Page 1: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

October 3, 2019UL and the UL logo are Trademarks of UL © 2019

Rich Walke

UL Codes and Regulatory Services

Fire-Resistance Test

Standards for

Elements and

Assemblies

Page 2: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

22

Fire-Resistance-Rated Construction

Page 3: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

3

Fire-Resistance-Rated Construction

Code

Requirements

for

Fire-Resistance-

Rated

Construction

Page 4: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

4

Code Requirements

• IBC Section 703.2 – Fire-resistance ratings

shall be determined in accordance with

ANSI/UL 263 or ASTM E119

• LSC 8.2.3.1 – The fire resistance of

structural elements and building

assemblies shall be determined in

accordance with test procedures set forth

in ANSI/UL 263 or ASTM E119

Page 5: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

5

Fire Resistance

• Expressed as an Hourly Time Period

• Ratings range from 1/2 to 4 hours

• Containment of Fire to Room or Floor of

Origin, and Structural Fire Resistance

Page 6: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

6

Fire-Resistance-Rated Construction

Establishing

Fire-Resistance

Ratings

Page 7: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

7

Standards

• ANSI/UL 263

• ASTM E119

• NFPA 251 (Withdrawn)

Page 8: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

8

Building Components

• Columns

• Beams

• Floor/Ceilings or Roof/Ceilings

• Walls

Page 9: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

9

Temp

(ºF)

Time (Hr)

Time - Temperature Curve

Page 10: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

10

Columns

• Sample size – Minimum 9 ft

• Tested unloaded

Page 11: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

11

Page 12: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

12

Page 13: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

13

Conditions of Acceptance – Columns

• 1000ºF / 1200ºF

Page 14: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

14

Page 15: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

15

Page 16: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

16

Beams

• Sample size – Minimum 12 ft

• Load applied – Per design

Page 17: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

17

Page 18: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

18

Page 19: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

19

Page 20: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

20

Page 21: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

21

Page 22: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

22

Page 23: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

23

Conditions of Acceptance – Beams

• Support load

• 1100ºF / 1300ºF

Page 24: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

24

Floor/Ceiling or Roof/Ceilings

• Sample size – 180 sq ft / 12 ft

• Load applied – Per design

180 sq ft12 ft

Page 25: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

25

Page 26: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

26

Page 27: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

27

Page 28: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

28

Page 29: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

29

Page 30: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

30

Page 31: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

31

Page 32: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

32

Page 33: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

33

Page 34: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

34

Page 35: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

35

Conditions of Acceptance

Floor/Ceilings or Roof/Ceilings

• Support load

• Flame passage

• 250ºF / 325ºF

• Support temperatures

Page 36: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

36

Page 37: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

37

Walls

• Sample size - 100 sq ft / 9 ft

• Load applied - Per design

100 sq ft9 ft

Page 38: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

38

Page 39: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

39

Page 40: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

40

Page 41: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

41

Page 42: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

42

Page 43: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

43

Page 44: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

44

Conditions of Acceptance – Walls

• Flame passage

• 250ºF / 325ºF

• Support load

• Hose stream

Page 45: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

45

Where Can I Find The

Most Current Listing?

UL Product iQ on

www.ul.com

Page 46: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

4646

Breaches in Fire-Resistance-Rated

Construction

• Penetrations

• Joint Systems

• Opening Protectives

• Ducts and Air Transfer Openings

Page 47: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

47

Breaches in Fire-Resistance-Rated

Construction Cont.

Do breaches really impact the performance

of a fire-resistance-rated assembly?

Absolutely!!!

Page 48: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

48

Breaches in Fire-Resistance-Rated

Construction Cont.

• Unsealed or improperly sealed breaches cost lives and

property!

• MGM Grand, Las Vegas, NV – Fire confined to 1st floor.

Eighty-four fatalities, most on upper floors.

• Hilton Hotel, Las Vegas, NV – Fire spread from 8th to 23rd

floor in 25 minutes at exterior of building. Eight fatalities.

• First Interstate Bank, Los Angeles, CA – Fire spread from

12th to 16th floor through improperly protected penetrations

and through unprotected perimeter joint. One fatality.

• One Meridian Plaza, Philadelphia, PA – Fire spread from

22nd to 30th floor through improperly protected penetrations

and through perimeter joint. Three fatalities.

Page 49: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

49

IBC Requirements

• IBC – Breaches shall be protected

•Section 714 – Penetrations

•Section 715 – Fire-Resistant Joint Systems

•Section 716 – Opening Protectives

•Section 717 – Ducts and Air Transfer Openings

Page 50: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

50

LSC Requirements

• LSC – Breaches shall be protected

•Penetrations

•Joint Systems

•Opening Protectives

•Ducts and Air Transfer Openings

Page 51: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

51

Code Requirements

• Each type of breach has a unique fire test

standard associated with it which

compliments ANSI/UL 263 and ASTM

E119

• Where breach occurs in, through or

between assemblies intended to restrict the

movement of smoke, the code also sets

limits on the leakage through the breach

Page 52: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

52

Where Can I Find The

Most Current Listing?

UL Product iQ on

www.ul.com

Page 53: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

5353

Fire Resistive Construction

UL’s

Product iQ

Online Directory

Page 54: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

54

Product iQ – UL’s New Online Directory

• Replaces the old Online Certifications

Directory which was developed in 1999

• Helps you achieve code compliance

• Is continuously updated

• Requires registration to create user account

• Basic Service – no charge for use

Page 55: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

55

Product iQ – UL’s New Online Directory

• Paid Subscription Service provides more

features

•Save Searches

•Tags and Groups

•Confirmation Letters

• Same listing information as the old platform

• No impact on testing results or

certifications

• https://iq.ulprospector.com/en/

Page 56: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

56

UL Product iQ – www.ul.com

Scroll to the bottom of the page

Page 57: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

57

UL Product iQ

Page 58: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

58

UL Product iQ Cont.

Page 59: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

59

UL Product iQ Cont.

Page 60: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

60

UL Product iQ Cont.

Page 61: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

61

UL Product iQ Cont.

Page 62: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

62

UL Product iQ Cont.

Page 63: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

63

UL Product iQ Cont.

Smart Search

Page 64: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

64

UL Product iQ Cont.

iQ Plus Search

Page 65: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

65

UL Product iQ Cont.

iQ Plus Search

Page 66: Fire Resistance Test Standards for Elements and Assemblies ......ANSI/UL 263 or ASTM E119 •LSC 8.2.3.1 –The fire resistance of structural elements and building assemblies shall

66