faultv6.2.xls

5
Job Name Company Name Available Fault Current Calculatio Utility Fault Current amperes kVA 300 E 240 trans. FL 1250 E = PF = 90% transform Z 3% % 46,296 amperes Point to Point Method Length (distance) L 150 'f ' fact 2 x L x I (ASC) 46,296 # conductors per phase N 1 Phase conductor consta C 13,923 Phase Con 240 Volt f 4.156 Neutral conductor const C 13,923 Neutral C Multiplier 120 Volt f 8.313 1 + f Line to Line M 0.194 Line to Neutral M 0.107 Fault Current at Service Equipment 8,978 7,457 Fault Current from Service disc. to panel "_____" Single Phase Feeder Length (distance) L 40 'f ' fact 2 x L x I (ASC) 8,978 Phase # conductors per phase N 1 Phase conductor consta C 2,430 Phase Con 240 Volt f 1.231 Neutral conductor const C 1,995 Neutral C 120 Volt Multiplier f 2.492 Line to Line M 0.448 I = kVA x 1000 = trans. FLA Isca = trans. FLA x 1 Isca = ampere short-circuit current RMS symmetrical. Isca Isca N x C x E L-N Volt Line to Line E L - L Volt Line to Neutral E L - N M = 1 Isca x M = fault current at terminals of main disconnect L- L = Isca x M = fault current at terminals of main disconnect L- N = Isca N x C x E L-N Volt Line to Line E L - L Volt Line to Neutral E L - N M = 1 Step 1 factor transf insert th and imped voltage f and Phase the value or Step 1a: Insert available fault current ampere rating from local utility Step 3: Insert the Length of one conductor Step 4: Insert the number of conductors per phase. Step 2: Select type of conductor and conduit S ne Step 5a: Select phase conductor size size. Finished product CALCULATED FAULT CURRENT Personalize by entering the 'Job Name' and 'Your Company Name' Continue by entering next point to point

Upload: adil-aberkan

Post on 24-Dec-2015

16 views

Category:

Documents


9 download

DESCRIPTION

FaultV6.2.xls

TRANSCRIPT

Page 1: FaultV6.2.xls

Job Name

Company Name

Available Fault Current Calculation by:John Sokolik

Utility Fault Current amperes kVA = 300 E = 240

trans. FLA = 1250E

= PF = 90%

transformer Z Z = 3% %46,296 amperes

Point to Point MethodLength (distance) L = 150

'f ' factor = 2 x L x I (ASC) 46,296

# conductors per phase N = 1 Phase conductor constant C = 13,923 Phase Conductor

240 Volt f = 4.156

Neutral conductor constant C = 13,923 Neutral ConductorMultiplier 120 Volt

f = 8.313

1 + f Line to Line M = 0.194Line to Neutral M = 0.107

Fault Current at Service Equipment

8,978 amperes7,457 amperes

Fault Current from Service disc. to panel "_____"

Single Phase Feeder Length (distance) L = 40

'f ' factor = 2 x L x I (ASC) 8,978 Phase 7,457

# conductors per phase N = 1 Phase conductor constant C = 2,430 Phase Conductor

240 Volt f = 1.231

Neutral conductor constant C = 1,995 Neutral Conductor120 Volt

Multiplier f = 2.492

Line to Line M = 0.448

I = kVA x 1000 = trans. FLA

Isca = trans. FLA x 100

Isca = ampere short-circuit current RMS symmetrical. Isca =

Isca = N x C x E L-N

Volt Line to Line E L - L =

Volt Line to Neutral E L - N =

M = 1

Isca x M = fault current at terminals of main disconnect L- L = Isca x M = fault current at terminals of main disconnect L- N =

Isca = N x C x E L-N

Volt Line to Line E L - L =

Volt Line to Neutral E L - N =

M = 1

Step 1b: Insert the kVA rating (PF) power factor and (Z) impedence of transformer. (Note: When you insert the kVA rating, power factor and impedence you must select a voltage from the select the Voltage and Phase from dropdown box before the value will be calculated.)

or

Step 1a: Insert available fault current ampere rating

from local utility

Step 3: Insert the Length of one conductor

Step 4: Insert the number of conductors per phase.

Step 2: Select type of conductor and conduit

Step 5b: Select neutral conductor size.

Step 5a: Select phase conductor size size.

Finished product CALCULATED FAULT

CURRENT

Personalize by enteringthe 'Job Name' and

'Your Company Name'

Continue by entering next point to point

F8
Clear Contents from this cell if using Step 1b.
I8
If you have inserted the Utility Fault Current amps, inserting the kVA in this cell is not required. If available fault current is not known, insert transformer kVA rating here.
I9
This value will be filled in when you 'Select Voltage & Phase' from the first dropdown box
I14
If you have inserted the Utility Fault Current amps inserting trans. impedence in this cell is not required. If transformer fault current is not known, insert transformer impedence here.
I18
Enter the length of one phase conductor in the group
I20
Enter the number of electrical conductors per phase between the transformer and the equipment
I21
Select a conductor and raceway from the top drop down box Then select phase conductor size from AWG drop down box.
I24
Select neutral conductor size from AWG drop down box.
I40
Data from above calculation
K40
Data from above calculation
I42
To select a conductor check the appropriate box to the right of the largest phase conductor
Page 2: FaultV6.2.xls

1 + f Line to Neutral M = 0.286

4,024 amperes2,135 amperes

Calculation does not include motor contribution

Branch Circuit Fault fr Point to Point

Single Phase Branch Length (distance) L = 30

'f ' factor = 2 x L x I (ASC) 4,024 Phase 2,135

# conductors per phase N = 1

Phase conductor constant C = 617 Phase Conductor

240 Volt

f = 1.630

Neutral conductor constant C = 617 Neutral Conductor

120 VoltMultiplier f = 1.730

Line to Line M = 0.380

1 + f Line to Neutral M = 0.366

1,530 amperes

782 amperes

Calculation does not include motor contribution

Isca x M = fault current at terminals of the panel L- L = Isca x M = fault current at terminals of the panel L- N =

Isca =

N x C x E L-N

Volt Line to Line E L - L =

Volt Line to Neutral E L - N =

M = 1

Isca x M = fault current at terminals of the panel L- L =

Isca x M = fault current at terminals of the panel L- N =

I63
Data from above calculation
K63
Data from above calculation
I65
To select a conductor check the appropriate box to the right of the largest phase conductor
Page 3: FaultV6.2.xls

Available Fault Current CalculationVer. 4.00

Neutral

Step 1b: Insert the kVA rating (PF) power factor and (Z) impedence of transformer. (Note: When you insert the kVA rating, power factor and impedence you must select a voltage from the select the Voltage and Phase from dropdown box before the value will be calculated.)

Step 5b: Select neutral conductor size.

V34
=choose(U34,0,208,208,480,480) Link to cell I9 for select voltage
P35
Neutral , Choose formula ref point
V35
=choose(U34,0,240,208,208,480,480) Link to cell I9 for select voltage
V36
=choose(U34,0,208,208,480,480) Link to cell I9 for select voltage
V37
=CHOOSE(U34,0,I8*1000/I9,I8*1000/I9,I8*1000/I9*1.732,I8*1000/I9,I8*1000/I9*1.732) Link to cell I9 for select voltage
V38
=choose(U34,0,120,120,120,277,277) Link to nuetral voltage
V39
=choose(U34,0,240,208,208,480,480) Link to line to line voltage
V41
=choose(U34,0,240,208,208,480,480) Link to cell I9 for select voltage
V44
=choose(U34,0,240,208,208,480,480) Link to cell I9 for select voltage
P49
Link cell to conductor size
V49
Link cell to conductor size
Page 4: FaultV6.2.xls

Neutral

V67
=choose(U34,0,240,208,208,480,480) Link to cell I9 for select voltage
P72
Link cell to conductor size
V72
Link cell to conductor size
W79
when cell = -1 then feeder is 3ph
X79
if cell = 1 then branch is 1ph
W80
when cell = -1 then feeder is 3ph
X80
if cell = 1 then branch is 1ph
Page 5: FaultV6.2.xls

Job Name

Your Company Name

Available Fault Current Calculation by: John Sokolik Ver. 6.6 Three Single conductors

Utility Symmetrical Fault Current 26,456 amperes kVA = in PVC raceway E = 240 AWG

trans. FLA = 0 ###E ###

###

= PF = ###

transformer Z Z = ###0 amperes ###

###Point to Point Method ###

Length (distance) L = 150 ###

'f ' factor = 2 x L x I (ASC) 26,456 ###

# conductors per phase N = 1 ### Phase conductor constant C = 13,923 Phase Conductor ###

240 Volt ### f = 2.375 ###

Neutral conductor constant C = 13,923 Neutral Conductor ###Multiplier 120 Volt ###

f = 4.750 400 kcmil500 kcmil

1 + f Line to Line M = 0.296 600 kcmilLine to Neutral M = 0.174 750 kcmil

Fault Current at Service Equipment 1000 kcmil

7,838 amperes6,901 amperes Neutral

###

###

[email protected]

I = kVA x 1000 = trans. FLA

Isca = trans. FLA x 100 x PF

Isca = ampere short-circuit current RMS symmetrical. Isca =

Isca = N x C x E L-N

Volt Line to Line E L - L =

Volt Line to Neutral E L - N =

M = 1

Isca x M = fault current at terminals of main disconnect L- L = Isca x M = fault current at terminals of main disconnect L- N =

F8
When the fault current is provided by the governing utility insert the value here. The KVA, power factor (PF) and impedence (Z) of the transformer is not required to continue. Go to L= ,and insert footage of conductor length. Use 'Edit', 'Clear', Comments' to clear any input cell.
I8
If you have inserted the Utility Fault Current amps, inserting the kVA in this cell is not required. If available fault current is not known, insert transformer kVA rating here.
I13
Inserting a (PF) power factor is only required when using method 1b, see example sheet tab in lower left of the sheet. The (PF) default for this cell should be 100% unless the power factor is known.
I14
If you have inserted the Utility Fault Current amps inserting trans. impedence in this cell is not required. If transformer fault current is not known, insert transformer impedence here.
I18
Enter the length of one phase conductor in the group
I20
Enter the number of electrical conductors per phase between the transformer and the service equipment
I21
Select a conductor and raceway from the top drop down box Then select phase conductor size from AWG drop down box.
I24
Select neutral conductor size from AWG drop down box.