• FB-1210 DUAL TURBINE •BI-DIRECTIONAL
INSERTION FLOW METERANALOG OUTPUT
DESCRIPTIONONICON insertion turbine flow meters are suitable for measuring electrically conductive water-based liquids. The FB-1210 model provides non-isolated 4-20 mA and 0-10 V analog output signals that are linear with the flow rate as well as a binary (digital) dry contact output for flow direction.
APPLICATIONS• Primary/secondary decoupling loop (bypass)• HVAC thermal storage tank• Domestic water tank charge/discharge
GENERAL SPECIFICATIONSACCURACY
± 0.5% of reading at calibrated velocity ± 1% of reading from 3 to 30 ft/s (10:1 range)± 2% of reading from 0.4 to 20 ft/s (50:1 range)
SENSING METHODElectronic impedance sensing
(non-magnetic and non-photoelectric)PIPE SIZE RANGE
2½” through 72” nominal diameterSUPPLY VOLTAGE 24 ± 4 V AC/DC at 90 mALIQUID TEMPERATURE RANGE
Standard: 180° F continuous, 200° F peakHigh Temp: 280° F continuous, 300° F peakMeters operating above 250° F require 316 SS
construction optionAMBIENT TEMPERATURE RANGE -5° to 160° F (-20° to 70° C)OPERATING PRESSURE 400 PSI maximumPRESSURE DROP
Less than 1 PSI at 20 ft/s in 2½” pipe, decreasing in larger pipes and lower
velocitiesOUTPUT SIGNALS PROVIDED
Directional Contact Output Isolated solid state dry contact Contact rating: 100 mA, 50 VSwitch closed when flow is in direction of arrowLatches at 0.18 ft/sSwitches within 20 seconds of direction change
Analog Output (non-isolated) Voltage output: 0-10 V (0-5 available)
Current output: 4-20 mAFrequency Output
0 – 15 V peak pulse, typically less than 300 Hz
(continued on back)
CALIBRATION
Every ONICON flow meter is wet calibrated in a flow laboratory against primary volumetric standards that are directly traceable to N.I.S.T. A certificate of calibration accompanies every meter.
FEATURES
Unmatched Price vs Performance - Custom calibrated, highly accurate instrumentation at very competitive prices.
Excellent Long-term Reliability - Patented electronic sensing is resistant to scale and particulate matter. Low mass turbines with engineered jewel bearing systems provide a mechanical system that virtually does not wear.
Industry Leading Two-year “No-fault” Warranty - Reduces start-up costs with extended coverage to include accidental installation damage (miswiring, etc.) Certain exclusions apply. See our complete warranty statement for details.
Installation Flexibility - Patented dual turbine models deliver outstanding accuracy in short pipe runs.
Simplified Hot Tap Insertion Design - Standard on every insertion flow meter. Allows for insertion and removal by hand without system shutdown.
Made in the USA
OPERATING RANGE FOR COMMON PIPE SIZES
0.17 TO 20 ft/s±2% accuracy begins at 0.4 ft/s
Pipe Size (Inches) Flow Rate (GPM)
2 ½ 2.5 - 2303 4 - 4604 8 - 8006 15 - 1,8008 26 - 3,10010 42 - 4,90012 60 - 7,05014 72 - 8,60016 98 - 11,40018 120 - 14,60020 150 - 18,10024 230 - 26,50030 360 - 41,90036 510 - 60,900
Typically 30" - 36"
depending on pipe size andheight of valve
assembly.
CLEARANCE REQUIRED
FOR INSTALLATION
½" FNPT conduit connection
Minimum Hole Size = 1"Must be centered
Insertion depthgage provided with each meter
FLOW
Connect factory wiresto field wires in appropriatejunction box.
Standard Installation Kit for Steel Pipe
1" Full port ball valve1" Close nipple 1" Branch outlet
Detail of hot tap adapterwith turbine assemblywithdrawn
1¼" for hot tap
To control system Onicon
Display orBTU Meter(Optional)
Typical Meter Installation(New construction or scheduled shutdown)
THIS AREA ACCEPTABLE
Horizontal Run Pipe
Acceptable to install in vertical pipe
Position meter anywhere in upper 240°for horizontal pipe
•
•
FB-1210 Wiring InformationWIRE COLOR DESCRIPTION NOTES
RED (+) 24 V AC/DCsupply voltage, 90 mA
Connect to power supply positive
BLACK (-) Common ground (Common with pipe ground)
Connect to power supply negative
GREEN (+) Frequency output signal: 0-15 V peak pulse
Required when meter is connected to local display or Btu meter
BLUE (+) Analog signal:4-20 mA (non-isolated) Both signals may be used
independentlyBROWN (+) Analog signal:
0-10 V (non-isolated)
GRAY Dry contact directional output - indicates flow direction
Contact closed when flow is in direction of arrow on meterVIOLET
DIAGNOSTIC SIGNALS
ORANGE Bottom turbine frequency These signals are for diagnostic purposes - connect to local display or Btu meterWHITE Top turbine frequency
FB-1210 Wiring DiagramFlow meter into control system (no display or Btu meter)
FB-1210 SPECIFICATIONS cont.MATERIAL
Wetted metal components: Standard: Electroless nickel plated brass
Optional: 316 stainless steelELECTRONICS ENCLOSURE
Standard: Weathertight aluminum enclosureOptional: Submersible enclosure
ELECTRICAL CONNECTIONS5-wire for minimum for directional switch and either 4-20 mA or 0-10 V outputSecond analog output and/or frequency output
requires additional wiresStandard: 10’ of cable with ½” NPT
conduit connectionOptional: plenum rated cable
ALSO AVAILABLE
NOTE: 1. Black wire is common with the pipe ground (typically earth ground).2. Frequency outputrequired for ONICON
display module or Btu meter, refer to wiring diagram for peripheral
device.
SCROLL RESET PROGRAM10 3/4”
6”Display Modules Btu Measurement Systems
NOTE: Installation kits vary based on pipe material and application. For installations in pressurized (live) systems, use “hot tap” 1¼” installation kit and drill hole using a 1” wet tap drill.
Power Source
• + 24 V• COM
Control System• SIGNAL GROUND• ANALOG SIGNAL INPUT
• •
REDBLACK
BLUEBROWN
GRAYVIOLET
••
•• OR
BINARY (DIGITAL) INPUT (DIRECTION)