K8140 & K8141 Series Installation, Commissioning and Operating Manual Man-1223 (K8140 & K8141 Series) Issue 01.07 January 2015 Fire Alarm Power Supplies

Upload: others

Post on 04-Oct-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Fire Alarm Power Supplies Installation, Commissioning and

K8140 & K8141 Series

Installation, Commissioning andOperating ManualMan-1223 (K8140 & K8141 Series) Issue 01.07 January 2015

Fire Alarm Power Supplies

Page 2: Fire Alarm Power Supplies Installation, Commissioning and

File number (S 8485)

Fire Alarm Equipment

Kentec Electronics Ltd.

Page 3: Fire Alarm Power Supplies Installation, Commissioning and

Kentec is a registered trademark of Kentec Electronics Ltd. All other product or service names are the property of their respective owners.

Copyright © 2014 Kentec Electronics Ltd. All rights reserved.

Page 4: Fire Alarm Power Supplies Installation, Commissioning and

i

Page 5: Fire Alarm Power Supplies Installation, Commissioning and

ii

Page 6: Fire Alarm Power Supplies Installation, Commissioning and

iii

Page 7: Fire Alarm Power Supplies Installation, Commissioning and
Page 8: Fire Alarm Power Supplies Installation, Commissioning and

Courier font

Page 9: Fire Alarm Power Supplies Installation, Commissioning and
Page 10: Fire Alarm Power Supplies Installation, Commissioning and
Page 11: Fire Alarm Power Supplies Installation, Commissioning and
Page 12: Fire Alarm Power Supplies Installation, Commissioning and
Page 13: Fire Alarm Power Supplies Installation, Commissioning and
Page 14: Fire Alarm Power Supplies Installation, Commissioning and

The figure below illustrates hardware features of the 10.25 Amp Power Supply:

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

F2

NONC C

C2

Battery 2

Battery 1MODEL – S408

INPUT VOLTAGE – 90V AC – 250V ACFREQUENCY – 50Hz or 60Hz

OUTPUT VOLTAGE – 22V DC – 29V DC POWER RATING – 10.25A MAX

24V BA

TTERY

- +24V D

C+ -

F2 250V 5AE N

L

ABC

D

E

F

Page 15: Fire Alarm Power Supplies Installation, Commissioning and

TB5

L5

F3J1

FB5FB7

C23

Q8

Q4

Q3

TB1

D9

QH3C3

FB6

R13

TB6

L3

SW1

D17D1

TB3

C10

Q5

J2

K2

C2

FB3FB4

Q26Q6

C81

C19

D15

C17C93

C16

C24

L6

C5

L7F2F1

C8

HS1

J5

R163

FB1

T4

C82

RV1

FB2

L10

C28

L8L9

C26

Q1

L17

R9

L1

L2C1

L4

R109

F4

T2

D12D28

Q2

K4

21

3

GND

1

+

YR

2

VO

LTA

GE

B

S408

OUT ON

+

+

DC

HIG

H

+

N

BEAT

+

ISS.07

2

DISCON

1

250V, 5A, SB, 5X20MM

L

+

14

BA T

13

1

AR

EA

2

HO

ST

I/F

+

NCC

NOGE

N TBL

HRT

BAT

FLT

LOW

BATT-

AC

+

FLT

RT

N24V

NORM

GEN

+

+

slot

slot

slot

TB6

21

TB6

21

A

B

C

D

E

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

F2 250V 5AE N

L24V D

C+ -

24V BA

TTERY

- +

Made in U.K.

EN54-4 (1997) + AC (199) + A1 (2002) + A2 (2006)

F

G

Page 16: Fire Alarm Power Supplies Installation, Commissioning and

TB5

L5

F3J1

FB5FB7

C23

Q8

Q4

Q3

TB1

D9

QH3

C3

FB6

R13

TB6

L3

SW1

D17

D1

TB3

C10

Q5

J2

K2

C2

FB3FB4

Q26Q6

C81

C19

D15

C17

C93

C16

C24

L6

C5

L7

F2F1

C8

HS1

J5

R163

FB1

T4

C82

RV1

FB2

L10

C28

L8

L9

C26

Q1

L17

R9

L1

L2C1

L4

R109

F4

T2

D12D28

Q2

K4

21

3

GND

1

+

YR

2

VO

LTA

GE

B

S408

OUT ON

+

+

DC

HIG

H

+

N

BEAT

+

ISS

.07

2

DISCON

1

250V,5A,S

B,5X20M

ML

+

14

BA T

13

1

AR

EA

2

HO

ST

I/F

+

NC

CNO

GEN

TBL

HRT

BAT

FLT

LOW

BATT-

AC

+

FLT

RT

N24V

NORM

GEN

+

+

slot

slot

slot

TB6

21

TB6 2

1

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

F2 250V 5AE N L

24V DC+ -

24V BATTERY

- +

Made in U .K.

EN54-4 (1997) + AC (199) + A1 (2002 ) + A2 (2006)

Dip Switches

TB5

L5

F3J1

FB5

FB7

C23

Q8

Q4

Q3

TB

1

D9

QH

3C

3

FB6

R13

TB6

L3

SW

1

D17

D1

TB3

C10

Q5

J2

K2

C2

FB3

FB4

Q26

Q6

C81

C19

D15

C17

C93

C16

C24

L6

C5

L7

F2F1

C8

HS1

J5

R1

63

FB1

T4

C82

RV1

FB

2

L10

C28

L8

L9

C2

6

Q1

L17

R9

L1

L2C

1

L4

R109

F4

T2

D12

D28

Q2

K4

21

3

GND

1

+

YR

2

VO

LTA

GE

B

S408

OUT ON

+

+

DC

HIG

H

+

N

BEAT

+

ISS

.07

2

DISCON

1

250V

,5A

,S

B,5

X2

0MM

L

+

14

BA T

13

1

AR

EA

2

HO

ST

I/F

+

NC

CN

OG

EN

TB

L

HRT

BAT

FLT

LOW

BA

TT

-

AC

+

FLT

RT

N24V

NORM

GEN

+

+

slot

slot

slot

TB6

21

TB6

21

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

F2 250V 5AE N L

24V DC+ -

24V BATTERY

- +

Made in U .K.

EN54-4 (1997) + AC (199) + A1 (2002 ) + A2 (2006)

Page 17: Fire Alarm Power Supplies Installation, Commissioning and

NO

+

NC

OU

T2O

UT1 IN

O/P2O/P1

C

RPSM2 ISS.03

-

-

+

+

-

F1

F2

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

A

B

E

F

G

H

J

D

C

Page 18: Fire Alarm Power Supplies Installation, Commissioning and
Page 19: Fire Alarm Power Supplies Installation, Commissioning and
Page 20: Fire Alarm Power Supplies Installation, Commissioning and
Page 21: Fire Alarm Power Supplies Installation, Commissioning and
Page 22: Fire Alarm Power Supplies Installation, Commissioning and
Page 23: Fire Alarm Power Supplies Installation, Commissioning and
Page 24: Fire Alarm Power Supplies Installation, Commissioning and
Page 25: Fire Alarm Power Supplies Installation, Commissioning and

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

F2

NONC C

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

24V BA

TTERY

- +24V D

C+ -

F2 250V 5AE N

L

C2

B

A

Page 26: Fire Alarm Power Supplies Installation, Commissioning and

C2

B

A

Page 27: Fire Alarm Power Supplies Installation, Commissioning and

TB5

L5

F3J1

FB5FB7

C23

Q8

Q4

Q3

TB1

D9

QH3C3

FB6

R13

TB6

L3

SW1

D17D1

TB3

C10

Q5

J2

K2

C2

FB3FB4

Q26Q6

C81

C19

D15

C17

C93

C16

C24

L6

C5

L7F2F1

C8

HS1

J5

R163

FB1

T4

C82

RV1

FB2

L10

C28

L8L9

C26

Q1

L17

R9

L1

L2C1

L4

R109

F4

T2

D12D28

Q2

K4

21

3

GND

1

+

YR

2

VO

LTA

GE

B

S408

OUT ON

+

+

DC

HIG

H

+

N

BEAT

+

ISS

.07

2

DISCON

1

250V,5A,SB,5X20MM

L

+

14

BA T

13

1

AR

EA

2

HO

ST

I/F

+

NCC

NOGE

NTBL

HRT

BAT

FLT

LOW

BATT-

AC

+

FLT

RT

N24V

NORM

GEN

+

+

slot

slot

slot

TB6

21

TB6 21

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

F2 250V 5AE N L

24V DC+ -

24V BATTERY

- +

Made in U .K.

EN54-4 (1997) + AC (199) + A1 (2002 ) + A2 (2006)

Page 28: Fire Alarm Power Supplies Installation, Commissioning and
Page 29: Fire Alarm Power Supplies Installation, Commissioning and

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6 21

F2

NONC C

C2

Battery 2

Battery 1MODEL – S408

INPUT VOLTAGE – 90V AC – 250V ACFREQUENCY – 50Hz or 60Hz

OUTPUT VOLTAGE – 22V DC – 29V DC POWER RATING – 10.25A MAX

24V BA

TTERY

- +24V D

C+ -

F2 250V 5AE N

L

Page 30: Fire Alarm Power Supplies Installation, Commissioning and

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6 21

F2

NONC C

C2

Battery 2

Battery 1MODEL – S408

INPUT VOLTAGE – 90V AC – 250V ACFREQUENCY – 50Hz or 60Hz

OUTPUT VOLTAGE – 22V DC – 29V DC POWER RATING – 10.25A MAX

24V BA

TTERY

- +24V D

C+ -

F2 250V 5AE N

L

( + )

( + )( - )

( - )

Page 31: Fire Alarm Power Supplies Installation, Commissioning and

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6 21

F2

NONC C

C2

Battery 2

Battery 1MODEL – S408

INPUT VOLTAGE – 90V AC – 250V ACFREQUENCY – 50Hz or 60Hz

OUTPUT VOLTAGE – 22V DC – 29V DC POWER RATING – 10.25A MAX

24V BA

TTERY

- +24V D

C+ -

F2 250V 5AE N

L

Page 32: Fire Alarm Power Supplies Installation, Commissioning and

NO

+

NC

OU

T2O

UT1 IN

O/P2O/P1

C

RPSM2 ISS.03

-

-

+

+

-

F1

F2

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

X6 X5

Page 33: Fire Alarm Power Supplies Installation, Commissioning and

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

F2

NONC C

C2

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

24V BA

TTERY

- +24V D

C+ -

F2 250V 5AE N

L

Page 34: Fire Alarm Power Supplies Installation, Commissioning and

NO

+

NC

OU

T2O

UT1 IN

O/P2O/P1

C

RPSM2 ISS.03

-

-

+

+

-

F1

F2

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

Page 35: Fire Alarm Power Supplies Installation, Commissioning and

TB5

L5

F3J1

FB5FB7

C23

Q8

Q4

Q3

TB1

D9

QH3

C3

FB6

R13

TB6

L3

SW1

D17

D1

TB3

C10

Q5

J2

K2

C2

FB3FB4

Q26Q6

C81

C19

D15

C17C93

C16

C24

L6

C5

L7F2F1

C8

HS1

J5

R163

FB1

T4

C82

RV1

FB2

L10

C28

L8

L9

C26

Q1

L17

R9

L1

L2C1

L4

R109

F4

T2

D12D28

Q2

K4

21

3

GND

1

+

YR

2

VO

LTA

GE

B

S408

OUT ON

+

+

DC

HIG

H

+

N

BEAT

+

ISS

.07

2

DISCON

1

250V,5A,S

B,5X20M

ML

+

14

BA T

13

1

AR

EA

2

HO

ST

I/F

+

NC

CNO

GEN

TBL

HRT

BAT

FLT

LOW

BATT-

AC

+

FLT

RT

N24V

NORM

GEN

+

+

slot

slot

slot

TB6

21

TB6 2

1

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

F2 250V 5AE N L

24V DC+ -

24V BATTERY

- +

Made in U .K.

EN54-4 (1997) + AC (199) + A1 (2002 ) + A2 (2006)

Page 36: Fire Alarm Power Supplies Installation, Commissioning and

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6 21

F2

NONC C

C2

Battery 2

Battery 1MODEL – S408

INPUT VOLTAGE – 90V AC – 250V ACFREQUENCY – 50Hz or 60Hz

OUTPUT VOLTAGE – 22V DC – 29V DC POWER RATING – 10.25A MAX

24V BA

TTERY

- +24V D

C+ -

F2 250V 5AE N

L

Ground-Stud

Page 37: Fire Alarm Power Supplies Installation, Commissioning and

C2

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

F2

NONC C

TB5

L5

F3J1

FB5

FB7

C23

Q8

Q 4

Q3

TB

1

D9

QH

3C

3

FB6

R13

TB6

L3

SW

1

D17

D1

TB3

C10

Q5

J2

K2

C2

FB3

FB4

Q26

Q6

C81

C19

D15

C17

C93

C16

C24

L6

C5

L7

F2F1

C8

HS1

J5

R1

63

FB1

T4

C82

RV1

FB

2

L10

C28

L8

L9

C2

6

Q1

L17

R9

L1

L2C

1

L4

R109

F4

T2

D12

D28

Q2

K4

21

3

G ND

1

+

YR

2

VO

LTA

GE

B

S408

OU T ON

+

+

D C

HIG

H

+

N

BEAT

+

ISS

.07

2

DISCO N

1

250V

,5A

,S

B,5

X2

0MM

L

+

14

BA T

13

1

AR

EA

2

HO

ST

I/F

+

NC

CN

OG

EN

TB

L

HRT

BAT

F LT

LO W

BA

TT

-

AC

+

F LT

RT

N24V

NO RM

G EN

+

+

slot

slot

slot

TB6

21

TB6

21

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

F2 250V 5AE N L

24V DC+ -

24V BATTERY

- +

Made in U .K.

EN 54 -4 (1997 ) + A C (199 ) + A 1 (2002 ) + A 2 (2006 )

Battery 1

Battery 2

AC input terminal for Line, Neutral and Ground of the external power cable. Connect the black Line wire to the “L” slot of the AC input terminal-block.

Connect the white Neutral wire to the “N” slot of the AC input terminal-block. A blue stripe is added to the illustration of the Neutral wire for image clarity.

The green Ground wire containing a yellow stripe is connected to the ground slot of the AC input terminal-block. The Ground wire connection is performed at the factory and terminates at cabinet-ground-stud.

The cabinet-ground-stud is the ground-star location for cabinet, cabinet-door and earth-ground of the power supply.

Connect the green Ground wire from the external power cable to the cabinet-ground-stud. This is the earth ground connection of the power supply.

Reference the ground symbol in the illustration for the location of the earth ground in the power supply.

C2

+

OU

T2O

UT1 IN

O/P2O/P1

RPSM2 ISS.03

-

-

+

+

-

F1

TB6

2 13

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

F2

NONC C

TB5

L5

F3J1

FB5

FB7

C23

Q8

Q 4

Q3

TB

1

D9

QH

3C3

FB6

R13

TB6

L3

SW

1

D17D1

TB3

C10

Q5

J2

K2

C2

FB3

FB4

Q26

Q6

C81

C19

D15

C17

C93

C16

C24

L6

C5

L7

F2F1

C8

HS1

J5

R1

63

FB1

T4

C82RV1

FB2

L10

C28

L8

L9

C2

6

Q1

L17

R9

L1

L2C1

L4

R109

F4

T2

D12D28

Q2

K4

21

3

G ND

1

+

YR

2

VO

LTA

GE

B

S408

OU T ON

+

+

D C

HIG

H

+

N

BEAT

+

ISS

.07

2

DISCO N

1

250V

,5A,

SB

,5X2

0MM

L

+

14

BA T

13

1

AR

EA

2

HO

ST

I/F

+

NC

CNO

GE

NT

BL

HRT

BAT

F LT

LO W

BA

TT

-

AC

+

F LT

RT

N24V

NO RM

G EN

+

+

slot

slot

slot

TB6

21

TB6

21

MODEL – S408INPUT VOLTAGE – 90V AC – 250V AC

FREQUENCY – 50Hz or 60HzOUTPUT VOLTAGE – 22V DC – 29V DC

POWER RATING – 10.25A MAX

F2 250V 5AE N L

24V DC+ -

24V BATTERY

- +

Made in U .K.

EN 54 -4 (1997 ) + AC (199 ) + A1 (2002 ) + A2 (2006 )

Relay terminals of the RPSM2 Board

OUT 1 and OUT 2 terminals are the 24V DC output terminals of the power supply.

Relay terminals of the power supply module

Page 38: Fire Alarm Power Supplies Installation, Commissioning and

1

2

3

4

5

The AC Normal LED indicator switches-off 30 seconds after removing power from the mains.

6

7

Page 39: Fire Alarm Power Supplies Installation, Commissioning and
Page 40: Fire Alarm Power Supplies Installation, Commissioning and
Page 41: Fire Alarm Power Supplies Installation, Commissioning and
Page 42: Fire Alarm Power Supplies Installation, Commissioning and
Page 43: Fire Alarm Power Supplies Installation, Commissioning and
Page 44: Fire Alarm Power Supplies Installation, Commissioning and
Page 45: Fire Alarm Power Supplies Installation, Commissioning and
Page 46: Fire Alarm Power Supplies Installation, Commissioning and
Page 47: Fire Alarm Power Supplies Installation, Commissioning and
Page 48: Fire Alarm Power Supplies Installation, Commissioning and

Pin 1

Pin 14

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Page 49: Fire Alarm Power Supplies Installation, Commissioning and
Page 50: Fire Alarm Power Supplies Installation, Commissioning and
Page 51: Fire Alarm Power Supplies Installation, Commissioning and
Page 52: Fire Alarm Power Supplies Installation, Commissioning and
Page 53: Fire Alarm Power Supplies Installation, Commissioning and
Page 54: Fire Alarm Power Supplies Installation, Commissioning and

VOUT 1 = 24V DC ( + )

( - )

( + )

Vload = 21V DC

Iload = 2 A

Voltage drop of the twin cable is

Vwire 1 + Vwire 2 = Vcable

1.5V DC + 1.5V DC = 3V DC

( - )

100 m (328 ft)

Vcable 1 = 1.5V DC

Vcable 2 = 1.5V DC

Page 55: Fire Alarm Power Supplies Installation, Commissioning and

1.0 mm 16 Ohms / Core

1.5 mm 12 Ohms / Core

2.5 mm 7.4 Ohms / Core Ft.

Page 56: Fire Alarm Power Supplies Installation, Commissioning and
Page 57: Fire Alarm Power Supplies Installation, Commissioning and
Page 58: Fire Alarm Power Supplies Installation, Commissioning and
Page 59: Fire Alarm Power Supplies Installation, Commissioning and

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Page 60: Fire Alarm Power Supplies Installation, Commissioning and

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Page 61: Fire Alarm Power Supplies Installation, Commissioning and
Page 62: Fire Alarm Power Supplies Installation, Commissioning and

0.000

0.200

0.400

0.600

0.800

1.000

1.200

1.400

1.600

0 5 10 15 20 25 30 35 40 45 50

Page 63: Fire Alarm Power Supplies Installation, Commissioning and

Wiri

ng D

iagr

am fo

r The

10.

25 A

mp

Pow

er S

uppl

y

NO

+

NC

OUT2OUT1

IN

O/P

2O

/P1

C

RP

SM

2 IS

S.03

- -+

+ -

F1 F2

TB6

21

3

TB1

21

TB6

21

TB1

21

TB6

21

TB1

21

TB6

21

A B

E

FGHJ

DC

TB5

L5

F3J1

FB5 FB7

C23

Q8

Q4

Q3

TB1

D9

QH3C3

FB6

R13

TB6

L3

SW1

D17 D1

TB3

C10

Q5

J2

K2

C2

FB3FB4 Q26Q6

C81

C19

D15

C17

C93C16

C24

L6

C5

L7

F2

F1

C8

HS1

J5

R163

FB1

T4

C82

RV1

FB2

L10

C28

L8L9

C26

Q1

L17

R9

L1

L2C1

L4

R109

F4

T2

D12 D28 Q2

K4

21 3

GN

D

1

+

YR

2

VOLTAGE B

S408

OU

TO

N

+

+

DC

HIGH

+

N

BEAT

+

ISS.07

2

DIS

CON

1

250V, 5A, SB, 5X20MML

+

14

BAT

13

1

AREA

2

HOST I/F

+

NC C NOGE N TBL

HRT

BAT

FLT

LOW

BATT-

AC

+

FLT

RTN24V

NO

RM

GE

N

+

+

slo t

sl ot

slot

TB6

21

TB6

21

A B C D E

MO

DEL

– S

408

INPU

T VO

LTAG

E –

90V

AC –

250V

AC

FREQ

UENC

Y –

50Hz

or 6

0Hz

OUT

PUT

VOLT

AGE

–22

V DC

–29

V DC

PO

WER

RAT

ING

–10

.25A

MAX

F2 250V 5AE N L24V DC

+ -24V BATTERY

- +

Mad

e in

U.K

.

EN54

-4 (

1997

) + A

C (1

99) +

A1

(200

2) +

A2

(200

6)

F G

For I

ndoo

r-D

ry U

se O

nly

10.2

5 A

mp

Pow

er S

uppl

y M

odul

eR

PSM

2 B

oard

RPS

M2

Boa

rd

Key

D

escr

iptio

n

A

OU

T1 to

fire

ala

rm e

quip

men

t

B

OU

T2 to

fire

ala

rm e

quip

men

t

C

Fuse

failu

re L

ED

indi

cato

rs

D

Con

nect

or fo

r Rib

bon

Cab

le A

ssem

bly

cont

aini

ng R

emot

e LE

D B

oard

E C

omm

on T

roub

le R

elay

F C

onne

ctor

for H

ost I

/F R

ibbo

n C

able

fro

m 1

0.25

Am

p P

ower

Sup

ply

Mod

ule.

G

Fuse

F2

for O

UT

2

H

Fuse

F1

for O

UT

1

J In

put t

erm

inal

s fro

m 2

4V a

nd R

TN o

f the

10

.25

Amp

Pow

er S

uppl

y.

Gen

eral

Spe

cific

atio

ns

AC

Inpu

t Fus

e 5

Am

p @

250

VA

C, S

low

-Blo

w, 5

x 2

0mm

Load

Fus

e S

elf-r

eset

ting

poly

fuse

rate

d @

10

Amps

, non

-repl

acea

ble

RPS

M2

Boa

rd F

uses

Tw

o 8

Amp

fuse

s pe

r boa

rd

Supe

rvis

ed In

put

120

– 24

0 V

AC

50/

60H

z, 2

75 V

A m

axim

um, n

on-p

ower

lim

ited

Tran

sfer

Vol

tage

90

VA

C

Stan

dby-

Bat

tery

Typ

e 12

VD

C, r

echa

rgea

ble,

val

ve-re

gula

ted,

lead

-aci

d

Bat

tery

Cur

rent

Dra

w

8 Am

ps m

axim

um d

raw

n fro

m s

tand

by-b

atte

ries

whe

n m

ains

is d

isco

nnec

ted

Bat

tery

Qui

esce

nt C

urre

nt

0.08

0 A

in m

ains

failu

re m

ode

Stan

dby-

Bat

tery

Cha

rgin

g

Two

stan

dby

batte

ries

wire

d in

ser

ies

Out

put V

olta

ge

24 V

DC

regu

late

d

Out

put C

urre

nt

8 Am

ps m

axim

um

Out

put R

ippl

e Vo

ltage

1.

2 Vp

k-pk

Bat

tery

Cha

rge

Volta

ge

26.4

VD

C (a

t 104

O F

, 40

O C

) to

28.9

VD

C (a

t 23O

F, -

5O C

)

Bat

tery

Cha

rge

Cur

rent

2.

25 A

max

imum

Bat

tery

Dis

conn

ect

Low

bat

tery

shu

toff

volta

ge -

19 V

(+/-

1 vo

lt)

Fiel

d W

iring

Pow

er S

uppl

y M

odul

e Te

rmin

al

Wire

Ran

ge

Des

crip

tion

Bat

tery

Con

nect

ion

+ R

ed le

ad

P

ositi

ve c

onne

ctio

n fo

r the

Sta

ndby

-bat

terie

s

- B

lack

lead

Neg

ativ

e co

nnec

tion

for t

he S

tand

by-

batte

ries

AC

Pow

er

L 12

– 1

4 AW

G

Line

con

nect

ion

N

12

– 1

4 AW

G

Neu

tral c

onne

ctio

n

E

12

– 1

4 AW

G

Gro

und

Con

nect

ion

Gen

eral

Tro

uble

Rel

ay

12

– 1

8 AW

G

24V

and

RTN

12 –

16

AWG

RPS

M2

Boa

rd

IN +

R

ed le

ad

12 –

16

AWG

P

ositi

ve c

onne

ctio

n fo

r the

RPS

M2

Boar

d

IN -

Bla

ck le

ad

12 –

16

AWG

N

egat

ive

conn

ectio

n fo

r the

RP

SM

2 B

oard

OU

T 1

+

Red

lead

12

– 1

6 AW

G

Pos

itive

con

nect

ion

for t

he R

PSM

2 Bo

ard

OU

T 1

- B

lack

lead

12

– 1

6 AW

G

Neg

ativ

e co

nnec

tion

for t

he R

PS

M2

Boa

rd

OU

T 2

+ R

ed le

ad

12 –

16

AWG

P

ositi

ve c

onne

ctio

n fo

r the

RPS

M2

Boar

d

OU

T 2

- B

lack

lead

12

– 1

6 AW

G

Neg

ativ

e co

nnec

tion

for t

he R

PS

M2

Boa

rd

Com

mon

Tro

uble

Rel

ay

NC

, C, N

O

12 –

18

AWG

N

orm

ally

clo

sed

cont

act,

com

mon

con

tact

, no

rmal

ly o

pen

cont

act.

The

Com

mon

Tro

uble

Rel

ay a

nd th

e G

ener

al T

roub

le R

elay

con

tain

vol

t fre

e co

ntac

ts ra

ted

at 3

0V D

C a

nd 1

Am

p.

Pow

er S

uppl

y M

odul

e

Key

D

escr

iptio

n

A

AC

line

inpu

t, G

roun

d, N

eutra

l, Li

ne

B

5

Amp,

Slo

w-b

low

, AC

-line

fuse

C

24

V D

C o

utpu

t, 24

V, R

TN

D

G

ener

al tr

oubl

e re

lay,

NC

, C, N

O

E

Hos

t I/F

, rib

bon

cabl

e co

nnec

tion

F

Stan

dby-

batte

ry in

put,

( - ),

( +

)

G

Fl

ying

-lead

tem

pera

ture

-sen

sor

A g

roun

d fa

ult

indi

catio

n oc

curs

on

mod

els

of th

e 10

.25

Am

p Po

wer

Su

pply

whe

n a

min

imum

of 3

0K

Ohm

s ex

ists

be

twee

n ea

rth-

grou

nd a

nd th

e 24

V te

rmin

als

of

the

10.2

5 A

mp

pow

er S

uppl

y.

RPS

M2

Boa

rd

Fuse

s

RPS

M2

Boa

rd

conn

ectio

ns a

t th

e te

rmin

als

of

OU

TPU

T 1

and

OU

TPU

T 2

pr

ovid

e se

para

tely

fuse

d an

d re

gula

ted

outp

uts.

UL

Com

plia

nce

Ope

ratin

g In

stru

ctio

ns

Ope

rate

the

10.2

5 A

mp

Pow

er S

uppl

y us

ing

O

pera

ting

Inst

ruct

ions

, K

8137

-00.

Inst

alla

tion

Req

uire

men

ts

Gro

und

Faul

t In

dica

tions

Com

bine

d St

andb

y-C

urre

nt

Stan

dard

Cab

inet

C

ombi

ned

Stan

dby-

Cur

rent

18 A

h: M

axim

um c

apac

ity fo

r st

anda

rd c

abin

et s

ize

517

mA

Dee

p C

abin

et

Com

bine

d St

andb

y-C

urre

nt

40 A

h: M

axim

um c

apac

ity fo

r de

ep c

abin

et s

ize

1.28

1 A

Com

bine

d S

tand

by-C

urre

nt in

clud

es O

UT

1 an

d O

UT

2

AC

Lin

e C

onne

ctio

ns

Term

inal

D

escr

iptio

n Vo

ltage

L A

C L

ine

120

- 240

V A

C

@ 5

0 / 6

0Hz,

S

uper

vise

d,

275V

A

Max

imum

N

AC

Neu

tral

G

Ear

th-G

roun

d

Labe

l Par

t Num

ber:

K81

38-0

0, R

evis

ion

E01.

03D

ate:

11/

26/2

014

File

num

ber (

S 84

85)

K18

40 a

nd K

1841

are

lis

ted

for c

ompl

ianc

e un

der U

L 14

81.

Fire

Ala

rm E

quip

men

t K

ente

c El

ectr

onic

s Lt

d.

Inst

all m

odel

s of

the

K18

40 a

nd K

1841

in a

ccor

danc

e w

ith th

e 10

.25

Am

p Po

wer

Su

pply

Inst

alla

tion

and

Ope

ratio

n M

anua

l, K

8139

-00.

Page 64: Fire Alarm Power Supplies Installation, Commissioning and
Page 65: Fire Alarm Power Supplies Installation, Commissioning and
Page 66: Fire Alarm Power Supplies Installation, Commissioning and

AC input fuse ...................................................... 36 AC Input Fuse ......................................... 36, 37, 38 AC Line ......................................................... 38, 58 AC Line Connection ........................................... 38 AC Neutral .......................................................... 38 Battery Charge Voltage ..................................... 39 Before you begin the installation ..................... 14 Cabling ............................................................... 41 Charge Current .................................................. 39 checklist .............................................................. 14 circuit overloads ............................................... 36 Contact Kentec technical support ................... 14 Contacting Kentec for Repair ............................. 6 Create a plan....................................................... 14 Document Conventions ....................................... 1 Earth-Ground ...................................................... 38 Electrical ............................................................. 38 Features ........................................................ 43, 45 Field Wiring......................................................... 40 File number (S 8485) ............................................ ii General Installation Checklist ........................... 13 Ground Strap ...................................................... 14 ground trouble indication .................................. 38 Ground Trouble Indication ................................ 38 If You Need Help ................................................... 1 Input (Supervised) .............................................. 38 Inspect the standby-batteries annually ............ 35 Inspecting Batteries ........................................... 35

Installing the AC Input Fuse ........................ 36, 37 Models ................................................................. 43 Mounting Hardware ........................................... 14 mounting site ...................................................... 14 NFPA 72 ............................................................... 13 Operating Environment ...................................... 41 Output Current .............................................. 38, 58 Permitted in UL 864 ? (Y / N) .............................. 12 Physical Specifications ...................................... 41 Power Supply ...................................................... 38 procedures for maintaining and repairing ....... 35 Product Return Address ..................................... 6 Rechargeable Battery Circuit ............................ 39 Relay Ratings ...................................................... 39 Removing and installing the AC input fuse 36, 37 Replace standby-batteries ................................. 35 sealed-lead-acid ................................................. 35 Selecting Standby-Batteries .............................. 15 Standby-Battery Charging ................................. 39 Standby-Battery Type ........................................ 39 Supporting Components and Replacements ... 43 supporting equipment and devices .................. 43 Test the standby-batteries annually ................. 35 Transfer Voltage ................................................. 38 Underwriters Laboratories (UL) ......................... ii Using This Manual ................................................ 1 wire length maximums ....................................... 49

Page 67: Fire Alarm Power Supplies Installation, Commissioning and