Fire Sprinkler Earthquake Protection – Sway Bracing
![Page 2: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/2.jpg)
Abstract
• Earthquake sway bracing for fire sprinklers will become normative in the EN12845 Annex
• Building structures are protected against earthquakes and so should the life safety system of fire sprinklers
![Page 3: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/3.jpg)
Abstract
• Fire sprinkler protection provided thru:– Joint flexibility– Proper clearances– Sway Bracing
• Sway bracing consists of:– Lateral– Longitudinal– 4Way
![Page 4: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/4.jpg)
Abstract
• Brace design is based on the amount of sprinkler pipe weight within a zone of influence (ZOI) for a given horizontal seismic load (“g” force)– Requires calculations and submittals to
AHJ’s showing brace meets design loads
![Page 5: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/5.jpg)
Abstract
• Brace assembly strength is limited to the load capacity of the weakest component– Requires 3rd party load testing & certification
![Page 6: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/6.jpg)
Today’s Presentation
• Importance of bracing fire sprinklers
• Brace assembly components
• General rules for brace placement
![Page 7: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/7.jpg)
Importance of Bracing
Fire Sprinklers
![Page 8: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/8.jpg)
FM Global - Understanding the Hazard
“Lack of Earthquake Bracing on Sprinkler System”
![Page 9: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/9.jpg)
10 Year Period (FM Global)
• 561 earthquakes worldwide
• $315 million (USD) in damages facilities
• $560,000 (USD) average loss
• 50% of average loss is due to sprinkler system failure
![Page 10: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/10.jpg)
How Damage Occurs
• Building movement is different than the fire sprinkler pipe
• Unbraced fire sprinklers damage may occur by:– Hitting walls, suspended ceilings or other
building systems– Fittings break due to twisting– Couplings can separate or leak during
excessive bending, rotation or movement
![Page 11: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/11.jpg)
Additional Concerns
• Protecting against loss from fire or water leakage is a critical towards recovery from an earthquake
• Time for water leak discharge to fill a 14 ft x 14 ft (4.3m x 4.3m) room to depth of 1 foot (30cm) based on 50 psi (3.4 bar):
Time(in) (mm) (minutes)1/2 12 37
1 32 8.11 1/2 40 4.0
2 50 2.74 100 1.56 150 1.3
Pipe Diameter
![Page 12: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/12.jpg)
Ways to Avoid Sprinkler Damage
• Bracing
• Flexibility
• Clearance
• Other Considerations– Brace suspended ceilings– Weak brace and/or hanger attachments– Anchoring of equipment, tanks & racks
![Page 13: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/13.jpg)
Costs to Brace
• 3 – 4% if installed with the sprinkler system
• Retrofit costs vary widely from an estimated $100 - $500 USD per brace location
![Page 14: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/14.jpg)
Importance of Sprinkler Bracing - Summary
• Critical after earthquake protection against:– Water leaks– Fires
• Decreases loss of:– Property– Function / use of facilities
• Increases life safety
![Page 15: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/15.jpg)
Brace Assembly Components
![Page 16: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/16.jpg)
Sway Brace Components
Brace Clamp
Structure Attachment
Brace
![Page 17: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/17.jpg)
Structural Attachments
CSBUNIV – Universal Structural
![Page 18: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/18.jpg)
Structural Attachments
CSBBARJ – I-Beam Attachment
![Page 19: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/19.jpg)
Structural Attachments
CSBIB – Adjustable I-Beam Attachment
![Page 20: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/20.jpg)
Structural Attachments
CSBMA – Multi Attachment
![Page 21: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/21.jpg)
Brace Clamps – Lateral Only
CSBQIKCL – Quick Grip Jr
CSBQG – Quick Grip
![Page 22: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/22.jpg)
Brace Clamps – Lateral & Longitudinal
CSBEZU and CSBSTU Universal Brace Clamp
![Page 23: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/23.jpg)
General Rules
For
Brace Placement
![Page 24: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/24.jpg)
Lateral Bracing
![Page 25: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/25.jpg)
Lateral Bracing
• What:– Feed and cross mains (any size)– Branch and other piping > 2 ½” (65mm)
diameter
• Where:– 40 ft o.c. (12m) maximum spacing– On the last length of pipe at the end of a main– Within 6 ft (1.8m) of the end of the pipe
![Page 26: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/26.jpg)
Lateral Bracing
![Page 27: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/27.jpg)
Lateral Bracing
• Can act as longitudinal brace if installed within 2 ft (0.6m) of piping braced longitudinally
Note that Pipe A Diameter > Pipe B Diameter
![Page 28: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/28.jpg)
Longitudinal Bracing
![Page 29: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/29.jpg)
Longitudinal Bracing
• What:– Feed and cross mains (any size)– Branches > 2 ½” (65mm) diameter
• NFPA 13 Not Required• FM DS 2-8 Required if longer than 40 ft (12.2m)
• Where:– 80 ft (24.2m) o.c. maximum spacing– Within 40 ft (12.2m) of the end of the pipe or
change in direction
![Page 30: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/30.jpg)
Longitudinal Bracing
![Page 31: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/31.jpg)
Longitudinal Bracing
• Can act as a lateral brace if installed within 2 ft (0.6m) of piping braced laterally
![Page 32: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/32.jpg)
Riser Bracing
• Riser tops exceeding 3 ft (0.9m) in length
• Maximum Spacing = 25 ft (7.6m) o.c.
![Page 33: Fire Sprinkler Earthquake Protection – Sway Bracing](https://reader036.vdocuments.site/reader036/viewer/2022062308/56649ce35503460f949afac3/html5/thumbnails/33.jpg)
Thank You