10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/38
First Revision No. 21NFPA 101A2016 [ Global Input ]
In Figure 7.5, revise Worksheet 7.5.4A in the "1 Story" row, Refuge Requirement (Sc), bychanging the entry 15 to 13.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Aug 18 11:30:25 EDT 2016
Committee Statement
CommitteeStatement:
Currently, a new singlestory Type V(111) biulding with no deficiencies will not pass theFSES because it fails under the Refuge Requirement safety parameter. If the RefugeRequirement safety parameter is reduced from 15 to 13, it will pass. A new building, built inaccordance with NFPA 101, should pass the FSES.
ResponseMessage:
Page 1 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/38
First Revision No. 3NFPA 101A2016 [ Section No. 1.3.1 ]
1.3.1* This guide consists of a number of alternative approaches to life safety applicable to new andexisting buildings . Each chapter is a different system independent of the others and is to beused in conjunction with the 2015 2018 edition of NFPA 101.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 11:28:22 EDT 2016
Committee Statement
CommitteeStatement:
The FR clarifies that NFPA 101A applies to new and existing buildings, and alsoupdates the referenced edition year of NFPA 101.
ResponseMessage:
Public Input No. 9NFPA 101A2016 [Section No. 1.3.1]
Page 2 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 3/38
First Revision No. 4NFPA 101A2016 [ Section No. 1.3.2 ]
1.3.2 This edition of NFPA 101A contains alternative approaches that are tied to NFPA 101. Each ofthese systems approaches, where approved by the AHJ, is recognized by in Annex A of theLife Safety Code, in its Annex A, as a method that can be used to assist the authority havingjurisdiction in determining equivalent compliance with various chapters of the Code.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 11:34:37 EDT 2016
Committee Statement
Committee Statement: The revisions clarify the intent of the paragraph.Response Message:
Public Input No. 47NFPA 101A2016 [Section No. 1.3.2]
Page 3 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 4/38
First Revision No. 19NFPA 101A2016 [ New Section after 1.3.4 ]
1.3.5* Previously approved fire safety evaluation systems (FSESs) are permitted to be continued inuse where permitted by the authority having jurisdiction.
Supplemental Information
File Name Description101A_FR19_Attachment.docx New A.1.3.5
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Aug 18 10:00:45 EDT 2016
Committee Statement
CommitteeStatement:
The intent of the FR is explained by the proposed A.1.3.5, as follows: The intent of thiscriterion is to allow previously approved FSESs, which demonstrated compliance withprevious editions of NFPA 101, to be continued in use without reevaluation subject toapproval of the AHJ. Where modification of the facility would be impractical in the judgmentof the AHJ, e.g., construction type issues, a previous edition of the FSES in NFPA 101Acould be utilized to demonstrate that a reasonable degree of safety is provided. Subject tothe approval of the AHJ, this could apply to existing buildings, including spaces involvingrenovation, modification, or reconstruction. See 4.6.5 of NFPA 101 for additional informationregarding modifications of requirements for existing buildings.
ResponseMessage:
Public Input No. 51NFPA 101A2016 [New Section after 4.1.3]
Public Input No. 48NFPA 101A2016 [New Section after 4.7.7]
Page 4 of 43
A.1.3.5 The intent of this criterion is to allow previously approved FSESs, which demonstrated compliance with previous editions of NFPA 101, to be continued in use without re‐evaluation subject to approval of the AHJ. Where modification of the facility would be impractical in the judgment of the AHJ (e.g., construction type issues), a previous edition of the FSES in NFPA 101A could be utilized to demonstrate that a reasonable degree of safety is provided. Subject to the approval of the AHJ, this could apply to existing buildings, including spaces involving renovation, modification, or reconstruction. See 4.6.5 of NFPA 101 for additional information regarding modifications of requirements for existing buildings.
Page 5 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 5/38
First Revision No. 24NFPA 101A2016 [ Section No. 2.2 ]
2.2 NFPA Publications.National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 021697471.
NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 2019 edition.
NFPA 13D, Standard for the Installation of Sprinkler Systems in One and TwoFamilyDwellings and Manufactured Homes, 2013 2019 edition.
NFPA 13R, Standard for the Installation of Sprinkler Systems in LowRise ResidentialOccupancies, 2013 2019 edition.
NFPA 72®, National Fire Alarm and Signaling Code, 2013 2019 edition.
NFPA 90A, Standard for the Installation of AirConditioning and Ventilating Systems, 2015 2018edition.
NFPA 92, Standard for Smoke Control Systems, 2012 2018 edition.
NFPA 101®, Life Safety Code®, 2015 2018 edition.
NFPA 204, Standard for Smoke and Heat Venting, 2012 2018 edition.
NFPA 220, Standard on Types of Building Construction, 2015 2018 edition.
NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2012 2017 edition.
NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies, 2012 2017 edition.
NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution ofTextile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, 2011 2015 edition.
NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and CeilingInterior Finish to Room Fire Growth, 2011 2015 edition.
NFPA 551, Guide for the Evaluation of Fire Risk Assessments, 2013 2016 edition.
NFPA 5000®, Building Construction and Safety Code®, 2015 2018 edition.
NFPA Fire Protection Handbook, 20th edition.
NFPA SFPE Handbook of Fire Protection Engineering , 4th edition.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Mon Aug 29 14:58:34 EDT 2016
Committee Statement
Committee Statement: Referenced publication updates.Response Message:
Page 6 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 6/38
First Revision No. 5NFPA 101A2016 [ Section No. 2.3.1 ]
2.3.1 ASTM Publications.ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 194282959, www.astm.org.
ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials,2013 2015b .
ASTM E119, Standard Test Methods for Fire Tests of Building Construction and Materials,2012a 2016 .
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 11:43:12 EDT 2016
Committee Statement
Committee Statement: Referenced publication updates.Response Message:
Public Input No. 1NFPA 101A2016 [Section No. 2.3.1]
Page 7 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 7/38
First Revision No. 25NFPA 101A2016 [ Section No. 2.3.2 ]
2.3.2 SFPE Publications.Society of Fire Protection Engineers, 7315 Wisconsin Avenue, SFPE, 9711 Washington Blvd.,Suite 620E 380 , BethesdaGaithersburg , MD 20814 20878 .
SFPE Engineering Guide to Fire Risk Assessment.
SFPE Handbook of Fire Protection Engineering , 5th edition, 2016.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Mon Aug 29 15:13:12 EDT 2016
Committee Statement
Committee Statement: Referenced publication update.Response Message:
Page 8 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 8/38
First Revision No. 6NFPA 101A2016 [ Section No. 2.3.3 ]
2.3.3 UL Publications.Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 600622096, www.ul.com.
ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008,Revised revised 2010 2013 .
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 11:45:17 EDT 2016
Committee Statement
Committee Statement: Referenced publication update.Response Message:
Public Input No. 49NFPA 101A2016 [Section No. 2.3.3]
Page 9 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 9/38
First Revision No. 26NFPA 101A2016 [ Section No. 2.4 ]
2.4 References for Extracts in Advisory Sections.NFPA 101, Life Safety Code, 2018 edition.
NFPA 5000®, Building Construction and Safety Code®, 2015 edition.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Mon Aug 29 15:18:43 EDT 2016
Committee Statement
Committee Statement: Referenced publication update.Response Message:
Page 10 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 10/38
First Revision No. 22NFPA 101A2016 [ New Section after 3.3 ]
3.3.1 Modification.The reconfiguration of any space; the addition or elimination of any door or window; theaddition or elimination of loadbearing elements; the reconfiguration or extension of anysystem; or the installation of any additional equipment. [ 101, 2018]
3.3.2 Reconstruction.The reconfiguration of a space that affects an exit or a corridor shared by more than oneoccupant space; or the reconfiguration of a space such that the rehabilitation work area is notpermitted to be occupied because existing means of egress and fire protection systems, ortheir equivalent, are not in place or continuously maintained. [ 101, 2018]
3.3.3 Renovation.The replacementinkind, strengthening, or upgrading of building elements, materials,equipment, or fixtures that does not result in a reconfiguration of the building spaces within. [101, 2018]
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Aug 18 11:49:04 EDT 2016
Committee Statement
CommitteeStatement:
The FR extracts selected definitions from NFPA 101 to NFPA 101A. However, it is notedthat 101A provides a general reference to Section 3.3 of 101 for all other general definitions.The inclusion of these selected definitions should be reconsidered at the public commentstage.
ResponseMessage:
Page 11 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 11/38
First Revision No. 7NFPA 101A2016 [ Section No. 4.3.2.1 ]
4.3.2.1 A story that is not subdivided by horizontal exits or smoke barriers is considered a singlezone.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 13:59:32 EDT 2016
Committee Statement
CommitteeStatement:
The statement is identical existing in fire/smoke/zone definition stated in section 4.3.1.It is recommended to be deleted to avoid repetition.
ResponseMessage:
Public Input No. 20NFPA 101A2016 [Section No. 4.3.2.1]
Page 12 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 12/38
First Revision No. 1NFPA 101A2016 [ Section No. 4.3.2.5 ]
Page 13 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 13/38
4.3.2.4
Page 14 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 14/38
Most health care facilities have repetitive arrangements so that a complete picture can bedeveloped by evaluating typical zones until all combinations are evaluated. The zones selectedshould include the following:
(1) Each type of patient zone having a different type of mobility, density, or attendant ratio, asspecified in Worksheet 4.7.2
(2) Each zone that represents a significantly different type of construction, finish, or protectionsystem
(3) Zones containing special medical treatment or support activities (e.g., operating suites,intensive care units, laboratories)
(4) Zones not involving housing, treatment, or customary access for four or more inpatientssimultaneously who are incapable of selfpreservation; such zones should be evaluated asfollows:
(a) Any zone, whether or not used for patient egress, shall be permitted to be evaluatedon the same basis as a patient use zone. In such case cases , the value of factor F inWorksheet 4.7.3 shall be assigned the value of factor L (“Zone Location”) fromWorksheet 4.7.2. In such cases, Safety Parameter 10, “Emergency MovementRoutes,” from Worksheet 4.7.6 shall be graded “deficient” if the exit capacity is lessthan that prescribed for the actual occupancy of the space and “<2 routes” if less than75 percent of the prescribed exit capacity is present.
(b) If the zone is separated by 2hour firerated construction from all patient use zones,( including any members that bear the load of a patient use zone) , and if anycommunicating openings through the 2hour firerated construction are protected by 11∕2hour fire protection–rated fire doors, the zone shall be permitted to be excluded fromevaluation. In such case cases , that space shall conform with the portion of the LifeSafety Code appropriate to its use. In addition, appropriate charges under SafetyParameter 8, “Hazardous Areas,” in Worksheet 4.7.6 shall be charged against otherzones in the facility.
(c) Evaluation of any unoccupied story or stories located above the highest floor used forhealth care occupancy is not required, provided each such unoccupied story meets theconstruction requirements of 18.1.6 ( of NFPA 101) for new buildings or 19.1.6 ( ofNFPA 101) for existing buildings, or if each unoccupied story is protected byautomatic sprinklers.
(5) Patient sleeping rooms or suites exceeding 1000 ft2 (92.9 m2) of floor area should beevaluated as follows:
(a) If the room or suite has a single exit access door, it should be evaluated as a singledeadend zone.
(b) A patient sleeping room or suite of sleeping rooms exceeding the 5000 ft2 (460 m2)limitation of 19.2.5.7.2.3(A) ( of NFPA 101) should be evaluated as a separate zonethat is not a suite. Safety parameters 4 and 5 from Worksheet 4.7.6 should be scoredas 0 for this zone.
(c) A patient sleeping room or suite of sleeping rooms exceeding the 7500 ft2 (700 m2)limitation of 18.2.5.7.2.3(B) or 19.2.5.7.2.3(B) ( of NFPA 101) should be evaluated asa separate zone that is not a suite. Safety parameters 4 and 5 from Worksheet 4.7.6should be scored as 0 for this zone.
(d) A patient sleeping room or suite of sleeping rooms exceeding the 10,000 ft2 (930 m2)limitation of 18.2.5.7.2.3(C) or 19.2.5.7.2.3(C) ( of NFPA 101) should be evaluated asa separate zone that is not a suite. Safety parameters 4 and 5 from Worksheet 4.7.6should be scored as 0 for this zone.
(6) Patient care nonsleeping rooms or suites exceeding 2500 ft2 (230 m2) of floor area shouldbe evaluated as follows:
(a) If the room or suite has a single exit access door, it should be evaluated as a singledeadend zone.
Page 15 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 15/38
(b) A patient care nonsleeping room or suite of nonsleeping rooms exceeding the10,000 ft2 (930 m2) limitation of 19.2.5.7.3.2 ( of NFPA 101) should be evaluated as aseparate zone that is not a suite. Safety parameters 4 and 5 from Worksheet 4.7.6should be scored as 0 for this zone.
(c) A patient care nonsleeping room or suite of nonsleeping rooms exceeding the12,500 ft2 (1160 m2) limitation of 18.2.5.7.3.2(A) or 19.2.5.7.3.2(A) ( of NFPA 101)should be evaluated as a separate zone that is not a suite. Safety parameters 4 and 5from Worksheet 4.7.6 should be scored as 0 for this zone.
(d) A patient care nonsleeping room or suite of nonsleeping rooms exceeding the15,000 ft2 (1390 m2) limitation of 18.2.5.7.3.2(B) or 19.2.5.7.3.2(B) ( of NFPA 101)should be evaluated as a separate zone that is not a suite. Safety parameters 4 and 5from Worksheet 4.7.6 should be scored as 0 for this zone.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 09:52:36 EDT 2016
Committee Statement
CommitteeStatement:
The FR adds guidance on the evaluation of oversized suites as recommended by the FireProtection Research Foundation report, "Validation of the Fire Safety Evaluation System(FSES) in the 2013 Edition of NFPA 101A, FPRF Final Report."
ResponseMessage:
Public Input No. 54NFPA 101A2016 [Section No. 4.3.2.5]
Page 16 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 16/38
First Revision No. 8NFPA 101A2016 [ Section No. 4.5.3.2 ]
4.5.3.2 Story Factor.The measured zone’s location shall be considered to be on the first story if the story has directaccess to the exterior at or within less than onehalf story height above or below grade. If abuilding is on a sloping grade, each story that has such exterior access shall be considered asa first story for the purpose of measuring fire zones on those stories. The measured zone shallbe considered to be on the second to third story range and the fourth to sixth story range, basedon the height of the zone above the nearest atgrade story. The zone shall be considered to beabove the sixth story if it is more than six stories above the nearest atgrade story. The riskfactor value for zones in basements is the same as for zones at or above the seventh story.The problems involved in emergency internal access, in fire fighting and rescue, and in theinability to make external attack in basements are approximately equivalent to those in theupper stories of buildings.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 14:01:47 EDT 2016
Committee Statement
CommitteeStatement:
There is no need to specify the type of zone (fire, smoke, or fire/smoke). The term'zone' is used in the first sentence.
ResponseMessage:
Public Input No. 21NFPA 101A2016 [Section No. 4.5.3.2]
Page 17 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 17/38
First Revision No. 2NFPA 101A2016 [ Section No. 4.6.2 ]
4.6.2 Interior Finish (Corridor and Exits).The classification wall and ceiling of interior finish materials shall be in accordance withSection 10.2 (NFPA 101). The flamespread classification shall be based on the mostcombustible surface after deleting trim. No allowance is made in the safety parameter valuesfor interior finish materials that fail to be classified as a minimum of Class C. It is notanticipated that such materials will be used in health care facilities. In the rare case that suchhigh flamespread interior finish materials are involved, an individual fire hazard assessmentoutside the capability of this evaluation system will be required. Interior wall and ceiling finishmaterials tested in accordance with NFPA 265 or NFPA 286, as permitted by Section 10.2(NFPA 101), and meeting the criteria established in Section 10.2 (NFPA 101) for those teststandards, shall be scored as Class A interior finish materials (flame spread ≤25). Newlyinstalled textile wall and ceiling coverings and expanded vinyl wall and ceiling coveringmaterials shall comply with 10.2.4 ( NFPA 101 ).
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 10:26:20 EDT 2016
Committee Statement
CommitteeStatement:
This was an issue identified in the Validation of the Fire Safety Evaluation System (FSES)in the 2013 Edition of NFPA 101A FPRF Final Report . This type of wall and ceilingcovering was not addressed in the NFPA 101 change that limited the use of these types ofClass A interior finish in non sprinkler protected facilities. The FR also incorporates therecommendation of PI23.
ResponseMessage:
Public Input No. 53NFPA 101A2016 [Section No. 4.6.2]
Public Input No. 23NFPA 101A2016 [Section No. 4.6.2]
Page 18 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 18/38
First Revision No. 9NFPA 101A2016 [ Section No. 4.6.6.3 ]
4.6.6.3 Since Because deadend corridors and single emergency movement routes (see 4.6.10) eachconfine the occupants of a fire zone to a single means of egress, the effect of these twofactors on the parameter value is not cumulative. As indicated by Note b to Worksheet 4.7.6,the parameter value for deadend corridors is to be 0 instead of either −2, −4, or −6 in thespecial case where a value of −8 is assessed under 4.6.10 for single emergency movementroutes.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 14:05:06 EDT 2016
Committee Statement
Committee Statement: There is no need to specify the type of zone (fire, smoke, or fire/smoke).Response Message:
Public Input No. 22NFPA 101A2016 [Section No. 4.6.6.3]
Page 19 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 19/38
First Revision No. 10NFPA 101A2016 [ New Section after 4.6.7.3 ]
4.6.7.4 Unenclosed vertical openings shall be considered enclosed if they are in accordance with18.3.1 or 19.3.1 ( NFPA 101 ).
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 14:14:07 EDT 2016
Committee Statement
CommitteeStatement:
The FR captures the vertical opening protection criteria permitted for health careoccupancies, in addition to those specified in PI4.
ResponseMessage:
Public Input No. 4NFPA 101A2016 [New Section after 4.6.7.3]
Page 20 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 20/38
First Revision No. 11NFPA 101A2016 [ Section No. 4.6.8.1 ]
4.6.8.1 In assessing the parameter value for hazardous areas, only one value shall be chosen. It shallbe the most severe value corresponding to the deficiencies present. A double deficiency canexist only where the hazard is severe and the space is not sprinkler protected. Doubleprotection consists of both a firerated enclosure and automatic sprinkler protection of thehazardous area. If both of these protections are lacking in a severe hazardous location, thedouble deficiency value shall be chosen. If double deficiencies exist both within the zone andoutside the zone, the higher lesser value (i.e., −11) for the condition inside the zone shall bechosen. The values are not cumulative, regardless of how many hazardous areas are present.Table 4.6.8.1 provides a matrix to be used to determine degree of deficiency to be assessed.
Table 4.6.8.1 Hazardous Areas Deficiencies
Hazard
Protection Severe Not Severe
Hazard
Protection Severe Not Severe
None Double SingleFire resistance–rated enclosures Single NoneAutomatic sprinklers and smoke partitions Single NoneAutomatic sprinklers and fire resistance–rated enclosures None None
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 14:26:24 EDT 2016
Committee Statement
Committee Statement: The safety parameter point score (11) is the lesser value, not the higher.Response Message:
Public Input No. 24NFPA 101A2016 [Section No. 4.6.8.1]
Page 21 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 21/38
First Revision No. 12NFPA 101A2016 [ Section No. 4.6.12.2 ]
4.6.12.2 Corridor Only.Smoke detectors are installed throughout the corridors of the zone involved in accordance withSection 9.6 ( NFPA 101 ) .
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 14:31:28 EDT 2016
Committee Statement
CommitteeStatement:
Subsection 4.6.12 states that smoke detectors must be installed in accordance withSection 9.6 (NFPA 101). The additional reference in 4.6.12.2 is unnecessary.
ResponseMessage:
Public Input No. 26NFPA 101A2016 [Section No. 4.6.12.2]
Page 22 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 22/38
First Revision No. 20NFPA 101A2016 [ Section No. 4.7 ]
4.7 Worksheets for Evaluating Fire/Smoke Zones.
The worksheets for evaluating fire/smoke zones use a 10step process found in Figure 4.7.Page 23 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 23/38
The worksheets for evaluating fire/smoke zones use a 10step process found in Figure 4.7.
Figure 4.7 Worksheets for Evaluating Fire/Smoke Zones.
DELETED
Page 24 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 24/38
DELETED
Page 25 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 25/38
DELETED
Page 26 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 26/38
4.7.1 Step 1 — Complete the Cover Sheet Using Worksheet 4.7.1.
See Figure 4.7.
4.7.2 Step 2 — Determine Occupancy Risk Parameter Factors Using Worksheet 4.7.2.
For each risk parameter in Worksheet 4.7.2, select and circle the appropriate risk factor value.Choose only one value for each of the five risk parameters.
4.7.3 Step 3 — Compute Occupancy Risk Factor F Using Worksheet 4.7.3.
The following steps should be taken:
(1) Transfer the circled risk factor values from Worksheet 4.7.2 to the corresponding blocks inWorksheet 4.7.3.
(2) Compute occupancy risk factor F by multiplying the risk factor values as indicated inWorksheet 4.7.3.
DELETED
Page 27 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 27/38
4.7.4 Step 4 — Compute Adjusted Occupancy Risk Factor R Using Worksheet 4.7.4 orWorksheet 4.7.5.
The following steps should be taken:
(1) If building is classified as “new,” use Worksheet 4.7.4. If building is classified as “existing,”use Worksheet 4.7.5.
(2) Transfer the value of F from Worksheet 4.7.3 to Worksheet 4.7.4 or Worksheet 4.7.5, asappropriate. Calculate R.
(3) Transfer R to the block labeled R in Worksheet 4.7.9.
4.7.5 Step 5 — Determine Safety Parameter Values Using Worksheet 4.7.6.
Select and circle the safety value for each safety parameter in Worksheet 4.7.6 that bestdescribes the conditions in the zone. Choose only one value for each of the 13 parameters. Iftwo or more values appear to apply, choose the one with the lowest point value.
4.7.6 Step 6 — Compute Individual Safety Evaluations Using Worksheet 4.7.7.
The following steps should be taken:
(1) Transfer each of the 13 circled safety parameter values from Worksheet 4.7.6 to everyavailable block in the line with the corresponding safety parameter in Worksheet 4.7.7. ForSafety Parameter 13, the value entered in the “People Movement Safety” column isrecorded in Worksheet 4.7.7 as onehalf the corresponding value circled in Worksheet4.7.6.
(2) Add each of the four columns, keeping in mind that any negative numbers need to bededucted.
(3) Transfer the resulting total values for S1, S2, S3, and S4 to the corresponding blocks inWorksheet 4.7.9.
4.7.7 Step 7 — Determine Mandatory Safety Requirements Values Using Worksheet 4.7.8A,4.7.8B, or 4.7.8C as Appropriate.
The following steps should be taken:
(1) Using the classification of the building (i.e., new or existing) and the story where the zoneis located, circle the appropriate value in each of the three columns in Worksheet 4.7.8A,4.7.8B, or 4.7.8C.
(2) Transfer the three circled values from Worksheet 4.7.8A, 4.7.8B, or 4.7.8C to the blocksmarked Sa, Sb, and Sc in Worksheet 4.7.9.
(3) The mandatory safety requirements values for basements are based on the distance of thebasement level from the closest level of discharge. (See also 4.6.1.2 and 4.6.1.3.)
4.7.8 Step 8 — Determine Zone Fire Safety Equivalency Using Worksheet 4.7.9.
The following steps should be taken:
(1) Perform the subtractions indicated in Worksheet 4.7.9. Enter the differences in theappropriate answer blocks.
(2) For each row, check “yes” if the value in the answer block is zero (0) or greater. Check “no”if the value in the answer block is a negative number.
4.7.9 Step 9 — Evaluate Other Considerations Not Previously Addressed Using Worksheet4.7.10.
The equivalency covered by Worksheets 4.7.2 through 4.7.9 includes the majority of theconsiderations covered by the Life Safety Code. Some considerations are not evaluated by thismethod and must be considered separately. These additional considerations are covered inWorksheet 4.7.10, Facility Fire Safety Requirements Worksheet. Complete one copy of thisseparate worksheet for each facility.
Page 28 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 28/38
4.7.10 Step 10 — Determine Equivalency Conclusion.
Conclude whether the level of life safety is at least equivalent to that prescribed by the LifeSafety Code using Worksheet 4.7.11, Conclusions. Worksheet 4.7.11 combines the zone firesafety equivalency evaluation of Worksheet 4.7.9 and the additional considerations ofWorksheet 4.7.10.
Supplemental Information
File Name Description101A_FR20_Attachment.pdf Fig. 4.7 revisions
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Aug 18 10:56:34 EDT 2016
Committee Statement
Committee Statement: Revise Fig. 4.7 as shown in the attachment. The revisions respond to PI28.Response Message:
Public Input No. 28NFPA 101A2016 [Section No. 4.7 [Excluding any SubSections]]
Page 29 of 43
Page 30 of 43
Page 31 of 43
Page 32 of 43
Page 33 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 29/38
First Revision No. 13NFPA 101A2016 [ Section No. 5.4.2.1.2 ]
5.4.2.1.2 Step 2 — Determine the Level of Hazard.
A hazardous area is classed as severe if it is an area requiring both automatic sprinklerprotection and firerated enclosure per 22.3.2.1 (and ,22.3.2.3, 22.3.5.2) or , 23.3.2.1, or23.3.5.2 (NFPA 101).
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 15:31:13 EDT 2016
Committee Statement
CommitteeStatement:
The FR includes all references which state that both automatic sprinkler protectionand a firerated enclosure are mandatory.
ResponseMessage:
Public Input No. 31NFPA 101A2016 [Section No. 5.4.2.1.2]
Page 34 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 30/38
First Revision No. 14NFPA 101A2016 [ Section No. 7.1 ]
7.1 Introduction General .7.1.1 This chapter is part of an NFPA guide and, therefore, is not mandatory. The term shall in thischapter is used to indicate that if the provisions of the chapter are applied, the proceduresmandated are to be followed to ensure the effectiveness of the evaluation system.
7.1.2 Chapter 33 (NFPA 101) defines three levels of evacuation capability for residents (with staffassistance): prompt, slow, and impractical. Chapter 33 (NFPA 101) also prescribes the firesafety protection requirements for each level of evacuation capability. This chapter describes aprocedure for determining whether a combination of fire safety features in a board and carefacility provides a level of safety equivalent to that provided by explicit conformance toChapters 32 and 33 (NFPA 101). The definition of evacuation capability is given in Section 3.3(NFPA 101), and one procedure for determining evacuation capability is presented in Chapter 6of this document.
7.1.3 Subsystems are provided as follows:
(1) Section 7.2 — Evaluating the fire safety protection in a small facility
(2) Section 7.4 — Evaluating the fire safety protection in a large facility
(3) Section 7.6 — Evaluating the suitability of an apartment building to house a board and careoccupancy
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 15:50:29 EDT 2016
Committee Statement
Committee Statement: The FR is for consistency with the remainder of the document.Response Message:
Public Input No. 43NFPA 101A2016 [Section No. 7.1]
Page 35 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 31/38
First Revision No. 15NFPA 101A2016 [ Section No. 7.5 [Excluding any Sub
Sections] ]
Page 36 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 32/38
A large facility normally is one that has a capacity for more than 16 residents. For each suchfacility to be evaluated, the sevenstep process in Figure 7.5 should be followed whenevaluating fire safety.
Figure 7.5 Worksheets for Evaluating Fire Safety in a Large Facility.
DELETED
Page 37 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 33/38
DELETED
Page 38 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 34/38
DELETED
Page 39 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 35/38
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 15:55:01 EDT 2016
Committee Statement
DELETED
Page 40 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 36/38
CommitteeStatement:
The TC reaffirms the action taken by TIA Log No. 1166, which revised Worksheet 7.5.4.A.It is noted this FR shows no change because the TIA was incorporated into NFPA 101A.
ResponseMessage:
Public Input No. 2NFPA 101A2016 [Section No. 7.5 [Excluding any SubSections]]
First Revision No. 16NFPA 101A2016 [ Section No. 8.1 ]
8.1 Introduction General .8.1.1 This chapter is part of an NFPA guide and, therefore, is not mandatory. The term shall in thischapter is used to indicate that if the provisions of the chapter are applied, the proceduresmandated are to be followed to ensure the effectiveness of the evaluation system.
8.1.2 The Fire Safety Evaluation System (FSES) is a measuring system. It compares the level ofsafety provided by an arrangement of safeguards that differ from those specified in NFPA 101to the level of safety provided in a building that conforms exactly with the details of the Code.
8.1.3 This chapter is provided to assist in completion of Figure 8.6, Worksheets for Evaluating FireSafety in Business Occupancies. The stepbystep instructions for completion appear in thetext of Section 8.6. This chapter provides expanded discussion and definition of the variousitems in the worksheet to assist the user when questions of definitions or interpretation arise.The chapter is organized to follow the format of the worksheet progressively.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 15:57:02 EDT 2016
Committee Statement
Committee Statement: The FR is for consistency with the remainder of the document.Response Message:
Public Input No. 44NFPA 101A2016 [Section No. 8.1]
Page 41 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 37/38
First Revision No. 17NFPA 101A2016 [ Section No. 9.1 ]
9.1 Introduction General .9.1.1 This chapter is part of an NFPA guide and, therefore, is not mandatory. The term shall in thischapter is used to indicate that if the provisions of the chapter are applied, the proceduresmandated are to be followed to ensure the effectiveness of the evaluation system.
9.1.2 The Fire Safety Evaluation System (FSES) is a measuring system. It compares the level ofsafety provided by an arrangement of safeguards that differ from those specified in NFPA 101to the level of safety provided in a building that conforms exactly with the details of the Code.
9.1.3 This Fire Safety Evaluation System FSES is designed and intended to be used for evaluatingeducational occupancies (as defined in NFPA 101 as applying through the 12th grade). It is notdesigned or intended to be used for evaluating day care occupancies, assembly occupancies,or other noneducational noneducational occupancy uses of educational facilities. Neither is itdesigned or intended to be used for evaluating educational occupancies located in highrisebuildings.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Aug 16 16:08:57 EDT 2016
Committee Statement
Committee Statement: The FR is for consistency with the remainder of the document.Response Message:
Public Input No. 45NFPA 101A2016 [Section No. 9.1]
Page 42 of 43
10/5/2016 National Fire Protection Association Report
http://submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 38/38
First Revision No. 27NFPA 101A2016 [ Section No. B.1.1 ]
B.1.1 NFPA Publications.National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 021697471.
NFPA 101®, Life Safety Code®, 2015 2018 edition.
Submitter Information Verification
Submitter Full Name:Gregory HarringtonOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Mon Aug 29 15:30:21 EDT 2016
Committee Statement
Committee Statement: Referenced publication update.Response Message: