Page 1: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Ferdinand Schad KGSteigstraße 25-27

D-78600 KolbingenTelephone +49 (0) 74 63 - 980 - 0

Fax +49 (0) 74 63 - 980 - [email protected]

Fan coil unitNBS 100/150

Page 2: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Contents

Construction subject to change. No return possible!

Klimakonvektor NBS 100/150

Z11/20 - 2 12.11.2012Version:

Description ........................................................................................................................................3Advantages ........................................................................................................................................3Description of the equipment ...................................................................................................................3

Base unit .................................................................................................................................................................................... 3Housing ..................................................................................................................................................................................... 3Heat exchanger .......................................................................................................................................................................... 3Motorised fan ............................................................................................................................................................................. 3Filter ........................................................................................................................................................................................... 4Accessories ................................................................................................................................................................................ 4

Models, dimensions and weights ..............................................................................................................5Dimensions ................................................................................................................................................................................ 5Weights ...................................................................................................................................................................................... 6

Circuit diagrams ..................................................................................................................................6Technical data ....................................................................................................................................9

NBS 100/1 - Filter G3 ................................................................................................................................................................. 9NBS 100/2 - Filter G3 ................................................................................................................................................................. 9NBS 100/3 - Filter G3 ............................................................................................................................................................... 10NBS 150/1 - Filter G3 ............................................................................................................................................................... 10NBS 150/2 - Filter G3 ............................................................................................................................................................... 11NBS 150/3 - Filter G3 ............................................................................................................................................................... 11NBS 150/1 - Filter G4 ............................................................................................................................................................... 12NBS 150/2 - Filter G4 ............................................................................................................................................................... 12NBS 150/3 - Filter G4 ............................................................................................................................................................... 13Acoustic data NBS 100 ........................................................................................................................................................... 13Acoustic data NBS 150 ........................................................................................................................................................... 13

Accessories ...................................................................................................................................... 14Droplet separator ..................................................................................................................................................................... 14Flexible connections (-FS-F) and flange (-FL) .......................................................................................................................... 14Supply air (-PZ) and return air boxes (-PA) ............................................................................................................................. 15Mixing unit (-ME) ..................................................................................................................................................................... 16Mineral fibre board silencers .................................................................................................................................................... 16Electric heating register (-BE) .................................................................................................................................................. 18Valves ...................................................................................................................................................................................... 19Actuators ................................................................................................................................................................................. 20Temperature controls ............................................................................................................................................................... 20

Installation ...................................................................................................................................... 21Maintenance .................................................................................................................................... 21Legend ........................................................................................................................................... 22Order details .................................................................................................................................... 23Specification text ............................................................................................................................... 24Selection program for a quick and accurate design ....................................................................................... 24

Page 3: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

DescriptionNBS fan coil units with small mounting height are used for de-centralised air treatment. They are particularly suitable for smallunits in which higher cooling capacities and pressures are re-quired than those that a standard fan coil unit is able to provide.Additionally, the NBS fan coil units outdo the performance ofstandard fan coil units.Its compact dimensions and low height make the NBS fan coilunit the perfect solution for horizontal installation in false ceil-ings or suspension-type mounting in industrial halls.The fan coil unit series consists of two model series, a modularunit (NBS 100) and a compact unit (NBS 150), which can bothbe delivered, depending on the desired performance profile,with different motor, register and filter equipment.

NBS 100

NBS 150

Advantages

Description of the equipmentBase unitThe base unit consists of a jacket made of galvanised sheet steelequipped with heat and noise insulation, a motorised fan, one ortwo heat exchangers, filters and a collecting pan for the water ofcondensation.

HousingIn the 100 series, the housing consists of galvanised sheet steelprofiles and plates and heat or sound insulation 12 mm in thick-ness.In the 150 series, the housing consists of aluminium profiles,galvanised sheet steel, plastic corners and a circumferential sealto guarantee tightness. The jacket is manufactured in sandwichdesign and has interior heat or sound insulation 25 mm in thick-ness.

Heat exchangerThe heat exchanger can con-sist of a single register(cooling or heating) or tworegisters (cooling and heat-ing). They consist of copperpipes, aluminium ribs, amanual diffuser system anda galvanised steel frame.This unit is completed by acollecting pan made of galvanised sheet steel for collecting thewater of condensation from the cooling register.The length of the register and the number of pipe rows or cir-cuits of each register depend on the performance required. Thewater connections can be attached to the left- or right-handside.

Motorised fanThe built-in fans are dynamical-ly balanced, double-sided in-take-operated centrifugalblowers with forward directedblades.The fans have been selected toallow the required static pres-sures to be achieved at lowsound power levels. The NBS100 model has a motor withone, two or three fans. The se-

ries 150 comprises a motorised fan with one motor (1 fan), 2motors (2 fans) or 3 motors (3 fans).

- Motorised fan: 1 motor with 1, 2 or 3 fans- Volumetric flow: from 500 to 3500 m3/h- Available static pressure: from 5 to 150 Pa- Cooling capacity: from 3 to 16 kW- Heating capacity: from 5 to 25 kW- Filtering efficiency G3

- Motorised fan: 1, 2 or 3 motorised fans- Volumetric flow: from 1500 to 6000 m3/h- Available static pressure: from 40 to 250 Pa- Cooling capacity: from 10 to 32 kW- Heating capacity: from 8 to 45 kW- Filtering efficiency G3 or G4

- High energy efficiency- High performance (compensation of high thermal loads)- Low noise level- Compact dimensions and low mounting height- Low mounting and maintenance expenditure- Decentral air conditioning

Z11/20 - 3

Construction subject to change. No return possible!

12.11.2012Version:

Page 4: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

FilterThe filter of filter class G3 or G4(only for NBS 150) consists of agalvanised steel frame and asynthetic filter medium.To facilitate maintenance work,the filters are guided in profilesso that they can be easily re-moved by pulling them out sideways or, optionally also down-wards or upwards.An optional multi-part filter facilitating filter removal can also beordered.

AccessoriesOptionally, upon customer request or when required, additionalaccessories can be delivered, such as: mixing unit, silencers forsupply air and return air, flange, multi-part filter, flexible con-nections, droplet separator and an electric heating register.SCHAKO offers an extensive product range of control equip-ment (temperature controls, valves, actuators, etc.).

Model

Components filter sectionStandard filter Multi-part filter

St Dimensions (mm) St Dimensions

(mm)NBS 100-1 1 295x685x10 2 295x342.5x10NBS 100-2 2 295x577x10 3 295x384.6x10NBS 100-3 2 295x832x10 3 295x554.6x10NBS 150-1 1 797x395x10 2 398.5x395x10NBS 150-2 2 648x395x10 3 432x395x10NBS 150-3 2 873x395x10 3 582x395x10

Z11/20 - 4

Construction subject to change. No return possible!

12.11.2012Version:

Page 5: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Models, dimensions and weightsDimensionsNBS 100 NBS 150

Available sizes (mm)Model B H L

NBS 100-1 680300 600NBS 100-2 1150

NBS 100-3 1660

B

50L

65H

1313

Available sizes (mm)Model B B1 H H1 L

NBS 150-1 874 800480 406 774NBS 150-2 1374 1300

NBS 150-3 1824 1750

B

HL

7550

B1

H1

Z11/20 - 5

Construction subject to change. No return possible!

12.11.2012Version:

Page 6: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Weights

(1) STANDARD UNIT: housing + cooling and heating registers (empty) + motorised fan + filter

Circuit diagramsNBS 100

NBS 150

Model / Size

Weights (kg)

Deviceunit(1)

Suction / Blow unit

(L 300 mm)Mixing unit

WaterCooling register

Water Heating register

NBS 100-1 36 9 18,5 1,89 0,985

NBS 100-2 56 13 24 3,39 1,69

NBS 100-3 75 17 29,5 5,04 2,55

NBS 150-1 57 11 20 3,50 1,73

NBS 150-2 77 15 26 5,82 2,97

NBS 150-3 98 18,5 33 7,82 3,95

Yellow / Green

Yellow

GreenBlueBrownGreyPurpleOrangeRed

Max.

Medium

Min.

1= Max. velocity5= Min. velocity

G

N12345G

Yellow / Green

Yellow

GreenBlueBrownGreyRed

Max.MediumMin.G

NN123G

C 15 µF

According to DIN EN 60335-1, an all-poledisconnecting device must be provided bythe customer.

Z11/20 - 6

Construction subject to change. No return possible!

12.11.2012Version:

Page 7: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Wiring for parallel operationNBS 100

Yellow / Green

Yellow

GreenBlueBrownGreyPurpleOrange

Max.

Medium

Min.

1= Max. velocity5= Min. velocity

G

N12345G

Yellow / Green

Yellow

GreenBlueBrownGreyPurpleOrangeRed

Max.

Medium

Min.

1= Max. velocity5= Min. velocity

G

N12345G

Wiring for parallel operationNBS 100

Speedselector

ON-SITE

Z11/20 - 7

Construction subject to change. No return possible!

12.11.2012Version:

Page 8: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

NBS 150

Wiring for parallel operationNBS 150

Speedselector

ON-SITE

Yellow / Green

Yellow

GreenBlueBrownGreyRed

Max.MediumMin.G

NN123G

C 15 µF

Yellow / Green

Yellow

GreenBlueBrownGreyRed

Max.MediumMin.G

NN123G

C 15 µF

Z11/20 - 8

Construction subject to change. No return possible!

12.11.2012Version:

Page 9: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Technical dataNBS 100/1 - Filter G3

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G3 � 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G3 � 4-pipe register

NBS 100/2 - Filter G3

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G3 � 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G3 - 4-pipe register

Available static pressure (Pa)

25 50 75 100 125 150V (m3/h) 1232 1141 1008 822 594 398V [l/s] 342 317 280 228 165 111

Qges (1) (kW) 6,9 6,59 6,09 5,32 4,24 3,13Qs (1) (kW) 5,07 4,8 4,38 3,76 2,91 2,1Q (2) (kW) 9,62 9,16 8,44 7,35 5,84 4,33

VWK (1) (l/h) 1187 1133 1047 915 729 538VWH (2) (l/h) 827 788 726 632 502 372PaWK (1) (kPa) 24 22 20 15 10 6PaWH (2) (kPa) 36 33 29 22 15 9TAK (1) (°C) 14,5 14,2 13,8 13,1 12,1 11,0rFAK (1) (%) 90,0 91,0 92,0 93,0 95,0 97,0TAH (2) (°C) 43,2 43,8 44,8 46,5 49,2 52,3rFAH (2) (%) 13,0 13,0 12,0 11,0 10,0 8,0

W (W) 196 182 168 152 133 120A (A) 0,85 0,79 0,73 0,66 0,58 0,52

LWA [db(A)] 67 67 67 67 67 67

Available static pressure (Pa)25 50 75 100 125 150

V (m3/h) 2306 2189 2009 1699 1321 982V [l/s] 641 608 558 472 367 273

Qges (1) (kW) 13,24 12,82 12,14 10,89 9,16 7,38Qs (1) (kW) 9,61 9,26 8,70 7,68 6,33 5,00Q (2) (kW) 17,83 17,24 16,31 14,59 12,27 9,90

VWK (1) (l/h) 2277 2205 2088 1873 1576 1269VWH (2) (l/h) 1533 1483 1403 1255 1055 851PaWK (1) (kPa) 39,0 37,0 34,0 28,0 20,0 14,0PaWH (2) (kPa) 24,0 23,0 21,0 17,0 12,0 8,0TAK (1) (°C) 14,3 14,2 13,9 13,3 12,5 11,6rFAK (1) (%) 90,0 91,0 91,0 92,0 94,0 96,0TAH (2) (°C) 42,9 43,4 44,1 45,5 47,6 49,9rFAH (2) (%) 14,0 13,0 13,0 12,0 11,0 10,0

W (W) 513 472 421 361 320 297A (A) 2,23 2,05 1,83 1,57 1,39 1,29

LWA [db(A)] 70 70 70 70 70 70

Z11/20 - 9

Construction subject to change. No return possible!

12.11.2012Version:

Page 10: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

NBS 100/3 - Filter G3

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G3 - 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G3 - 4-pipe register

NBS 150/1 - Filter G3

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G3 - 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G3 - 4-pipe register

Available static pressure (Pa)25 50 75 100 125 150

V (m3/h) 2921 2666 2382 2055 1688 1209V [l/s] 811 741 662 571 469 336

Qges (1) (kW) 17,82 16,79 15,58 14,07 12,12 9,50Qs (1) (kW) 12,72 11,89 10,93 9,76 8,27 6,36Q (2) (kW) 24,80 23,37 21,69 19,63 16,97 13,44

VWK (1) (l/h) 3065 2888 2680 2420 2085 1634VWH (2) (l/h) 2133 2010 1865 1688 1459 1156PaWK (1) (kPa) 30,0 27,0 23,0 19,0 15,0 10,0PaWH (2) (kPa) 32,0 29,0 26,0 21,0 16,0 11,0TAK (1) (°C) 13,8 13,5 13,1 12,6 11,9 11,0rFAK (1) (%) 91,0 92,0 93,0 94,0 95,0 97,0TAH (2) (°C) 45,2 46,0 47,0 48,3 50,2 53,0rFAH (2) (%) 12,0 12,0 11,0 10,0 9,0 8,0

W (W) 437 409,4 381,8 354,2 324,3 294,4A (A) 1,90 1,78 1,66 1,54 1,41 1,28

LWA [db(A)] 70 70 70 70 70 70

Available static pressure (Pa)75 100 125 150 175 200 225 250

V (m3/h) 2380 2256 2122 1975 1815 1640 1450 1249V [l/s] 661 627 589 549 504 456 403 347

Qges (1) (kW) 13,73 13,29 12,79 12,22 11,56 10,81 9,94 8,94Qs (1) (kW) 9,93 9,55 9,13 8,67 8,14 7,54 6,87 6,11Q (2) (kW) 18,11 17,50 16,82 16,05 15,18 14,17 13,04 11,74

VWK (1) (l/h) 2362 2286 2200 2102 1988 1859 1710 1538VWH (2) (l/h) 1557 1505 1447 1380 1305 1219 1121 1010PaWK (1) (kPa) 77,0 73,0 68,0 62,0 57,0 50,0 43,0 36,0PaWH (2) (kPa) 27,0 26,0 24,0 22,0 20,0 18,0 15,0 13,0TAK (1) (°C) 14,3 14,1 13,9 13,7 13,4 13,0 12,6 12,1rFAK (1) (%) 90,0 90,0 91,0 91,0 92,0 93,0 93,0 94,0TAH (2) (°C) 42,6 43,0 43,5 44,1 44,8 45,6 46,7 47,9rFAH (2) (%) 14,0 14,0 13,0 13,0 12,0 12,0 11,0 11,0

W (W) 623 598 575 550 529 506 483 460A (A) 2,71 2,6 2,5 2,39 2,3 2,2 2,1 2

LWA [db(A)] 78 78 78 78 78 78 78 78

Z11/20 - 10

Construction subject to change. No return possible!

12.11.2012Version:

Page 11: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

NBS 150/2 - Filter G3

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G3 - 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G3 - 4-pipe register

NBS 150/3 - Filter G3

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G3 - 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G3 - 4-pipe register

Available static pressure (Pa)75 100 125 150 175 200 225 250

V (m3/h) 4726 4462 4148 3785 3404 3036 2691 2358V [l/s] 1313 1239 1152 1051 946 843 748 655

Qges (1) (kW) 25,56 24,70 23,64 22,34 20,90 19,40 17,89 16,33Qs (1) (kW) 18,82 18,08 17,16 16,07 14,87 13,66 12,47 11,27Q (2) (kW) 34,25 33,04 31,56 29,76 27,78 25,75 23,73 21,67

VWK (1) (l/h) 4396 4248 4066 3843 3595 3337 3077 2809VWH (2) (l/h) 2946 2841 2714 2559 2389 2215 2041 1864PaWK (1) (kPa) 68 64 59 53 47 41,0 36 30PaWH (2) (kPa) 41 39 36 32 28 25 21 18TAK (1) (°C) 14,9 14,7 14,4 14,1 13,7 13,3 12,9 12,5rFAK (1) (%) 89 89 90 90 91 92 93 94TAH (2) (°C) 41,5 42 42,6 43,3 44,2 45,2 46,2 47,3rFAH (2) (%) 15 14 14 13 13 12,0 11 11

W (W) 1265 1205 1141 1079 1028 987 950 911A (A) 5,50 5,24 4,96 4,69 4,47 4,29 4,13 3,96

LWA [db(A)] 81 81 81 81 81 81 81 81

Available static pressure (Pa)75 100 125 150 175 200 225 250

V (m3/h) 5939 5720 5433 5060 4618 4153 3682 3192V [l/s] 1650 1589 1509 1406 1283 1154 1023 887

Qges (1) (kW) 33,44 32,69 31,67 30,30 28,59 26,68 24,60 22,28Qs (1) (kW) 24,35 23,69 22,84 21,69 20,28 18,75 17,11 15,34Q (2) (kW) 45,69 44,64 43,23 41,33 38,99 36,39 33,60 30,51

VWK (1) (l/h) 5752 5623 5447 5212 4918 4589 4231 3832VWH (2) (l/h) 3929 3839 3718 3554 3353 3130 2890 2624PaWK (1) (kPa) 64,0 61,0 58,0 54,0 48,0 43,0 37,0 31,0PaWH (2) (kPa) 40,0 39,0 37,0 34,0 30,0 27,0 23,0 20,0TAK (1) (°C) 14,6 14,4 14,2 14,0 13,7 13,3 12,9 12,4rFAK (1) (%) 89,0 90,0 90,0 91,0 91,0 92,0 93,0 94,0TAH (2) (°C) 42,8 43,2 43,6 44,2 45,1 46,0 47,1 48,4rFAH (2) (%) 14,0 13,0 13,0 13,0 12,0 12,0 11,0 10,0

W (W) 1601 1571 1536 1497 1454 1412 1375 1339A (A) 6,96 6,83 6,68 6,51 6,32 6,14 5,98 5,82

LWA [db(A)] 83 83 83 83 83 83 83 83

Z11/20 - 11

Construction subject to change. No return possible!

12.11.2012Version:

Page 12: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

NBS 150/1 - Filter G4

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G4 - 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G4 - 4-pipe register

NBS 150/2 - Filter G4

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G4 - 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G4 - 4-pipe register

Available static pressure (Pa)75 100 125 150 175 200 225 250

V (m3/h) 2201 2097 1982 1854 1712 1553 1379 1194V [l/s] 611 583 551 515 476 431 383 332

Qges (1) (kW) 13,09 12,69 12,24 11,73 11,30 10,42 9,59 8,66Qs (1) (kW) 9,38 9,06 8,69 8,27 7,79 7,24 6,61 5,90Q (2) (kW) 17,22 16,69 16,09 15,40 14,60 13,67 12,59 11,37

VWK (1) (l/h) 2252 2183 2105 2018 1914 1792 1649 1490VWH (2) (l/h) 1481 1435 1384 1324 1256 1176 1083 978PaWK (1) (kPa) 71,0 67 63,0 58,0 53,0 47,0 40,0 34,0PaWH (2) (kPa) 25,0 24,0 22,0 20,0 19,0 16,0 14,0 12,0TAK (1) (°C) 14,1 13,9 13,7 13,5 13,2 12,9 12,5 12,0rFAK (1) (%) 90,0 91,0 91,0 92,0 92,0 93,0 94,0 95,0TAH (2) (°C) 43,2 43,6 44,1 44,6 45,3 46,1 47,1 48,3rFAH (2) (%) 13,0 13,0 13,0 12,0 12,0 12,0 11,0 10,0

W (W) 589 570 552 534 515 495 476 453A (A) 2,56 2,48 2,40 2,32 2,24 2,15 2,07 1,97

LWA [db(A)] 78 78 78 78 78 78 78 78

Available static pressure (Pa)75 100 125 150 175 200 225 250

V (m3/h) 4561 4324 4034 3686 3307 2938 2594 2265V [l/s] 1267 1201 1121 1024 919 816 721 629

Qges (1) (kW) 25,03 24,24 23,24 21,98 20,51 18,98 17,45 15,88Qs (1) (kW) 18,35 17,67 16,82 15,76 14,56 13,32 12,12 10,92Q (2) (kW) 33,50 32,40 31,00 29,26 27,25 25,19 23,15 21,07

VWK (1) (l/h) 4305 4169 3997 3781 3528 3265 3001 2731VWH (2) (l/h) 2881 2786 2666 2516 2344 2166 1991 1812PaWK (1) (kPa) 65,0 62,0 57,0 52,0 46,0 40,0 34,0 29,0PaWH (2) (kPa) 40,0 37,0 35,0 31,0 27,0 24,0 20,0 17,0TAK (1) (°C) 14,8 14,6 14,3 14,0 13,6 13,2 12,8 12,4rFAK (1) (%) 89,0 89,0 90,0 91,0 91,0 92,0 93,0 94,0TAH (2) (°C) 41,8 42,2 42,8 43,6 44,5 45,4 46,5 47,6rFAH (2) (%) 14,0 14,0 14,0 13,0 13,0 12,0 11,0 11,0

W (W) 1228 1178 1120 1065 1017 975 938 899A (A) 5,34 5,12 4,87 4,63 4,42 4,24 4,08 3,91

LWA [db(A)] 81 81 81 81 81 81 81 81

Z11/20 - 12

Construction subject to change. No return possible!

12.11.2012Version:

Page 13: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

NBS 150/3 - Filter G4

(1) COOLING: air (27°C/50%), water (7°C /12°C) - filter G4 - 4-pipe register(2) HEATING: air (20°C/50%), water (70°C /60°C) - filter G4 - 4-pipe register

Acoustic data NBS 100 Acoustic data NBS 150

Available static pressure (Pa)75 100 125 150 175 200 225 250

V (m3/h) 5696 5481 5197 4825 4389 3940 3494 3034V [l/s] 1582 1523 1444 1340 1219 1094 971 843

Qges (1) (kW) 32,61 31,84 30,81 29,40 27,66 25,76 23,74 21,50Qs (1) (kW) 23,62 22,99 22,12 20,95 19,54 18,02 16,44 14,74Q (2) (kW) 44,53 43,47 42,04 40,10 37,73 35,15 32,45 29,46

VWK (1) (l/h) 5609 5477 5299 5057 4758 4431 4083 3698VWH (2) (l/h) 3830 3738 3615 3449 3245 3023 2791 2534PaWK (1) (kPa) 61,0 59,0 55,0 51,0 45,0 40,0 35,0 29,0PaWH (2) (kPa) 39,0 37,0 35,0 32,0 29,0 25,0 22,0 18,0TAK (1) (°C) 14,4 14,3 14,1 13,8 13,5 13,1 12,7 12,3rFAK (1) (%) 90,0 90,0 90,0 91,0 92,0 92,0 93,0 94,0TAH (2) (°C) 43,2 43,5 44,0 44,7 45,5 46,5 47,6 48,8rFAH (2) (%) 13,0 13,0 13,0 12,0 12,0 11,0 11,0 10,0

W (W) 1569 1543 1511 1472 1433 1396 1362 1329A (A) 6,82 6,71 6,57 6,40 6,23 6,07 5,92 5,78

LWA [db(A)] 83 83 83 83 83 83 83 83

NBS

Spee

d

De (dB/Oct)

fm (Hz)

63 125

250

500

1000

2000

4000

8000

100-

1

1 72 72 65 63 63 58 55 532 71 71 63 62 62 57 53 513 69 69 61 60 60 54 51 484 67 67 58 58 56 50 47 445 64 64 55 55 53 46 42 39

100-

2

1 72 72 68 67 67 62 58 552 70 70 66 65 65 59 55 523 68 68 63 62 61 55 51 474 64 64 59 58 56 50 45 405 59 59 54 53 50 42 37 32

100-

3

1 72 72 68 66 67 61 58 552 69 69 64 62 62 56 52 493 65 65 59 58 57 50 46 424 60 60 54 54 52 44 38 345 56 56 50 49 46 38 32 29

NBS

Spee

d

De (dB/Oct)

fm (Hz)

63 125

250

500

1000

2000

4000

8000

150-

1 1 80 80 76 73 75 70 68 612 80 80 72 71 73 68 65 583 78 78 69 70 66 64 60 52

150-

2 1 80 81 78 76 78 73,5 71 652 80 80 79 75 76 71 68 623 78 76 73 73 71 68 65 58

150-

3 1 80 83 83 78 78 75 72 652 80 82 81 76 76 73 70 623 78 78 76 73 72 69 66 58

Z11/20 - 13

Construction subject to change. No return possible!

12.11.2012Version:

Page 14: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

AccessoriesDroplet separatorFor NBS 150 with an air streamspeed exceeding 2.5 m/s, it is im-perative to use a droplet separator toavoid spreading of the condensate.The droplet separator consists ofpolypropylene leaves and a rackmade of galvanised or stainlesssheet steel.

Maximum admissible air flow to prevent condensate fromspreading

Flexible connections (-FS-F) and flange (-FL)The unit is connected to the air ducts via flexible connections (-FS-F), which prevent vibrations from being transmitted to thesystem, or via a flange (-FL).

Dimensions

Model V (m3/h)

NBS 150-1 2520NBS 150-2 4320NBS 150-3 5940

Flexible connections (-FS-F) Flange (-FL)

Model SizeB1

(mm)B2

(mm)B3

(mm)Numberbores

NBS 1001 290 680 720 102 350 1150 1190 123 312 1660 1700 16

NBS 1501 832 794 854

42 1332 1294 13543 1782 1744 1804

Flexible connections (-FS-F)

Flange (-FL)

NBS 100

NBS 150

NBS 100

NBS 150

Z11/20 - 14

Construction subject to change. No return possible!

12.11.2012Version:

Page 15: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Supply air (-PZ) and return air boxes (-PA)Made of galvanised sheet steel with open connection (standard)or round connection via connection piece plate.Depending on customer request, the round connection piecescan also be attached to the side of the plenum box.

Box connections

Dimensions

Connection piece plate

Supply air box with connection pipes

Other equipment is available on request

NBS 100

NBS 150

Model SizeB

(mm)B1

(mm)B2

(mm)H

(mm)Numberbores

NBS 1001 762 290 680

30010

2 1232 350 1150 123 1742 312 1660 16

NBS 1501 865 832 794

318,5 42 1365 1332 12943 1815 1782 1744

M6

B

H+42

7171

B2

H21 91 B1 11

11

31

B+42

L

Model SizeMax. number of connection

piecesØ 123 Ø 158 Ø 198 Ø 248

NBS 1001 4 3 3 22 7 6 5 43 10 8 7 5

NBS 1501 4 4 3 22 7 6 5 43 10 8 7 6

ModelLength of box

(mm)Max. number of connection

piecesØ 123 Ø 158 Ø 198 Ø 248

NBS 100NBS 150

300 1 1 1 -400 2 1 1 1500 2 2 1 1600 3 2 2 1700 4 3 2 2800 4 3 3 2900 5 4 3 2

1000 5 4 4 3

NBS 100

Joint

Suction box

Blow box Connecting plate with con-nection piece (optional)

Flexible connections

Flexible connections

Flange

Flange

NBS 150

Joint

Suction box

Blow box Connecting plate with con-nection piece (optional)

Flexible connections

Flexible connections Flange

Flange

The insulation is done on site.

Z11/20 - 15

Construction subject to change. No return possible!

12.11.2012Version:

Page 16: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Mixing unit (-ME)The mixing unit consists of galvanised sheet steel and is linedwith sound and heat insulation. The mixing unit allows the air to be replenished by introducinga fresh air portion.

Mixing unit NBS 100

Mixing unit NBS 150

Further information can be found in the technical documenta-tion of the HKP multi-leaf damper.

Mineral fibre board silencersFor noise reduction purposes in the return and supply air sec-tions, it is possible to install a silencer. The silencers consist of vertically arranged small cells on a gal-vanised sheet steel frame. The cells consist of mineral fibreboards (biodegradable, abrasion-resistant and fire-resistant ac-cording to DIN 4102) covered with a continuous glass fibre fil-ament. In order to reduce noise, while ensuring minimumpressure loss, the length of the cells and their spacing dependon the desired silencing effect. The cover of the baffles can bemade of smooth or perforated plates, as desired, which can alsobe combined on one or both sides or one or two half-covers.An intermediate piece (box) of 400 - 500 mm is needed betweenthe air outlet or the air intake of the the NBS and the silencer.

Models:MWS: Silencer made of galvanised sheet steel and mineral woolribs are mounted in a galvanised steel frame.MBS: Silencer made of galvanised sheet steel and mineral woolribs mounted in a galvanised steel frame (half of the surface iscovered by a sheet metal plate).

Further information can be found in the technical documenta-tion of the MWS/MBS mineral wool silencer.

Model SizeL

Front damper Lateral damper(mm)

NBS 1001

370

HKP 401x201

HKP 201x2012 HKP 711x201

3 HKP 894x201

NBS 1501

1180HKP 503x252

HKP 252x2522 HKP 797x2523 HKP 1003x252

L

NBS 100

Mixing unit

Front damper

Lateraldamper

L

50

NBS 150Front damper

Lateraldamper

Z11/20 - 16

Construction subject to change. No return possible!

12.11.2012Version:

Page 17: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

K

B

B+60

H

H+60

B1

H1

(30)

30

30 (30)

L

Model NBS 100/1 NBS 100/2 NBS 100/3 NBS 150/1 NBS 150/2 NBS 150/3B

(mm)

675 1145 1655 794 1294 1744B1 713 1183 1693 832 1332 1782H 340 405

H1 377 442K 100 / 200L 500 / 750 / 1000 / 1250 / 1500 / 1750 / 2000 / 2250 / 3000

Silencer NBS 100/150

Z11/20 - 17

Construction subject to change. No return possible!

12.11.2012Version:

Page 18: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Electric heating register (-BE)Additional module consisting of a galvanised steel frame and aheating coil made of stainless steel and 2 safety temperaturecontrols. Model with or without blades.

Without blades

With blades

Circuit diagram

Example of a connection circuit diagram

Model Capacity (W)

Operating voltage(V)

NBS 100-1 2500 3-400NBS 100-2 5000 3-400NBS 100-3 6750 3-400NBS 150-1 6000 3-400NBS 150-2 11500 3-400NBS 150-3 15000 3-400

ELEC

TRIC

HEAT

ING

REGI

STER

STAGE 1

STAGE 2 (optional)

STAGE 3 (optional)

Safety thermostats 85° C

Safety thermostats 60° C

Black

Black

Black

Black

Black

Black

Brown

Brown

Blue

Blue

SCHAKO scope of delivery:B1/B2/B3/B4: Terminals (in the terminal box of the de-vice)T1: Temperature control for autom. restartT2: Safety temperature control, recommended for manualrestartR: Electric register

Not included in the SCHAKO scope of delivery:M: Pushbutton for manual restartN: Restart from the control unitRA/RAB/RA1: Electrical transmitter for control, monitor-ing, switching onRA2: "Operation" auxiliary contact L1RA3: "Operation" auxiliary contact L2L1: Operation LEDL2: Fault LED(1): Connection option 1(2): Connection option 2(3): Switch(4): Control unit(5): Fuse(6): OFF(7): Automatic operation(8): ON /OFF

Z11/20 - 18

Construction subject to change. No return possible!

12.11.2012Version:

Page 19: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Valves

Version with pressure measuring nipple for ∆p measurement (option)

TypeDN

(mm)Connection

Kvs

(m3/h)

∆pS

(kPa)

Kvs bypass (m3/h)

∆pmax

(kPa)

Actuator

100 N 105 N

VVP 46 (2-door)

VVP469.10-1.010 G1/2 B

1

150

0,7

100 SSA STA VVP469.10-1.6 1,6 1,12

VVP469.15-2.5 15 G3/4 B 2,5 1,75

VVP469.20-4.0 20 G1B 4 2,8

VXP(3-door)

VXP469.10-1.010 G1/2 B

1

150

0,7

100 SSA STA VXP469.10-1.6 1,6 1,12

VXP469.15-2.5 15 G3/4 B 2,5 1,75

VXP469.20-4.0 20 G1B 4 2,8

VMP 46 (4-door)

VMP469.10-1.010 G1/2 B

1

150

0,7

100 SSA STA VMP469.10-1.6 1,6 1,12

VMP469.15-2.5 15 G3/4 B 2,5 1,75

VMP469.20-4.0 20 G1B 4 2,8

VVP 45(2-door)

VVP45.10-110 G1/2 B

1,0600

0,70200 SSB (200 N)

VVP45.10-1.6 1,6 1,12

VVP45.25-6.325 G11/4 B 6,3

3004,4

300SSB (300 N)

VVP45.25-10 G11/2 B 10 10 SSC (300 N)

VXP 45(3-door)

VXP45.10-110 G1/2 B

1,0600

0,70200 SSB (200 N)

VXP45.10-1.6 1,6 1,12

VXP45.25-6.325

G11/4 B 6,3300

4,4300

SSB (300 N)

VXP45.25-10 G11/2 B 10 10 SSC (300 N)

VMP 45(4-door)

VMP45.10-1

10 G1/2 B

1,0

600

0,70

200 SSB (200 N)

VMP45.10-1.6 1,6 1,12

TypeDN

(mm)Connection Vmin

(l/h)

V100

(l/h)

Actuator

∆pmin

(kPa)

∆pmax

(kPa)

VPI 45

VPI45.15F0.515 Rp1/2

90 620 16

400

VPI45.15F1.5 290 1730 18

VPI45.20F0.920 Rp 3/4

160 1050 16

VPI45.20F2 350 2040 22

VPI45.25F1.525 Rp 1

280 1720 16

VPI45.25F2 350 2040 22

VPI45.32F3 32 Rp 11/4 560 3050 18

Z11/20 - 19

Construction subject to change. No return possible!

12.11.2012Version:

Page 20: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

ActuatorsModel SSA

SSA31: Operating voltage 230 V AC, actuator signal 3-pointSSA61: Operating voltage 24 V AC/DC, actuator signal 0 ... 10 VSSA81: Operating voltage 24 V AC, actuator signal 3-point

Model SSB

SSB31: Operating voltage 230 V AC, actuator signal 3-pointSSB61: Operating voltage 24 V AC/DC, actuator signal 0 ... 10 VSSB81: Operating voltage 24 V AC, actuator signal 3-point

Model SSC

SSC31: Operating voltage 230 V AC, actuator signal 3-pointSSC61: Operating voltage 24 V AC/DC, actuator signal 0 ... 10 VSSC81: Operating voltage 24 V AC, actuator signal 3-point

Model STA

STA21: Operating voltage 230 V AC, actuator signal 2-pointSTA71: Operating voltage 24 V AC/DC, actuator signal 2-point or PWM

Model SSD

SSD31: Operating voltage 230 V AC, actuator signal 3-pointSSD81: Operating voltage 24 V AC, actuator signal 3-pointSSD61: Operating voltage 24 V AC/DC, actuator signal 0 ... 10 V DC

Temperature controlsFor two-pipe mountingModel RAB20

For four-pipe mountingModel RCC30

Model RDG

For two-pipe mounting with electric registerModel RCC20

- Actuating power 100 N- Automatic detection of the valve

stroke- Direct mounting- Connecting cable lengths 1.5, 2.5 or

4.5 m- Manual adjustment and position indicator

- Actuating power 200 N- Automatic detection of the valve

stroke- Direct mounting- Connecting cable length 1.5 m- Manual adjustment and position indicator

- Actuating power 300 N- Automatic detection of the valve

stroke- Direct mounting- Manual adjustment with position

and direction of rotation indicator

- Actuating power 105 N- Direct mounting- Standard version including 1.2 or

5 m connecting cables- Position indicator- Two-wire connection

- Actuating power > 250 N- Direct mounting

- Standard version including 1.5, 2.5or 4.5 m connecting cables

- Position indicator

- Changeover function- Two-point control behaviour- Manual 3-speed fan switch- Control output ON/OFF- Control voltage AC 250 V

- Outputs for On/Off valve actuators- Outputs for three-speed fan- Control either by room temperature or

return air temperature, as desired- Standard, Economy, Antifreeze operat-

ing modes or OFF- Operating voltage AC 230 V

- Display with backlight- Automatic switchover with selected fan

speedIII, II or I

- Automatic switchover between heatingand cooling mode by means of sensorQAH11.1

- Connection of return air sensor as anoption

- Operating modes: Comfort, Economyand Protective modes

- PWM regulation as an option- Automatic mode with timer program

- Outputs for three-speed fan- Control either by room temperature or

return air temperature, as desired- Automatic heating/cooling mode

switchover- Standard, Economy, Antifreeze operat-

ing modes or OFF- Operating mode switchover contact in-

put for remote circuit- Operating voltage AC 230 V

Z11/20 - 20

Construction subject to change. No return possible!

12.11.2012Version:

Page 21: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

InstallationInstallation in false ceilings is effected by means of fixing lugs attached to the unit.

Installation of NBS 100

Installation of NBS 150

MaintenanceMaintenance of the NBS units is easy. Depending on the degreeof soiling, the filter is cleaned or replaced (at least twice a year).The condensate drains must be checked and cleaned once ayear. The motorised fan is maintenance-free (self-lubricatingbearings). Maintenance is also subject to VDI 6022.

Minimum distance to obstacles L>300 mm

Check whether the condensate pan iscompletely emptied by partly filling it.Condensat

e drain

Ø16 mm

Minimum distance to obstacles L>400 mm

Check whether the condensate pan iscompletely emptied by partly filling it.Condensat

e drain

Ø16 mm

The register threads correspond to standard EN10226:Heating: external pipe thread EN 10226 R1/2Cooling: external pipe thread EN 10226 R 3/4

For maintenance, service, retrofitting, etc., inspec-tion openings in sufficient number and size mustbe provided on site.

Z11/20 - 21

Construction subject to change. No return possible!

12.11.2012Version:

Page 22: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

LegendV (m3/h) = Volumetric flowV [l/s] = Volumetric flowQges (kW) = Total cooling capacityQs (kW) = Sensible cooling capacityQ (kW) = Heating capacityVWK (l/h) = Water throughput with coolingVWH (l/h) = Water throughput with heatingPaWK (kPa) = Water-side pressure drop with coolingPaWH (kPa) = Water-side pressure drop with heatingTAK (°C) = Air outlet temperature with coolingTAH (°C) = Air outlet temperature with heatingrFAK (%) = Relative air outlet humidity with coolingrFAH (%) = Relative air outlet humidity with heatingW (W) = Current consumptionA (A) = Current intensityLWA [dB(A)] = A-weighted sound power levelL (mm) = Length of box / silencing baffles K (mm) = Baffle widthfm (Hz) = Octave / centre frequencyDe (dB/Oct) = Insertion lossDN (mm) = Diameter, nominal widthKvs (m3/h) = Nominal flow value of cold water through the fully open valve

(H100) at a differential pressure of 100 kPa (1 bar)∆ps (kPa) = Maximum allowed differential pressure (closing pressure)∆pmax (kPa) = Maximum allowed differential pressure above the control path

of the valve for the entire actuating range of the valve/actuator unit

Z11/20 - 22

Construction subject to change. No return possible!

12.11.2012Version:

Page 23: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Order details

Fan coil unitNBS series

Model 100-100

Model 150-150

2

Filter G3 (NBS 100 / NBS 150)-G3

Filter G4 (NBS 150)-G4

Accessories:

Order example:NBS-100-3 / 4+2F / LL / G3 / RUnless stated otherwise, the thick-frame model will be delivered!

Size3

Heat exchanger

System with 4 pipes -4+2F

Register connections

right-RR

Blow box(-PZ)

Suction box (-PA)

Flange (-FL)

Flexible connections (-FS-F)

Mixing unit(-ME)

Box (P)

300 400Box length

500 600 700 800 900 1000

Supply airZ

Return airA

Order example:PZ/100-1/500/R/3/123Other plenum box versions can be ordered.

Silencer

Droplet separator(NBS 150)

1

System with 2 pipes (cooling) -4F

left-LL

Valves

Electric register (-BE)

Control units

System with 2 pipes (heating) -2F

Model-100-1 -100-2 -100-3 -150-1 -150-2 -150-3

Joint-

Connection toconnection piece

-R

(*) Refer to table Page °15.

Actuators

Diameter-158-123 -198 -248

Without lateral connection

piece-

With lateral connection right-R

left-L

Diameter-158-123 -198 -248

Number of connection

Number of connection pieces (*)

Multi-part filter

Filter removal

right-R

top-O

left-L

bottom-U

Z11/20 - 23

Construction subject to change. No return possible!

12.11.2012Version:

Page 24: Fan coil unit - SCHAKO coil unit NBS 100/150. ... Heat exchanger The heat exchanger can con-sist of a single register ... 513 472 421 361 320 297 A (A)

Klimakonvektor NBS 100/150

Specification textNBS air-conditioning unit for horizontal installation in false ceil-ings. In the NBS 100 series, the housing consists of galvanisedsheet steel profiles and a heat and sound insulation. The hous-ing of the NBS 150 consists of aluminium profiles, a jacket insandwich design made of galvanised sheet steel, an interior heatand sound insulation, plastic corners and a circumferential seal.The motorised fan consists of a double-sided intake-operatedcentrifugal housing with built-in motor, heat exchanger registerwith galvanised steel frame, aluminium sheets and copperpipes. The filter element consists of a galvanised steel frame anda synthetic filter medium.Version with closed air circulation or mixture of fresh air and aircirculation or surrounding air.Product: SCHAKO type NBS

Accessories:

Selection program for a quick and accuratedesignOur selection program allows the optimum performance of eachmodel to be determined.

- Model- 100- 150

- Size- 1 - 2 - 3

- Heat exchanger- 4F- 2F- 4+2F

- Register connections- LL- RR

- Filtering efficiency- G3- G4 (only for NBS 150)

- Blow box (-PZ)- Suction box (-PA)- Flange (-FL)- Flexible connections (-FS-F)- Mixing unit (-ME)- Droplet separator (only for NBS 150)- Multi-part filter- Electric heating register (-BE)- Silencers - Valves- Actuators- Temperature controls

Z11/20 - 24