,., f) TTflcll/14£/1/ TB_ i SARGENT 8c LUNDY ENGINEERS CHICAGO Qualification of Mobil Oil Co. Greases Mobilux EP-0, EP-1, EP-2 and Mobi lgrease 28 Prepared for Dresden - Units 2 & 3 and Quad Cities - Units 1 & 2 by Component Qualification Division r:. Project No. 6896/97-00 February 20, 1989 .. . . - . .. - _, . --- ·- .- - - _; ..:-- .. . '·._n.' -·,.··,I .- _- .·., '. - .... _:-- --- ··cQo-042027 oo· · ) -- ' - - - .... ·-.... - .. .-· .< ' .... ·. - ) - . i

Upload: others

Post on 04-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • ,.,

    f) TTflcll/14£/1/ TB_ i

    SARGENT 8c LUNDY ENGINEERS

    CHICAGO

    Qualification of Mobil Oil Co. Greases Mobilux EP-0, EP-1, EP-2 and

    Mobi lgrease 28

    Prepared for Dresden - Units 2 & 3 and Quad Cities - Units 1 & 2

    by Component Qualification Division

    r:.

    Project No. 6896/97-00 February 20, 1989

    ..

    . . ~· -. :· .. - _,

    . ---

    ·- .-

    - - _; ..:--..

    . '·._n.'

    -·,.··,I .- _- .·., '.

    - .... :.~· _:-- ---

    ··cQo-042027 ~ev·. oo· ·

    )

    ;· -- ' - -'~~ - .... ~

    ·-.... - ..

    .-· .<

    ' -~-- .... ·. - ) ~~- -~ . ~ i ~:

  • REV. DESCRIPTION.

    00 Original Issue

    ' . .

    '•, •.

    •"'" ·.· ..

    ·'.",· .- • '!

    I

    '

    ··'

    ,. : '

    .... . ... '\ , ... . . ;·.-:1:·

    •. ,·.·, ·' i'

    • - : • '1 • ':. ' ~. ·~ ., " :

    "ISSUE SUMMARY:,.:: ... ·' . •• ( r: ... .

    F1352.001 01-89 .

    ... '.•.

    /

    RESPONSIBILITY SECTIONS DATE

    PREPARED BY: ~ .~~ /? f.af ~ :z_ -17- !fy REVIEWER COMMENTS & SIGNATURE :

    ~ /?/a/uy-lt-C~rJ:'if .. IJ., r~~ /-a/. ~/- 2-/7-Jf REVIEWER COMMENTS & SIGNATURE: v 1

    A){) CDIH M.L-n ../! ()ta 2·ZO-.$T ,,t6~~

    APPROVED BY: ,,---t}6·r?ntx:f.),,b(/V1.A._ Z- 2- 0 -89. - , PREPARED BY:

    REVIEWER COMMENTS & SIGNATURE:

    REVl.EWER COMMENTS & SIGNATURE·:

    APPROVED BY:

    PREPARED BY:

    REVIEWER COMMENTS & SIGNATURE :

    REVIEWER COMMENTS & SIGNATURE :

    APPROVED BY:

    PREPARED BY:

    REVIEWER COMMENTS & SIGNATURE:

    REVIEWER COMMENTS & SIGNATURE :

    APPROVED BY:

    COMPONENT ·· ,, ·QUALIFICATION

    DIVISION 11 SARGENT ~ LUNDYU PROJ. NO.: 6896197- 00

    ' ENGINEERS COD - ~0..:..4=-28:::..:2=-7.__ __ _ ·-,

  • PF~CJJ. NOS. ; 68~6 /97-00 CALC. NO. :CQD-042827 REV.00 DATE:02/20/89 PAGE 1 of 1121

    1. G PURPOSE

    The purpose of this analysis is to environmentally qualify Mobil Oil Corporation's Mobilux EPO, EPl and lP2 and Mobil grease 28 for use in Limitorque actuators at the Dresden and Quad Cities Nuclear Power Generating Stations.

    2. 0 REFERENCES

    1. Wyle Report #17019-01, Nuclear Environmental Ql1alification Test

    Program on Mobil Greases for Limitorque Actuators, dated 02-08-89,

    Preliminary Report.

    2. CQD-017511, CQD-017504, CQD-01/510, CQD-017512 and CQD-017509,

    Environmental Qualification of Limitorque Actuators, Dresden -

    Units 2 & 3.

    3. CQD-017515, CQD-017517, CQD-017514, CQD-017516 and CQD-017513, Environmental Qualification of Limitorque Actuators, Quad Cities -

    Units 1 & 2.

    4. CQD-015890, Environm~ntal Qual.ificatio~ of Mobil Greases, D~esden -

    Units 2 & 3. ••• ·.1

    -- - . ~ .. -· 5. CQD-015891, Environmental Qualification of Mobil.Greases,-:Quad

    . - · ...

    Cities - Units 1 & 2.

    6. Letter from (D. K. Yoshida) Nutech to (Z~J .. Bcixer)-CECo~·~ated: .--·

    • •••. • !.:-

    ~. .. ... --.- ',,_.;.·

    . -; ' ·.··~.-.... . ·,: :.. .. · .. _.- ~-- ' . ;···-:·-~,·

  • PROJ. NOS. :6896/97-00 CALC. NO. :CQD-042827 REV.00 DATE:02/20/89 PAGE 2 of 10

    3.0 EQUIPMENT DESCRIPTION, LOCATION AND FUNCTION

    Per References 4 and 5, Limitorque valve actuators at Dresden and Quad

    Cities use two types of lubricants:

    Mobilux EP Greases for actuator· main gear box

    Mobil grease 28 for actuator Limitswitch gear box.

    Per References 2 and 3, the following are the EQ actuators, their

    location in the plant, environmentai conditions and operability

    requirements:

    .-:.....

    :.- . •'

    .,._ .. ·· . '

    . :- ,:_. - .. ~-' ·:: ~.~ .. ....

    . -1. -

  • Tl'G Ml:lER

    MO- I - 1

  • . TAG UMl:lEF<

    MO-L-1402-~ ·lA ,d

    M0-2-1 -if12- .h.:1, b

    M0-2-140:;: .. ~c-,f, ,B M0-2-230 I - ::'.5 M0-2-1501-1 li'.,B M0-2-1501 -21A,8 M0-2-1501-2711,8 M0-2-1501-2!3A,8

    M0-2-1501-32A,B M0-2/3-7504A,8 M0-2/3-7505A,B M0-2/3-7507A,8 M0-2-1201-2,3

    M0-2-1201-1 M0-2-120 I -1/-. M0-2-3706 M0-2-220-1 M0-2- 1 50 I - 3/, , 13 M0-2-2301-4

    ~-?-202-7A,B

    -2-202-51'. ,B

    M0-2-2301-5 M0-2-2301-8 M0-2-220-2 M0-2-205-2-4 M0-2-1301 -2 M0-2-1301-3 M0-3-2301-3n

    M0-2-1001-IA,B M0-2-1301-1 M0-2-1301-4 M0-3-1001-11'. M0-3-1201-1 M0-3-1001-IU

    : OCAT I ON

    1Zone 28, 26)

    (Zone 28, 26)

    torus llPCI Room SE/SW Corner Room Torus (Zone 11, 24) (Zone 11, 24)

    SE/SW Corner Room (Zone 30)

  • PROJ. NOB. a6896/~7-00 CALC. NO. :CQD-042827 REV.00 DATE:02/20/89 PAGE 5 of 10

    Hence, the worst case environment for the subject gi·eases is as surrunarized below:

    Parameter

    Temperature (°F)

    Pressure

    Humidity

    Spray

    Radiation

    4.U SIMILARITY ANALYSIS

    Normal Service

    150°F

    14.7 psia

    20 - 901'

    2.0E06 Rads

    LOCA/HELB

    O to 30 min

    30 - 70 min

    70 psia

    100%

    Demineralized Water

    l.1E07 Rads

    Mobilux EP-0, EP-1, and EP-2 are used in Limitorque operators at Dredsen

    and Quad Cities stations. Per Refernce l, only EP-1 and EP-2 were

    tested to the postulated environmental condi_tions. Mobi lux EP-0 ·is

    qualified by material similarity to the tested EP-1 and EP-2

    forumlations. Per Mobil Oil Corporation Product Data Sheets, all three

    greases have the iame base oil thickening agents and additives.

    Typically the composition is as gi~en below:·

    CHARACTERISTIC NLGI No. Structure Soap Type Color Penetration at 77°F (25°C)

    Unworked, min-max. Worked 60 strokes, min-max.

    Dropping Point, min °F (C) Mineral Oi I % Viscosity of Oi I

    SUS at 100°F

    MOl:llLUX EPO 0 smooth

    MOBILUX EPl 1 smooth

    MOl:llLUX EP2 2 smooth

    Unleaded Lithium 12 Hydroxystearate Me:j i um brown Medi um orown Medi um brown

    3'.>0-390 355-385 340 ( 171) 92

    900

    305-34~

    310-340 340 ( 171) 89

    900

    260-300 265-295 350 ( 171) 87

    900

  • PROJ. NOS. : 089€:-/97-00 CALC. NO. :CQD-042827 REV.00 DATE:02/20/89 PAGE €. of 10

    SUS at 210°F 7C/80 70/80 70..'80 cSt at 40°C 1 70 170 170 cSt at 100°c 13.0;16.0 23.0/2c .o 13.0/16.0

    I i mhe;n OK Load. min. I b (kg) 40 ( 18) 40 ( 18) 40 ( l(l) l(us 1 Test ASTM D 1743 Pa~s Pass Pas;, l:lomb Oxidation Stabi I ity #PSI Drop ma-

  • • 6. 1

    PROJ. NOS. 16896197-00 CALC. NO. :CQD-042827 REV.00 DATE:02/20/89 PAGE 7 of 10

    Normal Radiation Exposure

    Thermal Aging

    Accident Radiation Exposure

    Penetration, Dropping Point and IR Tests

    Cyclic Aging

    DBE Simulation Test

    Penetration, Dropping Point and IR Tests .

    Penetration, Dropping Point and Mobil IR Test

    ASTM 0-217 - Cone penetration ot lubricating grease - Measurement of the grease consistency by penetration of a stari~ard cone.

    ASTM D-566 - Dropping point of. l.ubricati.ng-·greases ·,_·- Measu_r~meni· 'c»t". :\.;. the dropping point of the grease as an indfcation'of the n1aximu~ ·.-.: •.

    ·.temperature that it can be exposed .to without.iiquificationor oil.: .. - . ". '.

    separation.· · .. · ... • ' L ~· '• ' •

    ' "1 .

    The tests were performed on gre:ase'.samples _in b_qth i.Jnwo~ic'eiJ a11d· .:-. ·.:·':·· l '- • .. I_.,•

    ·_ .. · . .:,_ . -- . '""" ·:

    L. - ..

    worked conditi ans. · At· 1 east- 6.0 strokes:. were given :Prior. t6. -pe.ff-~rm-:' ·= >~:.-~~- .. . -- -· . -_- - - :: . - - . . :· - ': ;. . . . . . ...... . :, ._ . - . . : -. -·

    ing worked test.. .. ·- ... "' .-:;_:- .. -·-. ··.·· . .,, .·

    IR testing was performed on worked samples at Mobil Oil Cor.poration. =; (Results of IR testing are not currentlj included ih Reference 1).·

    6.2 Normal Radiation Exposure

    , ~ ..

  • PRO.J'. NOS. :6896/97-00 CALC. NO. :CQD-042827 REV.00 DATE:02/20/89 PAGE 8 of 10

    The greases were placed into static containers and irradiated to a level of 2.2E06 rads gamma air equivalent which envelops the required radia-tion dose during normal service operation.

    6.3 Thermal Aging

    Per Reference 1, Section 10, the samples of greases were thermally aged at 250°F for 100 days.

    6.4 Accident Radiation Exposure

    6 c • J

    The grease samples were irradiated to a level of l.1E07~rads at a rate

    of l.OE06 rads/hr using a Co-60 source. This meets the plant's require-ment for 40 years plus accident.

    Cycle Aging

    After thermal aging, radiation and the ASTM tests, ih~ grease samples

    were placed in each of three Limitorque actuators. The Mobilux EPO, EPl

    and EP2 were used in the main gear case and Mobil Gi·ease 28 was- used in

    the L imitswitch gear case. The actuators were then cycle tested to

    simulate at least 120 full stroke ·and return cycles.

    6.6 Accident Simulation

    After cycle aging, the actuators:~ere pl~c~d in ~n -~~vir~~~ental c~~mb~r ... and subjected to an accident test simulating the 70 minute OBA .. · · ' ..

    requirement as given below:

    for for

    30 minutes 40 minutes

    ,. .

    The Limitorque actuators (including lubricants) inside ~rywell are re-quired to remain operable for up to one hour after any OBA •. The worst

  • PROJ. NOS. :6896/97-00 CALC. NO. :CQD-042827 REV.00 DATE:02/20/89 PAGE 9 of 10

    case peak temperature during any DB~ for which the ~ubricants are re-

    quired to be qualified is 334°F in the drywell. This value has been

    enveloped by the test with a margin of 15°F.

    The actuators outside drywell are required to remain operable for up to

    one year after any OBA. The only harsh parameter dt1ring a LOCA is radi-

    ation. The HELB parameter for these actuators is less severe than that

    of the inside drywell actuators and; therefore, is enveloped by the

    test.

    6.7 Pressure

    The peak pressure during the accident test was 71 psia. This pressure

    exceeds the postulated worst case pressure of 62 psia in the drywell.

    Pressure qualification is; therefore, considered acceptable.

    6.8 Humidity

    6.9

    During the accident test, the actuators with greases were subjected to

    steam/100% RH environment for 70 minutes, which simulated the actu~l in-

    stallation requirement.

    r ... :_

    Demineralized Water Spray ':.

    The spray requirement for Oresden and Quad Citie·s Stations is _dem.irera..:·

    ..

    lized water spray and is manually initiated. During the-acci.de.nt~·test~ .·"· >< : : ~-- _ . . - .·• ~ - ' - ·.;- . .. - .

    a demineral1zed wa-ter spray was initiated after 30 minutes into the test· -·~., ... ··.\:. . • · .. " • : ." r .- : •• · .. , - • •.. , .. - .. ·:·. • i- . .,r-: .- '.

    and continued for the remaining 40 minutes.of·the_test.''The''spray·rate·:.-. >··:·:'. :-used was 0.15 gpm/ft 2• .-.- . -~-- .. __ '· .. · .'

    - .

    6.10 Submergency

    There are no submergence requirements fo~ the Limftorque actuators (with

    lubricants) at Dresden and Quad Cities.

  • ..... _

    6.11 Performance Evaluation

    PROJ. NOS. : 6896 /97-0121 CALC. NO. :CQD-042827 REV.00 DATE:02/20/89 PAGE 10 of 10

    The actuators, lubricated with thermally ageL1 and irradiated greases,

    were cycled for 120 full cycles before the accident simulation test.

    The values of motor current and the timing of each ~troke were recorded

    (Appendix VI of Reference 1). The actuators cycling was performed at a constant calculated load (Appendix IV of Reference 1).

    6.12 The Greases Life Evaluation

    In the calc~lation (provided with Reference 6), the activation energy -

    values were determined for each type of grease at temperatures ranging

    from 155°F to 265°F. These calculations are based on the oxidation

    testing performed in accordance with ASTM 0942 by Mobil Oil

    Corporation. Since the activation energy values vary as temperatures

    vary, it is not practical to use Arrhenius formula tor determination of qualified life of the greases.

    Reference 7 (Page 9) and Reference 8 (Page 505) indicate that the aging

    of lubricants follows to the 10°c rule which states that life doubles

    with every 10°c temperature decrease.

    With thermal aging at 250°F for 100 days, the qualified 11fe·of the· greases, based on 10°c rule, will be a.t least 8 years at ·1so°F~ :·This· value of grease life corresponds to t~e greas~s' life curves iimlt~

    provided on Pages 8, 9 and 10 of Reference 6.

    7. 0 CONCLUSION . _:. ..

    The preliminary test report (Reference 1) and its evaluation indicate that the tested greases met the acceptance criteria and are qu~lified to the intent of NUREG-0588 with a quali~ied life of at least 8 years •