  • 8/3/2019 Fire and Smoke Dampering

    1/3

    Fire and Smoke Dampering According to the International Building Code

    By J. Patrick Banse, P.E., Senior Mechanical Engineer, Smith, Seckman and Reid, Houston. -- Consulting-Specifying Engineer, 3/1/2007 1:00:00 AM

    Fire dampers, smoke dampers, smoke detectors, shaft enclosures, smoke barriers and fire-rated partitions, smoke compartmentation, ducted systems and transfer

    openings. There are a lot of different devices to consider in designing smoke and fire dampering systems.

    But while it may appear overwhelming and confusing, all these various types of equipment come down to one thing: life-safety protection for building occupants. Her

    want to concentrate on how these systems are defined by the International Building Code(IBC).

    So far, I've only listed some of the types of dampering equipment used in these systems. But we need to backtrack and ask a basic question: Why install dampers at

    all? The answer is that dampers are the primary means of maintaining the required rating integrity of a wall, floor or partition in order to prevent fire or smoke in the

    compartment of fire origin from entering into adjacent compartments or means of egress. This allows occupants to either shelter in place or evacuate with the building

    components remaining intact during the design time frame.

    The concept of sheltering in place is particularly important for facilities such as hospitals, outpatient facilities and nursing homes, where the occupants are generally

    not evacuated in the event of a fire and require special protection from the elements of a fire, of which smoke is one of the most dangerous. Smoke control, and thus

    dampering, is especially critical in these facilities.

    n the 2003 edition of the IBC (which I refer to because it is still more widely adopted by jurisdictions than the recent 2006 edition), Section 714 describes opening

    protectives and primarily identifies requirements for fire doors, glazing and fire shutters when required by other provisions of the code. Section 715, Ducts and

    Transfer Openings, governs the protection of ducts and air transfer openings and fire-resistance-rated assemblies. In these two sections, what the code seems to be

    aying is that dampers must be installed in air movement systems so that places of refuge, exit access and exits are maintained as smoke-free environments.

    What is the difference between smoke and fire partitions and why are dampers required? A smoke partition's primary objective is to prohibit the passage of smoke. It

    may also carry a fire rating. A fire-rated partition is a continuous membrane with a specified fire rating. Let's first look at some fire damper specifics. Fire dampers are

    built with a 1.5- and 3-hour ratings. They are designed to be installed in duct systems, penetrating 1-, 2-, and 3-hour wall and floor assemblies. Refer to Table 607.3.

    not shown here) of the International Mechanical Code(IMC). All dampers must be installed in accordance with the manufacturer's installation instructions and the U

    sting for the damper. Fire dampers are tested in accordance with UL 555 and must be labeled for use in dynamic systems designed to operate with fans turned on

    during a fire.

    Conforming to UL 555

    Fire dampers are constructed to meet the UL 555 test as to minimum construction gauge and edge seals, and are manufactured in three types: Type A, Type B and

    Type C. Type A is a frame construction with the damper framed the same size as a duct size and includes the blade stack and edge seals within the airstream,

    creating the highest air pressure drop. Type B has the blade stack out of the airstream, but the receiving channel is within the airstream. Air pressure drop is

    ubstantially reduced but does not provide full duct opening clearance. Finally, the Type C damper is mounted within a sleeve and maintains a 100% free area

    hrough the damper for a minimal air pressure drop.

    According to the IMC, an actuating device for fire dampers must meet one of three criteria:

    The operating temperature must be not less than 160F (a 165F fusible link or thermal actuating device is normally used)

    The devices's operating temperature shall not be greater than 286F where it is located in a smoke control system

    Where a combination fire/smoke damper is located in a smoke control system, the operating temperature rating should be approximately 50F above the

    maximum smoke control system designed operating temperature, or a maximum of 350F, and the temperature shall not exceed the UL 555S degradation

    temperature.

    Conforming to UL 555S

    Smoke damper ratings are subject to UL 555S testing and must be no less than Class II leakage with an elevated temperature not less than 250F. The Class II

    eakage rating translates to a maximum of 10 cfm per square foot at a differential pressure of 1.0 in. water column. As smoke dampers have four leakage

    classifications, it is important to always identify the leakage class when specifying smoke dampers. It is also important to note that the UL 555S requires the smoke

    damper and its actuator not only to be tested together but the actuator must be factory installed.

    Actuating methods for smoke dampers are identified in both the IMC and the IBC with one of five methods used for damper actuation:

    When a smoke damper is installed in a duct, a smoke detector shall be installed within five feet of the damper. (Of course, smoke control system exceptions

    do exist)

    Where a smoke damper is installed above a smoke barrier door, a spot-type detector listed for releasing service may be used

    Where a damper is installed within an unducted opening in a wall, a spot-type detector listed for releasing shall be installed within five feet of the damper

    Where a damper is installed in a corridor wall, the damper may be controlled by the corridor smoke detection system

    Where a total coverage smoke detector system is provided within the area served, the damper shall be permitted to be controlled by the smoke detection

    system.

    nspection and testing

    Page 1re and Smoke Dampering According to the International Building Code - 2007-03-01 07:00:00 | Consulti...

    1/28/tp://www.csemag.com/article/175399-Fire_and_Smoke_Dampering_According_to_the_International_Bui ...

  • 8/3/2019 Fire and Smoke Dampering

    2/3

    All fire and smoke damper installations must have suitably sized access panels for inspection and testing. All access panels must be labeled with minimum 1/2 in.

    high letters reading, Smoke Damper, Fire Damper or Fire/Smoke Damper. Fire dampers and fire/smoke dampers are required by code to be installed in rated

    partitions, walls and floors. There are also several instances where they can be omitted but, as a word of caution, all placements should be reviewed and approved b

    he authority having jurisdiction (AHJ).

    t is also advisable to review the IMC and IBC, as the language for damper placement may not be exactly the same for these two codes. For example, in the IMC, fire

    dampers are not required to be installed in duct systems that are used as part of an approved smoke control system in accordance with Section 513 of the IMC. The

    BC exception is similar, except it references Section 909 of the IBC. While both referenced sections are for smoke control systems, it is beneficial to read them both

    o ensure compliance with all aspects of the code.

    Damper actuation is still the key to proper air system operation. Control of dampers by fire alarm initiation is an option, as is initiation by the fire alarm system with

    control by the building automation system.

    Of course, exceptions exist for not installing dampers in corridor walls and shaft walls in some occupancies. These omissions generally require full sprinkler coverag

    and total coverage smoke detection. Or else they are allowed where the duct system is limited to a single smoke compartment.

    As systems are designed, it is important to remember that codes are written to protect the occupantsnot building contentsfrom fire and smoke. The AHJ always

    must be consulted to avoid any later surprises.

    RELATED CONTENT

    ICC, SFPE Collaborate on Key Initiatives

    The International Code Council (ICC), Washington, D.C., and the

    Society of Fire Protection Engineers (SFPE), Bethesda, Md.,

    announced last month that the organizations are working together on

    key strategic initiatives. The partnership is intended to facilitate fire

    protection design education and application and improve public safety

    nationwide.

    Fire protection is a crucial part of building safety and code

    compliance, said ICC CEO Rick Weiland. Performance-based fire

    protection designs are being used more and more. The code council's

    relationship with SFPE allows us to further the science of fire protection

    engineering and provide code officials with the technical assistance

    needed to review and evaluate these designs.

    SFPE's web-based training courses include the Code Official's Guide to

    Performance-Based Design, Fire Alarms Course for Fire Service/Fire

    Prevention Officer Training, Human Behavior in Fire, Principles of

    Structural Fire Protection, Sprinkler Course Fire Service/Fire

    Prevention Officer and Principles of Fire Protection Engineering.

    Other areas of cooperation include the joint development and

    distribution of new publications and training, the exchange of technical

    articles and the promotion of each other's products and services.

    The new SFPE and Code Council initiatives will enhance the already

    strong working relationship between our members, said SFPE

    Executive Director David Evans. Knowledge gained will facilitate the

    use of science and technology to protect people and property from fire

    around the world.

    In other ICC news, code enforcement and fire service officials,

    architects, engineers and other construction industry professionals will

    meet in Rochester, New York, May 20-26, for the 2007 International

    Code Council Codes Forum. Codes Forum includes the Code Council's

    Final Action Code Hearings and code update seminars.

    TALKBACK

    SUBMIT FEEDBACK

    Can a fire damper and duct detection take the place of a fire/smoke damper in a rated wall?

    jack masters - 10/12/2007 11:40:00 AM CDT

    SUBMIT FEEDBACK

    Page 2re and Smoke Dampering According to the International Building Code - 2007-03-01 07:00:00 | Consulti...

    1/28/tp://www.csemag.com/article/175399-Fire_and_Smoke_Dampering_According_to_the_International_Bui ...

  • 8/3/2019 Fire and Smoke Dampering

    3/3

    Featured Company

    SSRCx, LLC

    SSRCx, LLC is a commissioning provider that offers client-centered, high-quality services resulting in first class facilities and lasting relationships with builders

    and owners across the country. For hospitals, high-tech research labs...more

    Most Recent Resources

    Continuous architecture for your machine software

    TOPICS AUTHOR

    SPONSORED LINKS

    Resource Center Browse Categories Browse Companies

    Trends and positioning for fire protection engineers 11/30/2009

    More states adopt new standards for energy efficiency 01/28/2010

    Smoke management and the IBC 04/30/2008

    Industry Roundup 01/28/2010

    Factoring Smoke Dampers into the System 04/30/2004

    Page 3re and Smoke Dampering According to the International Building Code - 2007-03-01 07:00:00 | Consulti...

    1/28/tp://www csemag com/article/175399-Fire and Smoke Dampering According to the International Bui