fire resistance of materials & structures - analysing the steel structure

22
Fire Resistance of Materials & Structures 3rd Homework - Steel Structure Date of Submission 2016 Submitted by Seyed Mohammad Sadegh Mousavi 836 154 Submitted to Prof. R. Felicetti Prof. P. G. Gambarova Dr. P. Bamonte Structural Assessment & Residual Bearing Capacity, Fire & Blast Safety Civil Engineering for Risk Mitigation Politecnico di Milano [3rd Homework-Modelling of fire scenario]

Upload: arshia-mousavi

Post on 21-Jan-2018

56 views

Category:

Education


3 download

TRANSCRIPT

Page 1: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Fire Resistance of Materials & Structures 3rd Homework - Steel Structure

Date of Submission

2016

Submitted by

Seyed Mohammad Sadegh Mousavi

836 154

Submitted to

Prof. R. Felicetti

Prof. P. G. Gambarova

Dr. P. Bamonte

Structural Assessment & Residual Bearing

Capacity, Fire & Blast Safety

Civil Engineering for Risk Mitigation

Politecnico di Milano

[ 3 r d H o m e w o r k - M o d e l l i n g o f f i r e s c e n a r i o ]

Page 2: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 1 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Fire Resistance of Materials and Structures Prof. R. Felicetti, Prof. P.G. Gambarova and Dr. P. Bamonte

3rd Homework - Steel structure

The figures below show the plan and the section of a library room, whose structural steel members are to be checked

in fire conditions (in terms of bearing capacity, R criterion).

The required rate is 120 minutes under the fire scenario assessed in Homework 2 (Parametric Fire)

Page 3: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 2 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

The structural scheme of the beam can be assumed as follows:

(balanced load, no interaction between the beam and the column)

The two spans are L1 = L2 = 4 (1 + L/100)

The upper floors are subjected to the following loads:

· permanent load: Gk = 5.00 kN/m2

· variable load: Qk = 2.00 kN/m2 (office not open to public)

· snow load: Qsk = 1.20 kN/m2

1. Design of the beam and the column at room temperature

a) design the beam capacity at the ULS and the check the deflection at the SLS (d ≤ L1/250 in the rare combination)

b) design the column for its buckling resistance

2. Design the beam fire protection (boards) for the required fire resistance under the quasi-permanent load

combination and assuming a three-side exposure (concrete deck on top)

suggested steps: design load under fire ultimate load of the beam at time = 0 ductility class global failure or just a critical section? increased capacity of the critical sections by the adaptation factors degree of utilization of the structure (or the critical section) critical temperature

protection design & final check

3. Design the column fire protection

for the required fire resistance under the quasi- permanent

load combination (optional: accounting for the effect of the

thermal elongation of the beam).

suggested steps: design load under fire

thermal elongation of the beam

assessment of the equiv. uniform moment

critical temperature (spreadsheet file)

protection design & final check

If needed, the member cross-sections designed at room temperature may be adjusted in order to meet the required

fire resistance (parts 2 and 3)

L= 21 (U)

𝐿1 = 𝐿2 = 4 × (1 +𝐿

100) = 4 × (1 +

21

100) = 4.84 𝑚

Page 4: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 3 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 1 – Span

i. Design of the beam and the column at room temperature

a. Design of the beam at room temperature

Design the beam capacity at the ULS and the check the deflection at SLS

(d ≤ 𝐿1

250= 0.01936 in the rare combination)

Unit load on the floor:

𝑞𝑈𝐿𝑆 = 1.35 × 5 (𝐾𝑁

𝑚2) + 1.5 × 2 (

𝐾𝑁

𝑚2) = 9.75 (

𝐾𝑁

𝑚2)

𝑞𝑆𝐿𝑆 = 5 (𝐾𝑁

𝑚2) + 2 (

𝐾𝑁

𝑚2) = 7.00 (

𝐾𝑁

𝑚2)

The unit load on the beam depends on the width of the floor pertaining to it. If we assume bending continuity

between the two bays of the slab, this width is:

2 ×5

8× 6 = 7.5 𝑚

Figure 2 – Distance of 2 bays of the slab

Figure 2

Page 5: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 4 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Hence, the distributed load on the beam is:

𝑃𝑈𝐿𝑆 = 9.75 (𝐾𝑁

𝑚2) × 7.5 (𝑚) + 1.35 × 0.5 (

𝐾𝑁

𝑚) = 73.8 (

𝐾𝑁

𝑚)

𝑃𝑆𝐿𝑆 = 7.00 (𝐾𝑁

𝑚2) × 7.5 (𝑚) + 0.5 (

𝐾𝑁

𝑚) = 53.00 (

𝐾𝑁

𝑚)

Where the dead weight of the steel profile has been assessed as 0.5 (𝐾𝑁

𝑚) (on the safe side up to IPE 300)

Figure 3 – Permanent & Variable loads on the beam

Flexure Design (ULS):

The bending moment & Shear force diagrams are obtained by the SAP2000.

Figure 4 - Bending Moment Diagram

𝑀𝐸𝑑 = 216.10 𝐾𝑁.𝑚

𝑉𝐸𝑑 = 223.25 𝐾𝑁

Check

Applied Design Moment: MEd= puls*L2/8 = 216.10 kN.m

Resisting Design Moment: MRd= fyd . Wpl

Page 6: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 5 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Steel grade is S355 with its mechanical properties:

E=210 Gpa=210000000 (𝐾𝑁

𝑚2)

𝑓𝑦,𝑘 = 355000(𝐾𝑁

𝑚2)

𝑓𝑦,0 =𝑓𝑦,𝑘

𝛾𝑀0= 355000(

𝐾𝑁

𝑚2)

Where

𝛾𝑀0= Material Safety factor, applied to charactrsitic value of strength of section of any class, recommended value

is 1.0.

휀 = √235

𝑓𝑦,𝑘= √

235

355= 0.814

For design at ULS, requirement that bending moment resistance of the steel section has to be equal or

greater that design bending moment value has to be satisfied:

𝑀𝐸𝑑 ≤ 𝑀𝑅𝑑

For the following, Steel profile section should be chosen and check it with the ULS requirements. On one hand, for

the beam section, best choice is IPE profile that it’s characterized with small width of flange versus height of the

section. Also thickness of web and flange are small and so their area as well as weight.

On the other hand, IPE is basically used for the beams in order to high uniaxial bending moment capacity. They

have large moment of inertia, therefore they are very effective under bending moment and in limiting vertical

deflections, which is very important for horizontal elements such as beams.

𝑊𝑝𝑙 =216.10 × 100

35.5= 608.74 𝑐𝑚3

Steel section profile chosen is IPE 300 with the following properties:

IPE 300

𝑊𝑝𝑙 628.4 cm3

h 300 mm

b 150 mm

A 53.81 cm2

r 15 mm

𝑡𝑓 10.7 mm

𝑡𝑤 7.1 mm

𝐼𝑥 8356 cm3

Figure 5 - IPE 300 Properies

Classification is to identify the extent to which resistance and rotation capacity of the section is limited by its local

buckling resistance.

Resisting Design Moment:

MR,d= fyd . Wpl = 35.5 * 628.4/100 =223.011 kNm. > MEd = 216.10 kN.m

Table below gives conditions for web and flange. (The ductility class of the chosen profile is checked with respect

to the standard EN-1991)

Page 7: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 6 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 6 - Web & Flange Table (IPE)

Web check:

𝐶𝑤 = ℎ − 2. 𝑡𝑓 − 2. 𝑟 = 300 − 2 × 10.7 − 2 × 15 = 248.6 𝑚𝑚

𝐶𝑤𝑡𝑤=248.6

7.1= 35.01 < 72 × 휀 = 58.58 (𝐶𝑙𝑎𝑠𝑠 1)

Flange Check:

𝐶𝑓 =𝑏 − 𝑡𝑤𝑤

− 𝑟 =150 − 7.1

2− 15 = 56.45 𝑚𝑚

𝐶𝑓

𝑡𝑓=56.46

10.7= 5.28 < 9 × 휀 = 7.29 (𝐶𝑙𝑎𝑠𝑠 1)

Therefore, The section is classified to class 1. For class 1 cross sections, the total plasticization of the critical cross

section is assumed and the rotation capacity of the plastic hinges allows the formation of a failure mechanism (it is

a benefit for redundant structures).

Check the Bending moment resistance for ULS:

𝑀𝑅𝑑 = 𝑀𝑝𝑙,𝑅𝑑 =𝑊𝑝𝑙 . 𝑓𝑦

𝛾𝑀0=628.4 × 35.5

1= 223.08 𝐾𝑁.𝑚 > 𝑀𝐸𝑑 = 216.10 𝐾𝑁.𝑚

Check Shear force effect:

According to the presence of shear the theoretical plastic resistance moment of the cross section will be reduced.

For small values of shear force, this reduction is so small that it is counter-balanced by strain hardening and may

be neglected. Provided that the design value of the shear force 𝑉𝑠𝑑 doesn’t exceed 50% of the design plastic shear

resistance 𝑉𝑃𝑙,𝑅𝑑 no reduction need to be made in the resistance moments. On the other hand, when 𝑉𝑠𝑑 exceeds

50% of 𝑉𝑃𝑙,𝑅𝑑, the design resistance moment of the cross section should be reduced to 𝑀𝑉,𝑅𝑑, allowing for the shear

force.

Page 8: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 7 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Design value for shear force 𝑉𝑠𝑑 at each cross section should satisfy the following condition:

𝑉𝐸𝑑 = 5/8 ∗ 4. 84 ∗ 73.8 = 223.245 𝑘𝑁 ≤ 𝑉𝑃𝑙,𝑅𝑑 = 526.33 𝑘𝑁 (𝑆𝑎𝑓𝑒)

Where 𝑉𝑃𝑙,𝑅𝑑is the design plastic shear resistance given by the expression:

𝑉𝑃𝑙,𝑅𝑑 =𝐴𝑣 × 𝑓𝑦

√3 × 𝛾𝑀0

𝐴𝑣 = 𝐴 − 2 ∙ 𝑏 ∙ 𝑡𝑓 + (𝑡𝑤 + 2𝑟) × 𝑡𝑓 = 53.81 × 102 − 2 × 150 × 10.7 + (7.1 + 2 × 15) × 10.7

𝐴𝑣 = 2567.97 𝑚𝑚2 (Rolled I-beam)

𝑉𝑃𝑙,𝑅𝑑 =2567.97 × 35.5

√3 × 1= 526.33 𝐾𝑁

𝐼𝑓 𝑉𝑠𝑑≤0.5𝑉𝑃𝑙,𝑅𝑑⇒

𝑉𝐸𝑑𝑉𝑃𝑙,𝑅𝑑

=206.6

526.33= 0.395 < 0.5

So, we can neglect the effect of shear force on our beam.

Check deflection (SLS)

𝛿𝑙𝑖𝑚 ≤𝐿1250

≤484

250= 1.936 𝑐𝑚

Maximum deflection of beam:

𝛿𝑚𝑎𝑥 =3 × 𝑃𝑆𝐿𝑆 × 𝐿

4

384 × 𝐸𝐼=3 × 53 × 4.844

384 × 𝐸𝐼= 1.295 𝑐𝑚 < 𝛿𝑙𝑖𝑚 = 1.936 𝑐𝑚 (𝑆𝑎𝑓𝑒)

Maximum Deflection is satisfied.

b. Design of the Column for Buckling resistance

Floor area sustained by the column at eache story:

𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 = 7.5 × 2 × (5

8) × 4.84 = 45.375 𝑚2

Loads on the columns

All columns should be checked for buckling resistance. Procedure is the same for all the columns, taking into

account different values of actions for the columns on different storeys. Service load is assumed as dominant, thus

snow load is reduced by the coefficient 𝜓0 = 0.5 (Following Fig.4)

Page 9: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 8 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 7 - 𝝍 Factor Design values of permanent and variable load have been used. Actions on columns on all four storeys

have been computed and listed below:

permanent load: Gk = 5.00 kN/m2

variable load: Qk = 2.00 kN/m2 (office not open to public)

snow load: Qsk = 1.20 kN/m2

(The factor 1.01 is considered as self-weight of the cross section)

Last Floor

𝑁𝑒𝑑,4(𝐾𝑁) = (𝐺𝑑 +𝑄𝑠,𝑑) × 𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 = 1.01 × (1.35 × 5 + 1.5 × 0.5 × 1.2) × 45.375 𝑚2

3rd Floor

𝑁𝑒𝑑,3 (𝐾𝑁) = (𝐺𝑑 + 𝑄𝑑) × 𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 +𝑁𝑒𝑑,4

2nd Floor

𝑁𝑒𝑑,2(𝐾𝑁) = (𝐺𝑑 + 𝑄𝑑) × 𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 +𝑁𝑒𝑑,3

1st Floor

𝑁𝑒𝑑,1(𝐾𝑁) = (𝐺𝑑 + 𝑄𝑑) × 𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 +𝑁𝑒𝑑,2

Last Floor Ned,4 (KN) 347.12

3rd Floor Ned,3 (KN) 789.53

2nd Floor Ned,2 (KN) 1231.931

1st Floor Ned,1 (KN) 1674.338

Figure 8 - Loads on each storey (Obtained by Excel)

For designing the column is better to use the HE cross sections instead of IPE, due to it has large thickness, width

and height of the flanges of the HE sections is almost the same and also it has the biaxial bending moment resistance

in case of the direction of for e.g. earthquake and etc is not known and larger area, so great axial load capacity. For

the assumption, different profiles assumed for different columns, 𝐶𝑤

𝑡𝑤 and

𝐶𝑓

𝑡𝑓 ratios are checked in order to determine

class of profile.

Page 10: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 9 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Compression members should be verified against buckling resistance as follows:

𝑁𝑒𝑑𝑁𝑏,𝑅𝑑

≤ 1

𝑁𝑏,𝑅𝑑 = 𝜒 ∙ 𝐴 ∙𝑓𝑦

𝛾𝑀𝐼 (The column Resistance force)

Where:

𝜒 = reduction factor for the relevant buckling mode.

𝛾𝑀𝐼 = material safety factor, related to buckling strength of column, recommended value is 𝛾𝑀𝐼= 1.1.

For constant axial compression in members of constant cross section, value of 𝜒 for appropriate non dimensional

slenderness λ may be determined from:

𝜒 =1

∅ + √∅2 − 𝜆2≤ 1

∅ = 0.5 × [1 + 𝛼(𝜆 − 0.2) + 𝜆2]

Where:

𝛼 = Imperfection factor corresponding to the appropriate buckling curve that depends on the geometry of the

section.

Buckling Curve 𝑎0 a b c d

Imperfection factor (𝛼) 0.13 0.21 0.34 0.49 0.76

λ = the non dimensional slenderness for the relevant buckilng mode and can be determined from the formula

λ = √𝐴×𝑓𝑦

𝑁𝑐𝑟

In the following Fig.6, table shows how to assign the buckling curve and imperfection factor.

Page 11: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 10 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 9 – Selection of Buckling curve for a cross section

𝑁𝑐𝑟 =𝜋2 × 𝐸𝐼

𝑙𝑐𝑟2

Where:

𝑁𝑐𝑟: Elestic critical force for the relevant buckling mode.

𝐼𝑐𝑟: Buckling Length (Critical length) & can be equal to height of the column=3.5 m

Calculations should be done twice for each buckling directions. Direction of maximum slenderness, i.e.

minimum 𝜒 is then considered.

E = 210000 N/mm^2

l cr = 3500 mm

h = 220 mm

b = 206 mm

h/b (<1.2) = 1.068

tf (<100 mm) = 25 mm

I y = 106400000 mm^4

I z = 36510000 mm^4

f y = 355 N/mm^2

A = 13130 mm^2

γ M1 = 1.1

y-y z-z

Buckling Curve = b c

α = 0.34 0.49

EI = 2.234E+13 7.6671E+12

N cr = 18002158.43 6177244.4

λ = 0.5088 0.8687

∅ = 0.6820 1.0411

χ = 0.8803 0.6192

N b,Rd (KN)=

N ed (KN)=

N ed/N b,rd =

Safe

2623.8149

1674.34

0.6381

Buckling

HE 200 M

1st Floor Column

E = 210000 N/mm^2

l cr = 3500 mm

h = 200 mm

b = 200 mm

h/b (<1.2) = 1.000

tf (<100 mm) = 15 mm

I y = 56960000 mm^4

I z = 20030000 mm^4

f y = 355 N/mm^2

A = 7810 mm^2

γ M1 = 1.1

y-y z-z

Buckling Curve = b c

α = 0.34 0.49

EI = 1.196E+13 4.2063E+12

N cr = 9637245.71 3388940.16

λ = 0.5364 0.9045

∅ = 0.7010 1.0817

χ = 0.8677 0.5971

N b,Rd (KN)=

N ed (KN)=

N ed/N b,rd =

Safe

1504.9116

1231.93

0.8186

2nd Floor Column

HE 200 B

Buckling

Page 12: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 11 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 10 – HE Properties cross sections for each floors

In the previous tables (Figure.7), the imperfection factors (h/b) and tf are computed for each cross sections and their

requirements was checked.

Column on the fourth floor is definitely underutilized, but in case of simplicity of implemnetation it was chosen the

same profile section as for the third floor column.

Check the members’ class (Ductility class):

Figure 11 – Check the members’ Class

E = 210000 N/mm^2

l cr = 3500 mm

h = 180 mm

b = 180 mm

h/b (<1.2) = 1.000

tf (<100 mm) = 14 mm

I y = 38310000 mm^4

I z = 13630000 mm^4

f y = 355 N/mm^2

A = 6530 mm^2

γ M1 = 1.1

y-y z-z

Buckling Curve = b c

α = 0.34 0.49

EI = 8.045E+12 2.8623E+12

N cr = 6481792.19 2306103.57

λ = 0.5980 1.0026

∅ = 0.7465 1.1993

χ = 0.8380 0.5384

N b,Rd (KN)=

N ed (KN)=

N ed/N b,rd =

Safe

1134.6857

789.53

0.6958

3rd Floor Column

HE 180 B

Buckling

E = 210000 N/mm^2

l cr = 3500 mm

h = 180 mm

b = 180 mm

h/b (<1.2) = 1.000

tf (<100 mm) = 14 mm

I y = 38310000 mm^4

I z = 13630000 mm^4

f y = 355 N/mm^2

A = 6530 mm^2

γ M1 = 1.1

y-y z-z

Buckling Curve = b c

α = 0.34 0.49

EI = 8.045E+12 2.8623E+12

N cr = 6481792.19 2306103.57

λ = 0.5980 1.0026

∅ = 0.7465 1.1993

χ = 0.8380 0.5384

N b,Rd (KN)=

N ed (KN)=

N ed/N b,rd =

Safe

1134.6857

347.12

0.3059

4th Floor Column

HE 180 B

Buckling

Cw (mm)= 134

Cw/tw= 8.93 < 26.85

Cf (mm)= 77.5

Cf/tf= 3.10 < 7.32

Flange & Web Check (HE 200 M)

Class 1

Cw (mm)= 134

Cw/tw= 14.89 < 26.85

Cf (mm)= 77.5

Cf/tf= 5.17 < 7.32

Flange & Web Check (HE 200 B)

Class 1

Cw (mm)= 122

Cw/tw= 14.35 < 58.32

Cf (mm)= 70.75

Cf/tf= 5.05 < 7.29

Flange & Web Check (HE 180 B)

Class 1

Page 13: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 12 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

ii. Design the beam fire protection (boards) for the required fire resistance under the quasi-

permanent load combination and assuming a three-side exposure (concrete deck on top)

Design action in fire condition: quasi permanent load combination:

𝐹𝑓𝑖,𝑑 = 𝛾𝐺𝐴 ∙ 𝐺𝑘 +∑ 𝜓2𝑖 ∙ 𝑄𝑘𝑖𝑖≥1

Where:

𝛾𝐺𝐴 = Partial coefficient for permanent actions in accidental conditions. (Sugessted value = 1)

𝜓2𝑖 = Coefficient for quasi-permanent combination of loads. (equal to 0.3)

Figure 12 – Coefficient for Quasi-permanent combination of loads

Therefore, in this case the design load under fire is: 𝑞𝑓𝑖,𝑑 = 1 × 5 + 0.3 × 2 = 5.6 (𝐾𝑁

𝑚2)

The uniformly distributed load on the beam is: 𝑃𝑓𝑖,𝑑 = 5.6 × 7.5 = 42 (𝐾𝑁

𝑚2)

For the IPE 300 (1st Class) we have checked the ductility class and so it can be concluded that it will be the same

class in fire conditions and checking again the slenderness of the web and flange is not necessary.

We considering Global failure, If n is degree of redundancy of a structure, then n+1 plastic hinges would have to

form in the critical sections of the beam in order for beam to failure. Our beam is one times redundant, so two

plastic hinges to be formed where the moment reaches the plastic resisting moment. The following scheme is

considered for the failure mechanism:

Figure 13 – Location of x

𝑥

𝐿=

1

[((𝑀𝑅𝑑−

𝑀𝑅𝑑+ ) + 1)

0.5

+ 1]

Page 14: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 13 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

𝑃𝐶𝑜𝑙 = (2𝑀𝑅𝑑

+

𝐿2) × [((

𝑀𝑅𝑑−

𝑀𝑅𝑑+ ) + 1)

0.5

+ 1]

2

Where:

Pcol = Collapse Load (Depending on the coorection factor (κ1, κ2), temperature for the whole beam is assumed as a

single temp and so there is the value of ky,θ for the yield strength reduction for the entire beam.

κ1 = The correction factore accounting for the position of the section, in our case, it’s equal to 0.85 for protected

beam exposed on 3-sides.

κ2 = The correction factore accounting for the position of the section, in our case, it’s equal to 0.85 at the support

and 1 at the mid-span.

Calculation of the resistant bending moments for the 2 sections:

𝑀𝑅𝑑,𝜃− =

𝑘𝑦,𝜃 . 𝑓𝑦,𝑘 .𝑊𝑝𝑙

κ1κ2= 1.384 𝑘𝑦,𝜃 . 𝑓𝑦,𝑘 .𝑊𝑝𝑙 (𝑘𝑁.𝑚)

𝑀𝑅𝑑,𝜃+ =

𝑘𝑦,𝜃 . 𝑓𝑦,𝑘 .𝑊𝑝𝑙

κ1κ2= 1.177 𝑘𝑦,𝜃 . 𝑓𝑦,𝑘 .𝑊𝑝𝑙 (𝑘𝑁.𝑚)

𝑀𝑅𝑑−

𝑀𝑅𝑑+ = 1.176

𝑃𝐶𝑜𝑙 = (2𝑀𝑅𝑑

+

𝐿2) × [((

𝑀𝑅𝑑−

𝑀𝑅𝑑+ )+ 1)

0.5

+ 1]

2

= (2 × 1.177 𝑘𝑦,𝜃 . 𝑓𝑦,𝑘 .𝑊𝑝𝑙

4.842) × [(1.176 + 1)0.5 + 1]2

IPE 300

Wpl (cm^3) = 628.4

fy,k (KN/m^2)= 355000

𝑃𝐶𝑜𝑙,𝜃 = 137.22 𝑘𝑦,𝜃 (𝑘𝑁

𝑚)

As a result, when Pfi, Ed = Pcol, the failure of the beam is occuring so that means when 𝑘𝑦,𝜃 = 0.31

At fire time t=0, the collapse load is equal to Pcol,0=137.22 kN/m, and the applied load is Pfi, Ed=42 kN/m

Utilization factor :

𝜇0 =𝐴𝑝𝑝𝑙𝑖𝑒𝑑 𝑙𝑜𝑎𝑑

𝑈𝑙𝑡𝑖𝑚𝑎𝑡𝑒 𝑙𝑜𝑎𝑑 𝑎𝑡 𝑡𝑖𝑚𝑒 𝑡 = 0=

42

137.22= 0.31

So, the value of the utilization factor is the same as the strength reduction factor 𝑘𝑦,𝜃.

According to the utilization factor and using it, the critical temperature at which the collapse load equals to the

design fire load can be calculated in the following:

𝜃𝑎,𝑐𝑟 = 482 + 39.29 × ln(1

0.9674 × 𝜇03.833 − 1) = 𝟔𝟔𝟏. 𝟏𝟗 ℃

i. Thermal analysis of the Unprotected members

∆𝜃𝑎,𝑡 = 𝑘𝑠ℎ

𝐴𝑚𝑉⁄

𝑐𝑎𝜌𝑎ℎ̇𝑛𝑒𝑡∆𝑡

Page 15: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 14 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Where:

𝑘𝑠ℎ = Shadow effect correction factor (EN 1993-1-2)

𝐴𝑚 = Lateral surface area of the member (𝑚2)

ℎ̇𝑛𝑒𝑡 = Net heat flux per unit area (𝑊

𝑚2)

V = Volume of the member (𝑚3)

𝑐𝑎 = Specific heat of steel (𝐽

𝐾𝑔 ℃)

𝜌𝑎 = Steel Density (𝑘𝑔

𝑚3)

Comparing 𝒉𝒏𝒆𝒕

ℎ𝑛𝑒𝑡 = 𝛼𝑐(𝜃𝑐 − 𝜃𝑚) + 𝜎휀𝑟[(𝜃𝑟 + 273)4 − (𝜃𝑚 + 273)

4]

Where:

𝛼𝑐= Convective heat transfer coefficient (𝑊

𝑚2 ℃) 25 (

𝑾

𝒎𝟐 ℃) with no distinction

𝜃𝑐= Gas temperature next to the member (℃)

𝜃𝑚= Surface temperature of the member (℃)

휀𝑟= Resultant emissivity between the combusted gas and member surface

𝜃𝑟= Radiant temperature of the fire compartment (℃)

𝜎= Boltzman constant (5.77 × 10−8 𝑊

𝑚2𝐾4)

𝛼𝑟= Radiative heat transfer coefficient (𝑊

𝑚2 ℃)

In general it is assumed 𝜃𝑐 = 𝜃𝑟 = 𝜃𝑔 where 𝜃𝑔is the gas temperature.

휀𝑟 =1

(1휀𝑟+1휀𝑚− 1)

≅ 휀𝑟 × 휀𝑚 = 1 × 휀𝑚 = 0.5 𝑓𝑜𝑟 𝑐𝑎𝑟𝑏𝑜𝑛 𝑠𝑡𝑒𝑒𝑙, 0.4 𝑓𝑜𝑟 𝑠𝑡𝑎𝑖𝑛𝑙𝑒𝑠𝑠 𝑠𝑡𝑒𝑒𝑙.

𝑁𝑜 𝑎𝑙𝑙𝑜𝑤𝑎𝑛𝑐𝑒 𝑓𝑜𝑟 𝑡ℎ𝑒 𝑠ℎ𝑎𝑑𝑜𝑤 𝑒𝑓𝑓𝑒𝑐𝑡.

Section Factor – Calculation

Beam (IPE 300) Exposed on three sides

𝐴𝑚𝑉=𝐿𝑎𝑡𝑒𝑟𝑎𝑙 𝑠𝑢𝑟𝑓𝑎𝑐𝑒 𝑟𝑒𝑐𝑒𝑖𝑣𝑖𝑛𝑔 𝑡ℎ𝑒𝑟𝑚𝑎𝑙 𝑓𝑙𝑢𝑥

𝑀𝑎𝑡𝑒𝑟𝑖𝑎𝑙 𝑣𝑜𝑙𝑢𝑚𝑒 𝑠𝑡𝑜𝑟𝑖𝑛𝑔 𝑡ℎ𝑒 ℎ𝑒𝑎𝑡 (𝐴𝑟𝑒𝑎)

𝐴𝑚 = 2ℎ + 3𝑏 − 2𝑡𝑤 − 4(2 −𝜋

2)𝑟 = 1010 𝑚𝑚

𝐴𝑚𝑉=

1.001

0.005381= 187.8 𝑚−1

The assumption of uniform temperature inside the steel profile for 𝐴𝑚

𝑉>30, and for

𝐴𝑚

𝑉>300 profiles are very thin,

so the profile temperature is virtually the same as the gas temperature. With the exception of very massive members

Page 16: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 15 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

(small 𝐴𝑚

𝑉), after 30min 𝜃𝑎>700°C, and after one hour, the temperature is very high to neglect all the mechanical

strength.

Figure 14 – Shadow Effect

Correction factor for shadow effect for IPE Cross Sections:

𝑘𝑠ℎ = 0.9 ×[𝐴𝑚

𝑉⁄ ]𝑏𝑜𝑥𝐴𝑚

𝑉⁄= 0.9 ×

𝐴𝑚𝑏𝐴𝑚

= 0.9 ×𝑏 + 2ℎ

1010= 0.9 ×

750

1010= 0.668

In order to find out the steel temperature evolution in time “Steel Temperature” Excel sheet is used.

Figure 15 – Steel temperature evolution in time

According the 2nd homework, the value of gas temperature is taken, for the 2 hours fire duration and time dependent

openings.

Specific heat of carbon steel is temperature dependent (phase change at 735°C):

0

25 W/m2°C

0.70

187.8 1/m

0.668

5 s

steel type (1 = stainless)

coefficient of heat transfer by convection ac =

surface emissivity of the member = resultant emissivity er =

section factor Am / V =

correction factor for the shadow effect ksh =

time interval Dt =

0

1000

2000

3000

4000

5000

6000

0 200 400 600 800 1000 1200

sp

ecif

ic h

eat

(J/k

g°C

)

temperature (°C)

carbon

stainless

Page 17: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 16 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 16 – Specific heat of Carbon & Stainless Steel

Temperature in the steel profile after 2 hours is 𝜃𝑎 = 1227.9 ℃ that is higher than critical temperature computed

in the previous section. As a result, protection for the beam should be design.

ii. Thermal analysis of the Protected members

Several materials available for using as a fire protection of a member such as: Concrete, gypsum, Plaster, Fiber

gypsum and fire calcium-silicate boards, lightweight plasters, mineral fibre plasters, thin coating films and so on.

In the equation, due to assumption of surface protection temperature is the same as hot gas in the fire compartment

(insignificant thermal resistance compared to the insulation), the factors of thermal exchange at the surface

(convection & radiation) does not exist.

Page 18: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 17 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 17 – Protected steel graph

Assumption: Three sides of the section is exposed to the fire (Concrete slab on the top)

- Section Factor (𝐴𝑝

𝑉)

𝐴𝑝

𝑉=𝐸𝑥𝑝𝑜𝑠𝑒𝑑 𝑠𝑢𝑟𝑓𝑎𝑐𝑒 (𝑃𝑒𝑟𝑖𝑚𝑒𝑡𝑒𝑟)

𝑉𝑙𝑜𝑢𝑚𝑒 (𝐴𝑟𝑒𝑎)𝑜𝑓 𝑠𝑡𝑒𝑒𝑙 𝑝𝑟𝑜𝑓𝑖𝑙𝑒

Figure 18 – Section factor

For Hollow encasement reduces the exposed surface:

𝐴𝑝𝑉=

2ℎ + 𝑏

𝑉𝑙𝑜𝑢𝑚𝑒 (𝐴𝑟𝑒𝑎)𝑜𝑓 𝑠𝑡𝑒𝑒𝑙 𝑝𝑟𝑜𝑓𝑖𝑙𝑒=2 × 300 + 150

0.005381= 139.38 𝑚−1

According to design parameters for protected steel members:

Thermal ductility λp=0.135 W/m°C

Density ρ=550 kg/m3

Specific heat of the protection material cp= 1200 J/kg°C

Moisture content of the protection material

Protection thickness

Section Factor

And using thickness of the protection dp= 3 cm. The thermal analysis for IPE300 – protected beam exposed to the

Page 19: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 18 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

parametric fire evaluated in Homework 2 has done and excelsheet presented based on a time interval Δt= 15 sec.

The excelsheet is using the following equation that balance the heat flux input (through the conduction in the

protective material) to the stored thermal energy in the beam and the protection layer, assuming that the

temperature of the outer layer of the protection equals the gas temperature.

The parameters extracted from excelsheet (Steel+Temperature) for protected section:

steel type (1 = stainless) 0

conductivity of protection system p = 0.135 W/m°C

specific heat of protection system cp = 1200 J/kg°C

density of protection system p = 550 kg/m3

thickness of protection system dp = 0.030 m

moisture content (by mass) = 0%

section factor for protected members Ap / V = 139.38 1/m

time interval Dt = 15 s

Outputs:

Check:

Time Domain: θa = θa,cr = 661.9 °C, at time tcr=150 min > treq = 120 min.

The temperature domain: at time treq =120 min, θa =572.7 °C < θa,cr = 661.9 °C.

The load domain: at time treq = 120 min, ky,θ =0.627, Pcol,θ= 86.04 kN/m > Pfi,Ed =42 kN/m

iii. Design the column fire protection

For Quasi-permanent load combination, snow load was not taken into account.

𝑞𝑓𝑖 = 𝐺𝑘 + 0.3 𝑄𝑘 = 5.6 𝑘𝑁/𝑚2

Design load for the 2nd floor columns under fire (Neglecting the snow load)

𝑁𝑓𝑖,𝐸𝑑 = Σ(𝐺 + 𝜓2𝑄) × 𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 = [(5 + 0 × 1.2) + 2 × (5 + 0.3 × 2)] × 45.375 = 𝟕𝟑𝟓. 𝟎𝟕𝟓 𝑘𝑁

step # time time steel temp. gas temp.

t t qa qg Dqg ca f Dqa

(s) (min) (°C) (°C) (°C) (J/kg°C) (1) (°C)

0 0 0.0 20.0 20.0 108.8 440 0.799 -9.06

1 15 0.3 20.0 128.8 91.6 440 0.799 -7.39

2 30 0.5 20.0 220.4 77.2 440 0.799 -5.99

3 45 0.8 20.0 297.6 65.1 440 0.799 -4.82

4 60 1.0 20.0 362.7 55.1 440 0.799 -3.85

5 75 1.3 20.0 417.8 46.7 440 0.799 -3.03

6 90 1.5 20.0 464.5 39.7 440 0.799 -2.35

7 105 1.8 20.0 504.2 33.8 440 0.799 -1.77

8 120 2.0 20.0 538.0 28.9 440 0.799 -1.29

9 135 2.3 20.0 567.0 24.9 440 0.799 -0.89

10 150 2.5 20.0 591.8 21.4 440 0.799 -0.55

11 165 2.8 20.0 613.3 18.6 440 0.799 -0.27

12 180 3.0 20.0 631.8 16.2 440 0.799 -0.03

478 7170 119.5 571.0 1172.4 0.3 729 0.482 0.84

479 7185 119.8 571.8 1172.7 0.3 730 0.482 0.83

480 7200 120.0 572.7 1173.0 0.3 730 0.481 0.83

Page 20: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 19 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Last Floor 𝑁𝑒𝑑,4(𝐾𝑁) = 𝐺𝑘 × 𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 = 5 × 45.375 𝑚2

3rd Floor 𝑁𝑒𝑑,3 (𝐾𝑁) = 𝐺𝑘 + 0.3𝑄𝑘 × 𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 +𝑁𝑒𝑑,4

2nd Floor 𝑁𝑒𝑑,2(𝐾𝑁) = 𝐺𝑘 + 0.3𝑄𝑘 × 𝐴𝑖𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 +𝑁𝑒𝑑,3

Figure 19 – Quasi-Permanent load combination

According to the Hot Buckling spreadsheet file the value of Critical temperature can be found. The process of

calculating buckling strength of the cross sections is same as the steps done for room temperature, with difference

buckling length equal to 0.5 L = 1.75 and decay of mechanical properties (yield strength & modolus of elasticity)

at elevated temperature that should be takein into consideration at design in fire conditions. Critical temperature

for the 2nd floor: 𝜃𝑎 = 642 ℃

Figure 20 – HE200B (Hot Buckling Spreadsheet)

i) Thermal analysis of the Unprotected member

Section Factor – Assumption: Exposed on 4 sides

Last Floor Ned,4 (KN) 226.88

3rd Floor Ned,3 (KN) 480.98

2nd Floor Ned,2 (KN) 735.075

Loads on the Columns without snow

profile name = HE 200 B

bending axis (y: strong, z:weak) = z

cross-secton area - A = 7810 mm2

radius of gyration - i = 50.7 mm

buckling length - lf l = 1.75 m

yielding stress at 20°C - fy = 355 N/mm2

material factor - gM,f i = 1.0

imperfection factor - a = 0.52885073

non-dimensional slenderness a t = 0 - = 0.456

steel temperature - qa = 642.0 °C

ky ,q = 0.369

kE,q = 0.234

hot non-dimensional slenderness - q = 0.572

factor jq = 0.815

reduction factor cf i = 0.717

buckling strength - Nb,f i,q,Rd = 733 kN

design load Nf i,Ed = 735.075 kN

safety margin - Nb,f i,q,Rd / Nf i,Ed = 100%

profile name = HE 200 B

bending axis (y: strong, z:weak) = y

cross-secton area - A = 7810 mm2

radius of gyration - i = 85.4 mm

buckling length - lf l = 1.75 m

yielding stress at 20°C - fy = 355 N/mm2

material factor - gM,f i = 1.0

imperfection factor - a = 0.52885073

non-dimensional slenderness a t = 0 - = 0.271

steel temperature - qa = 663.0 °C

ky ,q = 0.319

kE,q = 0.197

hot non-dimensional slenderness - q = 0.345

factor jq = 0.651

reduction factor cf i = 0.832

buckling strength - Nb,f i,q,Rd = 735 kN

design load Nf i,Ed = 735.075 kN

safety margin - Nb,f i,q,Rd / Nf i,Ed = 100%

Page 21: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 20 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 21 – HE200B Properties

𝐴𝑚𝑉=

2ℎ + 4𝑏 − 2𝑡𝑤 − 4(2 −𝜋2)𝑟

𝑀𝑎𝑡𝑒𝑟𝑖𝑎𝑙 𝑣𝑜𝑙𝑢𝑚𝑒 𝑠𝑡𝑜𝑟𝑖𝑛𝑔 𝑡ℎ𝑒 ℎ𝑒𝑎𝑡 (𝐴𝑟𝑒𝑎)=1.151

0.00781= 147.38 𝑚−1

Correction factor for shadow effect for I profiles:

𝑘𝑠ℎ = 0.9 ×2𝑏 + 2ℎ

𝐴𝑚= 0.9 ×

800

1151= 0.625

Figure 22 – Steel Temperature spreadsheet

Calculated temp in the steel column after 2 hours is 𝜃𝑎 = 1227.9 ℃ that is higher than the critical temp, so the

fire protection should be design for the column.

ii) Thermal analysis of the Protected member

(Hollow encasement reduces the exposed surface)

The Section Factor

𝐴𝑝

𝑉=200 × 4 × 10−3

0.00781= 102.43 𝑚−1

According to design parameters for protected steel members:

Thermal ductility λp = 0.135 W/m°C

Density ρ = 550 kg/m3

Specific heat of the protection material cp = 1200 J/kg°C

Moisture content of the protection material

Protection thickness

Section Factor

And using thickness of the protection dp= 3 cm. The thermal analysis for HE 200 B – protected beam exposed to

the parametric fire evaluated in Homework 2 has done and excelsheet presented based on a time interval Δt= 15

sec.

Wpl (cm^3) = 642.5

h (mm)= 200

b (mm)= 200

A (cm^2)= 78.1

r (mm)= 18

tf (mm)= 15

tw (mm)= 9

HE 200 B

0

25 W/m2°C

0.70

147.38 1/m

0.625

5 s

steel type (1 = stainless)

coefficient of heat transfer by convection ac =

surface emissivity of the member = resultant emissivity er =

section factor Am / V =

correction factor for the shadow effect ksh =

time interval Dt =

Page 22: Fire Resistance of Materials & Structures - Analysing the Steel Structure

Page 21 of 21

Politecnico di Milano – Lecco Campus

Civil Engineering for Risk Mitigation

Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte

Seyed Mohammad Sadegh Mousavi (836154)

Figure 23 – Steel Temperature spreadsheet – Protected Member

Oputputs

Checks:

The time domain: θa = θa,cr = 642 °C, at time tcr=175 min > treq = 120 min.

The temperature domain: at time treq =120 min, θa =492.7 °C < θa,cr = 642 °C.

The load domain: at time treq = 120 min, θa =492.7 °C,

The safety margins are: y-axis: Nb,fi,Rd/Nfi,Ed = 255%

z-axis: Nb,fi,Rd/Nfi,Ed = 223%

0

0.135 W/m°C

1200 J/kg°C

550 kg/m3

0.030 m

0%

102.43 1/m

15 s

section factor for protected members Ap / V =

time interval Dt =

steel type (1 = stainless)

conductivity of protection system p =

specific heat of protection system cp =

density of protection system p =

thickness of protection system dp =

moisture content (by mass) =

step # time time steel temp. gas temp.

t t qa qg Dqg ca f Dqa

(s) (min) (°C) (°C) (°C) (J/kg°C) (1) (°C)

0 0 0.0 20.0 20.0 108.8 440 0.587 -6.58

1 15 0.3 20.0 128.8 91.6 440 0.587 -5.36

2 30 0.5 20.0 220.4 77.2 440 0.587 -4.33

3 45 0.8 20.0 297.6 65.1 440 0.587 -3.48

4 60 1.0 20.0 362.7 55.1 440 0.587 -2.76

5 75 1.3 20.0 417.8 46.7 440 0.587 -2.16

6 90 1.5 20.0 464.5 39.7 440 0.587 -1.66

7 105 1.8 20.0 504.2 33.8 440 0.587 -1.24

8 120 2.0 20.0 538.0 28.9 440 0.587 -0.88

9 135 2.3 20.0 567.0 24.9 440 0.587 -0.59

10 150 2.5 20.0 591.8 21.4 440 0.587 -0.34

11 165 2.8 20.0 613.3 18.6 440 0.587 -0.13

477 7155 119.3 490.4 1172.1 0.3 659 0.392 0.79

478 7170 119.5 491.2 1172.4 0.3 660 0.391 0.79

479 7185 119.8 491.9 1172.7 0.3 661 0.391 0.79

480 7200 120.0 492.7 1173.0 0.3 661 0.391 0.79