extended graphic library - aotewell master/3bse026427_adva… · extended graphic library...

120
Industrial IT 800xA - System 800xA for Advant Master System Version 4.0 Extended Graphic Library

Upload: duongnhi

Post on 01-Feb-2018

265 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

IndustrialIT800xA - System

800xA for Advant MasterSystem Version 4.0

Extended Graphic Library

Page 2: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant
Page 3: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Extended Graphic Library

IndustrialIT800xA - System

800xA for Advant MasterSystem Version 4.0

Page 4: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

NOTICEThe information in this document is subject to change without notice and should not beconstrued as a commitment by ABB. ABB assumes no responsibility for any errors thatmay appear in this document.

In no event shall ABB be liable for direct, indirect, special, incidental or consequentialdamages of any nature or kind arising from the use of this document, nor shall ABB beliable for incidental or consequential damages arising from use of any software or hard-ware described in this document.

This document and parts thereof must not be reproduced or copied without written per-mission from ABB, and the contents thereof must not be imparted to a third party nor usedfor any unauthorized purpose.

The software or hardware described in this document is furnished under a license andmay be used, copied, or disclosed only in accordance with the terms of such license.

This product meets the requirements specified in EMC Directive 89/336/EEC and in LowVoltage Directive 72/23/EEC.

Copyright © 2003 - 2004 by ABB. All rights reserved. Release: October 2004Document number: 3BSE026427R4001

TRADEMARKSRegistrations and trademarks used in this document include:

Process Portal A Trademark of ABB Ltd., Switzerland.

Microsoft Registered trademark of Microsoft Corporation.

Windows Registered trademark of Microsoft Corporation.

Windows 2000 and MS-DOS Registered trademarks of Microsoft Corporation.

ActiveX and Visual Basic Registered trademarks of Microsoft Corporation.

PostScript Registered trademark of Adobe Systems Inc.

Acrobat Reader Registered trademark of Adobe Systems Inc.

Ghost Registered trademark of Symantec Corporation.

Industrial IT Trademark of ABB.

Page 5: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

TABLE OF CONTENTS

About This BookGeneral ..............................................................................................................................9

Use of Warning, Caution, Information, and Tip Icons ....................................................11

Document Conventions ...................................................................................................12

Terminology.....................................................................................................................13

Related Documentation ...................................................................................................14

Section 1 - Extended Graphic ElementsAnalog Input, AI..............................................................................................................15

Integer Bargraph01...............................................................................................15

Integer Limit01.....................................................................................................18

Integer Percent01..................................................................................................20

Analog Output, AO..........................................................................................................22

Integer Button01...................................................................................................22

Binary Object, GENBIN .................................................................................................23

3-Valve01 .............................................................................................................23

3-Valve Long LLD01 (Left-Left-Down)..............................................................26

3-Valve Long LRD01 (Left-Right-Down) ...........................................................29

Breaker01 .............................................................................................................32

Choke Valve01 .....................................................................................................35

Damper01.............................................................................................................38

Fan01 .............................................................................................................41

Mixer01 .............................................................................................................44

Motor01 .............................................................................................................47

Pump01 .............................................................................................................50

Valve01 .............................................................................................................53

3BSE026427R4001 5

Page 6: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Table of Contents

Data Base Parameters, DAT(x)........................................................................................ 56

Square01 ............................................................................................................ 56

Digital Input, DI .............................................................................................................. 57

Arrow01 ............................................................................................................ 57

Breaker01 ............................................................................................................ 59

Damper01 ............................................................................................................ 61

Diamond01........................................................................................................... 63

Earth01 ............................................................................................................ 65

Fan01 ............................................................................................................ 67

IndicatorText01 .................................................................................................... 69

IndicatorText02 .................................................................................................... 71

IndicatorText03 .................................................................................................... 73

Motor01 ............................................................................................................ 75

Pump01 ............................................................................................................ 77

Reg Loop01.......................................................................................................... 79

Valve01 ............................................................................................................ 81

Digital Output, DO.......................................................................................................... 83

Diamond01........................................................................................................... 83

Reg Loop01.......................................................................................................... 85

Reg Loop02.......................................................................................................... 87

Square01 ............................................................................................................ 89

Valve01 ............................................................................................................ 91

Motor Control, MOTCON .............................................................................................. 93

Fan01 ............................................................................................................ 93

Pump01 ............................................................................................................ 96

Process Controller, PIDCON .......................................................................................... 98

Integer Limit01 .................................................................................................... 98

User Defined Object, GENUSD.................................................................................... 100

Choke Valve ....................................................................................................... 100

Pump Down 2-Way............................................................................................ 102

Pump Up 2-Way................................................................................................. 104

Valve01 .......................................................................................................... 106

6 3BSE026427R4001

Page 7: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Table of Contents

Valve Integer01 ..................................................................................................108

Valve Control, VALVECON..........................................................................................111

3-Valve01 ...........................................................................................................111

Damper01...........................................................................................................115

3BSE026427R4001 73BSE026427R4001 7

Page 8: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Table of Contents

8 3BSE026427R4001

Page 9: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

About This Book

GeneralThis book describes the Extended Graphic Elements for 800xA for Advant Master, which enables data retrieval from the Advant Controller 400 Series to IndustrialIT 800xA Core System. 800xA for Advant Master contains built in display elements and faceplates for the standard ABB object types below listed:

– Analog Input AI

– Analog Output AO

– Binary Object GENBIN

– Data Base Parameters DAT(x)

– Digital Input DI

– Digital Output DO

– Motor Control MOTCON

– Process Controller PIDCON

– User Defined Object GENUSD

– Valve Control VALVECON

• The Control Connection Aspects (CCA) for each object type. Each CCA contains the following:

– The name, data type, access rights (read/write) and subscription update rate of each attribute.

– The name of the corresponding OPC item (object of the controller).

– A user interface to inspect the object type attribute information. It can also be used to subscribe for the current value of each attribute.

3BSE026427R4001 9

Page 10: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Intended User About This Book

• The graphic elements aspects of each type (close-up where relevant and a number of additional graphical presentations).

• A faceplate aspect for each type.

The Object types also include additional aspects such as an Icon aspect, an Alarm List aspect (for the instantiated object), and Trend aspect. This book is focused on describing the graphic elements and faceplates.

Intended UserThis instruction is intended for application engineers that build process graphics and make modifications to standard faceplates and graphic elements.

The reader should have experience with process control systems and Microsoft® Windows® operating systems. In general, Microsoft Windows functions are not described in this instruction.

The faceplate images in this manual are not updated to the latest versions. For example, the pin button in a faceplate is not shown.

10 3BSE026427R4001

Page 11: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

About This Book Use of Warning, Caution, Information, and Tip Icons

Use of Warning, Caution, Information, and Tip IconsThis publication includes Warning, Caution, and Information where appropriate to point out safety related or other important information. It also includes Tip to point out useful hints to the reader. The corresponding symbols should be interpreted as follows:

Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage, it should be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all Warning and Caution notices.

Electrical warning icon indicates the presence of a hazard which could result in electrical shock.

Warning icon indicates the presence of a hazard which could result in personal injury.

Caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment/property.

Information icon alerts the reader to pertinent facts and conditions.

Tip icon indicates advice on, for example, how to design your project or how to use a certain function

3BSE026427R4001 11

Page 12: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Document Conventions About This Book

Document ConventionsThe following conventions are used for the presentation of material:

• The words in names of screen elements (for example, the title in the title bar of a window, the label for a field of a dialog box) are initially capitalized.

• Capital letters are used for the name of a keyboard key if it is labeled on the keyboard. For example, press the ENTER key.

• Lowercase letters are used for the name of a keyboard key that is not labeled on the keyboard. For example, the space bar, comma key, and so on.

• Press CTRL+C indicates that you must hold down the CTRL key while pressing the C key (to copy a selected object in this case).

• Press ESC E C indicates that you press and release each key in sequence (to copy a selected object in this case).

• The names of push and toggle buttons are boldfaced. For example, click OK.

• The names of menus and menu items are boldfaced. For example, the File menu.

– The following convention is used for menu operations: MenuName > MenuItem > CascadedMenuItem. For example: select File > New > Type.

– The Start menu name always refers to the Start menu on the Windows Task Bar.

• System prompts/messages are shown in the Courier font, and user responses/input are in the boldfaced Courier font. For example, if you enter a value out of range, the following message is displayed:

Entered value is not valid. The value must be 0 to30.

You may be told to enter the string TIC132 in a field. The string is shown as follows in the procedure:

TIC132

Variables are shown using lowercase letters.

sequence name

12 3BSE026427R4001

Page 13: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

About This Book Terminology

TerminologyThe following is a list of terms associated with the Extended Graphic Elements for 800xA for Advant Master for AC 400 Series, that you should be familiar with. The list contains terms and abbreviations that are unique to ABB or have a usage or definition that is different from standard industry usage..

Term Description

Graphic element A graphic aspect that has a reference to an Aspect Objects. Normally a part of a graphic display. A graphical object typically built up from several sub-elements and/or primitive elements. Some graphic elements are provided by ABB, while others may be built by the user.

Graphic element 1

Graphic element browser

A tool used to select object aware (graphic) elements in Graphics Builder.

Graphic expression Graphic expression is used to specify a data subscription and a relationship between process data and data to be displayed.

Examples of Graphic Elements provided by ABB:

81.4 M/MINValueField Bar Hscale

100.00.0

3BSE026427R4001 13

Page 14: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Related Documentation About This Book

Related Documentation

The following is a listing of documentation related to 800xA for Advant Master.

Graphic libraries Libraries of primitive elements, and standard graphic elements, for example faceplate element, object display and graphic element.

Faceplate Faceplates are used to monitor and control process data. A faceplate has a configuration view where you insert faceplate elements, buttons, status indicators and aspect links. The faceplate can have up to three run-time views:

reduced, normal and extended, depending on how much information the user wants.

Category Title Description

Installation IndustrialIT 800xA System Installation

This book describes the installation procedure for 800xA for Advant Master.

Configuration IndustrialIT 800xA System 800xA for Advant MasterConfiguration

This book describes how you connect AC 400 Series controllers to the Core System.

IndustrialIT 800xA System 800xA for Advant MasterGraphic Library

This book describes all the graphic elements and faceplates for AC 400 Series controllers specific object types.

Operation IndustrialIT 800xA System 800xA for Advant MasterOperation

This book describes how to operate the 800xA for Advant Master.

Term Description

14 3BSE026427R4001

Page 15: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements

Analog Input, AI

Integer Bargraph01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame White SELECTED = 1 Object select frame

Invisible SELECTED = 0

2 AI Error ? Red flashing ERR = 1 and AL_UNACK = 1

Unacknowledged and I/O Error

? Yellow ERR = 1 and BLOCKED = 1

Input blocked and I/O Error

? Red ERR = 1 I/O Error

ERR = 0 Invisible

1.4.

2.3.6.7.

5.?

3BSE026427R4001 15

Page 16: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Analog Input, AI Section 1 Extended Graphic Elements

No Description Presentation Condition Remarks

3 Measured Value VALUE The object value

ERR = 1 Invisible - I/O Error

Red flashing AL_UNACK = 1 Unacknowledged

Yellow BLOCKED = 1 Input blocked

Red DISTURB = 1 Alarm

Green -

4 High Limit 2 HI_LIM2 Alarm High limit 2

HI_LIM2 >= RANGEMAX or EN_H2 = 0

Invisible

Filled Yellow VALUE>H2 = 1 and AL_BLK = 1

Logical colorblockedSymbol

Unfilled Yellow AL_BLK = 1 Logical colorblockedSymbol

Filled Red VALUE>H2 = 1

Unfilled Grey -

5 High Limit 1 HI_LIM1 Warning High limit 1

HI_LIM1 >= RANGEMAX or EN_H1 = 0

Invisible

Filled Yellow VALUE>H1 = 1 and AL_BLK = 1

Logical colorblockedSymbol

Unfilled Yellow AL_BLK = 1 Logical colorblockedSymbol

Filled Red VALUE>H1 = 1

Unfilled Grey -

16 3BSE026427R4001

Page 17: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Analog Input, AI

Configuration:

No Description Presentation Condition Remarks

6 Low Limit 1 LO_LIM1 Warning Low limit 1

LO_LIM1 <= RANGEMIN or EN_L1 = 0

Invisible

Filled Yellow VALUE<L1 = 1 and AL_BLK = 1

Logical colorblockedSymbol

Unfilled Yellow AL_BLK = 1 Logical colorblockedSymbol

Filled Red VALUE<L1 = 1

Unfilled Grey -

7 Low Limit 2 LO_LIM2 Alarm Low limit 2

LO_LIM2 <= RANGEMIN or EN_L2 = 0

Invisible

Filled Yellow VALUE<L2 = 1 and AL_BLK = 1

Logical colorblockedSymbol

Unfilled Yellow AL_BLK = 1 Logical colorblockedSymbol

Filled Red VALUE<L2 = 1

Unfilled Grey -

Parameters AffectsOptions (bold is default)

Remarks

FrameStyle Raised, Sunken and Flat

FrameWidth 3, any width

Orientation Vertical, Horizontal

3BSE026427R4001 17

Page 18: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Analog Input, AI Section 1 Extended Graphic Elements

Integer Limit01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The object frame

Solid White SELECTED = 1 Object selected

Dotted Yellow AL_BLK = 1 Alarm blocked by operator

2 Measured Value VALUE Object value

Red / White cross VALUE is Bad No contact with Controller

Yellow BLOCKED =1 Input blocked

? ? ? Red flashing ERR = 1 andAL_UNACK = 1

Unacknowledged and I/O Error

Red flashing AL_UNACK = 1 Unacknowledged alarm

? ? ? Red ERR = 1 I/O Error

Red DISTURB = 1 Alarm

Green -

3.

2.1.

X

18 3BSE026427R4001

Page 19: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Analog Input, AI

Configuration:

3 Limit

Yellow BLOCKED =1 Input blocked

? Red flashing ERR = 1 andAL_UNACK = 1

Unacknowledged and I/O Error

Red flashing AL_UNACK = 1 Unacknowledged alarm

? Red ERR = 1 I/O Error

H2 Red ABOVE_HI_LIM2 = 1 Above High Limit 2

H1 Red ABOVE_HI_LIM1 = 1 Above High Limit 1

L2 Red BELOW_LO_LIM2 = 1 Below Low Limit 2

L1 Red BELOW_LO_LIM1 = 1 Below Low Limit 1

Limit is Invisible

Parameters Affects Options (bold is default) Remarks

BackgroundColor 2. Measured Value & 3. Limit Black, any other color

No Description Presentation Condition Remarks

3BSE026427R4001 19

Page 20: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Analog Input, AI Section 1 Extended Graphic Elements

Integer Percent01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame Solid White SELECTED = 1 Object select frame

Dotted Yellow AL_BLK = 1 Alarm blocked by operator

Invisible

2 Measured Value VALUE Object value

Red / White cross VALUE is Bad No contact with Controller

Yellow BLOCKED =1 Input blocked

? ? ? Red flashing ERR = 1 andAL_UNACK = 1

Unacknowledged and I/O Error

Red flashing AL_UNACK = 1 Unacknowledged alarm

? ? ? Red ERR = 1 I/O Error

Red DISTURB = 1 Alarm

Green -

1. 2.

X

20 3BSE026427R4001

Page 21: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Analog Input, AI

Configuration:

Parameters AffectsOptions (bold is default)

Remarks

BackgroundColor 2. Measured Value Black, any other color

FrameStyle Flat, Raised and Sunken

FrameWidth 0, any width

3BSE026427R4001 21

Page 22: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Analog Output, AO Section 1 Extended Graphic Elements

Analog Output, AO

Integer Button01

Presentation:

Behavior:

Configuration:

No Description Presentation Condition Remarks

1 Lock Frame White SELECTED = 1 Object select frame

Invisible SELECTED = 0

2 Output Value VALUE Object value

Red flashing AL_UNACK = 1 Unacknowledged alarm

Yellow OUTP_BLK = 1 Output blocked

Red ERR = 1 Alarm

Cyan MAN = 1

Magenta MAN = 0

Parameters Affects Options (bold is default) Remarks

BackgroundColor 2. Output Value Black, any other color

FrameWidth 2, any width

2.1.

22 3BSE026427R4001

Page 23: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Binary Object, GENBIN

3-Valve01

Presentation:

Down

Left

Right

3. Off-Symbol

Up

3. On-Symbol2.

1.

3BSE026427R4001 23

Page 24: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

24 3BSE026427R4001

Page 25: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Configuration:

No Description Presentation Condition Remarks

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Actuator ActuatorIndVis = 1 Actuator Indication Visible

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

Parameters Affects Options (bold is default) Remarks

Direction 3 Symbol Up, Down, Left, Right

ActuatorIndVis 3 Symbol false, true

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

3BSE026427R4001 25

Page 26: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

3-Valve Long LLD01 (Left-Left-Down)

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

3. On-Symbol 3. Off-Symbol

2.

1.

26 3BSE026427R4001

Page 27: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

Shape R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Actuator ActuatorIndVis = 1 Actuator Indication Visible

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

3BSE026427R4001 27

Page 28: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

ActuatorIndVis 3 Symbol false, true

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

28 3BSE026427R4001

Page 29: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

3-Valve Long LRD01 (Left-Right-Down)

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

False

3. On-Symbol 3. Off-Symbol

2.

True1.

3BSE026427R4001 29

Page 30: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

No Description Presentation Condition Remarks

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Actuator ActuatorIndVis = 1 Actuator Indication Visible

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

30 3BSE026427R4001

Page 31: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Configuration:

No Description Presentation Condition Remarks

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

Parameters Affects Options (bold is default) Remarks

ActuatorIndVis 3 Symbol false, true

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

3BSE026427R4001 31

Page 32: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Breaker01

Presentation:

Horizontal1.

3. On-Symbol 3. Off-Symbol

2.Vertical

32 3BSE026427R4001

Page 33: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3BSE026427R4001 33

Page 34: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

Parameters Affects Options (bold is default) Remarks

Orientation 3 Symbol Horizontal, Vertical

Dimension3D 3 Symbol false, true

ModeIndVis 2 Flag false, true

ControlIndVis 2 Flag false, true

34 3BSE026427R4001

Page 35: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Choke Valve01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

3. On-Symbol 3. Off-Symbol

2.

1.

3BSE026427R4001 35

Page 36: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Actuator ActuatorIndVis = 1 Actuator Indication Visible

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

36 3BSE026427R4001

Page 37: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Configuration:

Parameters Affects Options (bold is default) Remarks

VerticalPosition 3 Symbol Left, Right

ActuatorIndVis 3 Symbol false, true

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

3BSE026427R4001 37

Page 38: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Damper01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

3. On-Symbol 3. Off-Symbol

2.

1.

38 3BSE026427R4001

Page 39: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

3BSE026427R4001 39

Page 40: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

Orientation 3 Symbol Horizontal, Vertical

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

40 3BSE026427R4001

Page 41: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Fan01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.

3. On-Symbol 3. Off-Symbol

1.

3BSE026427R4001 41

Page 42: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

42 3BSE026427R4001

Page 43: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Configuration:

Parameters Affects Options (bold is default) Remarks

Direction 1 Symbol Right, Up, Down, Left

ModeIndVis 2 Flag false, true

ControlIndVis 2 Flag false, true

3BSE026427R4001 43

Page 44: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Mixer01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.

3. On-Symbol 3. Off-Symbol

1.

44 3BSE026427R4001

Page 45: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

3BSE026427R4001 45

Page 46: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

ModeIndVis 2 Flag false, true

ControlIndVis 2 Flag false, true

46 3BSE026427R4001

Page 47: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Motor01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

3. On-Symbol 3. Off-Symbol

2.

1.

3BSE026427R4001 47

Page 48: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

48 3BSE026427R4001

Page 49: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Configuration:

Parameters Affects Options (bold is default) Remarks

Orientation 3 Symbol Horizontal, Vertical

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

3BSE026427R4001 49

Page 50: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Pump01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

3. On-Symbol 3. Off-Symbol

2.

1.

50 3BSE026427R4001

Page 51: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

3BSE026427R4001 51

Page 52: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

Direction 1 Symbol Right, Up, Down, Left

ModeIndVis 2 Flag false, true

ControlIndVis 2 Flag false, true

52 3BSE026427R4001

Page 53: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Valve01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

3. Off-Symbol3. On-Symbol

2.

1.

3BSE026427R4001 53

Page 54: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Binary Object, GENBIN Section 1 Extended Graphic Elements

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

R Green PC_ST_18 = 1 Remote Indication

L Green PC_ST_17 = 1 Local Indication

C Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25 On

Off-Symbol PC_ST_24 = PC_ST_25 Off

Actuator ActuatorIndVis = 1 Actuator Indication Visible

Color Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 orAU_ST_04 = 1 orAU_ST_05 = 1 orAU_ST_06 = 1 orAU_ST_07 = 1

UnAck signal errorUnAck feedback errorUnAck alarm Hi limit2UnAck alarm HI limit1UnAck alarm Lo limit1UnAck alarm Lo limit2

Red PC_ST_00 = 1 orPC_ST_01 = 1 orPC_ST_04 = 1 orPC_ST_05 = 1 orPC_ST_06 = 1 orPC_ST_07 = 1

Signal errorAlarm feedback errorAlarm Hi limit2Alarm HI limit1Alarm Lo limit1Alarm Lo limit2

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

54 3BSE026427R4001

Page 55: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Binary Object, GENBIN

Configuration:

Parameters Affects Options (bold is default) Remarks

Orientation 3 Symbol Horizontal, Vertical

ActuatorIndVis 3 Symbol false, true

ModeIndVis 2 Flag false, true

ControlIndVis 2 Flag false, true

3BSE026427R4001 55

Page 56: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Data Base Parameters, DAT(x) Section 1 Extended Graphic Elements

Data Base Parameters, DAT(x)

Square01

Presentation:

Behavior:

Configuration:

No Description Presentation Condition Remarks

1 Symbol 2D Display Object

1.1 Shape On-Symbol VALUE = 1 Data true

Off-Symbol VALUE = 0 Data false

1.2 Color Green VALUE = 1

2 Label Black VALUE = 1

Grey VALUE = 0

Parameters Affects Options (bold is default) Remarks

FrameWidth 1 Symbol 2, 1..4

LabelText 2 Label ““, any other character

2.

1. On-Symbol 1. Off-Symbol

56 3BSE026427R4001

Page 57: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Digital Input, DI

Arrow01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 2D and 3D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2. On-Symbol 2. On-Symbol

1.

3BSE026427R4001 57

Page 58: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Light Blue

Parameters Affects Options (bold is default) Remarks

Direction 2 Symbol Right, Left, Up, Down

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

58 3BSE026427R4001

Page 59: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Breaker01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 2D and 3D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Horizontal1.

2. On-Symbol 2. Off-Symbol

Vertical

3BSE026427R4001 59

Page 60: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Green

Parameters Affects Options (bold is default) Remarks

Dimension3D 2 Symbol false, true

Orientation 2 Symbol Horizontal, Vertical

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

60 3BSE026427R4001

Page 61: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Damper01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 3D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Green

2. On-Symbol 2. Off-Symbol

1.

3BSE026427R4001 61

Page 62: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

Orientation 2 Symbol Horizontal, Vertical

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

FrameWidth 2 Frame 2, (1..4)

62 3BSE026427R4001

Page 63: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Diamond01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 3D Display Object

2.1 Shape Q ERROR = 1 Input error

On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2. On-Symbol 2. Off-Symbol

1,

3BSE026427R4001 63

Page 64: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Green

Parameters Affects Options (bold is default) Remarks

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

FrameWidth 2 Frame 2, (1..4)

64 3BSE026427R4001

Page 65: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Earth01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 2D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Green

2. On-Symbol 2. Off-Symbol

1.

3BSE026427R4001 65

Page 66: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

66 3BSE026427R4001

Page 67: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Fan01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 23D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Green

2. On-Symbol 2. Off-Symbol

1.

3BSE026427R4001 67

Page 68: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

Direction 2 Symbol Right, Left, Up, Down

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

68 3BSE026427R4001

Page 69: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

IndicatorText01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Symbol 2D Display Object

1.1 Shape Q SELECTED = 0 and ERROR = 1

Input error

[ Q ] SELECTED = 1 and ERROR = 1

Input error

On SELECTED = 0 and ((VALUE = 1 andInverted = 0) or(VALUE = 0 andInverted = 1))

Input closed

[ On ] SELECTED = 1 and ((VALUE = 1 andInverted = 0) or(VALUE = 0 andInverted = 1))

Input closed

Off SELECTED = 0 and ((VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1))

Input open

1. On-Symbol 1. Off-Symbol

3BSE026427R4001 69

Page 70: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

[ Off ] SELECTED = 1 and ((VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1))

Input open

1.2 Color

White SELECTED = 1 Object selected

Flashing Red ALARM_UNACK = 1 Alarm Unacknowledged

Yellow UPD_BLK = 1 andERROR = 1

Input Blocked andinput error

Red (DISTURBANCE = 1 andDisturbanceUsed = 1) or ERROR = 1

Alarm Acknowledgedorinput error

Yellow (VALUE = 1 andInverted = 0) or(VALUE = 0 andInverted = 1)

Input open

Magenta (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input closed

Parameters Affects Options (bold is default) Remarks

DisturbanceUsed 1. Symbol false, true

Inverted 1 Symbol false, true

LabelOffText 1. Symbol “Off“, any letter

LabelOnText 1. Symbol “On“, any letter

70 3BSE026427R4001

Page 71: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

IndicatorText02

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Symbol 2D Display Object

1.1 Label Q ERROR = 1 Input Error

Generator Not Available

(VALUE = 1 andInverted = 0) or(VALUE = 0 andInverted = 1)

Input On Label visibleLabelOnText

- (VALUE = 0 andInverted = 0) or(VALUE = 1andInverted = 1)

Input Off Label visibleLabelOffText

1. On-Label 1. Off-Label

3BSE026427R4001 71

Page 72: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

1.2 Color

White SELECTED = 1 Object Select

Flashing Red ERROR = 1 Input Error

Flashing Red (VALUE = 1 andInverted = 0) or(VALUE = 0 andInverted = 1)

Black (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Parameters Affects Options (bold is default) Remarks

Inverted 1. Symbol false, true

LabelOffText 1. Symbol “-“, any letter

LabelOnText 1. Symbol “Generator Not Available“, any letter

72 3BSE026427R4001

Page 73: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

IndicatorText03

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Solid White Line SELECTED = 1 Object selected

2 Symbol

2.1 Shape F (DISTURBANCE = 1 and DisturbanceUsed = 1) or ALARM_UNACK = 1

Alarm unacknowledged

B ALARM_BLK = 1 orALARM_PERIOD_BLK = 1 or REPEAT_FAIL_BLK = 1

Alarm Blocked

Invisible Else

2.2 Color Yellow flash REPEAT_FAIL_BLK = 1

Red flash ALARM_UNACK = 1 Alarm unacknowledged

Yellow ALARM_BLK = 1 orALARM_PERIOD_BLK = 1

Alarm Blocked

Red DISTURBANCE = 1 Alarm acknowledged

2. F-Symbol 2. B-Symbol

1.

3BSE026427R4001 73

Page 74: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

DisturbanceUsed 2. Symbol false, true

74 3BSE026427R4001

Page 75: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Motor01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 3D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2. On-Symbol 2. Off-Symbol

1.

3BSE026427R4001 75

Page 76: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Green

Parameters Affects Options (bold is default) Remarks

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

76 3BSE026427R4001

Page 77: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Pump01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 3D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Green

2. On-Symbol 2. Off-Symbol

1.

3BSE026427R4001 77

Page 78: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

Direction 2 Symbol Right, Left, Up, Down

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

78 3BSE026427R4001

Page 79: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Reg Loop01

Presentation:

Up1.

Down

Left

Right

2. Off-Symbol2. On-Symbol

3BSE026427R4001 79

Page 80: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Behavior:

Configuration:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 2D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance exists orInput error

Green

Parameters Affects Options (bold is default) Remarks

Direction 2 Symbol Up, Down, Right, Left

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

80 3BSE026427R4001

Page 81: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Input, DI

Valve01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Symbol 3D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Input closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Input open

Actuator ActuatorIndVis = True Actuator visible

2. On-Symbol 2. Off-Symbol

1.

3BSE026427R4001 81

Page 82: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Input, DI Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

2.2 Color Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Yellow UPD_BLK = 1 Input blocked

Red (DISTURBANCE = 1 andDisturbanceUsed = 1 orERROR = 1

Alarm acknowledgedbut disturbance existsorInput error

Green

Parameters Affects Options (bold is default) Remarks

Orientation 2 Symbol Horizontal, Vertical

ActuatorIndVis 2 Symbol false, true

DisturbanceUsed 2 Symbol false, true

Inverted 2 Symbol false, true

FrameWidth 1 Symbol 2, 1..4

82 3BSE026427R4001

Page 83: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Output, DO

Digital Output, DO

Diamond01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

2 Label

Label Character LabelText

Color Black

3 Symbol 3D Display Object

3.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Pressed inOutput On

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Output Off

Cross MAN_MODE = 0 Auto mode

3. On-Symbol 3 Off-Symbol

2.

1.

3BSE026427R4001 83

Page 84: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Output, DO Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

3.2 Color Yellow OUTP_BLK = 1 Output blocked

Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Red ERROR = 1 Output error

Cyan MAN_MODE = 1 Manual mode

Magenta MAN_MODE = 0 Auto mode

Parameters Affects Options (bold is default) Remarks

Inverted 3 Symbol false, true

FrameWidth 3 Symbol 2, 1..4

LabelText 2 Label “ “, any character

84 3BSE026427R4001

Page 85: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Output, DO

Reg Loop01

Presentation:

Up1.

Down

Left

2. Off-Symbol2. On-Symbol

Right

3BSE026427R4001 85

Page 86: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Output, DO Section 1 Extended Graphic Elements

Behavior:

Configuration:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

2 Symbol 2D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Output closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Output open

2.2 Color Yellow OUTP_BLK = 1 Output blocked

Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Red ERROR = 1 Output error

Cyan MAN_MODE = 1 Manual mode

Magenta MAN_MODE = 0 Auto mode

Parameters Affects Options (bold is default) Remarks

Direction 2 Symbol Up, Down, Left and Right

Inverted 2. Symbol false, true

86 3BSE026427R4001

Page 87: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Output, DO

Reg Loop02

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

2 Symbol 2D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Output closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Output open

2.2 Color Yellow OUTP_BLK = 1 Output blocked

Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Red ERROR = 1 Output error

Cyan MAN_MODE = 1 Manual mode

Magenta MAN_MODE = 0 Auto mode

2. On-Symbol 2. Off-Symbol

1.

3BSE026427R4001 87

Page 88: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Output, DO Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

Inverted 2 Symbol false, true

FrameWidth 2. Symbol 2, 1..4

88 3BSE026427R4001

Page 89: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Output, DO

Square01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

2 Label

Label Character LabelText

Color Black

3 Symbol 3D Display Object

3.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Pressed inOutput On

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Output Off

Cross MAN_MODE = 0 Auto mode

3. On-Symbol 3. Off-Symbol

2.

1.

3BSE026427R4001 89

Page 90: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Output, DO Section 1 Extended Graphic Elements

Configuration:

No Description Presentation Condition Remarks

3.2 Color Yellow OUTP_BLK = 1 Output blocked

Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Red ERROR = 1 Output error

Cyan MAN_MODE = 1 Manual mode

Magenta MAN_MODE = 0 Auto mode

Parameters Affects Options (bold is default) Remarks

Inverted 3 Symbol false, true

FrameWidth 3 Symbol 2, 1..4

LabelText 2 Label “ “, any character

90 3BSE026427R4001

Page 91: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Digital Output, DO

Valve01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

2 Symbol 3D Display Object

2.1 Shape On-Symbol (VALUE = 1 and Inverted = 0) or(VALUE = 0 andInverted = 1)

Output closed

Off-Symbol (VALUE = 0 andInverted = 0) or(VALUE = 1 andInverted = 1)

Output open

Actuator ActuatorIndVis = True Actuator visible

2.2 Color Yellow OUTP_BLK = 1 Output blocked

Flashing Red ALARM_UNACK= 1 Alarm unacknowledged

Red ERROR = 1 Output error

Cyan MAN_MODE = 1 Manual mode

Magenta MAN_MODE = 0 Auto mode

2. On-Symbol 2. Off-Symbol

1.

3BSE026427R4001 91

Page 92: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Digital Output, DO Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

Orientation 2 Symbol Horizontal, Vertical

ActuatorIndVis 2 Symbol false, true

Inverted 2 Symbol false, true

FrameWidth 2. Symbol 2, 1..4

92 3BSE026427R4001

Page 93: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Motor Control, MOTCON

Motor Control, MOTCON

Fan01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame Solid White SELECTED = 1 Selected

Solid Yellow IND2_00 = 1 Interlock override by operator

Dotted Yellow AL_BLK = 1 Alarm blocked by operator

Invisible -

3. On-Symbol 3. Off-Symbol

2.

1.

3BSE026427R4001 93

Page 94: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Motor Control, MOTCON Section 1 Extended Graphic Elements

No Description Presentation Condition Remarks

2 Mode ModeIndVis= True Status Indication

M Green IND2_05 = 0 andIND2_02 = 0 andIND2_03 = 0

Manual mode

A Green flashing IND2_05 = 1 andIND2_02 = 0 andIND2_03 = 0 andIND2_06 = 0 andIND1_12 = 0

Indicates Auto StartInit Not Performed

A Green IND2_05 = 1 andIND2_02 = 0 andIND2_03 = 0

Auto mode

* Yellow IND2_02 = 1 Test mode

ModeIndVis = False Mode invisible

3 Symbol 3D Display Object

3.1 Shape On-Symbol IND1_12 = 1 or

IND1_15 = 1 Started

Off-Symbol IND1_12 = 0 and

IND1_15 = 0 Stopped

3.2 Color Grey IMPLEMENTED = 0 Implemented

Grey IND2_03 = 1 Out of service

Red flashing AU_IND = 1 Alarm unacknowledged

Red IND1_DIST = 1 Error

Green flashing IND1_15 = 1 Change of Direction in progress

Green -

94 3BSE026427R4001

Page 95: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Motor Control, MOTCON

Configuration:

Parameters Affects Options (bold is default) Remarks

Direction 3. Symbol Right, Up, Down and Left

ModIndVis 2. Mode True, False

3BSE026427R4001 95

Page 96: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Motor Control, MOTCON Section 1 Extended Graphic Elements

Pump01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame Solid White SELECTED = 1 Selected

Solid Yellow IND2_00 = 1 Interlock override by operator

Dotted Yellow AL_BLK = 1 Alarm blocked by operator

Invisible -

2 Mode ModeIndVis= True Status Indication

M Green IND2_05 = 0 andIND2_02 = 0 andIND2_03 = 0

Manual mode

A Green flashing IND2_05 = 1 andIND2_02 = 0 andIND2_03 = 0 andIND2_06 = 0 andIND1_12 = 0

Indicates Auto StartInit Not Performed

A Green IND2_05 = 1 andIND2_02 = 0 andIND2_03 = 0

Auto mode

* Yellow IND2_02 = 1 Test mode

ModeIndVis = False Mode invisible

3. On-Symbol 3. Off-Symbol

2.

1.

96 3BSE026427R4001

Page 97: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Motor Control, MOTCON

Configuration:

No Description Presentation Condition Remarks

3 Symbol 3D Display Object

3.1 Shape On-Symbol IND1_12 = 1 or

IND1_15 = 1 Started

Off-Symbol IND1_12 = 0 and

IND1_15 = 0 Stopped

3.2 Color Grey IMPLEMENTED = 0 Implemented

Grey IND2_03 = 1 Out of service

Red flashing AU_IND = 1 Alarm unacknowledged

Red IND1_DIST = 1 Error

Green flashing IND1_15 = 1 Change of Direction in progress

Green -

Parameters Affects Options (bold is default) Remarks

Direction 3. Symbol Right, Up, Down and Left

ModIndVis 2. Mode True, False

3BSE026427R4001 97

Page 98: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Process Controller, PIDCON Section 1 Extended Graphic Elements

Process Controller, PIDCON

Integer Limit01

Presentation:

Behavior:

No Description Default Presentation Condition Remarks

1 Lock Frame

Solid White Line SELECTED = 1 Object select frame

Dotted Yellow Line ALARM_F1_BLK = 1 or ALARM_F2_BLK

Alarm blocked by Operator

? ? ? in Flashing Red TS_AI_ERROR = 1 and ALARM_UNACK 1

Alarm Unacknowledged

Flashing Red ALARM_UNACK = 1 Alarm Unacknowledged

? ? ? in Red TS_AI_ERROR = 1 Alarm Acknowledged

Red DIST = 1 Alarm Acknowledged

Green

3.

1. 2.

98 3BSE026427R4001

Page 99: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Process Controller, PIDCON

Configuration:

3 Limit

H2 Red TS_MV_ABOVE_H2 = 1 Alarm High Limit 2

H1 Red TS_MV_ABOVE_H1 = 1 Alarm High Limit 1

L2 Red TS_MV_BELOW_L2 = 1 Alarm Low Limit 2

L1 Red TS_MV_BELOW_L1 = 1 Alarm Low Limit 1

Limit is invisible

Parameters Affects Options (bold is default) Remarks

Format 2 Value “#0.00”, any other Visual Basic Format

No Description Default Presentation Condition Remarks

3BSE026427R4001 99

Page 100: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

User Defined Object, GENUSD Section 1 Extended Graphic Elements

User Defined Object, GENUSD

Choke Valve

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.

3. On-Symbol 3. Off-Symbol

1.

100 3BSE026427R4001

Page 101: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements User Defined Object, GENUSD

Configuration:

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

M3 Green PC_ST_18 = 1 Remote Indication

M2 Green PC_ST_17 = 1 Local Indication

M1 Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25

Off-Symbol PC_ST_24 = PC_ST_25

Actuator ActuatorIndVis = 1

3.2 Color

Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack signal errorUnAck feedback error

Red PC_ST_00 = 1 orPC_ST_01 = 1

Signal errorFeedback error

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

Parameters Affects Options (bold is default) Remarks

VerticalPosition 3 Symbol Left, Right

ActuatorIndVis 3 Symbol false, true

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

3BSE026427R4001 101

Page 102: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

User Defined Object, GENUSD Section 1 Extended Graphic Elements

Pump Down 2-Way

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

3. Forward-Symbol 3. Reverse-Symbol 3. Off-Symbol

2.

1.

102 3BSE026427R4001

Page 103: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements User Defined Object, GENUSD

Configuration:

No Description Presentation Condition Remarks

2.3 Control Indication ControlIndVis = 1

M3 Green PC_ST_18 = 1 Remote Indication

M2 Green PC_ST_17 = 1 Local Indication

M1 Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape Forward-Symbol PC_ST_24 = 1 and PC_ST_25 = 0

Reverse-Symbol PC_ST_24 = 0 and PC_ST_25 = 1

Off-Symbol PC_ST_24 = PC_ST_25

3.2 Color

Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack signal errorUnAck Feedback error

Red PC_ST_00 = 1 orPC_ST_01 = 1

Signal errorFeedback error

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

Parameters Affects Options (bold is default) Remarks

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

3BSE026427R4001 103

Page 104: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

User Defined Object, GENUSD Section 1 Extended Graphic Elements

Pump Up 2-Way

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

3. Forward-Symbol 3. Reverse-Symbol 3. Off-Symbol

2.

1.

104 3BSE026427R4001

Page 105: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements User Defined Object, GENUSD

Configuration:

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

M3 Green PC_ST_18 = 1 Remote Indication

M2 Green PC_ST_17 = 1 Local Indication

M1 Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape Forward-Symbol PC_ST_24 = 1 and PC_ST_25 = 0

Reverse-Symbol PC_ST_24 = 0 and PC_ST_25 = 1

Off-Symbol PC_ST_24 = PC_ST_25

3.2 Color

Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack signal errorUnAck Feedback error

Red PC_ST_00 = 1 orPC_ST_01 = 1

Signal errorFeedback error

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

Parameters Affects Options (bold is default) Remarks

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

3BSE026427R4001 105

Page 106: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

User Defined Object, GENUSD Section 1 Extended Graphic Elements

Valve01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.

3. On-Symbol 3. Off-Symbol

1.

106 3BSE026427R4001

Page 107: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements User Defined Object, GENUSD

Configuration:

No Description Presentation Condition Remarks

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

M3 Green PC_ST_18 = 1 Remote Indication

M2 Green PC_ST_17 = 1 Local Indication

M1 Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25

Off-Symbol PC_ST_24 = PC_ST_25

Actuator ActuatorIndVis = 1

3.2 Color

Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack signal errorUnAck feedback error

Red PC_ST_00 = 1 orPC_ST_01 = 1

Signal errorFeedback error

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

Parameters Affects Options (bold is default) Remarks

Orientation 3 Symbol Horizontal, Vertical

ActuatorIndVis 3 Symbol false, true

ModeIndVis 2 Flag false, true

ControlVis 2 Flag false, true

3BSE026427R4001 107

Page 108: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

User Defined Object, GENUSD Section 1 Extended Graphic Elements

Valve Integer01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame The Object frame

Color Solid White Line SELECTED = 1 Object selected

Dotted Yellow Line ALARM_BLK = 1 Alarm blocked

2 Flags Status Indication

2.1 Alarm Indication

F Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1 or

Unack Alarm Indication

F Red PC_ST_00 = 1 orPC_ST_01 = 1

Alarm Indication

X Yellow PC_ST_08 = 1 or PC_ST_09 = 1 orPC_ST_10 = 1 orPC_ST_11 = 1

Interlock Indication

2.2 Mode Indication ModeIndVis = 1

M Green PC_ST_20 = 1 Manual Indication

A Green PC_ST_19 = 1 Auto Indication

B Green PC_ST_21 = 1 Blocked Indication

5.

2.

4.

3. On-Symbol 3. Off-Symbol

1.

108 3BSE026427R4001

Page 109: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements User Defined Object, GENUSD

No Description Presentation Condition Remarks

S Green PC_ST_22 = 1 Standby Indication

2.3 Control Indication ControlIndVis = 1

M3 Green PC_ST_18 = 1 Remote Indication

M2 Green PC_ST_17 = 1 Local Indication

M1 Green PC_ST_16 = 1 Central Indication

3 Symbol 3D Display Object

3.1 Shape On-Symbol PC_ST_24 <> PC_ST_25

Off-Symbol PC_ST_24 = PC_ST_25

Label Actuator ActuatorIndVis = 1

3.2 Color

Flashing Red AU_ST_00 = 1 orAU_ST_01 = 1

Unack signal errorUnAck feedback error

Red PC_ST_00 = 1 orPC_ST_01 = 1

Signal errorFeedback error

Flashing Green PC_ST_25 = 1

Green PC_ST_25 = 0

4 MV Measured Value

4.1 Color Flashing Red AU_ST_00-07 = 1 or Unacknowledged alarm

Red PC_ST_00-07 = 1 or Alarm

Green

5 Label Actuator Label

5.1 Color Flashing Red AU_ST_00-02 = 1 or

Red PC_ST_00-02 = 1 or

Green Flashing PC_ST_25 = 1

Green PC_ST_25 = 0

3BSE026427R4001 109

Page 110: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

User Defined Object, GENUSD Section 1 Extended Graphic Elements

Configuration:

Parameters Affects Options (bold is default) Remarks

ActuatorIndVis 2 Flag false, true

ControlIndVis 2 Flag false, true

ModeIndVis 2 Flag false, true

Label 5 Label Actuator “M”, any character

UnitVisible 4 MV true, false

110 3BSE026427R4001

Page 111: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Valve Control, VALVECON

Valve Control, VALVECON

3-Valve01

Presentation:

Down

Left

Right

2.

3. On-Symbol 3. Off-Symbol

Up1.

3BSE026427R4001 111

Page 112: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Valve Control, VALVECON Section 1 Extended Graphic Elements

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame Solid White SELECTED = 1 Selected

Solid Yellow IND2_00 = 1 Interlock override by operator

Dotted Yellow AL_BLK = 1 Alarm blocked by operator

Invisible -

2 Flags Status Indication

2.1 Mode Indication ModeIndVis = 1

* Yellow IND2_02 = 1 andIND2_03 = 0

Test

A Green IND2_05 = 1 andIND2_02 = 0 andIND2_03 = 0

Auto Mode

M Green IND2_05 = 0 andIND2_02 = 0 andIND2_03 = 0

Manual Mode

2.2 Control Indication PointOfControlIndVis = 0

S Green IND2_04 = 1 Sequence control

L Green IND2_01 = 1 and IND2_04 = 0

Local control

C Green IND2_01 = 0 andIND2_04 = 0

Central control

- PointOfControlIndVis = 0 Point of control is invisible

2.3 Interlock Indication InterlockIndVis = 1 and IND2_03

XA Yellow IND2_14 = 1 IA1

IND2_07 = 1 Ready to start

112 3BSE026427R4001

Page 113: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Valve Control, VALVECON

Configuration:

No Description Presentation Condition Remarks

X Yellow IND2_08 = 1 orIND2_09 = 1 orIND2_11 = 1 or(IND2_13 = 1 andIND1_11 = 0) or(IND2_00 = 0 and(IND2_10 = 1 or(IND2_12 = 1 andIND1_11 = 0)))

IC1 orIC2 orIB2 or(IB4 &OPN = 0) or(Blkintl = 0 &(IB1 or(IB3 &OPN = 0)))

3 Symbol 3D Display Object

3.1 Shape On-Symbol IND1_11 = 1 Limit position for open

Off-Symbol IND1_11 = 0 No limit position for open

Actuator ActuatorIndVis = 1 Actuator visible

3.2 Color

Grey IMPLEMENTED = 0

Grey IND2_03 = 1 Out of service

Red Flashing IND1_09 = 1 Unacknowledged Alarm

Red IND1_08 = 1 Alarm or Error

Green flashing IND1_15 = 1 andIND1_12 = 0

Intermediate position Not open

Green flashing IND1_15 = 1 andIND1_12 = 1

Intermediate position Open

Green No intermediate position Limit position for open

Parameters Affects Options (bold is default) Remarks

Direction 3 Symbol Down, Up, Right, Left

ActuatorIndVis 3 Symbol false, true

ModeIndVis 2 Flag true, false

3BSE026427R4001 113

Page 114: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Valve Control, VALVECON Section 1 Extended Graphic Elements

PointOfControlIndVis 2 Flag true, false

InterlockIndVis 2 Flag false, true

Parameters Affects Options (bold is default) Remarks

114 3BSE026427R4001

Page 115: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Valve Control, VALVECON

Damper01

Presentation:

Behavior:

No Description Presentation Condition Remarks

1 Lock Frame Solid White SELECTED = 1 Selected

Solid Yellow IND2_00 = 1 Interlock override by operator

Dotted Yellow AL_BLK = 1 Alarm blocked by operator

Invisible -

2 Flags Status Indication

2.1 Mode Indication ModeIndVis = 1

* Yellow IND2_02 = 1 andIND2_03 = 0

Test

A Green IND2_05 = 1 andIND2_02 = 0 andIND2_03 = 0

Auto Mode

M Green IND2_05 = 0 andIND2_02 = 0 andIND2_03 = 0

Manual Mode

2.2 Control Indication PointOfControlIndVis = 0

S Green IND2_04 = 1 Sequence control

L Green IND2_01 = 1 and IND2_04 = 0

Local control

3. On-Symbol 3. Off-Symbol

2.

1.

3BSE026427R4001 115

Page 116: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Valve Control, VALVECON Section 1 Extended Graphic Elements

No Description Presentation Condition Remarks

C Green IND2_01 = 0 andIND2_04 = 0

Central control

- PointOfControlIndVis = 0 Point of control is invisible

2.3 Interlock Indication InterlockIndVis = 1 and IND2_03 = 0

XA Yellow IND2_14 = 1 IA1

IND2_07 = 1 Ready to start

X Yellow IND2_08 = 1 orIND2_09 = 1 orIND2_11 = 1 or(IND2_13 = 1 andIND1_11 = 0) or(IND2_00 = 0 and(IND2_10 = 1 or(IND2_12 = 1 andIND1_11 = 0)))

IC1 orIC2 orIB2 or(IB4 &OPN = 0) or(Blkintl = 0 &(IB1 or(IB3 &OPN = 0)))

3 Symbol 3D Display Object

3.1 Shape On-Symbol IND1_11 = 1 Limit position for open

Off-Symbol IND1_11 = 0 No limit position for open

3.2 Color

Grey IMPLEMENTED = 0

Grey IND2_03 = 1 Out of service

Red Flashing IND1_09 = 1 Unacknowledged Alarm

Red IND1_08 = 1 Alarm or Error

Green flashing IND1_15 = 1 andIND1_12 = 0

Intermediate position Not open

Green flashing IND1_15 = 1 andIND1_12 = 1

Intermediate position Open

Green No intermediate position Limit position for open

116 3BSE026427R4001

Page 117: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Section 1 Extended Graphic Elements Valve Control, VALVECON

Configuration:

Parameters Affects Options (bold is default) Remarks

Orientation 3 Symbol Horizontal, Vertical

ModeIndVis 2 Flag true, false

PointOfControlIndVis 2 Flag true, false

InterlockIndVis 2 Flag false, true

3BSE026427R4001 117

Page 118: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

Valve Control, VALVECON Section 1 Extended Graphic Elements

118 3BSE026427R4001

Page 119: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant
Page 120: Extended Graphic Library - AoteWell Master/3BSE026427_Adva… · Extended Graphic Library IndustrialIT 800xA ... Process Controller, ... which enables data retrieval from the Advant

3BSE026427R4001. Printed in Sweden October 2004Copyright © 2003–2004 by ABB. All Rights Reserved® Registered Trademark of ABB.™ Trademark of ABB.

Automation Technology ProductsMannheim, Germanywww.abb.de/processautomationemail: marketing.control-prod-

Automation Technology Products Västerås, Swedenwww.abb.com/processautomationemail: [email protected]

Automation Technology ProductsWickliffe, Ohio, USAwww.abb.com/processautomationemail: [email protected]

http://www.abb.com/control