Field measurement of air velocity: pilot traverse or vane anemometer?l f A rotating vane anemometer at a downstream coil face can ( provide the same accuracy as an in-duct pitot tube traverse f i By Ronald H. Howell and Hany J. Sauer, Jr. f Fellow ASHRAE Fellow ASHRAE W hen making testing and balancing measurements in heating, ventilat- ing and air-conditioning systems, it is necessary to obtain field measurements of airflow rates in duct systems. The ac- curate measurement of airflow in an ex- isting duct system or at a coil is a very im- portant measurement and yet very dif- ficult to obtain. r---ASHRAE In most existing duct/coil situations, there is not sufficient straight duct length or even access to the duct in order to make pilot tube measurements. Some- times, the only possibility is to take veloci- ty measurements at the coil face, where there is usually access in large cabinets or built-up units, using a hand-held ane- mometer such as the rotating vane. Pltot tube measurements 46 When the pitot traverse is used in About the authors Ronald Howell is a professor of me- chanical engineering at the University of Missouri-Rolla. He received B.S., M.S. and Ph.D. degrees in mechanical engineering from the University of Illinois-Urbana, Champaign. He is cur- rently a member of the ASHRAE R& T Committee, chainnan of the R&T Pro- ject Activities Subcommittee, and chairman of the ABET Participation Committee. He is a past member of Technical Committees I.I, 1.5 and 4.7 as well as a former chairman of SPC 41.6, TC 1.3. Howell is the recipient of the ASHRAE Distinguished Service Award and Best Technical Paper Award (1986). Harry J. Sauer, Jr. is the dean of grad- uate study and professor of mechanical and aerospace engineering at the Uni- versity of Missouri-Rolla. He received B.S. and M.S. degrees from the Mis- souri School of Mines and Metallurgy and a Ph.D. degree from Kansas State University, all in mechanical engineer- ing. Sauer is currently a member of the ASHRAE Journal/Insights Commit- tee, Technical Committees 1.6 and 7.6, andSPC-116R. Previously, he served on the Technology Council and other standing, technical and standards com- mittees. round duct, 24 total and 24 static pres- sure measurements are taken at speci- fied locations along three defined dia- meters across the duct. Specifications for how and where these measurements are to be made are given in ASHRAE Stan- dard 41.2 (ASHRAE 1987). Specific de- tails concerning the calculation pro- cedure for airflow rate are also outlined in Standard 41.2. To have airflow measurements at standard density, it is necessary to take dry-bulb and wet-bulb temperature mea- surements and barometric pressure. It is also specified that the pilot tube traverse measurements are to be taken a mini- mum of 8-1/2 duct diameters down- stream from the last fitting and that a straightener needs to be installed five duct diameters upstream of the traverse. Additional details concerning pitot tube traverses, tube construction and applica- tions of tube traverses are given by Streeter (1961) and Dean (1953) . Several sources, including Con- sidine (1976), also indicate that pilot tube measurements are not practical below a velocity of about 600 fpm. At this air speed, the velocity pressure would be 0.0037 in. of water. It is impractical to ob- tain reasonable accuracy at a pressure this low during field measurements. Several investigations (Dean 1953; Sauer and Howell 1990) report that the uncertainty (difference between the true value of the quantity measured and the observed value) in the pitot tube traverse method is between 5 to 10 percent for field measurement conditions. Combin- ing these facts with the necessity for hav- ing at least 8-1 /2 duct diameters available for pilot tube traverses, there are many field measurement situations where a traverse cannot be used. Research Anemometer procedures ; Recently, ASH RAE Research Pro- l ject RP-451 (Howell and Sauer 1986, ! 1987, 1989) addressed the problem of measuring airflow rates at coil faces us- ing the rotating vane anemometer. An ii- ;, lustration of this technique is shown in j Figure 1. In a paper resulting from that ! research (Sauer and Howell 1990), a ... measurement and calculation procedure ,. was developed (see Table 1). , In Table 1, all of the corrections for anemometer calibration density and ac- , ' tual air density are taken into account. In I Step 8, the volume flow rate through the . coil for standard density (0.075 lb/ft 3 ) is calculated. In Step 9, the volume flow rate ' for the actual air density is calculated. i The procedures for anemometer calibra- tion density corrections and airflow den-1 1 sity corrections are given by ASME t (1959) and Ower and Pankhurst (1960). In the technical papers prepared from the results of ASHRAE RP-451, it is shown that the use of the k-factor and the above measurement and culation procedure using the 4-in. rotat- ing vane anemometer provides volume ... flow rates at coil faces to an accuracy of ±7 percent, which is similar to the curacy obtained using pitot tube verses (Sauer and Howell 1990; and Sauer 1990). The procedure is valid in a velocity range of 100 to 1,500 fpm. Upstream disturbances such as elbows, partially blocked coils, dampers and blasts had virtually no effect on the ac· curacy of using the k-factor concept and procedure as long as the measured. velocities are positive and relatively uniform . Unfortunately, the complete meth· odology requires values of tube dis ASHRAE JOURNAL March 199C·

Upload: others

Post on 15-Aug-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Field measurement of air velocity: pilot traverse or vane ... · dard 41.2 (ASHRAE 1987). Specific de tails concerning the calculation pro cedure for airflow rate are also outlined

Field measurement of air velocity: ~ pilot traverse or vane anemometer?l

f A rotating vane anemometer at a downstream coil face can ( provide the same accuracy as an in-duct pitot tube traverse f

i

By Ronald H. Howell and Hany J. Sauer, Jr. f

Fellow ASHRAE Fellow ASHRAE

When making testing and balancing measurements in heating, ventilat­

ing and air-conditioning systems, it is necessary to obtain field measurements of airflow rates in duct systems. The ac­curate measurement of airflow in an ex­isting duct system or at a coil is a very im­portant measurement and yet very dif­ficult to obtain.

r---ASHRAE

In most existing duct/coil situations, there is not sufficient straight duct length or even access to the duct in order to make pilot tube measurements. Some­times, the only possibility is to take veloci­ty measurements at the coil face, where there is usually access in large cabinets or built-up units, using a hand-held ane­mometer such as the rotating vane.

Pltot tube measurements

46

When the pitot traverse is used in

About the authors Ronald Howell is a professor of me­chanical engineering at the University of Missouri-Rolla. He received B.S., M.S. and Ph.D. degrees in mechanical engineering from the University of Illinois-Urbana, Champaign. He is cur­rently a member of the ASHRAE R& T Committee, chainnan of the R&T Pro­ject Activities Subcommittee, and chairman of the ABET Participation Committee. He is a past member of Technical Committees I.I, 1.5 and 4.7 as well as a former chairman of SPC 41.6, TC 1.3. Howell is the recipient of the ASHRAE Distinguished Service Award and Best Technical Paper Award (1986).

Harry J. Sauer, Jr. is the dean of grad­uate study and professor of mechanical and aerospace engineering at the Uni­versity of Missouri-Rolla. He received B.S. and M.S. degrees from the Mis­souri School of Mines and Metallurgy and a Ph.D. degree from Kansas State University, all in mechanical engineer­ing. Sauer is currently a member of the ASHRAE Journal/Insights Commit­tee, Technical Committees 1.6 and 7 .6, andSPC-116R. Previously, he served on the Technology Council and other standing, technical and standards com­mittees.

round duct, 24 total and 24 static pres­sure measurements are taken at speci­fied locations along three defined dia­meters across the duct. Specifications for how and where these measurements are to be made are given in ASHRAE Stan­dard 41.2 (ASHRAE 1987). Specific de­tails concerning the calculation pro­cedure for airflow rate are also outlined in Standard 41.2.

To have airflow measurements at standard density, it is necessary to take dry-bulb and wet-bulb temperature mea­surements and barometric pressure. It is also specified that the pilot tube traverse measurements are to be taken a mini­mum of 8-1/2 duct diameters down­stream from the last fitting and that a straightener needs to be installed five duct diameters upstream of the traverse. Additional details concerning pitot tube traverses, tube construction and applica­tions of tube traverses are given by Streeter (1961) and Dean (1953).

Several sources, including Con­sidine (1976), also indicate that pilot tube measurements are not practical below a velocity of about 600 fpm. At this air speed, the velocity pressure would be 0.0037 in. of water. It is impractical to ob­tain reasonable accuracy at a pressure this low during field measurements.

Several investigations (Dean 1953; Sauer and Howell 1990) report that the uncertainty (difference between the true value of the quantity measured and the observed value) in the pitot tube traverse method is between 5 to 10 percent for field measurement conditions. Combin­ing these facts with the necessity for hav­ing at least 8-1 /2 duct diameters available for pilot tube traverses, there are many field measurement situations where a traverse cannot be used.

Research

Anemometer procedures ;

Recently, ASH RAE Research Pro- l ject RP-451 (Howell and Sauer 1986, ! 1987, 1989) addressed the problem of measuring airflow rates at coil faces us- ~ ing the rotating vane anemometer. An ii- ;, lustration of thi s technique is shown in j Figure 1. In a paper resulting from that ! research (Sauer and Howell 1990) , a ... measurement and calculation procedure ,. was developed (see Table 1). ,

In Table 1, all of the corrections for anemometer calibration density and ac- , ' tual air density are taken into account. In I Step 8, the volume flow rate through the . coil for standard density (0.075 lb/ft3) is calculated. In Step 9, the volume flow rate ' for the actual air density is calculated. i The procedures for anemometer calibra­tion density corrections and airflow den-11

sity corrections are given by ASMEt (1959) and Ower and Pankhurst (1960).

In the technical papers prepared from the results of ASHRAE RP-451, it is shown that the use of the k-factor concept~ and the above measurement and cal- ~ culation procedure using the 4-in. rotat­ing vane anemometer provides volume ... flow rates at coil faces to an accuracy of ±7 percent, which is similar to the ac· ~ curacy obtained using pitot tube tra~~ verses (Sauer and Howell 1990; Howell ~ and Sauer 1990). The procedure is valid in a velocity range of 100 to 1,500 fpm. Upstream disturbances such as elbows, partially blocked coils, dampers and fan ~ blasts had virtually no effect on the ac· curacy of using the k-factor concept and procedure as long as the measured. velocities are positive and relatively uniform .

Unfortunately, the complete meth· odology requires values of tube dis

ASHRAE JOURNAL March 199C·

Page 2: Field measurement of air velocity: pilot traverse or vane ... · dard 41.2 (ASHRAE 1987). Specific de tails concerning the calculation pro cedure for airflow rate are also outlined

r: proceedings of the ASHRAE IAQ 89 Conference in San Diego, CA

r? The Human Equation: Health and Comfort

an ~se In the tradition of IAQ 86, '01and88, ASHRAE

brings you the collection of indoor air quality conference papers presented in 1989-The Human Equation: Health and Comfort.

This year the focus of the 1989 conference was on the human effects of indoor air quality -a timely subject as the general public becomes more sensitive to indoor air quality issues.

The topics covered include: government activities in indoor air quality; pollutants and respective health effects; epidemio­logic approaches; air purification and humidity; ventilation and pressurization; case studies and investigations, evaluations and calculations.

IAQ89

The Human Equation:

Health and

Comfort

i l ! I ~

t. j I l

I ~ t > ?

t t ~

8h Pro· r 1986, blem of tees us· ar. An ii· 1own in om that 990), a :)Cedure

tions for and ac·

:':ount. In )Ugh the lb/ft3} is flow rate

, I

Code: 90063 11

List: $65.00 Member: $44.00 I' -----------------------------------------------------·t

lculated. r calibra· :1ow den­y ASME : (1960).

D Yes, please send me __ copy/ies of The Human Equation: Health and Comfort, IAQ 89.

Code: 90063 D List: $65.00 D Member: $44.00

)repared Membership Number '-451, it is r concepl ~---------------­and cal Name

~-in . rotat· s volume E::::::-:-~~------------­curacy Street Address (No PO Boxes. please.) o the ac· tube tra Fc:::·t-:------------------0; Ho 1 y ire is vall ,500 lprTlfC~=-=--=---------------­iS etbo rs and f )n the a:Cf7:::------------------­ncept a -neasur

relatlvelli"::0::-:u:::nt:---ry---------------

hone

Payment Options:

0 Check (U.S. funds only, please.)

0 VISA 0 MasterCard 0 American Express

Credit Card No.

Expiration Date

Signature (required)

Mail your order form and payment to Publication Sales/ ASH RAE/ 1791 Tullie Circle, NE/ Atl?11ta, GA 30329-2305. Call or fax your credit card order. Phone: ( 404) 636-8400 or Fax: (404) 321-5478.

! f t i

I I i

Page 3: Field measurement of air velocity: pilot traverse or vane ... · dard 41.2 (ASHRAE 1987). Specific de tails concerning the calculation pro cedure for airflow rate are also outlined

. j

Air velocity

meter, tube spacing , fins per inch, num­ber of tube rows, and actual air density. Of interest is the loss in accuracy if these factors are not known. Two specific cases of proceeding with less than complete

input were evaluated: density correction neglected ; and correlation of k-factor with face velocity only.

A modified procedure without densi­ty correction is identical to the previous

Figure 1. Positioning of rotating vane anemometer on the downstream side of dry coil at the face.

.. ·.

procedure except that the velocit) readings obtained in Step 4 are not cor rected to standard density at which thE anemometer was calibrated as indicatec in Step 5. The modified procedure i~ given in Table 2.

Simplified procedure

In this procedure, the k-factor is cor related only to face velocity and neglectf the separate effects of all other coil parn. meters, including air density. Figure ;: shows all of the k-factor data for the 4-in anemometer at all of the coil faces testec in ASHRAE RP-451. The best fit curve has been put through the data and the ± 10 percent deviation lines are alsc shown. Virtually all of the results lie withir the ± 10 percent accuracy limits .

In Figure 2, the k-factor is plottec · versus the average anemometer velocity of the traverse. By using the equatior· given in Figure 2, the user does not neec . to know number of rows, fins per inch , tube spacing or tube diameter for the j coil. This simplified procedure is given ir. Tabie3. I Comparison of the procedures I

Calculations were made for various

Selected Function Modules Available

l

48

® ® /lllQDU-/lllAX by H~CAC uses a "building block"

concept to create water treatment systems which meet a wide range of specifications . This modular approach to cooling tower and boiler water control offers flexibility previously nonexistent on conventional controllers. Each controller is manufactured to customer's specifications . This feature enables the user to "build" each controller with basic components and odd-on modules to accomplish only the functions required for each installation.

CALL TODAY, FOR A QUOTE TO YOUR SPECIFICATIONS 800-638-9566 or 301-228-5111

(Circle No. 29 on Reader Service Card)

e Boiler Blowdown Control Module with Indicating Dial or Bar Graph Display

e Tower Conductivity Control Module with Indicating Dial or Digital Display

e pH Control Module

e Counter - Timer Control Module

e Hi- Lo Conductivity Alarm Module

e Flasher/Driver Module for Alarm Outputs

e Time - Out Module to Eliminate Overfeed

• Various Relay Modules

CAMBRIDGE SCIENTIFIC INDUSTRIES: • ' '- ~C)x ,:Jb~ 1 ~'l.f'vlHH!f-:J, ,f V11 'b' J ..,..

ASHAAE JOURNAL March 1990

Page 4: Field measurement of air velocity: pilot traverse or vane ... · dard 41.2 (ASHRAE 1987). Specific de tails concerning the calculation pro cedure for airflow rate are also outlined

velocity not cor. 1ich the 1dicated ~dure is

>r is cor-1eglects oil para­=igure 2 the 4-in. s tested it curve and the ire also 1ewithin

plotted velocity quation 1ot need er inch, · for the given in

s various

1 le lule

ule

Jte

II

rows of tubes, tube diameters, tube spac­ing and fins per inch on coils with various values of air density. In these calcula­uons. the average velocity reading for the anemometer is varied from 100 to 1,400 fpm Fo~ all of these conditions, the actual volume flow rates are determined using the three measurement techniques de­scribed in the three tables.

The volume determined using the technique without density correction (Table 2) is compared to the RP-451 :echnique (Table 1). The simplified pro· cedure in Table 3 is also compared to the RP-451 technique. The maximum error at 600 tom in reference to the RP-451 :ecr!'.(1ue is computed for density varia· :ion between ± 10 percent of standard '.Jensrry.

In Figure 3, the error in the airflow measured quantity in percent is plotted for variations in the air density of plus to minus 10 percent from standard density of O.D75 lb/tt3. One bar graph is for the Modified Procedure Without Density Correction (Table 2). The maximum error ~ound there was about ±5 percent for a : 10 percent departure in the air density

:rom standard density. The other bar graph is for the Sim·

plified Procedure (Table 3) . The max­imum error for this procedure was plus 1°7 percent to minus 19 percent for a density departure of ± 10 percent. However, observe that at standard density (0 per­cent departure from standard density in Figure 3), the error due to not consider­ing rows of tubes, tube diameter, tube spacing and fins per inch was ±13 per­cent. This means that there is still about a ±5 percent deviation due to ignoring density corrections with a ± 10 percent density variation in this technique.

Conclusions

For the greatest precision in using a rotating vane anemometer at a coil face, the RP-451 Measurement and Calcula­tion Procedure shown in Table 1 should be used. This technique yields volume flow measurements accurate to within ± 7 percent, similar to the accuracy ex­pected from pilot tube measurements.

If the Modified Procedure Without Density Correction shown in Table 2 is used, up to an additional ±5 percent error could occur if the density is different from standard air density by ± 10 percent.

If the Simplified Procedure shown in Table 3 is used, an additional error of up to 19 percent in comparison to the RP-451 Measurement and Calculation Procedure could occur, with a density departure from standard air density of ±10 percent.

The user would have to decide how much error can be tolerated in trade-off for the simpler procedure in taking mea­surements. In general, it appears that the additional accuracy is well worth the ef· fort required in measuring the air density and determining the number of rows, tube diameter, tube spacing and fins per inch.

Table 1. RP-451 Measurement and Calculation Procedure

Step 1. Mark the coil so that standard and offset location readings can be taken on a dry coil on the downstream side. This should all be done according to the pat­tern indicated in Figure 4.

Step 2. Measure the coil height and width, and calculate the coil face area from

A= H x L/144 where:

Now you can get the Apco-matic Variable Speed Pumping System from Aurora Pump.

• Competitive Price • Lowest Installation Cost • Easy to Install • Easy to Start Up • Easy to Use and Upgrade

You save money in a wide range of HVAC pumping applications with the Apco-matic Variable Speed Pumping System.

Now you can get this dependable, reliable, and easy to use system that has been field-proven in thousands of installations for over 25 years.

Write or call for a free product bulletin.

800 North Airport Road North Aurora, IL 60542

TEL: (708) 859-7000 FAX: (708) 859-7060

:h 1990 ASHRAE JOURNAL March 1990 (Circle No. 30 on Reader Service Card)

49

Page 5: Field measurement of air velocity: pilot traverse or vane ... · dard 41.2 (ASHRAE 1987). Specific de tails concerning the calculation pro cedure for airflow rate are also outlined

Air velocity

A = coil face area, ft2

H = height of coil, in. L = length of coil, in.

Step 3. With the air flowing through the coil, measure the air dry-bulb tempera­ture, the wet-bulb temperature. and the barometric pressure. Calculate the spe­cific volume of the air flowing through the coil from

v = R8 T/P (1+1.6078 W)

where: v = specific volume, ft3 /lb

Ra = gas constant for air,

and

53.35 ft-lb1/lbm 0 R T = absolute temperature, 0 R P = total pressure. lb1/ft2

W = ·humidity ratio, lb)lba

w = (1093 - o.556 n w; - 0.24 (t - 1·) 1093 + 0.444 t - t*

where: t = air dry-bulb temperature. °F

t* = air wet-bulb temperature, °F W5 = humidity ratio of saturated air at

the wet-bulb temperature

P* ws = 0.62198 p - WP* w

P~ = saturation pressure for water vapor at the wet-bulb temperature

Step 4. Using a calibrated 4-inch rotating vane anemometer (calibrated to stan­dard density air), take 19 velocity read­ings at the standard location and 19 readings at the offset location (Figure 4).

a Measured Best Fit ±.100/olines

KAPROX = 0.616149 + 1.835E-04 x VAVG + 9.59 E-08 x VAVG 2

where:

50

KA PR OX = approximate k-factor tor the001I w1th·ou1 correcung lor density. rows of tubes. tube spacing, tOl:le dla'meter. a,nd fins per in.

VAVG = average air velocity for the 3&measured c0ll velocities from a traverse. fpm

0:3 0.5 0. 7 O ;~ t. I 1.3

(Thousands)

·K-factor variation with velocity only. -------

Departure from Standard Density, o/o

Figure 3. Comparison of the technique accuracy evaluated at 600 fpm face velocity.

..

These are to be fixed location readings 1~ •• allowing a reasonable time for the ane­mometer to respond to the velocity at that location (5-15 seconds}.

Step 5. Correct the measured velocity readings from Step 4 to standard density air at which the anemometer was cali­brated according to

MVSTD = V x (13.33/v)1' 2

where: V = measured velocity, fpm v = specific volume of air. ft3/lb

MVSTD = corrected velocity for calibra­tion density, fpm

Step 6. Determine the average velocity reading at the coil face using

where:

38

!:; MVSTD; MVSTDAV = _i=-1---

38

MVSTDAV average air velocity for the 38 measured coil velocities. fpm

Step 7 Determine the K-factor for this coil J. from the following equation.

KSTD = a0 + a, x MVSTDAV

where:

+ a2 x ROWS + a3 x FPI

+ a4 x SP + a5 x D

+ a6 x MVSTDAV2

MVSTDAV = average air velocity for the 38 measured coil velocities. fpm

ROWS = number of rows deep of tubes in coil

FPI = fins per inch for the coil SP = tube spacing at the coil

face. in. D = tube outside diameter, in.

KSTD = k-factor for coil and for 4-in. anemometers

aa o.65204515 a, 0.0001761 63 a2 0.000971875 a3 = - 0.006745072 a4 0.04736985 a5 = - 0.091 11 685 a6 = -8.68316 E- 08

Step 8. Calculate the volume flow rate through the coil from

OSTD = Ax MVSTDAV x KSTD

where:

QSTD = volume flow rate at stan­dard density air, scfm

Step 9. If the actual flow rate is desired, calculate this from

OACT = QSTD x v/13.33

where:

OACT =volume flow rate at actual i density air ihrough the

- coil, fpm

ASHRAE JOURNAL March 1990

'

Page 6: Field measurement of air velocity: pilot traverse or vane ... · dard 41.2 (ASHRAE 1987). Specific de tails concerning the calculation pro cedure for airflow rate are also outlined

ngs me­t hat

1city 1sity :ali-

b bra-

icily

coil

Pl

r

of

>ii iii

·,in.

rate ,

D

tn-

ired,

tual

1990

Table 2. Modified Procedure Without Density Correction

Step 1. Mark the coil s.o that standard and r, ffset location readings can be tak­en or; a dry coil on the downstream side. This should be done according to the pattern indicated in Figure 4 .

Step 2. Measure the coil height and width, and calculate the coil face area

from A = H x L/144

y z

1

A • 012 ' B~ L+ 2Dl6 C~L+0/4 E •· 2L + 016 f•U2 ... , .. ~

~ .. 0 +SP/2 · N; ... H + D-4SP/4 ·O H-SP/2 P.-..c3Ft-D-2SP/4 0 ~ 2H-_D-SP/l

where: A = coil face area, ft2

H = height of coil, in. L = length of coil, in.

Step 3. Using a calibrate 4-in. rotating vane anemometer, take 19 velocity read­ings at the standard location and 19 readings at the offset location (Figure 4). These are to be fixed location readings allowing a reasonable time for the ane­mometer to respond to the velocity at that location (5-15 seconds).

u = 012 W=H+D/4 X = Hl2 Y = 3H-D/4 Z = H-012

H =-Height of coil, in. l - Length of coil, in. D = Diameter of rotating

vane anemometer head, in,

SP= Tube spacing of coil. in.

ct:f. Figure 4. Location of anemometer readings taken on a dry coil on the downstream side for the k-factor procedure.

ASHRAE JOURNAL March 1990

Step 4. Determine the average velocity reading at the coil face using

38

L V; VAVG =~

where: 38

V; = measured velocity at the ith location on the coil face, fpm

VAVG = average air velocity for the 38 measured coil velocities, fpm

Step 5. Determine the K-factor for this coil from the following equation.

where:

KA = Clo + a1 x VAVG

+ a2 x ROWS + a3 x FPI

+ a4 x SP + a5 x D

+ a6 x VAVG2

KA = K-factor for this coil without any density correction factor

VAVG = average air velocity for the 38 measured coil velocities, fpm

ROWS = number of rows deep of tubes in coil

FPI = fins per in. for the coil SP = tube spacing at the coil face,

in. D = tube outside diameter, in.

and for 4-in. anemometers

a0 0.65204515 a1 0.000176163 a2 0.000971875 a3 = - 0.0067 45072 a4 0.04736985 as = - 0.09111685 a6 = -8.68316 E-08

Step 6. Calculate the actual volume flow rate through the coil from

QACT = A x VAVG x KA

where: QACT = volume flow rate at ac­

tual density air through the coil, cfm

Step 7. If the volume flow rate of standard density air is desired, calculate this from

QSTD = QACT x 13.33/v

where: QSTD = volume flow rate at stan­

dard density air, scfm v = specific volume of the air

flowing through the coil. This can be determined from Table 1, Step 3.

Table 3. Simplified Procedure

Step 1. Mark the coil so that standard and offset location readings can be tak­en on a dry coil on the downstream side. This should be done according to the pattern indicated in Figure 4.

51

I

' ~

i

i i

l

I l j;

f

Page 7: Field measurement of air velocity: pilot traverse or vane ... · dard 41.2 (ASHRAE 1987). Specific de tails concerning the calculation pro cedure for airflow rate are also outlined

Air velocity

Step 2. Measure the coil height and width, and calculate the coil face area from

where:

A=Hxl

A = coil face area, ft2

H = height of coil, in. L = length of coil, in.

Step 3. Using a calibrated 4-in. rotating vane anemometer, take 19 velocity read­ings at the standard location and 19 readings at the offset location (Figure 4). These are to be fixed location readings allowing a reasonable time for the ane­mometer to respond to the velocity at that location (5-15 seconds).

Step 4. Determine the average velocity reading at the coil face using

where:

38

I; V; VAVG=~

38

V; = measured velocity at the ith location on the coil face, fpm

VAVG = average air velocity for the 38 measured coil

velocities, fpm

Step 5. Determine the K-factor for this coil from the following equation from Figure 2.

KAPROX = 0.616149 + 1.835E-04 x VAVG + 9.59E-08 VAVG 2

where: KAP ROX = approximate K-factor for

the coil without correcting for density, rows of tubes, tube spacing, tube dia­meter, and fins per in.

Step 6. Calculate the actual volume flow rate through the coil from

OACT = A x VAVG x KAPROX

where: OACT = volume flow rate at actual

density air through the coil, cfm

Step 7. If the volume flow rate of standard density air is desired, calculate this from

QSTO = OACT x 13.33/v

where: QSTD = volume flow rate at stan­

dard density air, scfm v = specific volume of the air

flowing through the coil.

References

This can be determined from Table 1, Step 3.

ASHRAE. 1987, "Standard methods for laboratory air-flow measurement." ASHRAE Standard 41.2· 1987. Atlanta: American Society of Heating, Refrig­erating , and Air-Conditioning Engineers.

ASME. 1959. Fluid Meters: Their Theory and Appli· cation. 5th Ed. New York: The American Society of Mechanical Engineers.

Considine, D.M . 1976. Van Nostrand's Scientific En· cyclopedia, 5th Ed., New York: Van Nostrand Pub· lishing Co.

Dean, R.C. Jr. 1953. Aerodynamic Measurements. Cambridge, Massachusetts: MIT Press.

Howell , R.H ., Sauer, H.J. Jr. 1986, 1987, 1989. "Cor· rection factors tor measurement of airflow rate through coils using the rotating vane anemometm" ASHRAE Transactions, V. 92, Pt. 1; V. 93, Pt. 2; V. 95, Pt. 2.

Howell. R.H., Sauer, H.J. Jr. 1990. "Airflow measure­ments at coil faces with vane anemometers: experi· mental results." To be published in ASHRAE Transac· tions, V. 96, Pt. 1.

Ower, E., Pankhurst, R.C. 1966. The Measurement a/ Airflow. Pergamon Press.

Sauer, H.J. Jr., Howell, R.H. 1990. "Airflow measure· ments at coil faces with vane anemometers: statis· tical correlation and recommended field measure· ment procedure." To be published in ASH RAE Tran· sactions, V. 96, Pt. 1.

Streeter, V.L. 1961. Handbook of Fluid Dynamics.~ New York: McGraw-Hill Publishing Co. &.

~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~-!

52

CUAAAMTEED THERMAL 1'£111'00MANCE

**** LOOKING FOR OVERSEAS AGENTS

****

• IMPROVEMENT OF ENVIRONMENTAL CONDITIONS Low noise and low drift types can be supplied on request

• WITH HIGH EFFICIENCY AND LOW OPERATION COST

MEMBER OF COOLING TOWER INSTITUfE

The axial flow Ian is selected for maximum performance with minimum energy consumption

• LONG LIFE TOWER Made of NON-CORROSIVE material, assures you of MINIMIZED maintenance cost

• EASY INSTALLATION AND RELIABLE OPERATION With lighter weight and "BOITLE" shaped design, assures you of a great saving in MONEY and MANPOWER at installation and in reliable plant operation

• MESAN COVER FULL RANGE OF COOLING lUWERS Towers for use both in AIR CONDITIONING plants and INDUSTRY are available at anytime

• CONTROLS MICROBIAL CONTAMINATION Meets Australian Standard on measures to control Legionnaires' Disease

MESAN FIBERGLASS ENGINEERING (INTERNATIONAL) 110. Rex Building 2JF, 648-652 Nathan Road , Mongkok, Kowloon, Hong Kong Tel: 852-787-5717 Fax: 852-787-2983

(Circle No. 31 on Reader Service Card) ASHRAE JOURNAL March 1990

f

I I

E A d ic.

n ~·r

s It r