    Subject : Proposal of Dynamic Self-Balancing & Controls Solution

    Company : Abex Engineering Pte Ltd

    Product : FlowCon SME/SM

    Dynamic Self-Balancing Modulating Control Valve

    Prepared by : John Huang (9061 2332)

    Abex Engineering Pte Ltd

    Page 1 of 17

  • 7/28/2019 FlowCon PICV Write Out

    2/17

    Contents Page to Page

    1) Introduction to FlowCon International A/S 3 to 3

    2) Illustration of Hydronic Balancing

    a) Fractional losses 4 4

    b) Hydraulic Interactivity 4 4

    c) Control Valve Authority 5 5

    d) Pipe Pressure Drop Transition Chart 5 5

    e) Unbalanced System 6 6

    f) Balancing Procedure 7 7

    3) Needs & Types of Balancing System

    a) Variable Flow System(MBV) 8 9b) Variable Flow System(MBV & P Controller) 10 11

    4) FlowCon Dynamic Self-Balancing Control Valve 12 13

    in Variable Flow System

    5) FlowCon Dynamic Self-Balancing Control Valve

    a) Pressure Independent Working Principle 14 15

    b) SME/SM Selection and Flow Setting 16 16

    c) FlowCon Project References 17 17

    Page 2 of 17

  • 7/28/2019 FlowCon PICV Write Out

    3/17

    FlowCon International A/S

    FlowCon International A/S was originally founded in 1993 as a joint venture between the two dynamicbalancing market leaders in Europe and the USA. The fundamental purpose of this union was to

    combine these two companies' knowledge for joint development of dynamic valves.

    FlowCon International A/S was also appointed marketing and sales organization for the two owners

    on all external markets world-wide.

    Today FlowCon boasts more than 50 years of HVAC market experience. Our offices in North

    Carolina, Singapore, Dubai and Denmark handle all sales and marketing world-wide. Furthermore

    we act as the sales and marketing organization of Griswold Controls' products out of the USA.

    We are 100% devoted to dynamic flow regulation and pressure independent temperature control.

    We think balancing 24 hours a day and cannot suppress all of our exciting new ideas. FlowCon builds

    on innovation and shifts from idea to action very rapidly. Our goal is to offer a better product range

    and up-to-date Application know-how. Hence, we will be able, in cooperation with our distributors and

    other business partners, to offer the optimum solution for a well-balanced HVAC system.

    Page 3 of 17

  • 7/28/2019 FlowCon PICV Write Out

    4/17

    Illustration of Hydronic Balancing

    Figure 1: Frictional losses

    Assuming the above pipe was given a constant flow & Differential Pressure, we will be able to see

    the first hole will have the highest pressure and the last hole will have the lowest pressure. This is

    because of frictional losses along the pipeline, the water will rub against the pipe inner surface losing

    its energy/pressure to reach to the end.

    Figure 2 : Hydraulic interactivity

    If we close the first hole, we notice that the flow/pressure for rest of the holes is proportionally

    increased. This is because of hydraulic interactivity, closing one hole will interfere the rest.

    Closed

    P Increase

    Page 4 of 17

  • 7/28/2019 FlowCon PICV Write Out

    5/17

    Control Valve Authority

    Formula for Control Valve Authority;

    In general, the smaller the percentage of the calculated authority, the lousier the control characteristic.

    From the equation, we can see that most of the control valve is generally oversize due to the limited

    available Kvs values. In most cases, the control valve fully shut P is taken during partial load condition.

    Assuming a variable flow system with a pump head of 300kPa. Normally the pressure drop of thecontrol valve is 40kPa at design flow. At partial load condition the pipe frictions would transfer the 80%

    of the pump head to the control value based pressure drop transition chart (Figure 3).

    Then the calculated valve authority = 40/(300*0.8) =0.167

    The calculated valve authority is 0.167 which means the control valve lifting of 10% would give us more

    than the desired flow in the coil by 7 to 8 times. This means the low authority 0.167 would be too

    sensitive for the controller to handle.

    Piping Pressure Drop Transition Chart

    Figure 3 : P transition from pipe to control valve

    During 80% load condition, the pipe frictional losses will only be 20% as the control valve closes to

    50% of the flowrate. This means the 80%of the pump head pressure will transfer to the control valve

    during part-load condition.

    Variable dependent on flow and opening of all the

    other control Valves

    Constant based on the selected Kvs value of

    the valve which is limited to the increasing

    Reynard series; 1.0,1.6,2.5 and so on. Nothing

    in between.

    80%

    Flow (Q)

    Coil Emission %

    100%

    50%

    90%

    70%

    60%

    40%

    30%

    20%

    10%

    100%

    50%

    80%

    90%

    70%

    60%

    40%

    30%

    20%

    10%

    80%

    Flow

    Piping P %

    100%

    50%

    90%

    70%

    60%

    40%

    30%

    20%

    10%

    100%

    50%

    80%

    90%

    70%

    60%

    40%

    30%

    20%

    10%

    Page 5 of 17

  • 7/28/2019 FlowCon PICV Write Out

    6/17

    Unbalanced System

    Figure 4 : System without Hydronic balancing

    Figure 4 show a system which does not contain any form of hydronic balancing. The terminal units

    nearest to the pumps will have overflow and the furthest terminal units will have underflow

    because of pipe frictional losses.

    In most practice, the pump head pressure is oversized to in order to pump enough flow to the

    furthest unit. This practice will cause the control valve to work against a high close off pressure

    causing failures to actuators continuously. The worst condition of an unbalanced plant is that it

    will contribute a great amount of energy wastage.

    Common problems in unbalanced plant;

    a) Noise (hammering of control valves)

    b) Insufficient capacity(Need to run more chiller)

    c) Control problems(Control Valve Authority)

    d) Long start up time(high room temperature Oscillation)

    e) Energy wastage(Need to run more pump)

    High

    Differential

    Pressure

    Low

    Differential

    Pressure

    Overflow

    Underflow

    Page 6 of 17

  • 7/28/2019 FlowCon PICV Write Out

    7/17

    Balancing Procedure

    Partner Valve

    Figure 5 : Hydraulic Interactivity in Balancing

    The common practices of balancing method in the market is Proportional or Trial Error Method.

    Step required to do balancing:

    All Distribution pumps must be operating at constant speed and full load to ensure

    all terminal units has sufficient P.

    All control valves must be fully-opened.

    Strainers or any other congestion must be checked.

    Flushed and completely clean without air lock.

    Calibrated measurement instrument required.

    While the pumps are running at full load, the terminal units nearest to the pumps will have overflow.

    Balancing will begin by throttling the valves nearest to the pumps. By throttling the valves nearest to

    the pumps, the available P will be pushed to the further terminal units and they will obtain an

    increase of flow.

    After throttling down the furthest terminal units, noticeably there will be an increase of P in the

    terminal units nearest to the pumps. This procedure is repeated again and again resulting the

    balancing valves throttled down to 10% to 15% for units nearest to the pumps and 25% to 35% for the

    furthest units. The pumps are running at full load but the balancing valves are creating a huge amount

    of resistance to limit the excessive flow. Eventhough the terminal units may achieve 90% to its flow

    design, the balancing valves areinefficiently commissioned causing a great amount of energy

    wastage.

    Page 7 of 17

  • 7/28/2019 FlowCon PICV Write Out

    8/17

    Variable Flow System - Manual Balancing Valve

    Figure 6 : Variable Flow System(Manual Balancing Valve)

    Optimisation & Control Strategy

    Constant differential pressure of the system is maintained by modulating the speed of the pump. By

    sensing the pressure fluctuations(Index Loop) during different load conditions, the speed of the pump

    will be variable, hence the flow will be variable but the P is still maintained constant(DP Sensor).

    System Analysis Results

    The first benefit of this system is that the speed of the pump will react according to demand.Unfortunately, the drawback of this system is that the control valve authority varies because of having

    a variable flow in the distribution loop. By having poor control valve authority, the output of the controller

    hunts for the setpoint vigorously causing the room temperature to fluctuate continuously.

    During low load, the pressure drop from the pipes will transfer to the control valve (because control

    valve has the smallest orifice in the system when modulating). Channeling almost the entire pump

    head to the control valves will cause overflow. The desired characteristic for power output is not

    performing as expected due to overflows. Overflows will cause low T syndrome, therefore the

    chillers will have to work inefficiently again.

    Furthermore this system is sensitive to any hydraulic interactivities to any load conditions.

    Extra installations of partner balancing valves are essential to perform proportional rule balancing.Eventhough the system is balanced properly, the operation performance is still subjective to any

    movement of control valve.

    DP

    VSD

    Page 8 of 17

  • 7/28/2019 FlowCon PICV Write Out

    9/17

    Variable Flow System - Manual Balancing ValveSystem Analysis Breakdown

    Design Calulation

    - Traditional Calculation Required;

    Kvs of the valve, authority on the Control Valves, presetting of Manual Balancing Valves

    - Pump head calculation according to nominal f low

    System Operational cost

    - Very High pumping costs (Due to overflow phenomenon)

    - Heat losses and heat gains on the pipeline are High

    - Optimisation of pump head is Not Possible. Only if partner valves

    are implemented. Use propotional commissioning method.- Control valves - good authority and high efficiency cannot be achieved -

    higher room temperature oscillation(In case of modulation control)

    - Low T Syndrome - has no control on return temperature, lower

    heat-exchanger and cooling equipment efficiency

    - Re-commissioning is needed from time to time.

    Capital Cost

    - Capital cost - High (Control valve + Manual Balancing Valves + Commissioning)

    - Big partner valves are required

    - More valves therefore higher installation costs- Commissioning of the system required

    System Ready after Installation

    - Balancing at full load - Very Good, in part load only Acceptable

    - Commissioning of the system required in any cases

    - In part load, flow will be 25-40% higher than designed flow, bigger pump is needed

    - Pumping cost are far higher in part load operation

    Other

    - Closing pressure of terminal valves should be equal with the pump head at zeroflow, pressure is not relieved

    - Pump usually is oversized and overloaded to ensure the correct condition for the

    Manual Balancing Valve

    Page 9 of 17

  • 7/28/2019 FlowCon PICV Write Out

    10/17

    Variable Flow System

    - Manual Balancing Valve & P Controller

    Figure 7 : Variable Flow System(Manual Balancing Valve & P Controller)

    Optimisation & Control Strategy

    Constant differential pressure of the system is maintained by modulating the speed of the pump. By

    sensing the pressure fluctuations(Index Loop) during different load conditions, the speed of the pump

    will be variable, hence the flow will be variable but the P is still maintained constant(DP Sensor).

    Differential pressure sensor at the index loop should maintain the minimum specified P from the

    P Controller.

    System Analysis Results

    By adding P Controller to individual loop, balancing valve at the main & riser is not required as

    the membrane of the P Controller will react to the P fluctuations as a proportional controller making

    the loop independent of each other. There will not be overflow between loop, but slight overflow during

    part load condition from the manual balancing within the control loop. Good control valve authority

    can be easily achieved by ensuring the closing pressure of the control valve to be 50% more than

    the P Controller. Higher Pump head demand due to the extra pressure loss on the P Controller

    (Pressure drop dependent on the flow of the loop).

    Hydraulic Calculation is simplified by presetting valve on the control loop and sizing the authority on thecontrol valve.Commissioning of the system is not required only in case of a long control loop. Overall,

    as compare to the manual balancing valve, this is better system.

    DP

    VSD

    Page 10 of 17

  • 7/28/2019 FlowCon PICV Write Out

    11/17

    Variable Flow System

    - Manual Balancing Valve & P Controller

    System Analysis Breakdown

    Design Calulation- Traditional Calculation Required;

    Kvs of the valve, authority on the MCV,

    - Simplified hydraulic calculation (System Pressure sizing reduce to the

    individual controlled loop)

    - Presetting calculation within the controlled loop is needed

    - Pump head calculation according to nominal flow

    System Operational cost- Low pumping costs (overflow phenomenon with the controlled loop)

    - Heat losses and heat gains on the pipeline are small

    - Higher pump head demand - extra pressure loss on p controller required

    - Optimisation of the pump head is practical

    - Control valves- possible to achieve good authority and better efficiency

    - lower room temperature oscillation

    - Re-commissioning of the system is not required (only in case of long controlled loop)

    Capital Cost- Capital cost - High (Control valve + MBV)-Teminal & (p controller + MBV)-Loop

    - Expensive big p controller and manual balancing valve.

    - Most number of valves in a system therefore higher installation costs

    - Commissioning of the system not required (only in case of long controlled loop)- Variable speed pump is recommended (constant pressure characteristic)

    System Ready after Installation- Hydraulic regulation only in terminal units and the p on the control

    valve nearby is constant

    - Balancing at full and part load - Good

    - Commissioning not required only in case of long controlled loop

    - Variable speed pump ensures energy saving

    Other

    - Closing pressure of control valves(teminal) should be at least 50% of the pressuresetting on the P controller

    - Slight overflow during part load condition (manual balancing within the loop)

    - Pump usually oversized or overloaded to achieve normal authority on the Control Valve

    Page 11 of 17

  • 7/28/2019 FlowCon PICV Write Out

    12/17

    Variable Flow System

    - FlowCon Dynamic Self-Balancing Control Valve

    Figure 8 : Variable Flow System(FlowCon Dynamic Self-Balancing Control Valve )

    Optimisation & Control Strategy

    Constant differential pressure of the system is maintained by modulating the speed of the pump. By

    sensing the pressure fluctuations(Index Loop) during different load conditions, the speed of the pump

    will be variable, hence the flow will be variable but the P is still maintained constant(DP Sensor).

    Differential pressure sensor at the index loop should maintain the minimum specified P from the

    FlowCon Dynamic Self-Balancing Control Valve typically at 16/35kpa.

    System Analysis Results

    By applying the FlowCon PICV Method, all of the drawbacks of variable flow system have been solved.

    The diaphragm of the SME/SM will react to P fluctuations as a proportional controller. There

    is no overflow during part load condition; hence with unchanged characteristic output of the control valve,

    the control valve authority is considered as 1. Without overflow, high efficiency in pumps and

    chillers is ensure, eliminating low T syndrome, thus promoting comfort.

    There is no extra installation of partner valves and balancing needed because all the terminal units

    are pressure independent. Saving the installation, labour, commissioning, design calculations, time

    and energy costs. Therefore, all complications of the system are well taken care of by using FlowConDynamic Self-Balancing Control Valve.

    FlowCon PICV fulfilled three main key condition to ensure the lowest possible energy cost

    1 Design flow available in all terminal units at different load connditions

    2 Differential Prsssure Stability across all PICV

    3 Flow compatible between the production and distribution

    DP

    VSD

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    PICV

    Page 12 of 17

  • 7/28/2019 FlowCon PICV Write Out

    13/17

    Variable Flow System

    - FlowCon Dynamic Self-Balancing Control Valve

    System Analysis Breakdown

    Design / Sizing- Simple Calculation Method: neither Kvs, authority

    or hydraulic presetting calculation

    - Valve Authority 100% - pressure independent control

    - Simplified flow setting calculation according to heat demand

    - Pump head calculation according to min. p on the valve and

    system pressure loss at nominal flow

    System Operational cost- Lowest pumping costs (no overflow phenomenon)

    - Heat losses and heat gains on the pipeline are minimal

    - Lowest pump head demand

    - Optimisation of pump head is recommended

    - Control valves - 100% Authority and best efficiency - minimum

    room temperature oscillation

    - Re-commissioning of the system is not required

    Capital Cost- Capital cost - GOOD (only 2 Way PICV)-Terminal

    - Do not requried any balancing valve in the distribution system

    - The least number of valves in the system (least installation cost)

    - No Commissioning required- Variable speed drive is recommended (proportional characteristic)

    System Ready after Installation- Hydraulic regulation only in terminal units

    with 100% Valve Authority

    - Balancing at full and part load - Excellent

    - No Commissioning required

    - Variable speed pump ensures highest energy saving

    Other

    - High close off pressure at 600kPa- No overflow at all load

    - Simple and usual pump optimized

    - Minimal total energy consumption(Production & Distribution)

    - Maximum Energy Saving

    Page 13 of 17

  • 7/28/2019 FlowCon PICV Write Out

    14/17

    FlowCon Dynamic Self-Balancing Control ValvePressure Independent Working Principle

    Figure 9 : Internal Structure of FlowCon SM

    Figure 10 : Performance Curve of FlowCon SM

    CONTROL VALVE

    PCONTROLLER

    Movement of the plug controls the

    amount of water flowing thru the

    valve regardless of changes in P1

    and P2.

    Water enters via a small passage and

    builds up the pressure at P1, which

    pushes the diaphragm upwards,

    closing the outlet orifice area hence

    keepingP at a constant level

    Page 14 of 17

  • 7/28/2019 FlowCon PICV Write Out

    15/17

    FlowCon Dynamic Self-Balancing Control ValvePressure Independent Working Principle

    Figure 11 : Diaphragm position at higher Load Figure 12 : Diaphragm position at lower Load

    The diaphragm position will vary whenever the P across the control valve changes (due to change in

    the incoming pressure and movement of other control valves) the diaphragm will move to a new

    position thus controlling the outlet opening orifice which brings a new equilibrium and keeps the

    P at a constant level. Refer to Fig 12 for the relationship between the outlet opening and P.

    For example, during a low load condition, the diaphragm senses a pressure build up from the inlet tube

    below the diaphragm and then it will command the diaphagm to move upward to create a smalleroutlet orifice so that there will be no excessive flow going through. In short, flow will vary only when the

    control valve modulated and the diaphragm will maintain a constant P thus a constant flow regardless

    of pressure changes. Refer to Fig 9 for the performance of the valve.

    Figure 13 : Diaphragm position vs P Changes

    Position varies to keep

    P at a constant level

    Differential ressure increase

    P Controller= P2-P3

    Opening outlet orifice %

    0 35kPa 400kPa

    100%

    50%

    220kPa

    Page 15 of 17

  • 7/28/2019 FlowCon PICV Write Out

    16/17

    FlowCon Dynamic Self-Balancing Control ValveSME/SM Selection & Flow Setting

    SME(15-40mm) SM(50-150mm)

    Flow Setting on Valve Cartridge Flow Setting on Digital Actuator

    The selection for the valve only required two parameters(Design flowrate & Pipe size connection).

    For SME, simply select the f low from the chart and adjust on the cartridge from the valve. In-event of

    any flow changes, flow can be easily change without tampering the pipe or insulation.

    For SM, simply select the valve model(SM3.1) on the actuator and all the available flowrate will be shown

    for selection. SM actuator also include feature like high IP rating at 54, information in the display such

    as supply signal(2-10V), feedback signal(2-10V), current flow rate(L/S), battery condition and alarm. It

    also come with password activation and fail safe feature.

    Lastly, Kv value and authority of the valve does not need any calculation due to the pressure independent

    characteristic which ensure 100% authority at all setting and P. With this, it not just increase the

    control quality and precision, it also increase the flexibility of the system. The easy setting for FlowCon

    makes late changes in the designs or subsequent system retrofits a breeze to implement in the system.

    Page 16 of 17

  • 7/28/2019 FlowCon PICV Write Out

    17/17

    FlowCon Dynamic Self-Balancing Control ValveFlowCon Project References

    HotelCNA GROUPHyatt Hotel (Heat Recovery

    System)

    Singapore

    Office BuildingBECA CARTEROne Marina Boulevard (NTUC

    Centre)

    Singapore

    Office BuildingPARSONS BRINCKERHOFFSingapore Land TowerSingapore

    Office BuildingJOHNSON CONTROLGreat Eastern @ ChangiSingapore

    LabG-Energy GlobalShell Bukom (Central Lab)Singapore

    Shopping CentreTHAM & WONGSembawang Shopping CentreSingapore

    Integrated ResortPARSONS BRINCKERHOFFMarina Bay Sand IRSingapore

    Country Project name Consultant Kind of building

    Singapore SGX Center PARSONS BRINCKERHOFF Commercial

    Building

    Singapore May Bank Tower ALPHA CONSULTING Commercial

    Building

    Singapore Great Eastern Centre SQUIRE MECH Commercial

    Building

    Singapore Nayang Academy of Fine Arts SQUIRE MECH School

    Singapore China Square Parcel 'G' Shop

    Houses

    SQUIRE MECH Shopping Centre