  • 8/16/2019 Flue Gas Duct Opening Details at Chimney V1 R1

    1/2

    15095 Received bye-mail

    16.03.16 16.03.16

    1. The duct from ID fan to chimney should have an inclination of 30 degwith respect to horizontal till the inlet of chimney.2.0 With respect to flue gas duct opening dimension, Flue gas velocity isaround 19 m/s for guaranteed firing condition. Kindly revise the flue gasduct opening dimension to maintain flue gas velocity of 15 m/s.3.Clouded dimension shall be under hold, until the receipt of Chimney GADrawing.

    Refer Point no:3

    P.Ramesh Babu 25.03.16

  • 8/16/2019 Flue Gas Duct Opening Details at Chimney V1 R1

    2/2

    S.No Avant- Garde Comments dt.19.02.2016 Isgec reply on dated 16.03.2016 Avant- Garde Comments dt .

    1.Kindly consider flue gas terminal point up to the inlet ofchimney as indicated

    ISGEC agreed & the same is indicated in revised drawing

    2.

    With respect to above point, kindly provide insert plateembadded details in the drawing.

    We have shown the clear opening detail in the drawing.However chimney GA shall be submitted from your end todo our engineering activities.

    3.

    Isgec to revise the duct connection near to chimney as

    rectangular instead of circular.

    ISGEC agreed & the same is indicated in revised drawing

    4.

    Isgec to route the existing 200TPH flue gas ducting to thenew flue provided in new RCC chimmey and provide thechimmey connection details for existing 200 TPH boileralso with proposed duct routing

    It is not in Isgec scope of work. Kindly take care thesame from your end.

    Comments on Flue gas duct inlet opening detail at chimneyDrawing no: JB0963-50990100-SKT-0003