Fire-prevention solution on AC port circuit protectionPatent Protection

A0

Page 2: Fire prevention solution on AC power port

1. Background

3. Test Process

2. Test comparison and analysis of multiple solutions

4. Circuit cut off time and current for BCD test

Menu

5. Recommended solution of BCD product

Page 3: Fire prevention solution on AC power port

1. Background---Risks Originated from Conventional Application 1. The rated current of fuse which in series in the circuit of power, should be

higher than normal working current and withstand surge current. Assuming SPD paralleled in post circuit becomes disabled in short-circuit condition, fuse in primary circuit, it is possible not open and result in circuit catching fire.

2. Ground potential will rise up when extremely high voltage or lightning hit the ground. Because of the ground impedance(main) or uncertain factors(minor), current may reversely strike power network. In this situation, GDT in power port generates high temperature up to 1000℃ when breakdown last a while( 20A / 5S), and MOV catches fire finally.

Earthing Resistance

Page 4: Fire prevention solution on AC power port

2.Test Comparison and Analysis of Multiple Solutions FUSE+MOV+GDT

failOK OK

MOV+T-GDT T-MOV MOV

+BCD

fail

Circuit Diagram

Circuit Open Time@20A

Stability

Process Reliabilit

y

ITEM

Page 5: Fire prevention solution on AC power port

3.Test Process –Conventional Solutions

Test Environment:1000V 20A

Earthing Resistance

MOV2 MOV3

MOV1FUSE 15A

FUSE 15A

Fuse(15A) + MOV + GDT

Earthing Resistance

MOV2 MOV3

MOV1

T-GDT

MOV + T-GDT

Test Environment:1000V 20A

Page 6: Fire prevention solution on AC power port

3. Test Process- Alternative Solution of Others

Earthing Resistance

T-MOV1 T-MOV2

T-MOV3

T-MOV can not break the circuit @1000V 20A condition, also it generates the voltaic arc during the fire.

T - MOV

Test Environment:1000V 20A

Page 7: Fire prevention solution on AC power port

Earthing Resistance

MOV2 MOV3

MOV1

MOV + BCD

MOV+ Heat Shrinkable Tube +BCD

BCD

Bencent newly-developed part BCD could cut off the circuit rapidly and block the current . Test shows not a single firelight could be identified under the harsh condition of 40A thanks to wrapping heat shrinkable tube on BCD.

Test Environment:1000V 20A

3. Test Process- Alternative Solution of Bencent

Test Environment:1000V 40A

Page 8: Fire prevention solution on AC power port

4.Circuit cut off time and current for BCD test

MOV

Adjustable Resistance

AC1200V

BCD

Circuit Cut-off Time(s)

Current(A)

Page 9: Fire prevention solution on AC power port

5. Recommended Solution of BCD product

Above is circuit diagram for AC power which is common to see in telecommunication and industrial application. Fuse 1 for L and Fuse 2 for N, Fuse 3 for Safety fuse . If F1 and F2 has to pass impulse current 5KA@8/20us, then the I2t of fuse has to be more than 1000 A2s resulting in 15A static current flowing through fuse.

Above are the recommended circuit diagrams with BCD, left for differential mode(DM)protection, right for common mode(CM) integrated protection . Both solutions can save fuses (F1 for L, F2 for N). GDT can keep open both in CM and DM even when MOV fails. BCD can withstand the lightning level more than 10KA and disengaging at power current @1A.

This solution features 1.to provide simplified solution and save space in PCB layout,2. to provide fast responsiveness to cut off circuit to prevent fire.