EWWD 170-600 DJYNN. EWWD 170-600 DJYNN. Water Cooled Chiller 166 kW ÷ 604 kW Single Screw Compressor. TABLE OF CONTENT. Unit position into the range Operating Limits Compressor features Refrigerant Circuit Dry-eXpansion shell & tube evaporator Control & remote control Unit delivery - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: EWWD 170-600 DJYNN

EWWD170-600DJYNN

Page 2: EWWD 170-600 DJYNN

2Apr 21, 2023

Water Cooled Chiller

166 kW ÷ 604 kW

Single Screw Compressor

EWWD170-600DJYNN

Page 3: EWWD 170-600 DJYNN

3Apr 21, 2023

TABLE OF CONTENTA. Unit position into the range

B. Operating Limits

C. Compressor features

D. Refrigerant Circuit

E. Dry-eXpansion shell & tube evaporator

F. Control & remote control

G. Unit delivery

H. EWWD-DJYNN Options summary

1. Options as standard

2. Options on request

Page 4: EWWD 170-600 DJYNN

4Apr 21, 2023

EWWD-DJYNN: unit efficiency level

600

500

460

420380

320

300

260

210170

650

550500

460400

380

320

280230

190

3.50

3.70

3.90

4.10

4.30

4.50

4.70

4.90

100 200 300 400 500 600 700

kW

EE

R

EWWD-DJYNN EWWD-DJYNN/A

A. UNIT POSITION INTO THE RANGE (1/3)

Page 5: EWWD 170-600 DJYNN

5Apr 21, 2023

EWWD-DJYNN: cooling range

100 200 300 400 500 600 700

EWWD-DJYNN

EWWD-DJYNN/A

kW cooling @ Evap. 12/7°C - Cond. 30/35°C

1 Compressor 2 Compressors

1 Compressor 2 Compressors

A. UNIT POSITION INTO THE RANGE (2/3)

Page 6: EWWD 170-600 DJYNN

6Apr 21, 2023

EWWD-DJYNN: sizes distribution

555.7493.7448.3402.5372.2333.9280.4252.8201.2165.5

603.9540.5496443.6408.2366.3306.7276.5223.3186.4

100 200 300 400 500 600 700

kW

EWWD-DJYNNEWWD-DJYNN/A

A. UNIT POSITION INTO THE RANGE (3/3)

Link

back

Page 7: EWWD 170-600 DJYNN

7Apr 21, 2023

B. OPERATING LIMITS

Note: the use of glycol is necessary for evaporator leaving water temperature below +3°C

Operating range EWWD-DJYNN

20

25

30

35

40

45

50

55

-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

Evaporator leaving temperature - °C

Co

nd

en

se

r le

av

ing

te

mp

era

ture

- °

C

Link

back

Page 8: EWWD 170-600 DJYNN

8Apr 21, 2023

EWWD-DJYNN – Single Screw Compressor

“ Frame3200 ” single screw compressor

axial balanced loads

radial balanced loads

2 specular compression cycles

infinitely variable cooling capacity control

integrated oil separator

direct driven screw (no gear)

6 electrical terminals for Y-D as standard

fully semi-hermetic design

composite material on gate rotors

suctioncompressiondischarge

C. COMPRESSOR FEATURES (1/3)

Page 9: EWWD 170-600 DJYNN

9Apr 21, 2023

EWWD-DJYNN – Single Screw Compressor

“ Compressor ”radial balancing axial balancing

Composite material (carbon base composition) to improve compressor reliability and energy performances

Stepless slide valve (oil controlled) to change compressor capacity to match exactly the plant thermal request

better chilled water stability

C. COMPRESSOR FEATURES (2/3)

Page 10: EWWD 170-600 DJYNN

10Apr 21, 2023

EWWD-DJYNN – Single Screw Compressor

“ Frame 3100 ”

Six electrical terminals to allow as standard a star-delta (Y-D) compressor start

The integral oil separator is bolted to the rear of the main casing. The impingement type separator is fitted with a knitted stainless steel mesh element.

Fully semi-hermetic design to allow ordinary maintenance and to replace easily each component if necessary

C. COMPRESSOR FEATURES (3/3)

Link

back

Page 11: EWWD 170-600 DJYNN

11Apr 21, 2023

D. REFRIGERANT CIRCUIT

i.e. EWWD-DJYNN one compressor circuit P&I

Link

back

Page 12: EWWD 170-600 DJYNN

12Apr 21, 2023

E. Dry-eXpansion shell & tube evaporator

1) One pass configuration on refrigerant side (R-134a)

Better oil circulation and compressor oil return at part load operation

2) Higher water volume content (Vs PHE Plate Heat Exchanger) More thermal inertia for the chiller

Smaller external water tank installation (when required)

No freezing risk at any chiller load

No “water hummer” phenomena damage

copper tube internally enhanced

Link

back

Page 13: EWWD 170-600 DJYNN

13Apr 21, 2023

EWWD-DJYNN – Electrical Panel Features

Main switch: only on OFF position, it allows the access inside the panel.

Control keypad and display are located outside on the front door.

F. CONTROL AND REMOTE CONTROL (1/4)

Page 14: EWWD 170-600 DJYNN

14Apr 21, 2023

EWWD-DJYNN – Microprocessor Control “Microtech II C Plus”

Motherboard with microprocessors

Unit Controller fully programmed and engineered by Daikin on Carel hardware

P.I.D. logic (proportional, integrative, derivative)

Compressor regulated according leaving evaporator water temperature (LEWT) to match customer set-point within ± 0.2°C

Easy visual interface with 4 rows and 20 characters display and 15 keypad

F. CONTROL AND REMOTE CONTROL (2/4)

Page 15: EWWD 170-600 DJYNN

15Apr 21, 2023

EWWD-DJYNN – Microprocessor Control “Microtech II C Plus”

High value control functions implemented as standard into the logic

Link back options summary

F. CONTROL AND REMOTE CONTROL (3/4)

Page 16: EWWD 170-600 DJYNN

16Apr 21, 2023

EWWD-DJYNN – Microprocessor Control “Microtech II C Plus”

Easy integration into building automation systems via separate digital connection for unit start/stop and 4-20 mA signals for chilled water reset and demand limiting; Communications capabilities for remote monitoring, changing of setpoint, trend logging, alarm and event detection, via a compatible IBM-PC with Daikin PlantVisor 1.0 software; BMS communication capability via Modbus, BacNet, LonWorks protocol; Remote communications capabilities via modem/GSM (up to 8 chillers with Gateway Modem); Compatibility with Daikin CSC II (Chiller Sequencing Control)

Link back options summary

F. CONTROL AND REMOTE CONTROL (4/4)

Link back table of

content

Page 17: EWWD 170-600 DJYNN

17Apr 21, 2023

EWWD-DJYNN – Unit delivery, moving and lifting

Unit is delivered EXW (Ex works);

Each unit is tested at full load before shipping;

Unit handling must be according to IOM manual.

G. UNIT DELIVERY

Link

back

Page 18: EWWD 170-600 DJYNN

18Apr 21, 2023

H. EWWD-DJYNN: OPTIONS SUMMARY

• Standard options– Heatpump version

– Brine version (OPZH;OPZL)

– Double setpoint

– Thermal relays compressors

– Under/over voltage controller

– Victaulic on condenser

– Flow switch for evaporator

– Setpoint reset and demand limit

– Alarm from external device

– Rubber type antivibration mounts

– Main switch (OP52)

– Electronic Expansion valve (OPEX)

– Suction stop valve (OP12)

• Available options– Power factor 0.9 (OPPF)

– A/V meter (OP57)

– Soft starter (OPSS)

– Cu/Ni heat exchanger

– Low noise version (OPLN)

– Heat Recovery (OPPR;OPTR

– Option /A available with EWWD190-650DJYNN/A

Page 19: EWWD 170-600 DJYNN

19Apr 21, 2023

1. OPTIONS AS STANDARD (1/2)

OP12 - Suction line shut off valve – Suction shut-off valve installed on the suction port of the compressor to facilitate maintenance operation.

ALARM FROM EXTERNAL DEVICE – Microprocessor is able to receive an alarm signal from an external device (pump etc…). User can decide if this alarm signal will stop or not the unit

FLOW SWITCH – Supplied separately to be wired and installed on the evaporator water piping (by the customer).

COMPRESSOR THERMAL OVER RELAYS – Safety devices against compressor motor overloading in addition to the normal protection envisaged by the electrical windings.

Link back options summary

Page 20: EWWD 170-600 DJYNN

20Apr 21, 2023

UNDER/OVER VOLTAGE CONTROLLER – Phase monitor to control the minimum and maximum voltage value that the user can set.

RUBBER TYPE ANTIVIBRATION MOUNTS – Supplied separately, these are positionned under the base of the unit for “floor installation”

OPEX – Electronic expansion valve – It proposes features that makes it unique:

short openning and closing time, high resolution, positive shut-off function to

eliminate use of additional solenoid valve, highly linear flow capacity,

continous modulation of mass flow without stress in the refrigerant circuit and

corrosion resistance stainless steel body

1. OPTIONS AS STANDARD (2/2)

Link back options summary

Page 21: EWWD 170-600 DJYNN

21Apr 21, 2023

2. OPTIONS ON REQUEST (1/2)

OPSS Soft start – Electronic starting device to reduce starting current. An overload protection is included (no need of compressors thermal relays).

OPLN Sound proof cabinet – Made of sheet metal and internally insulated, the sound proof cabinet is around the compressor/s reach the best performance in noise reduction.

OPPF- Capacitor power factor correction - Installed on the electrical control panel to ensure it conforms to the plant rules (Daikin advises maximum 0,9).

OP57- Ammeter and voltmeter – Digital meters of unit drawn amperes and voltage values, installed on the electrical control panel.

Link back options summary

Page 22: EWWD 170-600 DJYNN

22Apr 21, 2023

OPTR – 100% total heat recovery – Produced with tube bundle placed in a single

shell with the water condensers heads are provided with 2 connections for

entering/leaving heat recovery water and 2 separate connections for

condensing water.

OPPR – Partial heat recovery – Produced with plate to plate heat exchangers

installed on discharge side of compressor gas. Yhese allow hot water to be

produced up to a maximu temperature of +50°C

2. OPTIONS ON REQUEST (2/2)

Link back options summary