.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.4.2[FI20]3
Temperature controls have setpointoverlap restrictions.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.4.3[FI39]3
Each zone equipped with setbackcontrols using automatic time clock orprogrammable control system.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.4.3[FI40]3
Automatic Controls: Setback to 55°F(heat) and 85°F (cool); 7-day clock, 2-hour occupant override, 10-hourbackup
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C403.2.4.3.3[FI41]3
Systems include optimum startcontrols.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.5.1[FI7]3
Furnished HVAC as-built drawingssubmitted within 90 days of systemacceptance.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C303.3,C408.2.5.3[FI8]3
Furnished O&M manuals for HVACsystems within 90 days of systemacceptance.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.5.3[FI43]1
An air and/or hydronic systembalancing report is provided for HVACsystems.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.3.2[FI10]1
HVAC control systems have beentested to ensure proper operation,calibration and adjustment of controls.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C404.3[FI11]3
Public lavatory faucet watertemperature <=110°F.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C404.5[FI45]2
First 8 ft of outlet piping is insulated CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:Data filename:
STEM PREPARATORY ACADEMYM:\2015 Job Numbers\15114 STEM High School\0-General\Basis of Design\COMCHECK\15114MECHANICAL.cck
04/21/16Report date:86 ofPage
Section#
& Req.IDFinal Inspection Complies? Comments/Assumptions
C403.2.2[FI27]3
HVAC systems and equipmentcapacity does not exceed calculatedloads.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.1[FI28]1
Commissioning plan developed byregistered design professional orapproved agency.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.4[FI29]1
Preliminary commissioning reportcompleted and certified by registereddesign professional or approvedagency.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.5.4[FI30]1
Final commissioning report due tobuilding owner within 90 days ofreceipt of certificate of occupancy.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.3.1[FI31]1
HVAC equipment has been tested toensure proper operation.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C408.2.3.3[FI32]1
Economizers have been tested toensure proper operation.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
C406[FI34]1
Efficient HVAC performance, efficientlighting system, or on-site supply ofrenewable energy consistent withwhat is shown the approved plans.
CompliesDoes NotNot ObservableNot Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:Data filename:
STEM PREPARATORY ACADEMYM:\2015 Job Numbers\15114 STEM High School\0-General\Basis of Design\COMCHECK\15114MECHANICAL.cck
04/21/16Report date:87 ofPage
Project Title:Data filename:
STEM PREPARATORY ACADEMYM:\2015 Job Numbers\15114 STEM High School\0-General\Basis of Design\COMCHECK\15114MECHANICAL.cck
04/21/16Report date:88 ofPage